Omega Products LVCN700 Installation Manual

Page 1
http://www.omega.com
e-mail: info@omega.com
®
User’s Guide
LVCN700 Series
Multi-Point Ultrasonic Level Switch
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace
period to the normal one (1) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon
examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge.
OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not
limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unautho-
rized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or
shows evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control.
Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result
from the use of its products in accordance with information provided by OMEGA, either verbal or writ-
ten. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects.
OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATS0EVER,
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY
WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DIS-
CLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the
total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component
upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or spe-
cial damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth
in our basic WARRANTY/ DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in
such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on
any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR W
ARRANTY
RETURNS, please have the fol-
lowing information available BEFORE contacting
OMEGA:
1. P.O. number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA
for current repair charges. Have the following
information available BEFORE contacting OMEGA:
1. P.O. number to cover the COST
of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific
problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible.
This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 1996 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied,
photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior
written consent of OMEGA ENGINEERING, INC.
Servicing North America:
USA: One Omega Drive, Box 4047
ISO 9001 Certified Stamford, CT 06907-0047
Tel: (203) 359-1660
Fax: (203) 359-7700
e-mail: infor@omega.com
Canada: 976 Bergar
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928
FAX: (514) 856-6886
email: canada@omega.ca
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
SM
Customer Service: 1-800-622-2378 / 1-800-622-BEST
SM
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
SM
Mexico En Espanol: (001) 203-359-7803
e-mail: espanol@omega.com
FAX: (001) 203-359-7807
info@omega.mx
Servicing Europe:
Czech Republic: Frystatska 184, 733 01 Karvina, Czech Republic
Tel: +420 (0)59 6311899
FAX: +420 (0)59 6311114
Toll Free: 0800-1-66342
e-mail: info@omegashop.cz
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
Tel: +49 (0)7056 9398-0
FAX: +49 (0)7056 9398-29
Toll Free in Germany: 0800 639 7678
e-mail: info@omega.de
United Kingdom: One Omega Drive, River BendTechnology Centre
ISO 9002 Certified Northbank, Irlam, Manchester
M44 5EX, England
Tel: +44 (0)161 777-6611
FAX: +44 (0)161 777-6622
Toll Free in England: 0800-488-488
e-mail: sales@omega.co.uk
omega.com
OMEGAnet
SM
On-Line Service Internet e-mail
http://www.omega.com info@omega.com
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly
pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every
appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it con-
tains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
TEMPERATURE

Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies

Wire: Thermocouple, RTD & Thermistor

Calibrators & Ice Point References

Recorders, Controllers & Process Monitors

Infrared Pyrometers
PRESSURE, STRAIN AND FORCE

Transducers & Strain Gauges

Load Cells & Pressure Gauges

Displacement Transducers

Instrumentation & Accessories
FLOW/LEVEL

Rotameters, Gas Mass Flowmeters & Flow Computers

Air Velocity Indicators

Turbine/Paddlewheel Systems

Totalizers & Batch Controllers
pH/CONDUCTIVITY

pH Electrodes, Testers & Accessories

Benchtop/Laboratory Meters

Controllers, Calibrators, Simulators & Pumps

Industrial pH & Conductivity Equipment
DATA ACQUISITION

Data Acquisition & Engineering Software

Communications-Based Acquisition Systems

Plug-in Cards for Apple, IBM & Compatibles

Datalogging Systems

Recorders, Printers & Plotters
HEATERS

Heating Cable

Cartridge & Strip Heaters

Immersion & Band Heaters

Flexible Heaters

Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL

Metering & Control Instrumentation

Refractometers

Pumps & Tubing

Air, Soil & Water Monitors

Industrial Water & Wastewater Treatment

pH, Conductivity & Dissolved Oxygen Instruments
M-4465/0707
OMEGA
®
TM
Page 2
Step One
SPECIFICATIONS
Range: LVCN704: 2" to 4'
(5 cm to 1.2m) LVCN709: 4" to 9.8' (10 cm to 3m) LVCN716: 4" to 16.4' (10 cm to 5m) LVCN126: 8" to 26.2'
(20 cm to 8m) Repeatability: 0.25" (6 mm) Adjustability: Over entire range Hysteresis: LVCN704/709: 0.5" (1.2 cm)
(single set point)
LVCN716/726: 1" (2.5 cm)
(single set point) Beam width: LVCN704/709: 2" (5 cm) dia.
LVCN716/726: 3" (7.6 cm) dia. Dead band: LVCN704: 2" (5 cm)
LVCN709/716: 4" (10 cm)
LVCN726: 8" (20 cm) LED indication: Power, relay and echo status Calibration: Target, push button Memory: Non-volatile Supply voltage: AC: 95-250 VAC
DC: 12-28 VDC (Optional) Consumption: AC: 20 watts max.
DC: 100 mA @ 24 VDC (Optional) Contact type: (3) SPDT relays Contact rating: 60 VA Contact logic: Single point: alarm
Two point: latching or
out of bounds alarms
Duplex or Alternation:
(Relays 1 and 2 only) Contact fail-safety: De-energizes during echo signal loss Process temp.: F: -4° to 140°
C: -20° to 60° Temp. comp.: Automatic Electronics temp.: F: -40° to 160°
C: -40° to 71° Pressure: 30 psi (2 bar) @ 25° C., derated @
1.667 psi (.113 bar) per °C. above
25° C. Enclosure rating: NEMA 4X (IP65) Enclosure vent: Water tight membrane Encl. material: PC/ABS FR Trans. material: PVDF Kynar® Process mount: LVCN704/709: 1" NPT (1" G)
LVCN716/726: 2" NPT (2" G) Mount. gasket: Viton® Conduit entrance: Dual, 1/2" NPT Classification: General purpose CE compliance: EN 61326 EMC
[DC series only (DC powered)]
Handling Static-Sensitive Circuits/Devices: When han-
dling the Ultrasonic switch, the technician should follow these guidelines to reduce any possible electrostatic charge build-up on the technicians body and the electronic part.
1. Always touch a known good ground source before handling the
part. This should be repeated while handling the part and more frequently after sitting down from a standing position, sliding across the seat or walking a distance.
2. Avoid touching electrical terminals of the part unless making connections.
3. DO NOT open the unit cover until it is time to calibrate.
1.2"
(32 mm)
1.9"
(49 mm)
3.9"
(100 mm)
5.2"
(133 mm)
2.4"
(62 mm)
1" NPT
(1" G)
0.75"
(19 mm)
LU75
LU72
2.5"
(63 mm)
4.5"
(114 mm)
5.2"
(133 mm)
3.0"
(76 mm)
2" NPT
(2" G)
1.7"
(44 mm)
4.1"
(104 mm)
5.2"
(133 mm)
3.8"
(96 mm)
40
30
20
10
00
-40 -20 00 20 40 60 80
Acceptable
Range
Unacceptable
Range
Temperature/Pressure Derating
Operating Pressure (psi)
Temperature (C¡)
LVCN716 LVCN726
Enclosure (Side View)
LVCN704 LVCN709
Enclosure (Side View)
LVCN700 Series
Enclosure (Top View)
Page 3
INTRODUCTION TECHNOLOGY
Step Three
A. Application: The general purpose ultrasonic level switch pro-
vides non-contact level detection up to 26’ or 8m with 3 relays. Each relay can be configured on a single set point alarm, two latched set points for automatic fill or empty, two set points for out of bounds alarms or three set point (relays 1 and 2 only) alternation / duplexing . The switch is well suited for a wide range of corrosive, waste and slurry type media, and is broadly selected for atmospheric day tank, pump lift station and waste sump applications.
B. Part Number: The part and serial numbers are located on the wrench flat. Check the part number on the product label and confirm which of the below model configurations you have purchased:
