Omega Products LVCN210-B User Manual

ULTRASONIC LEVEL TRANSMITTER AND CONTROLLER
LVCN210 Series
U Level Detection, Switch
and Control Functions Up to 3 m (9.8')
Configuration Via Free Software Download and USB Adaptor
U Narrow 5.08 cm (2")
Beam Width and Short 10 cm (4") Dead Band
U Four Programmable
Relays
U PVDF Transducer and 6P
Polycarbonate Enclosure
U Automatic Temperature
Compensation For Accurate Measurement
Dimensions: mm (inch)
1.2 m (48")
27
(1.1)
68
(2.7)
27
(1.1)
½ NPT
27
(1.07)
78
(3.06)
Red Blk Wht Gry Blu Org Yel Pur Brn
- Power
- Return
- TX (Out)
- RX (In)
- Rly 1
- Rly 2
- Rly 3
- Rly 4
- Rly Com
1 NPT or G
(optional)
OMEGA’s LVCN210 Series ultrasonic level transmitter and controller provides continuous level measurement up to 3 m (9.8') with a 4 to 20 mA signal output, and is configured via our free software download. The level sensor has 4 programmable relays with selectable hysteresis and fail-safe logic. The embedded level controller can lower cost by replacing external control hardware. This non-contact liquid level sensor is ideally suited for corrosive, sticky or dirty liquids, and is widely selected for day tank, skid, IBC, sump and process tank level applications.
SPECIFICATIONS
Range: 3 m (9.8') Accuracy: ±0.2% of range Resolution: 1 mm (0.039") Dead Band: 10 cm (4") Beam Width: 5.08 cm (2") Configuration: Free PC Windows
USB 2.0.The level sensor is configurable via our free PC software and USB adaptor. The sensors are offered with and without USB connectors. Connectors can be used to configure many compatible level products. Download your free copy at:
omega.com/ftp Memory: Non-volatile Supply Voltage: 24 Vdc (loop) Consumption: 0.5 W Loop Resistance: 400Ω max Signal Output: 4 to 20 mA, two-wire Signal Invert: 4 to 20 mA or 20 to 4 mA Signal Fail-Safe: 4 mA, 20 mA, 21 mA,
22 mA or hold last
Contact Type: (4) SPST relays Contact Rating: 60 VA, 1A max Contact Fail-Safe: Power loss; Hold last Echo Loss: Open, close or hold last
®
LVCN210.
Hysteresis: Selectable Process Temp: -7 to 60°C (20 to 140°F) Temp Comp: Automatic Ambient Temp: -35 to 60°C
(-31 to 140°F) Pressure: Maximum Working Pressure = 2 bar (30 psi) Enclosure Rating: Type 6P, encapsulated, corrosion resistant and submersible
Enclosure Material: Polycarbonate Trans. Material: PVDF Cable Jacket Mat: Polyurethane Cable Type: 9-conductor, shielded Cable Length: 1.2 m (48") Process Mount: 1 NPT (1" G optional) Mount Gasket: FKM Classification: General purpose Compliance: CE, RoHS
K
To Order
Visit omega.com/lvcn210 for Pricing and Details
Model No. Description
LVCN210 Level transmitter 4 to 20 mA and 4 relays, and USB connector, range 3 m (9.8') LVCN210-B Level transmitter 4 to 20 mA and 4 relays (requires LVCN414-USB), range 3 m (9.8') LVM31 Mounting reducer 1 female NPT to 2 male NPT LVCN414-USB USB connector
Comes complete with mounting gasket and operator’s manual. For units with G threads add “-G” to model number, for additional cost. Configuration software for programming available free at omega.com/ftp Ordering Example: LVCN210, level transmitter with relays and USB connector, 1 NPT, 3 m (9.8') range.
K-1