MCCB-UL 489 Listed
MoLded Case
CirCUit Breakers
TD/TS Series
Power
Breakers
l 4 Compact Frame Sizes Rated
15 to 800 Amps
l 600 Vac Maximum Rated
Operational Voltage
l Standard or High Capacity
Breaking Choices
l Thermal Magnetic
l 3 Poles-240, 480, 600 Vac
l Up to 100 kA Short Circuit
Interrupting Capacity
l Circuit Breakers are Supplied
with Line and Load Terminals
l HACR Rated
l CE Version (without UL Approval)
Available Upon Request
The TD/TS Series MCCB–molded case
circuit breakers–main function are to protect
electrical applications form short circuit or
earth leakage, overload current and
under-voltage conditions. These devices
are used to isolate the power, or to trip
the power, at the time of fault in line and
thus save the circuit from further damage.
MCCB’s are well suited for OEM designed
equipment in both light commercial and
industrial applications. Their compact size
saves space and reduces overall panel size
and the field-installable accessories allow
for last minute changes.
The TD/TS Series MCCB’s are available with
three different trip units that are installed in
the housing; FTU–fixed-thermal and fixed
magnetic; FMU–adjustable-thermal and
fixed magnetic; ATU-adjustable-thermal and
adjustable-magnetic. The following internal
electrical accessories are also available
auxiliary and alarm switches, shunt releases,
and under voltage releases. See the online
manual for additional information and trip
curves at omega.com/circuit-breakers
SPECIFICATIONS
MODEL NO. TD125 TS250 TS400 TS800
Current Rating
@ 600 Vac 15 to 125A 150 to 250A 300 to 400A 500 to 800A
Wire Rating
CU only 60/75ºC 60/75ºC 75ºC 75ºC
NU STANDARD BREAKING CAPACITY
240V 50/60Hz 50 50 50 50
480V 50/60Hz 35 35 35 35
600V 50/60Hz 10 10 10 10
HU HIGH BREAKING CAPACITY
240V 50/60Hz 100 100 100 100
480V 50/60Hz 65 65 65 65
600V 50/60Hz 14 18 20 35
Mechanical
Operations
Electrical
Operations
at 600 Vac 4000 1000 1000 500
Wire/ AWG AWG 250 to 500 250 to 500
Cable Size 14-1/0 1 to 400 kcmil kcmil kcmil
DIMENSIONS mm (in)
Height 90 (3.54) 105 (4.13) 140 (5.51) 210 (8.27)
Width 164 (6.46) 178 (7.01) 292 (11.5) 428 (16.85)
Depth 86 (3.39) 86 (3.39) 110 (4.33) 135 (5.31)
Note: Calibration Temperature 40ºC (104ºF)
TD125NU-FTU-LL-50,
50 A MCCB electrical.
4000 5000 5000 3000
M-1
MCCB FIXED - THERMAL AND FIXED MAGNETIC FTU UNITS
To Order Visit omega.com/circuit-breakers
MODEL NO.
STANDARD FRAME AMPERAGE
CAPACITY BREAKER SIZE RATED
TD125NU-FTU-LL-15
TD125NU-FTU-LL-20 125 20
TD125NU-FTU-LL-30 125 30
TD125NU-FTU-LL-40 125 40
TD125NU-FTU-LL-50 125 50
TD125NU-FTU-LL-60 125 60
TD125NU-FTU-LL-80 125 80
TD125NU-FTU-LL-100 125 100
TD125NU-FTU-LL-125 125 125
TS250NU-FTU-LL-150 250 150
TS250NU-FTU-LL-175 250 175
TS250NU-FTU-LL-200 250 200
TS250NU-FTU-LL-225 250 225
TS250NU-FTU-LL-250 250 250
TS400NU-FTU-LL-300 400 300
TS400NU-FTU-LL-350 400 350
TS400NU-FTU-LL-400 400 400
TS800NU-FTU-LL-500 800 500
TS800NU-FTU-LL-600 800 600
TS800NU-FTU-LL-700 800 700
TS800NU-FTU-LL-800 800 800
Comes complete with line and load terminal lugs and operator’s manual.
Note: For adjustable-thermal/fixed-magnetic (FMU), or adjustable-thermal/Adjustable-magnetic (ATU), visit omega.com/auto for selection.
Ordering Examples: TD125NU-FTU-LL-50, MCCB with standard interrupting capacity, 35 kA at 480V, rated for 50 Amp, fixed-thermal/
fixed-magnetic trip unit with line and load lugs.
TD125HU-FTU-LL-100, MCCB with high capacity, 65k A at 480V, rated for 100 A, TDTS-S-AX, auxiliary switch, TDTS-S-AL alarm switch,
TDTS-S-SHT-24, 24 Vdc shunt trip unit, TDTS-F-FH1-36, flange mount handle for disconnect enclosure with 36" cable.
125 15
To Order Visit omega.com/circuit-breakers
MODEL NO.
HIGH FRAME AMPERAGE
CAPACITY BREAKER SIZE RATED
TD125HU-FTU-LL-15
TD125HU-FTU-LL-20 125 20
TD125HU-FTU-LL-30 125 30
TD125HU-FTU-LL-40 125 40
TD125HU-FTU-LL-50 125 50
TD125HU-FTU-LL-60 125 60
TD125HU-FTU-LL-80 125 80
TD125HU-FTU-LL-100 125 100
TD125HU-FTU-LL-125 125 125
TS250HU-FTU-LL-150 250 150
TS250HU-FTU-LL-175 250 175
TS250HU-FTU-LL-200 250 200
TS250HU-FTU-LL-225 250 225
TS250HU-FTU-LL-250 250 250
TS400HU-FTU-LL-300 400 300
TS400HU-FTU-LL-350 400 350
TS400HU-FTU-LL-400 400 400
TS800HU-FTU-LL-500 800 500
TS800HU-FTU-LL-600 800 600
TS800HU-FTU-LL-700 800 700
TS800HU-FTU-LL-800 800 800
125 15
ACCESSORIES
TDTS-S-FH-36.
Both models shown
smaller than actual size.
M-2
M-2
TDTS-S-EHU1-12.