P
ar
t Number Range Supply Mount
LVCN704 4’ (1.2m) 95-250 VAC 1” NPT LVCN704G 4’ (1.2m) 95-250 VAC 1” NPT LVCN704-DC 4’ (1.2m) 12-28 VDC 1” NPT LVCN704G-DC 4’ (1.2m) 12-28 VDC 1” NPT LVCN709 9.8’ (3m) 95-250 VAC 1” NPT LVCN709G 9.8’ (3m) 95-250 VAC 1” NPT LVCN709-DC 9.8’ (3m) 12-28 VDC 1” NPT LVCN709G-DC 9.8’ (3m) 12-28 VDC 1” NPT LVCN716 16.4’ (5m) 95-250 VAC 1” NPT LVCN716G 16.4’ (5m) 95-250 VAC 1” NPT LVCN716-DC 16.4’ (5m) 12-28 VDC 1” NPT LVCN716G-DC 16.4’ (5m) 12-28 VDC 1” NPT LVCN726 26.2’ (8m) 95-250 VAC 2” NPT LVCN726G 26.2’ (8m) 95-250 VAC 2” NPT LVCN726-DC 26.2’ (8m) 12-28 VDC 2” NPT LVCN726G-DC 26.2’ (8m) 12-28 VDC 2” NPT
C. NEMA 4X Enclosure:The enclosure has a flip cover with two 1/2” NPT female conduit ports and an internal terminal strip for wiring. To open the enclosure, you will need a small insertion tool such as a screwdriver. Insert the tool into the hole located at the front of the enclosure and gently push on the latching mechanism to release the cover. Rotate the hinged cover up for 135° access to the faceplate and terminal strips. Before closing the enclosure,
make sure that the enclosure gasket is properly seated, and that any conduit fittings, cable connectors or plugs are installed correctly and sealed.
Step Tw o
About this Manual: PLEASE READ THE ENTIRE MANU-
AL PRIOR TO INSTALLING OR USING THIS PRODUCT. This manual includes information on the LVCN700 series Ultrasonic Level Switch. Please refer to the part number located on the switch label to verify the exact model con­figuration which you have purchased.
User’s Responsibility for Safety: Omega manufactures a
broad range of level sensing technologies. While each of these sen­sors is designed to operate in a wide variety of applications, it is the user’s responsibility to select a sensor model that is appropriate for the application, install it properly, perform tests of the installed sys­tem, and maintain all components. The failure to do so could result in property damage or serious injury.
Proper Installation and Handling: Only properly trained
staff should install and/or repair this product. Install the switch with the included Viton gasket and never overtighten the switch within the fitting. Always check for leaks prior to system start-up.
Wiring and Electrical: A supply voltage of 95-250 VAC is
used to power the Ultrasonic switch, and a supply voltage of 12-28 VDC is used to power the optional DC version of the LVCN700 series Ultrasonic switch. Electrical wiring of the switch should be performed in accordance with all applicable national, state, and local codes.
Material Compatibility: The LVCN700 series enclosure is
made of a flame retardant Polycarbonate (PC/ABS FR). The trans­ducer is made of Polyvinylidene Fluoride (PVDF). Make sure that the model which you have selected is chemically compatible with the application media.
Enclosure: While the LVCN700 series housing is liquid-resis-
tant, the unit is not designed to be operational when immersed. It should be mounted in such a way that the enclosure and transduc­er do not come into contact with the application media under nor­mal operational conditions.
Make a Fail-Safe System: Design a fail-safe system that
accommodates the possibility of switch and/or power failure. OMEGA recommends the use of redundant backup systems and alarms in addition to the primary system.
Flammable, Explosive or Hazardous Applications:
The LVCN700 series should not be used within classified haz-
Warning
Always use the Viton gasket when installing the Ultrasonic switch, and make sure that all electrical wiring of the switch is in accordance with applicable codes.
LVCN726
Shown
RELAY
1
RELAY2RELAY
3
L
1 L2
POWER
Cal. Run
High Low
Select
Page 4
Step Four Step Five
CALIBRATION
A. Introduction: The switch has two modes, the RUN and CAL
modes. In the RUN mode, the switch is operational and the relay(s) will energize or de-energize at the calibrated set point distances. In the CAL mode, the relay set point distances and states may be target-cal­ibrated into memory. The switch arrives from the factory without any preset calibration. Each relay channel may be user calibrated into one of the following configurations; 1) high or
low level alarm,
2) high and
low level out of bounds alarm, 3) automatic fill or empty,
or 4) duplexing/Alternating.
High or Lo
w Level Alarm: The high or
