Omega Products PX209 Installation Manual

PX209, PX219, PXM209, PXM219
Pressure Transducers
INSTRUCTION
SHEET
M4085-0407
Shop online at: omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info
COMMON SPECIFICATIONS FOR ALL UNITS
ACCURACY: 0.25% (Linearity, Hysteresis, and Repeatability)
ZERO BALANCE: 2% FS COMPENSATED TEMP: -20 to 80°C
(-4 to 176°F) THERMAL EFFECTS: 0.04% FS over
(-20 to 80°C) (-4 to 176°F) VIBRATION: Withstands 20 g peak,
PRESSURE PORT: 1/4-18 NPT (G1/4 on PXM) BURST PRESSURE: 300% (250% > 200 PSI) PROOF PRESSURE: 150%
VOLTAGE OUTPUT
EXCITATION: 5 Vdc Output - 7 to 35 Vdc 10 Vdc Output - 12 to 35 Vdc @ 15mA (reverse polarity protected) OUTPUT: 0 to 5 Vdc or 0 to 10 Vdc, ±1.5% FSO, 3-wire
ZERO BALANCE: 0 Vdc ±2% FSO OPERATING TEMPERATURE: -65 to 250°F OUTPUT RESISTANCE: 100 WIRING: +EXC Red/Pin 1; COMMON Black/Pin 2;
+OUT White/Pin 3
WIRING PIN CONNECTOR
To access the terminals inside the DIN connector proceed as follows:
1. Remove the screw at the top of the connector.
2. Separate the DIN connector from the transducer.
3. Insert a small blade screwdriver into the slot provided and pry the DIN connector apart.
4. After wiring the terminals, snap the DIN connector back together.
5. Mount the DIN connector to the transducer (using the rubber gasket in between), observing the blade orientations.
6. Insert the screw at the top of the DIN connector and tighten.
RESPONSE TIME: 2 msec typ GAGE TYPE: Diffused silicon strain gages ELECTRICAL Miniature DIN connection
CONNECTION: screw terminals or 36" pigtail WETTED PARTS: 316 SSTL, borosilicate glass, silicon
nitrite, aerospace epoxy
CASE: Stainless steel FATIGUE: 100 million cycles FS WEIGHT: 4.5 oz (128 g) max
CURRENT OUTPUT
EXCITATION: 24 Vdc (7 to 35 Vdc) reverse polarity protected
OUTPUT: 4 to 20 mA (2-wire) ±1% FSO ZERO BALANCE: 4 mA ±2% FSO OPERATING -54 to 121°C
TEMPERATURE: (-65 to 250°F) MAX LOOP RESISTANCE: 50 x (supply voltage - 10) WIRING: +Red/Pin 1; Black/Pin 2
WARNING! READ BEFORE INSTALLATION!
Fluid hammer and surges can destroy any pressure transducer and must always be avoided. A pressure snubber should be installed to eliminate the damaging hammer affects. Fluid hammer occurs when a liquid flow is suddenly stopped, as with quick closing solenoid valves. Surges occur when flow is suddenly begun, as when a pump is turned on at full power or a valve is quicky opened.
Liquid surges are particularly damaging to pressure transducers if the pipe is originally empty. To avoid damaging surges, fluid lines should remain full (if possible), pumps should be brought up to power slowly, and valves opened slowly. To avoid damage from both fluid hammer and surges, a surge chamber should be installed, and a pressure snubber should be installed on every transducer.
Symptoms of fluid hammer and surge's damaging effects:
1. Pressure transducer exhibits an output at zero pressure (large zero offset). If zero offset is less than 10% FS, user can usually re-zero meter, install proper snubber and continue monitoring pressures.
2. Pressure transducer output remains constant regardless of pressure.
3. In severe cases, there will be no output.
DIMENSIONS WIRING
G 1/4
219
18.79 (0.74)
53.59 ±0.5
(2.11 ±0.02)
34.26 MAX. (1.35)
9mm DIN 43650
WITH PG7 GLAND
209/219
VOLTAGE
POWER SUPPLY
METER
++–
BLACK (COMMON)
WHITE (+ OUTPUT)
RED (+ EXC)
PIN #
1
2
TRANSDUCER
3
1/4 NPT
19.8
(0.78)
53.59 ±0.5
(2.11 ±0.02)
2 COND.
209
DIMENSIONS mm (in)
Cable shielding must be terminated at the meter to earth ground to comply with CE.
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 37 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal three (3) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibra­tion; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of pur­chaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2007 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
WARRANTY/DISCLAIMER
RETURN REQUESTS/INQUIRIES
RETURNS, please have
FOR NON-WARRANTY REPAIRS, OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the
product, and
3. Repair instructions and/or specific problems
relative to the product.
consult
POWER SUPPLY
++–
209/219
CURRENT
METER
OMEGAnet®Online Service Internet e-mail
omega.com info@omega.com
RED (+)
BLACK (–)
PIN #
1
TRANSDUCER
2
Servicing North America:
U.S.A.:
ISO 9001 Certified
Canada: 976 Bergar
For immediate technical or application assistance:
U.S.A. and Canada:
Mexico:
One Omega Drive, Box 4047 Stamford, CT 06907-0047
Tel: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
Laval (Quebec) H7L 5A1, Canada Tel: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca
Sales Service: 1-800-826-6342/1-800-TC-OMEGA Customer Service: 1-800-622-2378/1-800-622-BEST Engineering Service: 1-800-872-9436/1-800-USA-WHEN
En Espan˜ol: (001) 203-359-7803 FAX: (001) 203-359-7807 e-mail: espanol@omega.com info@omega.com.mx
®
®
®
Servicing Europe:
Czech Republic:
Germany/Austria:
United Kingdom:
ISO 9002 Certified Northbank, Irlam, Manchester
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, human applications.
Frystatska 184, 733 01 Karviná, Czech Republic Tel: +420 (0)59 6311899 FAX: +420 (0)59 6311114 Toll Free: 0800-1-66342 e-mail: info@omegashop.cz
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany Tel:+ 49 (0)7056 9398-0 FAX: +49 (0)7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: info@omega.de
One Omega Drive, River Bend Technology Centre
M44 5BD United Kingdom Tel: +44 (0)161 777 6611 FAX: +44 (0)161 777 6622 Toll Free in United Kingdom: 0800-488-488 e-mail: sales@omega.co.uk
Loading...