An ultrasonic sound wave is pulsed two times per second fromthe base of the transducer. The sound wave reflects against theprocess medium below and returns to the transducer. Themicroprocessor based electronics measure the time of flightbetween the sound generation and receipt, and translates thisfigure into the distance between the transmitter and processmedium below.
LOST Signal:
A reading of LOST in the display of the
LVU-201
series indi-cates the transmitter is not receiving a valid return signal. IfLOST appears, please check the following troubleshootingitems:
1.
Beam cone interference such as the side wall, ladders,
seams, rungs or pipes within the LVU-201 series beam cone.
2.
Proper installation such that the LVU-201 series is installed
from
level and free
interference from the installation fitting
or flange.Sufficient power being supplied to the LVU-201 series. The
3.
transmitter requires 12-36 VDC power with a minimum sup-ply of 25
4.
Proper programming of the MAXR or MINR function. For
mA.
best results, set the MAXR function as the distance from thebottom of the tank to the bottom of the transmitter. Also setthe MTNR distance above the highest level in the tank.
MNR
u1wuy.r
optimum performance,greatest setting.
5.
Make sure that the transmitter is not installed at an angle.
set the
value to
Even a 5 degree offset can reduce the signal return strengthgreatly.
I
For
it:k
162024
Supply Voltage
263236
(WC)
A Warning
A
The LVU-201 series is a loop powered device. The loadshould never exceed 900 Ohms.
When installing the LVU-201 series, never tighten the trans-mitter from the body. Always use the wrench flat locatedabove the threads.
Page 3
SAFETY PRECAUTIONS
1
Step Two
DEFINITIONS
)
Step
Three
h
About this Manual:
PLEASE READ THE ENTIRE MANUAL PRIOR TOINSTALLING OR USING THIS PRODUCT. This manualincludes information on all versions of the continuous ultrasoniclevel transmitter from Omega; model LVU-201. Please refer to thepart number located on the sensor label to verify the exact modelwhich you have purchased.
User’s Responsibility for Safety:
h
Omega manufactures a wide range of liquid level sensors and tech-nologies. While each of these technologies are designed to operatein a wide variety of applications, it is the user’s responsibility toselect a technology that is appropriate for the application, install itproperly, perform tests of the installed system, and maintain allcomponents. The failure to do so could result in property damageor
serious injury.
h
Proper Installation and Handling:
Because this is an electrically operated device, onlytrained staff should install and/or repair this product. Use a proper
sealant with all installations.Never overtighten the transmitter
within the fitting. Always check for leaks prior to system start-up.
A
Wiring and Electrical:
A supply voltage of 12-36 VDC is used to power the LVU-201series transmitter. The sensor systems should never exceed a max-imum of 36 VDC for the LVU-20 I series.sensor should bcnational, state, and local codes.
$
Temperature and Pressure:
The
LVU-201 series is designed for use in application temperaturesfrom -40 to 30 psi
Material Compatibility:
d
The continuous ultrasonic level transmitter, LVU-201 series, ismade of two materials. The enclosure is of Polypropylene (PP) andthe transducer is made of Polyvinylidene Fluoride (PVDF). Makesure that the model which you have selected is chemically compat-ible with the application liquids. liquid-resistant when installed properly, it is not designed to beimmersed. mally come into contact with fluid.
1
Flammable, Explosive and Hazardous Applications:
DO NOT USE THE LVU-201 SERIES TRANSMITTER INCLASSIFIED HAZARDOUS LOCATIONS.
ti
Make a Fail-Safe System:
Design a fail-safe system that accommodates the possibility oftransmitter or power failure. In critical applications, Omega rec-ommends the use of redundant backup systems and alarms in addi-tion to the primary system.
“C@
performed
(-40 “F) to 60
25 “C, derated
It
should be mounted in such a way that it does not nor-
in accordance with all applicable
“C
(140 “F), and for use at pressures up
@
1.667 psi per
While
Electrical wiring of the
“C
above 25 “C.
the transmitter housing is
properly-
mA
EC4:
The 4 201 series. The EC4 is the distancefrom the bottom of the LVU-201 to
mA
the 4
measured in either inches or cen-timeters on the display. The EC4 set-ting is typically greater than theEC20 setting and is equal to the dis-tance from the bottom of the trans-ducer to the bottom of the tank.