low level alarm is programmed with a sin­gle set point at the desired tank level. Configured as a high alarm, the relay will energize if the level rises above the set point. Configured as a low level alarm, the relay will energize if the level falls below the set point.
High and Lo
w Level Out of Bounds
Alarm: Programmed with two set points,
the high and low level out of bounds alarm protects the top of the tank from overspill and the bottom of the tank from run-dry. If the level rises above or falls below the set points, the relay will energize. The relay will remain de-energized as long as the level is in between the set points.
A
utomatic Fill or Empty: Programmed
with two set points, the latched automatic fill or empty will control a pump or valve. When the level reaches the energize set point, the latching relay will energize, and remain energized until the level reaches the de-energize set point.
Duple
x/Alternate: Programmed with
three set points and two relays, duplexing will automatically fill or empty the tank with two pump alternation for maintenance and lead-lag control for back up operation. When the level reaches the energize set point, the latching relay will energize, and remain energized until the level reaches the de-energize set point. Each time the level reaches the energize set point, the relays will alternate. If the level reaches the back-up energize set point, both relays will energize until the level reaches the de-energize set point. Alternation will automati­cally fill or empty the tank with two pumps switching after each cycle.
PREPARATION
A. Supply V oltage: The power supply voltage should never exceed
the maximum rating of 250 VAC for the LVCN700 series AC switch or 28 VDC for the LVCN700-DC series switch.
B. Conduit Entrance: The enclosure has two 1/2” NPT female conduit ports for routing of the switch supply and relay circuit wiring. Do not
run mixed AC and DC voltages through the same conduit port. Route
the supply voltage circuit through one port and the relay circuit(s) through the opposite port.
C. Relay Fail-Safe Design:
The switch has (3) relay channels. Each relay is a SPDT (single pole, double throw) type rated at 60 VA. Normally open (NO) or normally closed (NC) operation is user selected based on the desired system control and fail-safe logic. Always design a fail-safe system that accommo-
dates for the possibility of relay and/or power failure. The "nor­mal" relay state is where the relay coil is de-energized and the Red relay LED is OFF. Therefore, if power is cut OFF to the switch it will de-energize the relay . Make sure that the de-ener gized state is the safe state in your system design. As such, if switch power is lost, a pump will turn OFF if it is connected to the normally open side of the relay.
E. Maximum Applied Range: Individual or cumulative effects of agitation, vapor or foam can reduce the overall quality of signal return and shorten the maximum applied range of the switch. To determine the maximum applied range of the switch in your application, refer to the below derating chart.
LVCN700 series
shown
1/2 NPT Conduit
Supply
Port
Relay
Port
Ultrasonic Derating Chart
LVCN704/709 LVCN716/726
Agitation = 1-3 @ 100 kHz Agitation = 1-3 @ 50 kHz Vapor = 4-6 @ 100 kHz Vapor = 3-5 @ 50 kHz Foam = 5-6 @ 100 kHz Foam = 4-6 @ 50 kHz
(Auto-Fill Shown)
LVCN700-DC series
shown
POWER
L1 L
VAC
2
HOT NEUTRAL
VAC
INPUT
POWER
(+) (-)
VDC
Positive Negative
INPUT
VDC
RELAY
1
0%
100Khz
50Khz
Energize
De-energize
High Alarm Shown
Energize
De-energize
Energize
De-energize
Energize
50%
100%
012345678910
Energize (Primary)
High
Energize (Backup)
High High
De-energize (All) Low
Page 5
Step SevenStep Six
CALIBRATION
B. Calibration Tools: To target calibrate the switch set points, you
will need the appropriate power supply (95-250 VAC or 12-28 VDC for DC version), tape measurer, flat reflective target such as a wall, and optional Omega box insert for use as a product holder.
C. Off Tank T arget Calibration: The switch’s relay set points may be target calibrated OFF the tank or installed ON the tank. Generally, target calibration is done OFF the tank because it is easier to move the switch rather than raise or lower the liquid level to the desired relay set point distances. Locate a flat reflective calibration target such as a wall. Place the switch perpendicular to the target in the provided Omega box insert or equivalent holder. Alternatively, you may
