Ideal for small-scale control applications,
the ZEN provides an economical alternative
to discrete timers, counters and generalpurpose relays. This single unit easily
provides relay, timer, counter, and time
switch functions. Wiring work is greatly
reduced because separate wiring is not
required for devices such as timers and
counters. Programs can be easily written,
saved, and monitored by personal computer.
Programs can also be simulated on the
personal computer without connecting to the
ZEN. Communication models with an RS485
interface allow production line conditions to
be remotely monitored by monitoring the
ZEN control status.
Applications
Designed for use in automation for
commercial and industrial sectors,
ZEN programmable relays provide the
ideal solution for lighting, energy
management, industrial control, watering
and pump control.
ZEN-8E1DR, $110.
ZEN-20C1AR-A-V2,
$254.
K-1
RATINGS SPECIFICATIONS
Q
4
I 6I 7I 8I 9I aI
b
Q6Q5Q
7
60 (2.36)
70 (2.75)
112.5 (4.30)
122.5 (4.82)
4.7 (0.18)
(Sliding: 13 max)
4.7 (0.18)
(Sliding: 13 max)
60 (112.5)*
80
(3.15)
Tw o, M4
45
(1.77)
45
(1.77)
44 (1.73)
44 (1.73)
Mounting Hole Dimensions
* The dimensions in parentheses
refer to models with 20 I/O points.
CPU Units with 10 I/O Points
C
90
(3.54)
90
(3.54)
80
(3.15)
80
(3.15)
ZEN-10C1AR-A-V2
ZEN-10C1AR-A-V2
ZEN-20C1AR-A-V2
56 (2.20)
56 (2.20)
4.5 (0.17)
5.5
(0.21)
Unit Mounting Holes
Note: Use M4 screws for mounting
CPU Units with 20 I/O Points
ZEN-20C1AR-A-V2
MODEL NO.ZEN-xCxAR-A-V2/ZEN-8E1AR ZEN-xCxDx-D-V2/ZEN-8E1Dx
RATED SUPPLY VOLTAGE100 to 240 Vac, 50/60 Hz 12 to 24 Vdc (DC ripple rate: 5% max.)
OPERATING VOLTAGE RANGE 85 to 264 Vac 10.8 to 28.8 Vdc
POWER CONSUMPTIONZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2/ZEN-10CxDR-D-V2 12/24 Vdc: 3 W max
CPU UNITS WITHOUT
EXPANSION I/O UNITS
POWER CONSUMPTION ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2ZEN-10CxDR-D-V2 12/24 Vdc: 4 W max
CPU UNITS WITH THREE100 Vac: 6 VA max, 240 Vac: 8 VA max
EXPANSION I/O UNITS
EXPANSION I/O UNITS ZEN-8E1ARZEN-8E1DR 12/24 Vdc: 2 W max
INRUSH CURRENT ZEN-10CxAR-A-V2 4.5 A max ZEN-10CxDx-D-V2 30 A max
AMBIENT TEMPERATURE 0 to 55°C (-25 to 55°C) for ZEN-xC2xx-x-V2 models
AMBIENT STORAGE -20 to 75°C (-40 to 75°C) for ZEN-xC2xx-x-V2 models
TEMPERATURE
AMBIENT HUMIDITY 10 to 90% (with no condensation)
AMBIENT CONDITIONSNo corrosive gases
MOUNTING METHODSurface mounting, DIN track mounting [standard (vertical) installation and horizontal
TERMINAL BLOCKSolid-line terminal block (use solid wire or fine-stranded wire)
TERMINAL SCREW 0.565 to 0.6 N·m (5 to 5.3 in-lb)
TIGHTENING TORQUE
DEGREE OF PROTECTIONIP20 (mounted inside a control panel)
Dimensions: mm (in)
ZEN-10C3AR-A-V2(ZEN-10C3DR-D-V2: 2.8 W max)
100 Vac: 5 VA max, 240 Vac: 7 VA max
ZEN-10CxDT-D-V2 12/24 Vdc: 2 W max
ZEN-10C4AR-A-V2ZEN-20CxDR-D-V2 12/24 Vdc: 4 W max
100 Vac: 6 VA max, 240 Vac: 8 VA maxZEN-20CxDT-D-V2 12/24 Vdc: 2 W max
ZEN-20CxAR-A-V2
100 Vac: 7 VA max, 240 Vac: 10 VA max
ZEN-10C4AR-A-V2 ZEN-20CxDR-D-V2 12/24 Vdc: 5 W max
100 Vac: 7 VA max, 240 Vac: 9 VA max ZEN-20CxDT-D-V2 12/24 Vdc: 3 W max
ZEN-20CxAR-A-V2
100 Vac: 8 VA max, 240 Vac: 11 VA max
100 Vac: 3 VA max, 240 Vac: 4 VA max
ZEN-20CxAR-A-V2 4.5 A max ZEN-20CxDx-D-V2 30 A max
ZEN-8E1AR 4 A max ZEN-8E1DR 15 A max
installation]
K-2
ZEN-10CxDT-D-V2 12/24 Vdc: 3 W max
Dimensions with Battery Unit
Q
4
I 6I 7I 8I 9I aI
b
Q6Q5Q
7
ZEN-BAT01