EC20: The 20
LVU-201 series. The EC20 is the
distance from the bottom of the
LVU-201 to the 20
This setting is measured in either
inches or centimeters on the display. The EC20 setting is typically thedistance from the bottom of the transducer to the highest level in thetank.
SAFlISAFZISAF3:
SAF_
the When
becomes LOST. When
mAremain constant if the signal becomes LOST.
FAST/SLOW:
is the typical setting for the LVU-201 series to operate. [SLOW] isdesigned to help dampen out effects caused by severe turbulence. Inthe [FAST] mode, the LVU-201 series will es per second and update every second. In the [SLOW] mode, theLVU-20 onds. When used with [SAF is 30 seconds for [FAST] mode and 2.5 minutes for [SLOW] mode.
ALIN:
show the return signal strength in
mechanical alignment of the LVU-201 series and/or signal attenua-tion. Typical readings range between 2 and 60 alignment, first energize the unit and receive a valid return signal.Then select the display is maximized.
ON/OFF:
turned [OFF] when alignment is completed.This mode will not automatically default backto [LEVL].
MAXR:
maximum range. The MAXR setsmum tank height and will filter out
all (value):
maximum distance is 216.0 inches.The MAXR value is typically setequal to the EC4 setting.
MINR:
[MINR] or the minimum range. TheMINR value is the to the transducer face where no sig-nal will be generated. The MINR sets the minimum distance betweenthe liquid and the transducer.
(value):
The
settings to determine a fail-safe mode for the current signal.
[SAFl] is set, the current will increase to 22
if the signal becomes LOST. When
1
series will average signal returns over the preceding 10 sec-
Indicates that the unit is in the Alignment mode. Display will
Actual
Used as an indication for
returns greater than this value.
Actual MAXR setting. The
Used as an indication for
Actual MINR setting. The minimum distance is 6.0 inches,
MINR
value is typically set equal to the EC20 setting.
Fail-Safe setting for the LVU-201 series. Use
[SAF2]
is set, the current will decrease to 4
Setting for echo averaging on the LVU-201. [FAST]
l/2/3], the time for the current to default
dB’s.
ALIN mode and adjust the LVU-201 series until the
setting
for
ALM mode. The
[
deadband
closest
setting for the
set point. This setting is
mA
setting for the
mA
mA
if the signal
the
[SAF3]
average
Used
is set,
ALIN
current will
2 signal respons-
as an indicator for
dB’s.
For optimum
mode must be
set point.
LVU-
Page 4
PROGRAMMING
Step Four
EC4:
I.
Hold [MENU] key until EC4 appears in display.
2. Release [MENU] key and wait until a value appears. This value isthe
current measured level value.
3. If this is
4. From here, use the
5. Press the [SET] key to enter this value as the new EC4 set point.
EC20:
I.
Hold [MENU] key until EC20 appears in display.
2. Release [MENU] key and wait until a value appears. This value is
3. If this is acceptable, press [SET] to lock the value as the new EC20
4. From here, use the
5. Press the [SET] key to enter this value as the new EC20 set point.
SAFlISAFZISAF3:
I.
Hold [MENU] key until
2. Release [MENU] key and hold [SET] key to toggle between SAF 1,
3. When desired setting is reached, release [SET] key. The last dis-
acceptable, press [SET] to lock set point. If not, press either the setting for the EC4 will appear.
]
keys to raise or lower the value to the
]
or [t
[s
desired value.
the current measured level value.
set point. If not, press either the setting for the EC4 will appear.
desired value.
play.
SAF2 and SAF3.
played setting will bc locked into memory. To change, start againat step 1.
]
keys to raise or lower the value to the
]
or [t
[e
SAFl, SAF2 or SAF3 appears in the dis-
the
value as the new
]
keys once and the old
]
or [t
[S
]
keys once and the old
]
or [t
[S
EC4
WIRING
Step Five
LVU-201
the in order to operate.
1. Wiring
2.
Wiring to a Two-Wire Loop Indicator:
3.
Wiring to a PLC:
1
requires 12-36 VDC power with at least 25
to a Omega Continuous Controller:
mA
supply
FAST/SLOW:
1.
Hold [MENU]
2. Relcasc [MENU] key and hold [SET] key to toggle between FASTand SLOW.
3. When desired setting is reached, release [SET] key. The last dis-played setting will be locked into memory. To change, start againat step 1.
