Omega Products LDPF63100 User Manual

M
M-X
EXTRA LARGE DISPLAY METER
FOR DIGITAL INPUT
LDPF63100 Series
$
696
Large LED Display
Readable to 54 m (180')
Digital Input; Count and
Rate Input Serial Slave
Alarms, Analog Output,
and Communication
Programmable
User Inputs
Universal AC Powered
(85 to 250 Vac)
PC Software for Meter
Configuration
NEMA 4X (IP65)
The LDPF63100 display is a versatile display that can increase productivity by offering the plant floor or production area a large visual display of their current status. Whether your measurement is rate, count, or time. The LDPF63100 can satisfy your requirement. The displays accept various digital inputs through the use of input modules that allow the unit to adapt to most any application. Additional plug-in option cards can add alarms, analog output, and communication/ bus capabilities, making the it a truly intelligent panel meter.
SPECIFICATIONS
Display: 101 mm (4") red LED
6-Digit (-99999 to 999999) Power Requirements: 85 to 250 Vac, 50/60 hz, 10 VA
Inputs A and B
DIP switch selectable to accept pulses from a variety of sources including switch contacts, TTL outputs, magnetic pickups and all standard sensors. Logic: Input trigger levels V
IL
= 1.5V max; VIH= 3.75V min Current Sinking: Internal 7.8 KΩ pull-up to +12 Vdc, I
MAX
= 1.9 mA Current Sourcing: Internal 3.9 KΩ pull-down, 7.3 mA max @ 28 Vdc, V
MAX
= 30 Vdc Filter: Damping capacitor provided for switch contact bounce. Limits input frequency to 50 hz and input pulse widths to 10 msec minimum
Magnetic Pickup
Sensitivity: 200 mV peak Hysteresis: 100 mV Input Impedance: 3.9 KΩ @ 60 hz Max Input Voltage: ±40V peak,
30 Vrms
Dual Count Modes:
When any dual count mode is used, then user inputs 1 and/or 2 will accept the second signal of each signal pair. The user inputs do not have the Logic/Mag, High/Low Freq, and Sink/Source input setup switches. The user inputs are inherently a logic input with no low frequency filtering. Any mechanical contacts used for these inputs in a dual count mode must be debounced externally. The user input may only be selected for sink/source by the user jumper placement.
Prescaler Output
NPN Open Collector: I
SNK
= 100 mA
max @ V
OL
= 1 Vdc max, VOH= 30 Vdc max with duty cycle of 25% min and 50% max
Display Indication: Three vertical dots on the left side of the unit identify the displays for the following modules Setpoint Indication: Four vertical dots on the right side of the unit identify the setpoint “ON” condition, with SP 1 being the top position through SP 4 at the bottom Programming: The unit is a large display, designed to be remotely mounted. Therefore, the unit does not have a programming keypad. Unit programming should be accomplished by one of the following methods:
Rear Terminal Block: External switches can be wired via the terminal block to allow unit programming. A minimum of 3 switches would be required.
Optional Programming Remote (LD6-PGM): This option provides a
10' interconnecting cable and programming box. The programming remote contains buttons allowing easy programming of the display.
Optional Serial Programming:
You can purchase an RS232 or RS485 Comms card and program the unit via Windows
®
based software programs. See available Comm cards shown on ordering page
Environmental Conditions
Operating Temperature Range:
Determined by the input module
Storage Temperature Range:
-40 to 60°C (-40 to 15°F)
Operating and Storage Humidity:
0 to 85% max RH (non-condensing)
Altitude: Up to 2000 m (6562')
Mounting Requirements:
Max panel thickness is 9.5 mm (0.375") Min panel thickness for NEMA 4 (IP65) sealing is 1.52 mm (0.060")
M-X
Dimensions: mm (in)
629
(24.77)
183
(7.22)
118
(4.65)
91.5
(3.60)
154.7 (6.09)
Connections: Wiring connections are made to the terminal block and input module via high compression cage-clamp terminal blocks
Terminal Block Wiring
Wire Strip Length: 7.5 mm (0.3") Wire Gage: 30-12 AWG copper wire Maximum Torque: 5-7 inch-lbs
(0.58-0.81 N-m) Construction: Aluminum front panel, enclosure, and rear cover with textured black polyurethane paint for scratch and corrosion resistance protection. Sealed front panel meets NEMA 4X (IP65) specifications for indoor use when properly installed. Installation Category II, Pollution Degree 2. Panel gasket and keps nuts included.
