Machinery On/Off Data Logging System  
Part of the NOMAD
®
 Family 
OM-CP-MOTOR101A 
Series
U Measure and Record On/Off 
Status of Motors, Fans, Pumps 
and Other Equipment
U 150 mA Trip Point 
U Compatible up to 200 A 
U Real Time Operation 
U Useful for Energy Audits and 
Time Studies
U Complete Kit Includes Data 
Logger and Current Switch 
with Mounting Bracket
Mounting 
bracket
OM-CP-MOTOR101A,  
data logger and current switch.
Current switch
Data logger
The OM-CP-MOTOR101A Series 
measures and records on and off 
status changes for motors or other 
equipment drawing up to 200 Amps. 
Simply route the current carrying wire 
for the equipment being monitored 
through the current switch. The state 
change occurs when the current 
switch exceeds the 150 mA set point. 
This allows for most basic equipment 
to be monitored. The current switch 
monitors whether there is current 
passing through a wire around which 
it is attached. 
When the current exceeds 150 mA, 
the output changes and provides a 
voltage for the OM-CP-MOTOR101A 
to measure. The device can hold 
up to 406,323 state changes, but 
memory will only be used if the 
status has changed. The device can 
be programmed to check for status 
changes 4 times per second up to 
once every 24 hours. 
Data retrieval is simple. Simply plug 
it into an available USB port and 
our user-friendly software does the 
rest. The software converts a PC 
into a real-time strip chart recorder. 
Data can be printed in graphical and 
tabular format or exported to a text 
or Microsoft Excel
®
 file. The storage 
medium is non-volatile solid state 
memory, providing maximum data 
security even if the battery becomes 
discharged.
OM-CP-MOTOR101A, 
data logger and 
current switch, shown 
smaller than.
OM-CP-IFC200 Windows software displays data  
in graphical or tabular format, included with the 
OM-CP-MOTOR101A-KIT
To Order, Call  or Shop Online at omega.com
SM
1

Specifications
Amperage Range: 
0.15 to 200 A 
Trip Point: 0.15A (150 mA) 
fixed (200 mA AC for 50 Hz 
operation)
Status Output (Max): 
N.O. 1.0 A @ 30 Vac/Vdc
Current Switch Housing: Split core 
Reading Rate: 4 Hz to 1 every 24 hr 
Memory: 406,323 readings; 
software configurable memory wrap
Wrap Around: Yes 
Start Modes: Immediate start, 
delay start up to 18 months,  
multiple pushbutton start/stop
Multiple Start/Stop Mode: Start 
and stop the device multiple times 
without having to download data or 
communicate with a PC
Multiple Start/Stop Mode 
Activation: 
 To Start the Device: 
 Press and hold the pushbutton 
 for 5 seconds, the green LED will  
 flash during this time; the device  
 has started logging
 To Stop the Device: 
 Press and hold the pushbutton 
 for 5 seconds, the red LED will  
 flash for three seconds and then  
 the green LED will flashfor two  
 seconds; the device has stopped  
 logging
Real Time Recording: The device 
may be used with PC to monitor and 
record data in real-time
LED Functionality: 
 Green LED Blinks: 10 second  
 rate to indicate logging, 15 second 
 rate to indicate delay start mode
 Red LED Blinks: 10 second 
 rate to indicate low battery and/or  
 full memory
Password Protection: 
An optional password may be 
programmed into the device to 
restrict access to configuration 
options; data may be read out 
without the password
Engineering Units: Native 
measurement units can be scaled  
to display measurement units of  
another type such as on/off, open/ 
closed and more
Battery Type: 3.6V lithium battery 
included; user replaceable
Battery Life: 10 years typical, 
dependent upon frequency 
and duty cycle
Time Accuracy: ±1 minute/month 
(at 20ºC/68ºF, stand alone data 
logging)
OM-CP-MOTOR101A shown monitoring 
current in an electrical panel.
Computer Interface: USB 
(interface cable required);  
115,200 baud
Software: XP SP3/Vista/Windows® 7 
Operating Environment:
-15 to 40ºC (5 to 104ºF),  
10 to 90% RH non-condensing
Dimensions (Data Logger): 
36 x 56 x 16 mm (1.4 x 2.2 x 0.6")
Current Switch: 
54 x 89 x 26 mm (2.1 x 3.5 x 1.0")
Weight: 113 g (4 oz)
With OM-CP-IFC200: 255 g (9 oz)
Materials: ABS plastic
 To Order
 Visit omega.com/om-cp-motor101a for Pricing and Details
 Model No.  Description
 OM-CP-MOTOR101A-KIT  Machinery on/off status data logging system, includes data logger, current switch and 
   OM-CP-IFC200 Windows software and USB interface cable
 OM-CP-MOTOR101A  Machinery on/off status data logging system, includes data logger, current switch; 
   (OM-CP-IFC200 Windows software and USB interface cable sold separately)
 OM-CP-IFC200  Windows software and 1.8 m (6’) USB interface cable  
 OM-CP-BAT105  Replacement battery
Comes complete with 3.6 V lithium battery and operator’s manual. OM-CP-MOTOR101A-KIT includes OM-CP-IFC200 Windows software and  
USB interface cable.
Ordering Example: OM-CP-MOTOR101A-KIT, data logging system, includes data logger, current switch and OM-CP-IFC200 Windows 
software and USB interface cable.
2
To Order, Call  or Shop Online at omega.com
SM
®