3. 20. SET HOST WATCHDOG TIMER & SAFETY V ALUE3-24
3. 21. READ HOST WATCHDOG TIMER & SAFETY V ALUE3-26
3. 22. HOST IS OK 3-28
4. DATA FORMAT..............................................................................................4-1
4. 1. UNIT CONVERSION4-1
4. 2. ENGINEERING UNITS4-1
4. 3. PERCENT OF FSR 4-1
4. 4. HEXDECIMAL FORMAT4-2
4. 5. SUMMARY OF DATA FORMAT4-3
5. ANALOG OUTPUT CALIBRATION..........................................................5-1
5. 1. CALIBRATION5-1
5. 2. ANALOG OUTPUT MODULE CALIBRATION5-1
Contents i
1. Introduction
1. 1. About the OMR Analog Output Modules
The OMR Series provides analog output modules, which can convert the digital command to analog. The basic
features of each module are shown here.
• OMR-6021 : analog signal output module with safety functions
• OMR-6024 : 4 channel analog output module
1. 2. Overview of OMR -6021
What is OMR-6021 ?
OMR-6021 is an analog signal output module. It receives the digital command from host computer through
RS-485 network. The format of the digital value can be engineering units, hexadecimal format or percentage of
full-scale range(FSR). A microprocessor is used to convert the digital command to digital value to send to DAC.
The DAC converts the digital value into analog form. The analog output can be either voltage or current output.
The OMR -6021 is designed for safety. It provides many safety functions such as isolation, watchdog, and power
on safe value. The opto -isolators provide 5000Vrms isolation voltage to isolate the digital section and the remote
controlled analog equipments. The damage of power surges is avoided.
Another safety function is the watchdog. Whenever the host is loss contact with the remote OMR module, or the
microprocessor is down, the module will reset itself and send the safety value to the analog output therefore the
industry safety is guarantee. The safety value / power-up value can be set by configuration software.
The analog output can be read back through the module‘s ADC. Which can monitor the ’real‘ output of the
device. The host can check the digital command and the real output to avoid short circuits. The slew rate of the
output signal is also controllable by software.
Features of OMR-6021
• One uni-polar analog output channel
• Two sets of differential current and voltage output terminals
• Versatile digital signal format
• Programmable host watchdog timer for host failure protection
• Internal watchdog timer for device failure protection
• Accuracy: ±0.1% of FSR for current output
±0.2% of FSR for voltage output
Initialization & Installation 1-1
• Unit Convertion: V or mA
• Output range:
Voltage output: 0 to 10 V (uni-polar)
Current output: 0 to 20 mA
4 to 20 mA
• Maximum Sampling Rate: 100 samples /sec
• Slew rate:
Voltage output: 0.0625 to 64 V/sec
Current output: 0.125 to 128 mA/sec
• Internal Current Load Resistor: 500Ω (%1)
² Read back Analog Input
• Accuracy: ±0.2% of FSR
² Isolation
• Isolation voltage: 5000 Vrms
² Watchdog Function
• Module internal watchdog timer : 150 ms
• Power failure threshold : 4.65 V
• Host programmable watchdog : 100 ms ~ 25.500 sec
² Power
• Power supply : +10V to +30V
• Power consumption : 1.0W
Pin Definitions of OMR-6021
Pin # Signal Name Description
1 +IOUT Positive Current Output Terminal
2 -IOUT Negative Current Output Terminal
3 +VOUT Positive Voltage Output Terminal
4 -VOUT Negative Voltage Output Terminal
6 Default* Initial state setting
7 (Y) DATA+ RS-485 series signal, positive
8 (G) DATA - RS-485 series signal, negative
9 (R) +Vs Power supply, +10V~+30V
10 (B) GND Ground
1-2 Initialization & Installation
(Current/Voltage)
O
Code
Output Range
303132
0 ~ 10V1120
A Look at OMR-6021 & Pin Assignment
OMR-6021
+I
-
O
IO
Analog Output
0 ~20 mA
4 ~ 20 mA
D
+V
O
U
EF
A
V
U
(G
(Y
)D
)D
A
A
T
T
(B)
10
(R
G
)+
N
Initialization & Installation 1-3
Functional Block Diagram of OMR-6021
Data+
RS-485
Rec/DRv
Data-
RS-485
Terminator
Watchdog / Power Failure
Supervisor
+10V ~ +30 V
GND
EEPROM
Power
Regulator
Micro
Processor
+5V
GND
Photo
Isolators
DC to DC
Convertor
(12 bits)
*Defalut Setting
(1 bit Digital In)
DAC
Isolated Power
Isolated Ground
Voltage Output
V to I
Current Output
VOUT +
VOUT -
IOUT +
IOUT -
1. 3. Overview of OMR -6024
What is OMR-6024 ?