Weight: 2.25 kg (5 lbs) (less module)
OPTION BOARDS SPECIFICATIONS
RS485 Communication Card (LDP6-CDC10 or LDP6-CDC1C)
Type: RS485 multi-point
balanced interface
Isolation to Sensor and User Input Commons: 500 Vrms for 1 min Working Voltage: 50V not isolated from
all other commons
Baud Rate: 300 to 19.2k Data Format: 7/8 bits; odd, even,
or no parity Bus Address: 0 to 99, max 32 meters per line Transmit Delay: Selectable; 2 to 50 msec or 50 to 100 msec
RS232 Communication Card (LDP6-CDC20 or LDP6-CDC2C) Type: RS232 half duplex
Isolation to Sensor and User Input Commons: 500 Vrms for 1 min Working Voltage: 50V not isolated from
all other commons
Baud Rate: 300 to 19.2k Data Format: 7/8 bits; odd, even
or no parity
Modbus Communications Card (LDP6-CDC40 or LDP6-CDC4C)
Type: RS485; RTU and ASCII
MODBUS modes
Isolation to Sensor and User Input Commons: 500 Vrms for 1 minute Working Voltage: 50V not isolated from
all other commons
Baud Rates: 300 to 38400 Data: 7/8 bits Parity: No, Odd, or Even Addresses: 1 to 247 Transmit Delay: Programmable; See
Transmit Delay explanation.
Analog Output Card (LDP6-CDL)
Types: 0 to 20 mA, 4 to 20 mA and
0 to 10 Vdc
Isolation to Sensor and User Input Commons: 500 Vrms for 1 min Working Voltage: 50V not isolated
from all other commons Accuracy: 0.17% of FS (18 to 28°C);
0.4% of FS (0 to 50°C)
Resolution: 1/3500 Compliance: 10 Vdc: 10 KΩ load min 20 mA: 500 Ω load max Update Time: 200 msec max to within
99% of final readout value (digital filter and internal zero correction disabled) 700 msec max (digital filter disabled, internal zero correction enabled) LDP63000-AC: 1 sec max to within 99% of final readout value (digital filter disabled)
Setpoint Output Cards (Four Types of Field Installable Cards)
Response Time: 200 msec max
to within 99% of final readout value (digital filter and internal zero correction disabled) 700 msec max (digital filter disabled, internal zero correction enabled)
LDP63000-AC Only: 1 sec max to within 99% of final readout value (digital filter disabled) LDP63000-T Only: 200 msec typ; 700 msec max (digital filter disabled)
Dual Relay Card (LDP6-CDS10)
Type: Two FORM-C relays Isolation to Sensor and User Input Commons: 2000 Vrms for 1 min Working Voltage: 250V Contact Rating:
One Relay Energized: 5 Amps
@ 120/240 Vac or 28 Vdc (resistive load), 1⁄8 HP @120 Vac, inductive load (total current with both relays energized not to exceed 5 Amps) Life Expectancy: 100 K cycles min at full load rating. External RC snubber extends relay life for operation with inductive loads
Quad Relay Card (LDP6-CDS20)
Type: Four FORM-A relays Isolation to Sensor and User Input
Commons: 2300 Vrms for 1 min Working Voltage: 250 Vrms Contact Rating:
One Relay Energized: 3 amps @
250 Vac or 30 Vdc (resistive load),
1
10 HP @120 Vac, inductive load (total current with all four relays energized not to exceed 4 Amps)
Life Expectancy: 100 K cycles min at full load rating. External RC snubber extends relay life for operation with inductive loads
Quad Sinking Open Collector
(LDP6-CDS30) Type: Four isolated sinking NPN
transistors
Isolation to Sensor and User Input Commons: 500 Vrms for 1 min Working Voltage: 50V not isolated from
all other commons Rating: 100 mA max @ V
SAT
= 0.7V max
V
MAX
= 30V
Quad Sourcing Open Collector
(LDP6-CDS40) Type: Four isolated sourcing PNP
transistors
Isolation to Sensor and User Input Commons: 500 Vrms for 1 min Working Voltage: 50V not isolated from
all other commons
Rating:
Internal Supply: 24 Vdc ± 10%,
30 mA max total all four External Supply: 30 Vdc max, 100 mA max each output
Programming Software (Free download at omega.com)
Allows configuration of the LDPF63100 meter from a PC. This software offers standard drop-down menu commands, that make it easy to program the meter. The unit program can then be saved in a PC file for future use. A serial plug-in card is required to program the meter using the software.