hold the switch with your hand, but it is critical that prior to entering any relay set point dis­tances, the product is held steady and perpendicular to the target for at least 15 seconds. If
calibrating against a wall, it is recommended that the switch be elevated 3’ (1m) off the ground by placing it on a table or equiv­alent flat surface.
D. Entering the CAL Mode:To enter the CAL mode, you must
first disable the calibration lock out feature. To do so, press and hold the SELECT button down. While holding the SELECT button, slide the RUN/CAL switch LEFT to the CAL position, and then release the SELECT button. At this point, all relay LEDs should be OFF.
E. Selecting a Relay Channel: After entering the CAL mode,
press the SELECT button once and the Relay 1 LED will turn ON indicating that the channel is now active for set point calibration. Press the SELECT button again until the desired Relay channel becomes active.
F. Erasing a Relay Channel:With the exception of new prod-
ucts out of the box, all previously entered relay set points should be erased prior to new programming with the following procedure:
1. Enter CAL mode and SELECT the relay channel to erase.
2. Simultaneously press and hold down both the HIGH and LOW
buttons, and then release the buttons.
3. The Relay and Power LEDs will blink in an alternating pattern
indicating that the relay set points have been erased.
4. At this point, once the LED becomes solid, you may either re-pro-
gram the channel with new set points or leave it inactive.
PROGRAMMING
A. Programming a Relay Channel: The relay set points are tar-
get calibrated using the appropriate HIGH and/or LOW two key­stroke button sequence at each target distance (D1=distance one, D2 = distance two and D3 = Distance 3) per the following logic.
Relay Function
Button Sequence @ Distance(s)
1. High level alarm High-High (D1)
2. Low level alarm Low-Low (D1)
3. Out of bounds alarm High-High (D1) & Low-Low (D2)
4. Automatic fill Low-High (D1) & High-Low (D2)
5. Automatic empty High-Low (D1) & Low-High (D2)
6. Duplexing/Alternation [High-Low (D1) & Low-High (D2), Rly 1] & [High-High (D3), Rly 2]
B. Programming a High or
Low Level Alarm: After having
powered the switch with the appropriate supply voltage, entered the CAL mode, selected a relay channel and erased any previously input set points, follow the below procedure (LOW level alarm instructions are in parenthesis):
1. Stretch the tape measurer out to the appropriate distance in
between the switch and target.
2. Position the switch at the desired HIGH (LOW) set point distance
defined as the air gap space between the transducer and the target.
Make sure that the switch is stationary and perpendicular to the target before continuing.
3. Press the HIGH (LOW) button
for the first key-stroke and the Relay LED will blink once.
4. Press the HIGH (LOW) button
again for the second key-stroke and the Relay LED will blink twice.
5. The Power LED will flash from
AMBER to GREEN when the set point has been accepted into memory.
6. Press SELECT to program the next relay channel or slide the
RUN/CAL switch RIGHT to exit the CAL mode.
T
High Level Alarm
Low Level Alarm
After the second High or Low button key-stroke, the Power LED will flash from AMBER to GREEN indicating that the set point has been accepted into memory. If all three Relay LEDs
flash RED and remain ON, then the button sequence was done incorrectly. If so, press SELECT to return to the appropriate
relay channel and erase the previous set points per the CALI­BRATION section (Step #6-F) of this manual.Then re-program the channel with the correct button sequence.
Set Point
Calibration
Tape
Box
Insert
Table
Cal. Run
High Low
Select
L
RELAY
1
RELAY2RELAY
1 L2
POWER
3
Set Point Distance
Target
Wall
High or Low Level Alarm
Programming
ape
Box
Insert
Set Point Distance
Table
Target
Wall
Energize
De-energize
De-energize
Energize
Page 6
Step Eight
PROGRAMMING
Step Nine
PROGRAMMING
C. Programming a High and
Low Level Out of Bounds
Alarm: After having powered the switch with the appropriate supply
voltage, entered the CAL mode, selected a relay channel and erased any previously input set points, follow the below procedure:
1. Stretch the tape measurer out to the appropriate distance in between the switch and target.
2. Position the switch at the desired HIGH set point distance defined as the lesser of the two air gap spaces between the transducer and the target. Make sure
that the switch is stationary and per­pendicular to the target before con­tinuing.
