S8VS-06024A, power
supply, 24 Vdc, 2.5 A,
with display, $187.
l Smart Display Simplifies
Troubleshooting of DC Supply
Problems Inside the Control Cabinet
l Built-In Functionality of a
Multimeter on the Power Supply
l Instant Read-Out Of: Output
Voltages, Output Currents, Peak
Hold Currents, Remaining Service
Life of Power Supply
l Ultra-Compact, DIN Rail Mount
l Unique Led Displays for
Diagnostics (60 to 480 W Models)
l Protect Critical Processes Against
Line Power Brownouts
l Constant Output Maintained Even
with a 10% Input Voltage Sag
l Meets SEMI F47 Requirements
l Universal Supply Voltage
(85 to 264 Vac; 50/60 Hz)
Engineers and plant managers searching for
ways to improve equipment uptime and
reduce overall operating costs are finding
smarter components, such as OMEGA’s
S8VS Series switching power supplies with
built-in diagnostic displays, essential to
support their preventive maintenance
programs and shorten troubleshooting inside
the control panel.
The S8VS responds to their needs with a
reliable power supply combined with a
Smart Display™ that provides operators with
at-a-glance status of output voltage, output
current and peak hold current. On display
models, the display and alarm output indicate
the power supply’s remaining service life
signaling time for maintenance or
replacement. The single-phase, single output
AC-to-DC power supplies are available with
display on models ranging from 60 to 480 W.
In addition, the S8VS features overload and
overvoltage protection. For increased safety,
the overload protection function allows the
power supply to shutdown automatically if the
outputs are shorted or if there is excessive
current flow in the output.
All models shown
smaller than actual size.
S8VS-09024A, power supply,
24 Vdc, 3.75 A,with display, $239.
To order, see page M-7.
S8VS-06024, power supply,
24 Vdc, 2.5 A, no display, $124.
M-1
SPECIFICATIONS
15 AND 30 W RATINGS/CHARACTERISTICS
POWER RATINGS 15 W 30 W
ITEM TYPE STANDARD STANDARD
5V Models 72% min 70% min
Efficiency (Typical)12V Models74% min 76% min
Voltage
Frequency
*1
*1
Current
Power Factor—
InputHarmonic Current EmissionsConforms to EN61000-3-2
Leakage Current
Inrush Current
Voltage Adjustment Range
Ripple2.0% (p-p) max (at rated input/output voltage)
Input Variation Influence0.5% max (at 85 to 264 Vac input, 100% load)
Load Variation Influence
Output (Rated Input Voltage)
Temperature Variation Influence 0.05%/°C max
Startup Time
Hold Time20 ms min (at rated input/output voltage)
Overload Protection
Overvoltage ProtectionYes (a zener diode clamp)
Output Voltage IndicationNo
Output Current IndicationNo
Peak-Hold Current IndicationNo
Maintenance Forecast
Total Run Time Monitor Indication No
Total Run Time Monitor OutputNo
Undervoltage Alarm IndicationYes (color: red)
Undervoltage Alarm OutputNo
Parallel OperationNo
Series Operation
Operating Ambient Temperature Refer to the derating curve in engineering data (15 W, 30 W models)
Storage Temperature-25 to 65°C
Operating Ambient Humidity25 to 85% (storage humidity: 25 to 90%)
Dielectric Strength
Insulation Resistance100 MΩ min (between all outputs and all inputs/PE terminals) at 500 Vdc
Vibration Resistance10 to 55 Hz, 0.375 mm single amplitude for 2 h each in X, Y, and Z directions
Shock Resistance150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
OtherOutput IndicatorYes (color: green)
EMI
EMSConforms to EN61204-3 high severity levels
Approved Standards
SEMIF47-0200 (200-Vac input)
Weight160 g (6 oz) max
Refer to page 7 for notes 1 to 4.