ALIN:
1. Hold [MENU] key until
2. Continue to hold [MENU] key until OFF appears in the display.
3. Release [MENU] key and hold [SET] key to toggle from OFF toON.
4. Release [SET] key. the LVU-20 1 is now in
5. To exit
MAXR:
I. Hold [MENU] key until MAXR appears in
2. Continue to hold [MENU] key until a value appears in the display.This value is the current MAXR setting.
3. If this is acceptable, press [SET] to lock the value as the MAXRsetting. If not, use the the desired setting.
4. Press the [SET] key to enter this value as the new MAXR setting.
MINR:
I.
Hold [MENU] key until MINR appears in the display.
2. Continue to hold [MENU] key until a value appears in the display.This value is the current
3. If this is acceptable, press [SET] to lock the value as the ting. If not, use the desired value.
4. Press the [SET] key to enter this value as the new MINR setting.
key until FAST or SLOW appears in the display.
ALIN
appears in the display.
ALIN
ALIN
mode, repeat steps 1-4 changing from ON to OFF.
the
raise
]
keys to
]
or [t
[s
MINR
setting.
]
keys to raise or lower the value to the
]
or [t
[s
or lower
mode.
display.
the
MINR
value to
set-
Hints:
Icvcl.
Current must change with tion below, as level increases, the current output will increase and asthe level decreases, the current output will decrease. If the output ofthe LVU-201 series is always reading 4 values for the LVU-201 series.
changes
Example: For the illustra-
in
mA
or 20
mA,
check the input
El
20
4
mA
mA-
-3
EC4
I
Page 5
INSTALLATION
Step Six
1
INSTALLATION
Step Seven
Mounting the LVU-20
1
series is critical to the successful
operation
the transmitter. Avoid the following parameters:
Avoidlntetierencefrom side of
tank
i----l
Minimum Range
(MINR) Setting
The MINR setting is typically the dis-tance from the bottom of the transducer tothe highest level in the tank.
installing the LVU-201 series in a flangeor any device which recesses the bottomof the transmitter, the minimum setting
for the MINR is the distance
from
tom of the transmitter to the end of the
flange. Never set MINR to less than 6.0
set the
MINR value to
Alwyvs
inches.
greatest setting.
Maximum Application Range
The maximum range of LVU-20lseries is
I8
feet at 1 IO
dB.less than ideal conditions, a number of factors can reduce the overallquality of signal return and shorten the accurate range of the
determine
tcr. To
the
signal return formula against the echo attenuation graph below.
low
the maximum application range of the product, fol-
Echo Attenuation Graph
ALIGNMENT
m
transducer = 40”
ALIN
sible
= 26dB
anical
alignment of unit
displayed
MAXIMUM RANGE
ALIN
BatD=40”
When
the bot-
Under
transmit-
value
of
it?
Factory Settings:
The LVU-201 series is preset at the factory. When powering up thetransmitter the first time, the factory settings will be active. If at anytime in you need to return to these settings, remove power from theLVU-201 series and wait IO seconds. Press the [Set] and [Menu] but-tons simultaneously while powering up the transmitter.
EC4EC208” (20.3 cm)
216” (548.4
cm)
OFF
MAXR
OFFWA
Changing Display Units:
The LVU-201 series comes preset to measure in inches. To change theunit to display centimeters, remove wait IO seconds. Press
]
and [Set] simultaneously while powering
[S
power to the LVU-201
series
up the transmitter. The LVU-201 series will now read in centimeters.
To return to inches, remove power and wait 10 seconds. Press [t
[Set] simultaneously while powering up the transmitter.
Depth Radius Radius(Feet) (Inches) (cm)
1
234
5678
9IO1112131415161718
1.23.1
2.1
2.97.3
3.79.5
4.6
5.4
6.2
7.1
7.9
8.8
9.6
10.4
11.3
12.1
13.0
13.8
14.6
15.5
5.2
11.6
13.7
15.9
18.0
20.1
22.3
24.4
26.5
28.7
30.8
32.9
35.1
37.2
39.3
I
I
I
f_
C--G
I
\
\
I
Radius
I
I
I
I
-_-z
1
k
w--w-
and
]
and
00
40
80
120
DISTANCE FROM FACE OF TRANSDUCER (inches)
160200
240
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.