3. Press the HIGH button for the first key­stroke and the Relay LED will blink once.
4. Press HIGH again for the second key-stroke and the Relay LED will blink twice.
5. The Power LED will flash from AMBER to GREEN when the HIGH set point has been accepted into memory.
6. Position the switch at the desired LOW set point distance defined as the greater of the two air gap spaces between the transducer and the target. Make sure that the switch is stationary and perpen-
dicular to the target before continuing.
7. Press LOW for the first key-stroke and the Relay LED will blink three times.
8. Press LOW for the second key-stroke and the Relay LED will blink four times.
9. The Power LED will flash from AMBER to GREEN when the LOW set point has been accepted into memory.
10. Press SELECT to program the next relay channel or slide the RUN/CAL switch RIGHT to exit the CAL mode.
Out of Bounds
D. Programming Automatic Fill: After having powered the
switch with the appropriate supply voltage, entered the CAL mode, selected a relay channel and erased any previously input set points, follow the below procedure:
1. Stretch the tape measurer out to the appropriate distance in between the switch and target.
2. Position the switch at the desired LOW set point distance defined as the greater of the two air gap spaces between the transducer and the target. Make sure
that the switch is stationary and per­pendicular to the target before con­tinuing.
3. Press the LOW button for the first key­stroke and the Relay LED will blink once.
4. Press the HIGH button for the second key-stroke and the Relay LED will blink twice.
5. The Power LED will flash from AMBER to GREEN when the LOW set point has been accepted into memory.
6. Position the switch at the desired HIGH set point distance defined as the lesser of the two air gap spaces between the transducer and the target. Make sure that the switch is stationary and perpen-
dicular to the target before continuing.
7. Press the HIGH button for the first key-stroke and the Relay LED will blink three times.
8. Press the LOW button for the second key-stroke and the Relay LED will blink four times.
9. The Power LED will flash from AMBER to GREEN when the HIGH set point has been accepted into memory.
10. Press SELECT to program the next relay channel or slide the RUN/CAL switch RIGHT to exit the CAL mode.
Automatic Fill
6
2
2
6
Energize
De-energize
Energize
De-energize
Energize
High and Low Level
Out of Bounds Alarm Programming
Tape
Box
Insert
Table
Low
Set Point
Distance
High
Set Point
Distance
Target
Wall
Automatic Fill
Programming
Tape
Box
Insert
Table
Low
Set Point
Distance
High
Set Point
Distance
Target
Wall
Page 7
Step Ten
PROGRAMMING
E. Programming Automatic Empty: After having powered the
switch with the appropriate supply voltage, entered the CAL mode, selected a relay channel and erased any previously input set points, follow the below procedure:
1. Stretch the tape measurer out to the appropriate distance in between the switch and target.
2. Position the switch at the desired HIGH set point distance defined as the lesser of the two air gap spaces between the transducer and the target. Make sure
that the switch is stationary and per­pendicular to the target before con­tinuing.
3. Press the HIGH button for the first key­stroke and the Relay LED will blink once.
4. Press the LOW button for the second key-stroke and the Relay LED will blink twice.
5. The Power LED will flash from AMBER to GREEN when the HIGH set point has been accepted into memory.
6. Position the switch at the desired LOW set point distance defined as the greater of the two air gap spaces between the transducer and the target. Make sure that the switch is stationary and perpen-
dicular to the target before continuing.
7. Press the LOW button for the first key-stroke and the Relay LED will blink three times.
8. Press the HIGH button for the second key-stroke and the Relay LED will blink four times.
9. The Power LED will flash from AMBER to GREEN when the LOW set point has been accepted into memory.
10. Press SELECT to program the next relay channel or slide the RUN/CAL switch RIGHT to exit the CAL mode.
Automatic Empty
2
6
Step Eleven
PROGRAMMING
Programming Duplexing Pump Control: After having powered
the switch with the appropriate supply voltage, entered the CAL mode, selected relay channel 1 and erased any previously input set points, follow the below procedure:
