Omega Products SBG144600 Installation Manual

SBG144600SBG144600
SBG144600
SBG144600SBG144600 Intrinsic Safety RelayIntrinsic Safety Relay
Intrinsic Safety Relay
Intrinsic Safety RelayIntrinsic Safety Relay
Instruction Sheet M-2474/1096
DESCRIPTIONDESCRIPTION
DESCRIPTION
DESCRIPTIONDESCRIPTION
The OMEGA® SBG144600 Solid-State Relays are used as "intrinsically safe switching circuits in hazardous locations, with non-voltage- producing sensors". When installed in accordance with this manual, these field sensors are suitable for Classes I and 2 , Divisions 1 and 2, Groups A, B, C, D, E, F, and G, as defined by the National Electrical Code Handbook.
VAC
Neutral
Hot
Fuse F1
Load
*See Note #2
(EXIA)
UNPACKINGUNPACKING
UNPACKING
UNPACKINGUNPACKING
Remove the Packing List and verify that you have received all equipment. If you have any questions about the shipment, please call the OMEGA Customer Service Department at 1-800-622-2378 or (203) 359-1660. When you receive the shipment, inspect the container and equipment for any signs of damage. Note any evidence of rough handling in transit. Immedi­ately report any damage to the shipping agent.
NOTENOTE
The carrier will not honor any claims unless all shipping material is saved for their examination. After examining and removing contents, save
packaging material and carton in the event reshipment is necessary.
Important: Read carefully and completely beforeImportant: Read carefully and completely before
Important: Read carefully and completely before
Important: Read carefully and completely beforeImportant: Read carefully and completely before installing or connecting the intrinsic safety relay.installing or connecting the intrinsic safety relay.
installing or connecting the intrinsic safety relay.
installing or connecting the intrinsic safety relay.installing or connecting the intrinsic safety relay.
Associated EquipmentAssociated Equipment
Associated Equipment
Associated EquipmentAssociated Equipment
Caution:Caution:
Caution: The intrinsically safe relays must be mounted outside the
Caution:Caution:
hazardous location. Only the sensor's terminals provide an intrinsically safe switch circuit (Fig. 1). (Exia) means associated equipment "Appareilage connexe", located in safe area.
Mounting and Enclosure ConsiderationMounting and Enclosure Consideration
Mounting and Enclosure Consideration
Mounting and Enclosure ConsiderationMounting and Enclosure Consideration
Field wiring of intrinsically safe circuits is to be segregated from non­intrinsically safe wiring by use of suitable barriers, separate wireways or trays (see Fig. 2). Wire insulation to be .010", minimum. Intrinsically safe and non-intrinsically safe connection points should be located sufficiently apart to prevent any possibility of bypassing or miswiring during installation or servicing of equipment. The enclosure shall contain a cautionary statement as follows:
"CAUTION: ANY SUBSTITUTION OF COMPONENTS "CAUTION: ANY SUBSTITUTION OF COMPONENTS
"CAUTION: ANY SUBSTITUTION OF COMPONENTS
"CAUTION: ANY SUBSTITUTION OF COMPONENTS "CAUTION: ANY SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY". MAY IMPAIR INTRINSIC SAFETY".
MAY IMPAIR INTRINSIC SAFETY".
MAY IMPAIR INTRINSIC SAFETY". MAY IMPAIR INTRINSIC SAFETY".
The mounting plate must be grounded to ensure intrinsic safety. Resistance between the plate and earth ground should be less than one ohm. (See Figs. 3 and 4 for recommended selection of grounding hardware and refer to Article 250 of the National Electrical Code for methods and practices.)
NOTENOTE
Non-Hazardous
Location
Hazardous
Location
Sensor
Switch
NotesNotes
Notes
1. For 120V application, only one fuse is required in the ungrounded circuit of the input line.
2. Required torque on these terminals not to exceed 10 lb-inches on stranded wire - 8 lb-inches on solid wire.
Fig. 1. Fig. 1.
Fig. 1.
Fig. 1. Fig. 1.
Earth Ground
(2 Places)
Common
Earth-
Grounded
Mounting
Plate
NotesNotes
Connection DiagramConnection Diagram
Connection Diagram
Connection DiagramConnection Diagram
Non-Intrinsically
Safe Wiring
Mul­tiple
Units
Installation of Sensor Switch and Associated Field WiringInstallation of Sensor Switch and Associated Field Wiring
Installation of Sensor Switch and Associated Field Wiring
Installation of Sensor Switch and Associated Field WiringInstallation of Sensor Switch and Associated Field Wiring
The nature of the sensor switch must be that it is a non-voltage­producing, essentially resistive termination or other device specifically examined and approved for use with the intrinsically safe solid-state relay. The conductors of the intrinsically safe circuit should be sealed in a rigid metal conduit at the point where the wiring enters the hazardous area. The wiring and sensor switch should be such that conductive dusts in the hazardous area will not close the circuit. Hazardous area field wiring will store energy due to distributed capacitance and inductance in proportion to its length. It is therefore recommended that the characteristics of the cable be known and judged against the length of run and atmosphere of exposure.
The following chart is presented as a guideline in determining the limits of reactance for signal loops in the hazardous area wiring for the intrinsically safe solid-state relays.
GROUP
A & B
C & E
D, F, G
ExampleExample
Example: Typical values of capacitance for a twisted pair of
ExampleExample
copper wires is between 20 and 60 pF per foot. Using the maximum value of 60pF/ft, Groups A & B could have a run of 1500+ feet with safety. Inductance of a typical twisted pair is between
0.10 and 0.20 µH/ft, thus making a cable run in this example essentially determined by the capacitance.
