LVE 115/116 Series
Electro-Optic Level Switch
M-5175/1112
Instal lati on:
1b 1/ 2" N P T Swi tch : A pp ly a cu r ing t yp e t hre a d se a la nt (s uc h as Loctit e #5 65 w it h pri m er " N") , wh ich is c omp a ti bl e w ith the liq uid m ed ia.
W e do n ot r ecom m end pip e t ap e. For Car b on S te el u nits tor q ue o ne t o
two t u rns ( m a xi m um) p ast the h a nd -t igh t e n gag eme n t. For S t ain l es s
Ste e l u nit s t or qu e on e t urn ( m ax i mum ) pa s t t he h an d- ti gh t en g ag emen t .O ver T or qu e o f s e ns or c an p e rm an en t ly d am ag e s ens o r.
2. Se nso r ma y be in st alle d ho r iz o nta l ly or up t o 4 5° fr om ho riz ont al,
onl y. ( See Fi gure 1)
3. Do no t in s tal l se nso r c lo se t o infr a re d so u rce s .
4. Pr i sm s ur face mus t b e at le as t 2" f r om a ny re fle c ti ve s urfa c es.
5. C onne c t ap p ro p ri at e vo l ta ge sup p ly t o re d lea d . Fo r 12 VD C un i ts ,
con nec t t o 12 VDC ±5% .
6. In duct i ve l oa ds m ust b e diod e - sup p re s sed .
7.
Maintenance:
Sensor may require a periodic cleaning of prism surface. A mild detergent may be
used to clean prism surface.
This product complies with EN61326 Electrical Equipment for Measurement, Control
and Laboratory use - EMC Requirements for Minimum Requirements and Industrial
Locations. Special caution should be taken to meet EN61000-4-5 Surge Immunity if
any of the following conditions apply to the installation: The product is installed
outside; the cable is greater than 30 meters in length. In order to meet the Surge
Immunity requirements, the following conditions must be followed during installation:
1. Shielded cable must be used, and the shield must be tied to earth ground (not
3. For the sensor with metal body or enclosure the body/enclosure must be grounded to earth. If a protective metal housing is used, the metal housing should be
grounded to earth.
4. If a protective plastic housing is used, the housing must be able to withstand at
least 2 kV from the housing to earth ground.
power supply ground) on at least one end of the cable shield/drain
wire. The shield must be maintained all the way from sensor to the
power supply.
2. If unshielded cable is used, an earth grounded metal conduit can
be used to replace the shielded cable.
Important Points:
· Omega products must be maintained and installed in strict accordance with the
National Electrical Code and the applicable Omega Product Instruction Bulletin that
covers installation, operation and proper maintenance. Failure to observe this information may result in serious injury or damages.
· For hazardous area applications involving such things as, but not limited to, ignitable mixtures, combustible dust and flammable materials, use an appropriate explosionproof enclosure or intrinsically safe interface device.
· Please adhere to the pressure and temperature limitations shown throughout this
catalog for our level and flow sensors. These limitations must not be exceeded.
These pressures and temperatures take into consideration possible system surge
pressures, temperatures and their frequencies.
· Selection of materials for compatibility with the media is critical to the life and
operation of Omega products. Take care in the proper selection of materials of
construction, testing is required.
· Our sensors have been designed to resist shock and vibration. However, shock
and vibration should be minimized.
· Filter liquid media containing particulate and/or debris to ensure the proper operation of our products.
· Electrical entries and mounting points in an enclosed tank may require liquid/
vaporsealing.
· Our sensors must not be field-repaired.
· Physical damage sustained by product may render it unserviceable.
Max Ambient Light
Black Container Opaque Container
390 FT-CD 30 FT-CD
Note:
Above testing is based on minimum readings
of at least two (2) samples.
The test depicted to the left was performed to
determine the sensor immunity level to
ambient light. The recorded ambient is the
Materials:
Housing
Prism Fused Glass
Operating Pressure 0 to 2500 psig, Max
Operating Temperature -40°F to 212°F (-40°C to 100°C)
Current Consumption 12V ~34mA No Load
Output Open Collector Output,
Electrical Termination 22 AWG, Polymeric, 12” to 14” Extended Lead
Repeatability ±1 mm
Approvals Units Labeled
Specifications
Nickel-Plated Carbon Steel
18 mA Sink Max.
Wires
C.E. EN 61326
Note: Not for use in freezing liquids.
Mounting Attitude
These units must be
mounted horizontally
or up to 45° from
Typical Wiring Dia-
+12 VDC
+12 VDC
1/2” NPT Thread Mounting