Omega Products PX138-001D5V Installation Manual

Page 1
General Description
The OMEGA®PX138 Series uses state-of-the-art micro-machined silicon pressure sensors in conjunction with stress-free packaging techniques to provide highly accurate, temperature-compensated pressure transducers for the most demanding applications. When operated from an 8 Vdc regulated power source, they provide a 1 to 6 Vdc output. Other regulated voltages from 7 to 16 volts can be used, but the output will change in proportion to the excitation.
PX138 pressure transducers are available in absolute and differential models. Differential models can also be used to measure gage pressure or vacuum by simply varying the pressure connections. To measure gage pressure, make the pressure connection to port B and leave port A open to the atmosphere. For vacuum measurement, connect to port A and leave port B open. When using absolute models, connect to port A.
Available Models
Differential
Pressure Ranges Model
±0 to 0.3 psi PX138-0.3D5V ±0 to 1 psi PX138-001D5V ±0 to 5 psi PX138-005D5V ±0 to 15 psi PX138-015D5V ±0 to 30 psi PX138-030D5V ±0 to 100 psi PX138-100D5V
Absolute
Pressure Ranges Model
0 to 15 psia PX138-015A5V 0 to 30 psia PX138-030A5V 0 to 100 psia PX138-100A5V
PX138 Pinouts
1 = + Excitation (Black dot is next to pin 1) 2 = Common 3 = + Signal 4 = No Connection
PX138 Series
Pressure Sensors
1
INSTRUCTION
SHEET
M2002/1008
Shop online at: omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info
Page 2
NOTE
WARNING
Read Before Installation
Fluid hammer and surges can destroy any pressure transducer and must always be avoided. A pressure snubber should be installed to eliminate damaging hammer effects. Fluid hammer occurs when a liquid flow is suddenly stopped, as with quick-closing solenoid valves. Surges occur when flow is suddenly begun, as when a pump is turned on at full power or a valve is quickly opened. Liquid surges are particularly damaging to pressure transducers if the pipe is originally empty. To avoid damaging surges, fluid lines should remain full (if possible), pumps should be brought up to power slowly, and valves should be opened slowly. To avoid damage from both fluid hammer and surges, a surge chamber and a pressure snubber should be installed on every transducer. Symptoms of fluid hammer and surge’s damaging effects:
1. Pressure transducer exhibits an output at zero pressure (large zero offset). If zero offset is less than 10% FS, user can usually re-zero meter, install proper snubber, and continue monitoring pressures.
2. Pressure transducer output remains constant regardless of pressure.
3. In severe cases, there will be no output.
PX138 Series Pressure Sensors
Unpacking
Remove the Packing List and verify that you have received all equipment, including the following:
PX138 Series Pressure Sensor Operator’s Manual
If you have any questions about the shipment, please call the OMEGA Customer Service Department at:
1-800-622-2378 or 203-359-1660. We can also be reached on the Internet at omega.com e-mail: info@omega.com
When you receive the shipment, inspect the container and equipment for any signs of damage. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent.
The carrier will not honor any damage claims unless all shipping material is saved for inspection. After examining and removing contents, save packing material and carton in the event reshipment is necessary.
2
Page 3
Dimensions
Specifications
Excitation Voltage: 8 Vdc (7 to 16 limits)
Output: 1 to 6 V (@ 8 V excitation)
Linearity and Hysteresis: ±0.1% FS typical, 0.5% max.
(0.5% typ., 1% max. for 0.3 psi range)
Repeatability: ±0.1% FS typical, 0.3% max.
Zero Balance Diff: 3.5 Vdc ±0.05 Vdc (@ 8 V excitation)
Abs: 1 Vdc ±0.05 Vdc (@ 8 V excitation)
Storage Temperature: -40 to 125°C (-40 to 257°F)
Compensated Temp. Range: 0 to 50°C (32 to 122°F)
Zero Temp. Effects: ±0.5% FS (±1% FS for 0.3 psi)
Span Temp. Effects: ±0.5% FS (±1% FS for 0.3 psi)
Proof Pressure: >3X FS pressure
Burst Pressure: >5X FS pressure
Common Mode Pressure: 50 psi
Media Compatibility: For use with clean, dry, non-corrosive gases
PX138 Series Pressure Sensors
1. + Excitation
2. Common
3. + Signal
4. No Connection
3
6.4
(0.25)
0.356 x 0.508
(0.014 x 0.020)
4 PLACES FOR ELECTRICAL CONNECTION
DIMENSIONS: mm (in)
Page 4
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, human applications.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY
RETURNS, please have the following informa-
tion available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for cur­rent repair charges. Have the following information avail­able BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to
the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2008 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or
reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
Servicing North America:
U.S.A.: One Omega Drive, Box 4047
ISO 9001 Certified
Stamford, CT 06907-0047 Tel: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
Canada: 976 Bergar
Laval (Quebec) H7L 5A1, Canada Tel: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca
For immediate technical or application assistance:
U.S.A. and Sales Service: 1-800-826-6342/1-800-TC-OMEGA
®
Canada: Customer Service: 1-800-622-2378/1-800-622-BEST
®
Engineering Service: 1-800-872-9436/1-800-USA-WHEN
®
Mexico: En Espan˜ol: (001) 203-359-7803 e-mail:espanol@omega.com
FAX: (001) 203-359-7807 info@omega.com.mx
OMEGAnet®Online Service Internet e-mail
omega.com info@omega.com
Servicing Europe:
Czech Frystatska 184, 733 01 Karviná, Czech Republic Republic: TEL: +420 (0)59 6311899
FAX: +420 (0)59 6311114 Tol Free: 0800-1-66342 e-mail: info@omegashop.cz
Germany/ Daimlerstrasse 26, D-75392 Deckenpfronn, Germany Austria: Tel: +49 (0)7056 9398-0
FAX: +49 (0)7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: info@omega.de
United One Omega Drive, River Bend Technology Centre Kingdom: Northbank, Irlam, Manchester
ISO 9001 Certified
M44 5BD United Kingdom Tel: +44 (0)161 777 6611 FAX: +44 (0)161 777 6622 Toll Free in United Kingdom: 0800-488-488 e-mail: sales@omega.co.uk
Loading...