44 (1.73)
87.5 (3.44)
70 (2.75)
17.5
(0.69)
17.5
(0.69)
122.5 (4.82)
140 (5.51)
CPU Units with 10 I/O PointsCPU Units with 20 I/O Points
ZEN-10C1AR-A-V2
ZEN-20C1AR-A-V2
45
(1.77)
45
(1.77)
Expansion I/O Units
45
(1.77)
45 (1.77)
97
(3.81)
97
(3.81)
7.6 (0.29)
7.6 (0.29)
17.5
(0.69)
Tw o, 3.5 dia.
35
(1.37)
Tw o, M3
DIN Track Hook
(Using Slide)
Mounting Hole Dimensions
ZEN-8E1AR
ZEN-8E1AR
ZEN-8E1AR
2
(0.078)
2
(0.078)
90
(3.54)
90
(3.54)
54 (2.13)
SPECIFICATIONS
Control Method: Stored
program control
I/O Control Method: Cyclic scan
Programming Language:
Ladder diagram
Program Capacity: 96 lines (3 input
conditions and 1 output per line)
Max No. of Control I/O Points:
44 points
CPU Units with 20 I/O Points:
12 inputs and 8 outputs
Expansion I/O Units: 4 inputs and
4 outputs each, up to 3 units
LCD Display:
12 characters × 4 lines, with backlight
Operation Buttons:
8 (4 cursor buttons and
4 operation buttons)
User Program Back-Up: Internal
EEPROM, memory cassette (optional)
Power Interruption Hold: Internal
holding bit status, holding timer/counter
present values, calendar and clock
(year, month, day of month, day of
week, time)
Super Capacitor Backup Time:
2 days min (25°C)
Life of Optional Battery:
10 years min (25°C)
Calendar and Clock Function:
Accuracy: ±15 s/month (at 25°C)
Timer Accuracy:
0.01s Unit: -0.05%, -10 mS max
(rate for set value)
0.02 min/s Unit: -0.05%, -1 s max
(rate for set value)
0.03 h/min Unit: -0.05%, -1 min max
(rate for set value)
Maximum Counting Speed: 150 Hz
8-digit counter (F) set to high-speed
operations (CPU units with DC power
supplies only) (the counting speed may
be less than 150 Hz depending on the
cycle time of the program
Insulation Resistance: 20 MΩ
(at 500 Vdc) min between power supply
terminals and all output terminals,
terminals of different output circuits;
between all terminals of CPU unit and all
terminals of expansion I/O unit
Insulation: Reinforced insulation
between power supply or input
terminals and output terminals;
terminals of different output circuits; all
terminals of CPU unit and all terminals
of expansion I/O unit; no separation
between power supply and input
terminals of the same unit, power
supply terminals of CPU unit and
computer connector, battery unit
connector, or all expansion unit
connectors (all interfaces are live parts)
Dielectric Strength: 2300 Vac, 50/60 Hz
for 1 min (leakage current 1 mA max)
between power supply terminals and all
output terminals; terminals of different
output circuit; all terminals of CPU unit
and all terminals of expansion I/O unit
K-3
Dimensions: mm (in)
Vibration Resistance: Conforms to
IEC60068-2-6, 5 to 9 Hz with 3.5 mm
single amplitude, 9 to 150 Hz
acceleration 9.8 m/s
in X, Y, and Z directions (1 octave/min)
Shock Resistance: Conforms to
2
, 10 sweeps each
IEC60068-2-27, 147 m/s2, 3 times
each in X, Y, and Z directions
Weight:
CPU Unit with 10 I/O Points:
Approx 300 g max
CPU Unit with 20 I/O Points:
Approx 350 g max
Expansion I/O Unit:
Approx 120 g max
COMMUNICATIONS
(TYPE CPU UNITS)
ZEN-10C4XR-X-V2
Communications: RS485
Baud Rate: 4800, 9600, or 19,200 bps
Transmission Code: ASCII
Data Bit Length: 7 or 8 bits
Stop Bit Length: 1 or 2 bits
Error Detection: Vertical parity (none,
SAFETY STANDARDScULus: UL508/CSA C22.2 No.142 Class I Div2
EMCRadiation field emission noiseCISPR11Class A, Group 1
*
EMC conforms to EN 61131-2 clause 8 except in the following cases.