*
24V Models77% min 80% min
100 to 240 Vac (85 to 264 Vac)
50/60 Hz (47 to 450 Hz)
100V Input0.45 A max0.9 A max
200V Input0.25 A max0.6 A max
100V Input 0.5 mA max
200V Input1.0 mA max
100V Input25 A max (for a cold start at 25°C)
200V Input50 A max (for a cold start at 25°C)
*2
-10 to 15% (with V. ADJ)
2.0% max (5V), 1.5% max (12V, 24V), (with rated input, 0 to 100% load)
100 ms max1000 ms max
(at rated input/output voltage)(at rated input/output voltage)
105 to 160% of rated load current,105 to 160% of rated load current,
automatic reset
*3
voltage drop, intermittent, automatic reset
*4
Yes
No
No
Models with 24V output: possible for up to 2 power supplies
(with external diode) models with 5 or 12V output: not possible
(with no icing or condensation)
3.0 kVac for 1 min (between all inputs and outputs; detection current: 20 mA)
2.0 kVac for 1 min (between all inputs and PE terminals; detection current:
20 mA) 1.0 kVac for 1 min (between all outputs and PE terminals;
detection current: 20 mA)
Conducted
Emissions
Radiated
Emissions
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B
UL: UL508 (Listing; Class 2: Per UL1310), UL60950-1, UL1604
(Class I/Division 2) cUL: CSA C22.2 No.14 (Class 2), No.60950-1, No.213
(Class I/Division 2) EN/VDE: EN50178 (=VDE0160), EN60950-1 (SELV)
(=VDE0805 Teil 1) According to VDE0106/P100, IP20 (except terminal block)
M-2
SPECIFICATIONS
60 AND 90 W RATINGS/CHARACTERISTICS
POWER RATINGS 60 W 90 W
MAINTENANCETOTAL MAINTENANCETOTAL
ITEMTYPESTANDARD MONITORMONITOR STANDARD MONITORMONITOR
Efficiency (Typical)78% min80% min
Voltage
Frequency
Current
*1
*1
100 to 240 Vac (85 to 264 Vac)
50/60 Hz (47 to 450 Hz)
100V input 1.7 A max2.3 A max
200V input 1.0 A max1.4 A max
InputPower Factor —
Harmonic Current Emissions Conforms to EN61000-3-2
Leakage Current
Inrush Current
100V input 0.5 mA max
200V input 1.0 mA max
100V input 25 A max (for a cold start at 25°C)
200V input 50 A max (for a cold start at 25°C)
Voltage Adjustment Range*2-10 to 15% (with V. ADJ)
Ripple 2.0% (p-p) max (at rated input/output voltage)
Input Variation Influence 0.5% max (at 85 to 264 Vac input, 100% load)
OutputLoad Variation Influence
(Rated Input Voltage)
Temperature Variation Influence
1.5% max (with rated input, 0 to 100% load)
0.05%/°C max
Startup Time1000 ms max (at rated input/output voltage)
Hold Time20 ms min (at rated input/output voltage)
Overload Protection105 to 160% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage Protection
Output Voltage Indication
Output Current Indication
*3
Yes
*4
No
*4
No
Peak-Hold Current Indication*4No
Maintenance Forecast
Monitor Indication
Maintenance Forecast
Monitor Output
Additional Total Run Time
Functions Monitor Indication
Total Run Time
Monitor Output
Undervoltage Alarm
Indication
*4
*4
Undervoltage Alarm
Output Terminals
*4
*4
No
No
No
No
No
No
Parallel OperationNo
Series OperationYes for up to 2 power supplies (with external diode)
Operating Ambient Temperature
Refer to the derating curve in engineering data (60, 90, 120, 180, 240, and 480 W
models) (with no icing or condensation)
Storage Temperature-25 to 65°C
Operating Ambient Humidity 25 to 85% (storage humidity: 25 to 90%)
3.0 kVac for 1 min (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVac for 1 min (between all inputs and PE terminals; detection current: 20 mA)
Dielectric Strength
1.0 kVac for 1 min (between all outputs/ alarm outputs and PE terminals;
detection current for standard models: 30 mA, detection current for models with
indication monitor: 20 mA)
Other500 Vac for 1 min (between all outputs and alarm outputs; detection current: 20 mA)
Insulation Resistance
Vibration Resistance
100 MΩ min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 Vdc
10 to 55 Hz, 0.375 mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35 mm single amplitude (5 G max) for 80 min each in X, Y, and Z directions
Shock Resistance150 m/s2, 3 times for 2 h each in ±X, ±Y, and ±Z directions
Output Indicator Yes (color: green)
Conducted
Emissions
EMI
Radiated
Emissions
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A and based
on FCC Class A, Conforms to EN61204-3 EN55011 Class B
Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Models with indication monitor: Conforms to EN61204-3 EN55011 Class A,
Conforms to EN61204-3 EN55011 Class B
EN61204-3 EN55011 Group 1 Class B
EMS Conforms to EN61204-3 high severity levels
SEMIF47-0200 (200 Vac input)
Weight330 g (12 oz) max490 g (17 oz) max
Refer to page 7 for notes 1 to 9.
*
FORECAST RUN TIMEFORECASTRUN TIME
The voltage cannot be adjusted
for the S8VS-09024S