ULTRASONIC LEVEL TRANSMITTER
AND CONTROLLER
LVCN210 Series
U Level Detection, Switch
and Control Functions
Up to 3 m (9.8')
U Fast and Easy
Configuration Via
Free Software Download
and USB Adaptor
U Narrow 5.08 cm (2")
Beam Width and Short
10 cm (4") Dead Band
U Four Programmable
Relays
U PVDF Transducer and 6P
Polycarbonate Enclosure
U Automatic Temperature
Compensation For
Accurate Measurement
Dimensions: mm (inch)
1.2 m
(48")
27
(1.1)
68
(2.7)
27
(1.1)
½ NPT
27
(1.07)
78
(3.06)
Red
Blk
Wht
Gry
Blu
Org
Yel
Pur
Brn
- Power
- Return
- TX (Out)
- RX (In)
- Rly 1
- Rly 2
- Rly 3
- Rly 4
- Rly Com
1 NPT or G
(optional)
OMEGA’s LVCN210 Series
ultrasonic level transmitter and
controller provides continuous level
measurement up to 3 m (9.8') with a
4 to 20 mA signal output, and is
configured via our free software
download. The level sensor has
4 programmable relays with
selectable hysteresis and fail-safe
logic. The embedded level controller
can lower cost by replacing external
control hardware. This non-contact
liquid level sensor is ideally suited
for corrosive, sticky or dirty liquids,
and is widely selected for day tank,
skid, IBC, sump and process tank
level applications.
SPECIFICATIONS
Range: 3 m (9.8')
Accuracy: ±0.2% of range
Resolution: 1 mm (0.039")
Dead Band: 10 cm (4")
Beam Width: 5.08 cm (2")
Configuration: Free PC Windows
USB 2.0.The level sensor is
configurable via our free PC software
and USB adaptor. The sensors
are offered with and without USB
connectors. Connectors can be used
to configure many compatible level
products. Download your free copy at:
omega.com/ftp
Memory: Non-volatile
Supply Voltage: 24 Vdc (loop)
Consumption: 0.5 W
Loop Resistance: 400Ω max
Signal Output: 4 to 20 mA, two-wire
Signal Invert: 4 to 20 mA or 20 to 4 mA
Signal Fail-Safe: 4 mA, 20 mA, 21 mA,
22 mA or hold last
Contact Type: (4) SPST relays
Contact Rating: 60 VA, 1A max
Contact Fail-Safe: Power loss; Hold last
Echo Loss: Open, close or hold last
®
LVCN210.
Hysteresis: Selectable
Process Temp: -7 to 60°C (20 to 140°F)
Temp Comp: Automatic
Ambient Temp: -35 to 60°C
(-31 to 140°F)
Pressure: Maximum Working Pressure
= 2 bar (30 psi)
Enclosure Rating: Type 6P,
encapsulated, corrosion resistant
and submersible
Enclosure Material: Polycarbonate
Trans. Material: PVDF
Cable Jacket Mat: Polyurethane
Cable Type: 9-conductor, shielded
Cable Length: 1.2 m (48")
Process Mount: 1 NPT (1" G optional)
Mount Gasket: FKM
Classification: General purpose
Compliance: CE, RoHS
K
To Order
Visit omega.com/lvcn210 for Pricing and Details
Model No. Description
LVCN210 Level transmitter 4 to 20 mA and 4 relays, and USB connector, range 3 m (9.8')
LVCN210-B Level transmitter 4 to 20 mA and 4 relays (requires LVCN414-USB), range 3 m (9.8')
LVM31 Mounting reducer 1 female NPT to 2 male NPT
LVCN414-USB USB connector
Comes complete with mounting gasket and operator’s manual.
For units with G threads add “-G” to model number, for additional cost.
Configuration software for programming available free at omega.com/ftp
Ordering Example: LVCN210, level transmitter with relays and USB connector, 1 NPT, 3 m (9.8') range.
K-1