*
When expansion I/O units with DC inputs are connected to a CPU unit with an AC power supply, the burst immunity between power
supplies will be 1 kV.
When the signal wire for transistor outputs exceeds 10 m, the surge immunity of DC output signal lines will not conform.
excluding 11.7.2.2 (overvoltage category 2 and pollution degree II conforms to IEC 60664-1)
terminal voltage emissionCISPR11 Class A, Group 1
Electrostatic discharge immunityIEC61000-4-2In air: 8 kV, in contact: 6 kV
Electromagnetic field immunityIEC61000-4-310 V/m
Electrical fast transient/IEC61000-4-4Power line
burst immunityAC I/O: 2 kV
Surge immunity IEC61000-4-5 Normal noise
Immunity to conducted disturbances IEC61000-4-6 3V
induced by radio-frequency fields
Momentary power interruptionIEC61131-2CPU units with AC power supplies:
immunity10 ms max
conforms to EN/IEC 61131-2 clause 11,
DC I/O: 1 kV
AC power supply, AC I/O: 1 kV
DC power supply, DC I/O: 0.5 kV
Common Noise
AC power supply, AC I/O: 2 kV
DC power supply: 1 kV
DC I/O: 0.5 kV
CPU units with DC power supplies:
2 ms max (level: PS1)
CPU UNITS SPECIFICATIONS
AC INPUTS (NOT ISOLATED)
Input Voltage: 100 to 240 Vac +10%,
ON Voltage: 80 Vac min
OFF Voltage: 25 Vac max
ON Response Time: 50 or 70 mS
at 100 Vac
OFF Response Time: 100 or 120 mS
at 240 Vac
††
Can be selected using the input
filter settings.
DC INPUTS
ZEN-8E1DR: Not isolated
ZEN-8E1DT: Photocoupler isolated
Input Voltage: 12 to 24 Vdc
+20%, -10%
Input Impedance: 6.5 kΩ
Input Current: 3.7 mA (typ)/24 Vdc
ON Voltage: 8 Vdc min
OFF Voltage: 5 Vdc max
ON/OFF Response Time: 15 or
50 mS†††
†††Can be selected using the input
filter settings.
