Omega Products LVC551 Installation Manual

APPROVED
INSTALLATION OF
Am OMEGA
One Omega Drive, Box 4047 Stamford, Connecticut 06907-0047 (203) 359-1660 Telex: 996404 Cable: OMEGA FAX: (203) 359-7700
LVC551
Tlhhnoleghs
-
Cb~&my
INTRINSICALLY SAFE CONTROLS
This bulletin should be used by experienced personnel as a guide to the installation of the LVC551 intrinsically safe control. Selection or installation of equipment should always be accompanied by competent technical assistance. We encourage you to contact OMEGA for complete details.
IMPORTANT: BEFORE PROCEEDING
WIRE THE CONTROL, READ AND THOROUGHLY UNDERSTAND THESE INSTRUCTIONS.
When installed according to these instructions, the unit is intrinsically safe for Class I and II, Division
1, Groups A, B, C, D, E, F, and G
Electrical equipment connected to associated appartus should not use or generate more than 250V RMS.
LOCATION: The control must be situated in a non-
hazardous area where an explosive atmosphere will
not exist at any time. WIRING:
1.
Intrinsically safe wiring must be kept separate from non-intrinsically safe wiring.
Intrinsically safe and non-intrinsically safe
2.
wiring may occupy the same enclosure or raceway if they are at least 2 inches (50mm) apart and separately tied down. Inside panels, field wiring terminals for intrinsically safe circuits must be separated by at least 2 inches (50mm) from non-intrinsically safe terminals. Wire the control device(s) to the LVC551 relay
3. as shown in the specific application wiring diagram on reverse side. A separate rigid metallic conduit should be used to enclose the conductors of the intrinsically safe control circuit. An approved seal should be used at the point
4. where the intrinsically safe control circuit wiring enters the hazardous area.
INDUCTANCE AND CAPACITANCE: For intrin- sically safe wiring use 16 AWG TYPE MTW or 14 AWG TYPE THHN.
By using these types of wire in conjunction with the following distance recommendations, you will not exceed the 500 mh inductance for field wiring.
.45
mf maximum capacitance, and
INSTALL AND
To
Use the following chart to determine the limits of run:
Max. Sensitivity (K OHMS)
3.3
4.7
10 22 47
100
GROUNDING: Both tabs of the LVC551 provide an electrical connection for earth grounding. To insure grounding, use only metal screws and lockwashers. Do not use nylon or any other nonmetallic material to mount the unit in the enclosure.
NOTES:
Connecteions may be made to nonenergy
1. generating or storing hazardous location devices, such as switch contacts, noninductive resistance thermometer detectors thermocouples without necessitating a specific approval except when the device is mounted inside a tank subjected to pressure greater than
15 psi.
To prevent electrical shock, controller must be
2. mounted inside a tool accessible enclosure.
For guidance on the installation see ANSI/ISA
3.
RP 12-6.
Distance (Ft.)
5000 3500 1750 1000
500 250
(RTDs)
and
SPECIFICATIONS
CONTACT DESIGN: D PST: One normally open (N.O.) and one normally closed (N.C.)
CONTACT RATINGS: 8 Amperes resistive load at 250 Volts A.C. and 5 ampheres at 30 Volts D.C.
CONTACT LIFE: Electrical at rated load
50/60
=
10,000,000
minus
Hertz.
.5
cycles.
50/60
15%,
seconds on rising level.
cycles. Mechanical
ELECTRONICS MODULE: Solid state components
epoxy encapsulated in nylon shell.
PRIMARY AC SUPPLY LINE:
(a) Voltage: Standard 120 VAC, optional 24,240 VAC
.5
Watt.
lo%,
models, plus (b) Frequency: (c) Power:
SENSITIVITY: Operates from 0
maximum specific resistance.
TEMPERATURE: (Minus) -40 to (Mlus) + 120
degrees F. ambient. TERMINALS: Size 6 pan head screws with
= 100,000
Hz.
-
100,000 Ohm
SINGLE LEVEL SERVICE
ACTUATED
;;;nect
terminal palr 1-2 to (24, 120,240) VAC supply
LVC551
-
CONDUCTANCE
INTRINSICALLY SAFE CONTROLS
-
INSTALLATION OF
DIFFERENTIAL LEVEL SERVICE
ACTUATED:
;;;;ect
terminal pair 1-2 to
(24,120,240)
.
-
CONDUCTANCE
VAC supply
.
.-
Install sensitivity resistor between terminals RH-H and metallic jumper between termlnals H-L. Connect terminal L to the electrode.
Terminal G must be grounded to the tank If
metallic.
When the tank Is non-metallic, terminal G must be con-
nected to an additional electrode of length equal to
the longest electrode.
NOTE: Jumpers and resistors must be installed as
shown to insure proper operation.
r-----
--------pENcLosURE
/xq
I
Install sensltivity resistors between terminals RH-H
RL-L.
and Connect terminal H to high electrode and terminal L
low
electrode.
to Terminal G must be grounded to the tank If metallic. When the tank Is non-metallic, terminal G must be con-
nected to an additional electrode of length equal to the longest electrode.
NOTE: Jumpers and resistors must tie Installed as shown to Insure proper operation.
__--_--___-
NON-HAZAROOUS AREA
________---_- HAZARDOUS AREA
CLASS
fn$uam
NOTE: RESISTOR MUST AS SHOWN TO INSURE PROPER
OPERATION
AWD 1
BE
INSTALLED
2.
DIVISION
c. A,
F.
E. 0. 0.
_----
1.
i
q--y-__
1
PILOT
SINGLE INPUT (NON-LATCHING)
-
CONTACT
ACTUATED:
l-2
Connect terminal pair
to (24, 120,240) VAC supply line. Install metallic jumpers between terminals RH-H and terminals H-L. Wire contacts 3-4 (normally open) and 5-6 (normally closed) into load circuits as required. Connect the pilot contact to terminals G-L. NOTE: Jumpers must be Installed as shown to insure proper operation.
-+-
I
ii
DEWCC
/
_-__
NON-HAZARDOUS
-_-_-_-_-_-_-_-_-_
HAZARDOUS WC&W
CLISB A.
AREA
DlvlaI0M
2. A0 1
AREA
9.
E.
F.I D.
1. C.
-
DUAL INPUT (LATCHING)
PILOT CONTACT
ACTUATED:
;;remect terminal pair 1-2 to
(24,120,240)
VAC supply
Install metallic jumpers between terminals RH-H and terminals RL-L.
5-6
Wire contacts 3-4 (normally open) and
(normally closed) into load circuits as required. Connect the latch pilot contact to terminals G-H and the unlatch pilot contact to terminals G-L. NOTE: Jumpers must be installed as
proper operation.
NON-HAZARDOUS AREA
______-_-_-_-_-_-- HAZARDOUS AREA
CLASS
EJW
A,
DWISION 1,
1 AU0 1
E.
D. do 6.
F.I
I
I II
shown to
I II
1 !46
insure~V
9
INC.
0
Copyright 1990 OMEGA ENGINEERING,
manner, either wholly or in part for any purpose whatsoever without written permission from OMEGA ENGINEERING, INC.
All rights reserved including illustrations. Nothing in this
M1224/1290
,
manual+may
be reproduced in any
Loading...