Omega Products LDP6-CDL10 Installation Manual

LDP6-CCDL10
Analog Output Option Card
M4538-0408
1
Caution: The option and main circuit cards contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges. Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
Warning: Exposed line voltage exists on the circuit boards. Remove all power to the meter AND load circuits before accessing the unit.
1. Remove the main assembly from the rear of the case. Squeeze the finger holds on the rear cover, or use a small screwdriver to depress the side latches to release it from the case. It is not necessary to separate the rear cover from the main circuit card.
2. Locate the option card connector for the type of option card to be installed. Hold the unit by the rear connector, not the display board, when installing an option card.
3. Install the option card by aligning the option card connector with the slot bay in the rear cover. The cards are keyed by position with different main board connector locations. Be sure the connector is fully engaged and the tab on the option card rests in the alignment slot on the display board.
4. Slide the assembly back into the case. Be sure the rear cover latches fully into the case.
5. Apply the option card label to the bottom side of the meter. Do not cover the vents on the top surface of the meter. The surface of the case must be clean for the label to adhere properly. Apply the label to the area designated by the large case label.
DESCRIPTION
This bulletin serves as a guide for the installation, configuration and operation of the Analog Output card. The analog output can be configured for 0 to 20 mA, 4 to 20 mA or 0-10 VDC. Only one range can be used at a time.
The meter can be fitted with up to three optional plug-in cards. The slot bays of the plug-in cards are dedicated to a particular card function. The plug-in card functions are: serial communications, analog output and setpoint output. Only one card from each function category can be installed.
TOP VIEW
LP0684A
INSTRUCTION
SHEET
Shop online at: omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info
Enter the analog output type. For 0-20 mA or 4-20 mA use terminals 18 and 19. For 0-10 V use terminals 16 and
17. Only one range can be used at a time.
ª
«

U:1&
ª
«
*OQ
"4*/
ANALOG TYPE
ANALOG ASSIGNMENT



SELECTION
0 to 10 V
4 to 20 mA
0 to 20 mA
RANGE
InP totLOHI
Enter the Display Value that corresponds to 0 mA (0-20 mA) , 4 mA (4-20 mA) or 0 VDC (0-10 VDC).
ª
«

"/-0
ANALOG LOW SCALE VALUE
ª
«

"/)*
ª
«

VEU
ª
«
-0
CVSO
ANALOG HIGH SCALE VALUE
ANALOG UPDATE TIME
PROBE BURN-OUT ACTION (DP63500 ONLY)
-19999 to 99999
-19999 to 99999
0.0 to 10.0
LO HI
MODULE 8 - Analog Output Parameters (
0VU
)
PARAMETER MENU
Indicates Program Mode Alternating Display.
Factory Settings are shown.
ª
«

U:1&
Parameter
Selection/Value
Enter the source for the analog output to retransmit:
InP = Display Input Value HI = Maximum Display Input Value LO = Minimum Display Input Value tot = Totalize Display Value
Enter the Display Value that corresponds to 20 mA (0-20 mA) , 20 mA (4-20 mA) or 10 VDC (0-10 VDC).
Enter the analog output update rate in seconds. A value of 0.0 allows the meter to update the analog output at a rate of 20/sec.
Enter the probe burn-out action. In the event of a temperature probe failure, the analog output can be programmed for low or high scale.
SPECIFICATIONS
Analog Output Card
Types: 0 to 20 mA, 4 to 20 mA and 0 to 10 VDC Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not isolated from all other commons.
DP63700 Only:
Isolation To Sensor Common: 1400 Vrms for 1 min.
Working Voltage: 125 V
Isolation To User Input Common: 500 Vrms for 1 min.
Working Voltage: 50 V
Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C) Resolution: 1/3500 Compliance:
10 VDC: 10 Kload min. 20 mA: 500 load max. (self-powered)
Update Time: 200 msec. max. to within 99% of final readout value (digital
filter and internal zero correction disabled) 700 msec. max. (digital filter disabled, internal zero correction enabled)
DP63700 only: 1 sec. max. to within 99% of final readout value (digital filter
disabled)