OMR-6024 is a 4-channel bipolar analog signal output module. It receives the digital command from host
computer through RS-485 network. A microprocessor is used to convert the digital command to digital value to
send to DAC. The DAC converts the digital value into analog form.
The OMR -6024 is designed for safety. It prov ides many safety functions such as isolation, watchdog, and power
on safe value. The opto -isolators provide 5000Vrms isolation voltage to isolate the digital section and the remote
controlled analog equipments. The damage of power surges is avoided.
Another safety function is the watchdog. Whenever the host is loss contact with the remote OMR module, or the
microprocessor is down, the module will reset itself and send the safety value to the analog output therefore the
industry safety is guarantee. The safety value / power-up value can be set by configuration software.
Features of OMR-6024
• 4 channel bipolar analog output
• Programmable host watchdog timer for host failure protection
• Internal watchdog timer for device failure protection
• Host programmable watchdog : 100 ms ~ 25.500 sec
² Power
• Power supply : +10V to +30V
• Power consumption : 2.5W
Pin Definitions of OMR-6024
Pin # Signal Name Description
1 DI4 Digital input channel 4
2 DI3 Digital input channel 3
3 DI2 Digital input channel 2
4 DI1 Digital input channel 1
5 DI0 Digital input channel 0
6 Default* Initial state setting
7 (Y) DATA+ RS-485 series signal, positive
8 (G) DATA - RS-485 series signal, negative
9 (R) +Vs Power supply, +10V~+30V
10 (B) GND Ground
11 VOUTA+ Positive Voltage Output A Terminal
12 AGND Negative Voltage Output A Terminal
13 VOUTB+ Positive Voltage Output B Terminal
14 BGND Negative Voltage Output B Terminal
15 VOUTC+ Positive Voltage Output C Terminal
16 CGND Negative Voltage Output C Terminal
17 VOUTD+ Positive Voltage Output D Terminal
18 DGND Negative Voltage Output D Terminal
19 DI6 Digital input channel 6
20 DI5 Digital input channel 5
Initialization & Installation 1-5
A Look at OMR-6024 & Pin Assignment
DI5
DI6
DGND
VOUTD+
CGND
VOUTC+
BGND
VOUTB+
AGND
OMR-6024 4-CH
Analog Output
CodeSignal
33
±10V
VOUTA+
DI4
DI3
DI2
DI1
DI0
DEFAULT*
(Y)DATA+
(G)DATA-
(R)+Vs
(B)GND
1-6 Initialization & Installation
Functional Block Diagram of OMR-6024
Data+
RS-485
Rec/DRv
Data-
RS-485
Terminator
Watchdog / Power Failure
Supervisor
+10V ~ +30 V
GND
EEPROM
Power
Regulator
Micro
Processor
+5V
GND
Photo
Isolators
DC to DC
Convertor
(12 bits)
*Defalut Setting
(1 bit Digital In)
DIØ…… DI6
DAC
Isolated Power
Isolated Ground
Voltage Output
•VOUTA+
AGND
•VOUTB+
BGND
•VOUTC+
CGND
•VOUTD+
DGND
Initialization & Installation 1-7
2. Initialization & Installation
2. 1. Software Installation
1. If you have already installed “OMR Administration” then skip other steps.
2. Backup your software diskette.
3. Insert “OMR Administration” diskette into floppy drive A:
4. Change drive to A:
5. Installation command syntax
INSTALL drive:
drive name is C to Z.
Example 1 : install to drive C:
A:\> INSTALL C:
Example 2 : install to drive F:
A:\> INSTALL F:
6. OMR Administration Utility will be installed in the directory C: \OMR
2. 2.Initializing a Brand New Module
Objective of Initializing a Brand New OMR
All OMR modules, except OMR-6520 and OMR-6510, in a RS -485 network must have a unique address ID.
Every brand-new OMR has a factory default setting as following:
• Address ID is 01.
• Baud rate is 9600 bps
• Check-sum disable
• Host Watchdog timer is disable
Therefore, to configure the brand new OMR before using is necessary to av oid conflicting address. The baud rate
may also be changed according to user‘s requirements.
The initialization procedures of a brand new OMR are shown in the following sections.