††
††
OUTPUT SPECIFICATIONS
(CPU UNITS AND EXPANSION
I/O UNITS)
UNITS WITH RELAY OUTPUTS
Maximum Switching Capacity:
250 Vac/8 A (resistive load; cos = 1),
24 Vdc/5 A (resistive load) use the
following values for the total of all
outputs
CPU Units with 10 I/O Points:
20 A max (15 A max for
communications-type CPU units)
CPU Units with 20 I/O Points:
40 A max
Expansion I/O Units: 20 A max
Minimum Switching Capacity:
5 Vdc/10 mA (resistive load) (failure
level: P, reference value)
Relay Life:
Electrical: Resistive load; 50,000
times (cos= 1)
Inductive Load: 50,000 times
(cos= 0.4)
Mechanical: 10 million times
ON Response Time: 15 mS max
OFF Response Time: 5 mS max
UNITS WITH
TRANSISTOR OUTPUTS
Maximum Switching Capacity: 24 Vdc
+20%, 500 mA
Leakage Current: 0.1 mA max
Residual Voltage: 1.5V max
ON Response Time: 1 mS max
OFF Response Time: 1 mS max
To Order (Specify Model Number)
MODEL NO.PRICEDESCRIPTION
ZEN-10C3AR-A-V2$160 LCD display, 6 AC inputs, 4 relay outputs, AC power, no expansion I/O
ZEN-10C3DR-D-V2160 LCD display, 6 DC inputs, 4 relay outputs, DC power, no expansion I/O
ZEN-10C1AR-A-V2190 LCD display, 6 AC inputs, 4 relay outputs, AC power
ZEN-10C1DR-D-V2190 LCD display, 6 DC inputs, 4 relay outputs, DC power
ZEN-10C1DT-D-V2190 LCD display, 6 DC inputs, 4 transistor outputs, DC power
ZEN-20C3AR-A-V2214 LCD display, 12 AC inputs, 8 relay outputs, AC power, no expansion I/O
ZEN-20C3DR-D-V2214 LCD display, 12 DC inputs, 8 relay outputs, DC power, no expansion I/O
ZEN-20C1AR-A-V2254 LCD display, 12 AC inputs, 8 relay outputs, AC power
ZEN-20C1DR-D-V2254 LCD display, 12 DC inputs, 8 relay outputs, DC power
ZEN-20C1DT-D-V2254 LCD display, 12 DC inputs, 8 transistor outputs, DC power
EXPANSION I/O
ZEN-8E1DT$96 Expansion I/O, 4 DC inputs, 4 transistor outputs
ZEN-8E1DR110 Expansion I/O, 4 DC inputs, 4 relay outputs
ZEN-8E1AR115 Expansion I/O, 4 AC inputs, 4 relay outputs
ZEN-BAT01,
battery unit, $52.
Ladder programs and parameter settings
are saved to the CPU Unit EEPROM but
calendar, clock, and holding timer bits and
holding timer/ counter present values are
held by the capacitor. Therefore, if the power
supply is interrupted for 2 days or more
(at 25°C), this data will be reset. Use a
battery unit for systems where the power
supply may be interrupted for long periods.
Enables programs and parameter settings
to be saved or copied to another ZEN.
smaller than actual size.
ZEN-ME01, memory
cassette, $47.
All models shown
MOST POPULAR MODELS HIGHLIGHTED!
ZEN-CIF01,
programming
cable, $124.
Required for programming and simulating
using ZEN-SOFT01V4 software. Ladder
logic programs can be entered using the
front-panel display and buttons, but the
software makes it easier to visualize and
the program can be simulated before
downloading to the CPU unit.
SOFTWARE AND ACCESSORIES
MODEL NO.PRICEDESCRIPTION
ZEN-SOFT01V4$81Programming software
ZEN-CIF01124Programming cable, RS232C, 2 m (6.5')
ZEN-BAT0152Battery unit, 10 year min battery life
ZEN-ME0147Memory cassette
Calibrators, Connectors, General Test and Measurement
Instruments, Glass Bulb Thermometers, Handheld Instruments
for Temperature Measurement, Ice Point References,
Indicating Labels, Crayons, Cements and Lacquers, Infrared
Temperature Measurement Instruments, Recorders Relative
Humidity Measurement Instruments, RTD Probes, Elements
and Assemblies, Temperature & Process Meters, Timers and
Counters, Temperature and Process Controllers and Power
Switching Devices, Thermistor Elements, Probes and
Assemblies,Thermocouples Thermowells and Head and Well
Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level
Measurement, Magnetic Flowmeters, Mass Flowmeters,
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel
Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area
Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen
Instrumentation, Environmental Instrumentation, pH
Electrodes and Instruments, Water and Soil Analysis
Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems,
Communication Products and Converters, Data
Acquisition and Analysis Software, Data Loggers
Plug-in Cards, Signal Conditioners, USB, RS232, RS485
and Parallel Port Data Acquisition Systems, Wireless
Transmitters and Receivers
Band Heaters, Cartridge Heaters, Circulation Heaters,
Comfort Heaters, Controllers, Meters and Switching
Devices, Flexible Heaters, General Test and Measurement
Instruments, Heater Hook-up Wire, Heating Cable
Systems, Immersion Heaters, Process Air and Duct,
Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.