CAPACITANCE
0.6 µF
1.9 µF
1.9 µF
Product must be maintained and installed in strict accordance with the National Electrical Code. Failure to observe this warning could result in serious injuries or damages.
WARNING
INDUCTANCE
1.3 mH
5.4 mH 10 mH
Intrinsically Safe Wiring To Sensors Located in Hazardous Area
Note:Note:
Note: All intrinsically safe wiring must be segregated
Note:Note:
from non-intrinsically safe wiring and shall have a minimum insulation thickness of .010".
Fig. 2. Multiple units (located in a non-hazardousFig. 2. Multiple units (located in a non-hazardous
Fig. 2. Multiple units (located in a non-hazardous
Fig. 2. Multiple units (located in a non-hazardousFig. 2. Multiple units (located in a non-hazardous area) grouped on a common, earth-grounded area) grouped on a common, earth-grounded
area) grouped on a common, earth-grounded
area) grouped on a common, earth-grounded area) grouped on a common, earth-grounded mounting plate. mounting plate.
mounting plate.
mounting plate. mounting plate.
Mounting
Plate
1. Grounding Hardware to be #8 or larger and stainless steel
* *
2.
*Lockwashers to be internal or external tooth-type
* *
Resistance to ground must be from bracket to earthing member to insure integrity of system. (Must be below one ohm.)
Intrinsically Safe
Solid-State Relays
#10 Screw
**
*
**
**
*
**
NotesNotes
Notes
NotesNotes
#10 Lockwasher
#10 Lockwasher
#10 Nut
Fig. 3. Unit Mounting DetailFig. 3. Unit Mounting Detail
Fig. 3. Unit Mounting Detail
Fig. 3. Unit Mounting DetailFig. 3. Unit Mounting Detail
Installation of Sensor Switch and Associated Field Wiring Installation of Sensor Switch and Associated Field Wiring
Installation of Sensor Switch and Associated Field Wiring (Cont.)
Installation of Sensor Switch and Associated Field Wiring Installation of Sensor Switch and Associated Field Wiring
Whenever possible, the actual measured parameters should be used in making the determination of allowable length. Shielded cable is not required, but if used in the application, the shield must be returned to ground, the same point at mounting tab. Non-intrinsically safe wiring cannot be run in conduit or open raceways together with intrinsically safe wiring. (See **Note - next page.) Fusing of the solid-state relays to be in accordance with Fig. 1. Fuse F1 to be 6 amps slo-blo, 120 VAC for 120V line voltage; 250 VAC for 240 V application.
****
NoteNote
: :
**
Note
: All intrinsically safe wiring to intrinsically safe solid-state relays must be segregated from non-intrinsically safe wiring.
****
NoteNote
: :
Mounting
Tab
Mounting
Plate
Lockwasher*
Nut
Screw
Lockwasher*
2-5/8"
(66.6 mm)
3"
(76.2 mm)
Lockwasher*
Notes:Notes:
Notes:
Notes:Notes:
Nut
Terminal Lug
1. *(Lockwasher to be internal or external tooth type)
2. Grounding hardwre to be #8 or larger and S.S.
Fig. 4. Fig. 4.
Fig. 4.
Fig. 4. Fig. 4.
Mounting Plate Grounding DetailMounting Plate Grounding Detail
Mounting Plate Grounding Detail
Mounting Plate Grounding DetailMounting Plate Grounding Detail
Line & LoadLine & Load
Line & Load
ModelModel
Model
ModelModel
NumberNumber
Number
NumberNumber
SBG144600SBG144600
SBG144600
SBG144600SBG144600
DescriptionDescription
Description
DescriptionDescription
SSR for Intrinsic
Safety
Line & LoadLine & Load
VoltageVoltage
Voltage
VoltageVoltage
RangeRange
Range
RangeRange
105 to
125 VAC
LoadLoad
Load
LoadLoad
CurrentCurrent
Current
CurrentCurrent
MaxMax
Max
MaxMax
5A
Table 1. SpecificationsTable 1. Specifications
Table 1. Specifications
Table 1. SpecificationsTable 1. Specifications
Turn-OnTurn-On
Turn-On
Turn-OnTurn-On
SensitivitySensitivity
Sensitivity
SensitivitySensitivity
(Typical)(Typical)
(Typical)
(Typical)(Typical)
< 500
Turn-OffTurn-Off
Turn-Off
Turn-OffTurn-Off
SensitivitySensitivity
Sensitivity
SensitivitySensitivity
(Typical)(Typical)
(Typical)
(Typical)(Typical)
2000
VoltageVoltage
Voltage
VoltageVoltage
LossLoss
Loss
LossLoss
2 VAC
1-3/8"
(35 mm)
OperatingOperating
Operating
OperatingOperating
TemperatureTemperature
Temperature
TemperatureTemperature
RangeRange
Range
RangeRange
-40°F to 120°F
(-40°C to +48.9°C)
7/32" Dia.
(5.5 mm)
Fig. 5. Fig. 5.
Fig. 5.
Fig. 5. Fig. 5.
OutputOutput
Output
OutputOutput
LeakageLeakage
Leakage
LeakageLeakage
Current Max.Current Max.
Current Max.
Current Max.Current Max.
6mA @
120 VAC
(33.3 mm)
2-7/8"
(73 mm)
DimensionsDimensions
Dimensions
DimensionsDimensions
SwitchingSwitching
Switching
SwitchingSwitching OperationOperation
Operation
OperationOperation
SPST N.O.
1-5/16"
7/8"
(22.2 mm)
WeightWeight
Weight
WeightWeight
198g
P/N 169692
Loading...