Default State
The OMR modules must be set at Default State when you want to change the default settings, including the ID
address, baud rate, check-sum status etc. All OMR modules have a special pin labeled as DEFAULT*. The
module will be in Default State if the DEFAULT* pin is shorted to ground when power ON. Under this stat e, the
default configuration is set as following:
• Address ID is 00.
• Baud rate is 9600 bps.
• Check-sum disable.
• Watchdog timer is disabling.
Therefore, the configuration of the host and the module can be easily set identically and initializing a module will
be possible no matter what configuration is set under operating state.
Initialization Equipments
2-1 Initialization & Installation
• Host computer with an RS -232 port.
+Vs GND
Converter
• An installed RS -485 module (OMR-6520) with 9600-baud rate.
• The brand new OMR module
• Power supply (+10 to +30 VDC) for OMR modules
• Administrating utility software
Initialization Procedure
1. Power off the host computer and the installed OMR -6520. Be sure of the baud rate of the OMR -6520 is 9600
bps.
2. Connect a brand new OMR module with the RS -485. Set the module in Default State by shorting the
DEFAULT* pin. Refer to Figure 2.1 for detailed wiring.
3. Power on the host computer.
4. Power on the power supply for OMR modules.
5. Use the OMR Administrating utility to configure the address ID, Baud rate and check-sum status of the
module.
Initialization Wiring
Host
Computer
RS-232
Local Power Supply
+10 V to +30 V
OMR-6520
RS-232/RS-485
DATA +
DATA -
+Vs GND
New
OMR
module
DATA+
DATA Default*
+Vs GND
Figure 2-1 Layout for Initialization the OMR module
2. 3. Install a New OMR to a Existing Network
Equipments for Install a New Module
• A existing OMR network
• New OMR modules.
• Power supply (+10 to +30 VDC).
Installing Procedures
1. Configure the new OMR module according to the initialization procedure in section 2.2.
2. The baud rate and check-sum status of the new module must be identity with the existing RS-485 network.
The address ID must not be conflict with other OMR modules on the network.
3. Power off the OMR power supply of the existing RS -485 network.
4. Power off the host computer.
5. Wire the power lines for the new OMR with the existing network. Be careful about the signal polarity as
wiring.
6. Wire the RS-485 data lines for the new OMR with the existing network. Be careful about the signal polarity
as wiring.
7. Wire to the input or output devices. Refer to section 2.4 for illustrations.
2-2 Initialization & Installation
+IOUT
Differential Current Output Channel of OMR-6021
DAC
-IOUT
Current Loading
+VOUT
Differential Voltage Output Channel of OMR-6021
DAC
-VOUT
Voltage Loading
+VOUT
Differential Voltage Output Channel of OMR-6024
DAC
-VOUT
Voltage Loading
8. Power on the host computer.
9. Power on the OMR local power supply.
10. Use the OMR administration utility to check entire network.
2. 4. Application Wiring for OMR -6021
Differential Current Output
Differential Voltage Output
2. 5. Application Wiring for OMR -6024
Differential Voltage Output
2-3 Initialization & Installation
Response :
3. Command Set
3. 1. Command and Response
Introduction
The OMR command is composed by numbers of characteristics, including the leading code, address ID, the
variables, the optional check-sum bytes, and a carriage return to indicate the end of a command. The host
computer can only command only one OMR module except those synchronized commands with wildcard
address “**”. The OMR may or may not give response to the command. The host should check the response
to handshak e with the modules.
Document Conventions
The following syntax conventions describe the OMR commands in this manual.
(Leading Code) Leading Code is the first characteristic of the OMR
command. All OMR commands need a command
leading code, such as %,$,#,@, ...etc.
1- character
(Addr) Module’s address ID, the value is in the range of 00 - FF
(Hex).
2- character
(Command
Variable)
[Data] Some commands need additional data.
[Checksum] Checksum in brackets indicate optional parameter,
< > Identifies a control code character, such as <CR> for
Command codes or value of variables.
Variable length
Variable length
only if checksum is enabled then this field is required.
Note : 1. There is no spacing between the command words and the checksum characters.
2. Every command follows a <CR> carriage return for ending.
3. The checksum characters are optional.
Response of OMR Commands
The response message depends on versatile OMR command. The response is composed with a few
characteristics, including leading code, variables, and carriage return for ending. There are two categories of
leading code for response message, ”!“ or ”>“ means valid command and ”?“ means invalid. By checking the
response message, user can monitor the command and verify if it is valid or not.
Note : Under the following conditions, there will have no response message.
1. The specified address ID is not exist.
2. Syntax error.
3. Communication error.
4. Some special commands does not have response message.
3-2 Initialization & Installation
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.