1. Stretch the tape measurer out to the appropriate distance in between the switch and target.
2. Position the switch at the desired HIGH set point distance defined as the lesser of the two air gap spaces between the transducer and the target. Make sure
that the switch is stationary and per­pendicular to the target before con­tinuing.
3. Press the HIGH button for the first key­stroke and the Relay LED will blink once.
4. Press the LOW button for the second key-stroke and the Relay LED will blink twice.
5. The Power LED will flash from AMBER to GREEN when the HIGH set point has been accepted into memory.
6. Position the switch at the desired LOW set point distance defined as the greater of the two air gap spaces between the transducer and the target. Make sure that the switch is stationary and perpen-
dicular to the target before continuing.
7. Press the LOW button for the first key-stroke and the Relay LED will blink three times.
8. Press the HIGH button for the second key-stroke and the Relay LED will blink four times.
9. The Power LED will flash from AMBER to GREEN when the LOW set point has been accepted into memory.
10. Press SELECT to program relay channel 2.
11. Position the switch at the desired HIGH HIGH set point distance defined as the air gap space between the transducer and the target.
Make sure that the switch is stationary and perpendicular to the target before continuing.
Duplex
Box
Insert
Table
Target
Wall
Tape
Duplex Programming
(Primary)
High
Set Point
Distance
Low
Set Point
Distance
2
6
Energize
De-energize
Energize (Primary)
High
De-energize (All) Low
Energize (Backup)
High High
Automatic Empty
Programming
Box
Insert
Tape
Table
Low
Set Point
Distance
Set Point
Distance
High
Target
Wall
Page 8
A. Fitting Selection: Check the switch part number
to determine the required fitting mount size and thread type. The switch is commonly installed in tank adapters, flanges, brackets or stand pipes.
1. Adapter: Select a tank adapter fitting with
minimal height so as to ensure that the installed transducer will not be substantially elevated into the fitting. Avoid tank adapter styles with threads and/or pipe stops forward of the installed transducer.
2. Flange: Tall flanges with narrow risers
impede the acoustic signal. Select a fitting with the right riser height versus inner diame­ter geometry. The switch may be elevated up to 12” (30 cm) in a 6” (15 cm) riser, 8” (20 cm) in a 4” (10 cm) riser and 3” (7.6 cm) in a 2” (5 cm) riser.
3. Bracket: A LVM-30 side mount bracket or
equivalent can be used for open tank top installations against the side wall.
4. Stand Pipe: A stand pipe may be used to dampen turbulence or separate surface foam. Select a 2” or larger pipe for model LVCN704/709. Select a 3” or larger pipe for model LVCN716/726. The pipe length should run the measurement span. Cut a 45° notch at the bottom of the pipe and drill a 1/4” pressure equalization hole high in the dead band.
Step Thirteen
INSTALLATION
Adapter
VACUUM
Do not install at
angle relative
to the liquid
Do not install with-
in 3” of
tank side wall
Do not install
with objects in the beam
Do not install
in applications
with vacuum
Warning
Install the appropriate installation fitting. Make sure that the fitting and switch threads are not damaged or worn. Install the switch with the included Viton mounting gasket. Hand tighten the switch within the fitting. Perform an installed leak test under normal process conditions prior to system start up.
Gasket
Flange
on Riser
Height
Inner Diameter
Riser
Bracket
Stand Pipe
Step Twelve
PROGRAMMING
12. Press the HIGH button for the first key-stroke and the Relay LED will blink once.
13. Press the HIGH button again for the second key-stroke and the Relay LED will blink twice.
14. The Power LED will flash from AMBER to GREEN when the set point has been accepted into memory.
15. Press the SELECT switch repeatedly until BOTH LEDs for Relay 1 and Relay 2 are ON (after Relay 3).
16. Press the HIGH button for the first key-stroke and Relay LED will blink once.
17. Press the HIGH button again for the second key-stroke and Relay LED will blink twice.
18. Press SELECT to program the next relay channel or slide the RUN/CAL switch RIGHT to exit the CAL mode.
Note: The duplexing mode can be disabled by repeating Steps #15-18 and pressing the LOW button instead of the HIGH button in the HIGH/HIGH combination.
Programming Alternating Control Only:
