Omega Products OM-CP-State101A User Manual

State Data Logger Part of the NOMAD®Family
OM-CP-STATE101A
Interfaces to Contact Closures
or TTL Inputs up to 30V
10 Year Battery Life4 Hz Second Reading RateMultiple Start/Stop FunctionUltra High Speed DownloadMemory WrapBattery Life IndicatorOptional Password ProtectionField Upgradeable
OM-CP-STATE101A, shown larger than actual size.
The OM-CP-STATE101A is one of our newest data loggers. It is part of a new series of low cost, state-of­the-art data logging devices that has taken the lead in offering the most advanced, low cost, battery powered data loggers in the world today.
The OM-CP-STATE101A offers a 10 year battery life, 4 Hz reading rate, a multiple start/stop function, ultra-high speed download capability, 406,323 reading storage capacity, optional memory wrap, battery life indicator, optional password protection and more.
The OM-CP-STATE101A senses input transitions or contact closures from external sources such as transducers and/or state initiators and records the time and input state of the device when a transition occurs. Once activated the data logger senses and records transition or state changes at the input. The device’s real-time clock ensures that all data is time and date stamped. The storage medium is non-volatile solid state memory, providing maximum data security even if the battery becomes discharged.
The device can be started and stopped directly from your computer and its small size allows it to fit almost anywhere.
1
To Order, Call or Shop Online at omega.com
Data retrieval is simple. Simply plug it into an available USB port and our user-friendly software does the rest.
The software converts a PC into a real-time strip chart recorder. Data can be printed in graphical and tabular format or exported to a text or Microsoft Excel file.
The OM-CP-STATE101A was designed with our customers in mind. We offer free firmware upgrades for the life of the product so that data loggers already deployed in the field can grow with new technological developments. Units do not need to be returned to the factory for upgrades. The user can do this automatically from any PC.
Specifications
Input Connection:
Removable screw terminal
Input Range: 0 to 30V Input Low: <0.4V Input High: >2.8V Internal Weak Pull-Up: <60µA Input Impedance: >60 k Time Resolution: 4 Hz (reading
rate selectable in software) Reading Rate: 4 Hz to 1 every
24 hours Memory: 406,323 readings;
software configurable memory wrap
Wrap Around: Yes Start Modes:
• Immediate start
• Delay start up to 18 months
• Multiple pushbutton start/stop
Multiple Start/Stop Mode: Start and stop the device multiple times without having to download data or communicate with a PC
Multiple Start/Stop Mode Activation:
To Start the Device:
Press and hold the pushbutton for 5 seconds, the green LED will flash during this time. The device has started logging.
To Stop the Device:
Press and hold the pushbutton for 5 seconds, the red LED will flash for three seconds and then the green LED will flash for two seconds. The device has stopped logging.
Real Time Recording: The device may be used with PC to monitor and record data in real-time
LED Functionality:
Green LED Blinks: 10 second
rate to indicate logging 15 second rate to indicate delay start mode
Red LED Blinks:
10 second rate to indicate low battery and/or full memory
SM
OM-CP-STATE101A
Average battery life vs. reading
rate the OM-CP-STATE101A
recording in a 25°C environment.
OM-CP-WATERBOX101A, optional weatherproof enclosure for data logger, shown smaller than actual size.
Password Protection: An optional
password may be programmed into the device to restrict access to configuration options. Data may be read out without the password.
Engineering Units: Native measurement units can be scaled to display measurement units of another type such as on/off, open/closed and more.
Battery Type: 3.6V lithium battery (included); user replaceable
Battery Life: 10 years typical, dependent upon frequency and duty cycle
Time Accuracy:
±1 minute/month [at 20ºC (68ºF), stand alone data logging]
Computer Interface: USB (interface cable required); 115,200 baud
Software: XP SP3/Vista/Windows 7 (32 and 64-bit)
Operating Environment:
-40 to 80ºC (-40 to 176ºF), 0 to 95% RH non-condensing
Dimensions:
Data Logger:
36 H x 56 W x 16 mm D (1.4 x 2.2 x 0.6")
Waterbox Enclosure:
74 H x 148 W x 39 mm D (2.9 x 5.8 x 1.5")
OM-CP-IFC200, Windows
data in graphical or tabular format
Weight: 24 g (0.9 oz) Materials:
Data Logger:
ABS Plastic
Waterbox Enclosure:
Black anodized aluminum
®
software displays
AVAILABLE FOR FAST DELIVERY!
To Order
Model No. Description OM-CP-STATE101A State data logger OM-CP-IFC200 Windows software and 3.7 m (12') USB interface cable OM-CP-BAT105 Replacement 3.6V lithium battery OM-CP-WATERBOX101A Weatherproof NEMA 4 (IP65) enclosure for data logger
Comes complete with 3.6V lithium battery. USB cable and operator’s manual are included with the OM-CP-IFC200 Windows software (required to operate the data logger and sold separately).
Ordering Example: OM-CP-STATE101A, state data logger and OM-CP-IFC200 Windows software
To Order, Call or Shop Online at omega.com
visit omega.com/om-cp-state101a for pricing and details
SM