1. To program the switch for alternating control only without the lead-lag func­tion, follow the instructions for Programming Duplexing Pump Control (Steps 11 and 12). The difference between Duplexing and Alternation is the location of the Relay 2 set point. Set Relay 2 close to the deadband without crossing into the deadband and above the highest level of expected liquid.
Note: The alternation mode can be disabled by repeating Steps #15-18 and pressing the LOW button instead of the HIGH button in the HIGH/HIGH combi­nation.
Duplex Programming
Alternating
11
Alternating Programming
(Backup)
Box
Insert
Table
Target
Wall
Tape
Distance
Set Point
2
Programming Duplex Pump Control (continued):
(Backup)
Set Point Distance
Target
Wall
Tape
Box
Insert
Table
High High
De-energize (All) Low
Energize
High
Ventilation Hole
2"/3" Minimum Diameter
Dead Band
Highest Liquid Level
Operational Range
Lowest Liquid Level
Page 9
Step Fourteen
High Alarm
VAC
INPUT
HOT NEUTRAL
Motor Starter
(Pump)
RELAY
1
RELAY2RELAY
3
L
1 L2
POWER
VAC
Cal. Run
High Low
Select
Low Alarm
VAC
INPUT
NEUTRAL HOT
High Alarm
VDC
INPUT
HOT NEUTRAL
Motor Starter
(Pump)
RELAY
1
RELAY2RELAY
3
(+) (-)
POWER
VDC
Cal. Run
High Low
Select
Low Alarm
VDC
INPUT
NEUTRAL HOT
WIRING
Step Fifteen
TROUBLESHOOTING
A. Power LED SOLID GREEN in RUN Mode: During normal
operation in the RUN mode, the Power LED will remain solid GREEN indicating that the switch has power and is tracking the level. The RED Relay LEDs will be ON or OFF as programmed per the cur­rent level state.
B. P ower LED AMBER in RUN Mode:If while in the RUN mode, the Power LED turns solid AMBER, this indicates that the switch has power, but is not tracking the level and has entered into it’s FAIL­SAFE mode. Coincidently, all Relay LEDs will be OFF, indicating that the relays are in their de-energized safe-state. The switch will remain in the FAIL-SAFE mode until such time that it re-acquires the level and automatically returns to normal operation as programmed. Check the following points in determining why the switch is not tracking the level:
1. Observe and attempt to correlate an application event such as foaming, substantial vapor and/or turbulence that may reduce or eliminate the acoustic signal strength. Read the Maximum Applied Range (Step #4-E) and consider rein­stalling the switch in a Stand-Pipe (Step #11-A-4) to dampen turbulence and/or separate the point of measurement from surface foam and/or vapor.
2. Verify the switch is installed correctly per the INSTALLATION section (Step #11) of this manu­al. Initially focus on the fitting and/or obstructions within the beam that may reduce or eliminate the acoustic signal transmission-receipt. Consider changing the fitting or relocating the switch to another area of the tank.
3. Verify that the tank height is not greater than the maximum range of the switch. If so, purchase and install a switch with the appropriate range for your tank height or level distance.
Installation
Application
Green
(Solid ON)
RED
(Solid ON or OFF)
Amber
(Solid ON)
RED
(All OFF)
C. Relay LED Changes State, But Relay Doesn’t Change:
Verify that the switch is wired correctly per the WIRING section (Step #12) of this manual. If so, the Relays may have been damaged due to a high inductive load or carbon build-up over time.
A. Wiring a LVCN700 series (95-250 VAC) to a Pump (Automatic Fill or Empty) and (Independent High and Low) Alarms
Warning
To prevent damaging the relays, the use of an appropriate motor starter or secondary relay is ALWAYS recommended when actuating pumps or valves.
B. Wiring a LVCN700-DC (12-28 VDC) to a Pump (Automatic Fill or Empty) and (Independent High and Low) Alarms
C. Wiring a LVCN700 (95-250 VAC) to Pumps (Duplex or Alternating) and Alarm (Out of Bounds, High or Low)
L
RELAY2RELAY
RELAY
1
3
1 L2
POWER
L
RELAY
1
RELAY2RELAY
1 L2
POWER
3
HOT
VAC
NEUTRAL
INPUT
NEUTRAL HOT
Alarm
Motor Starter
(Pump 1)
Motor Starter
(Pump 2)
VAC
INPUT
Duplex/Alternation
RELAY
1
RELAY2RELAY
High Low
Cal. Run
Select
3
L
1 L2
POWER
VAC
Page 10
Relay 1 Relay 2
Energize
De-Energize
Energize
De-Energize
Backup
Primary
Stop
Relay 1 Relay 2
Energize
De-Energize
Energize
De-Energize
Backup
Primary
Stop
Duplexing
Control
Operation
Alternating
Control
Operation
OPERATION
Step Sixteen
Relay X
Energize
De-Energize
Start
Stop
Automatic
Empty
Operation
Automatic
Fill
Operation
Out of
Bounds
Operation
Relay X
Energize
De-Energize
Stop
Start
Relay X
Energize
De-Energize
High
Low
Functional Chart for Relay On/Off Operations
Loading...