Omega Products LDP63200-4 User Manual

Large Display Process Meter
LDP63200 Series
Starts at
$
520
57 mm (2.25") and
Programmable Scaling
and Decimal Points
Programmable User InputDual 5 Amp
Form C Relay
Aluminum NEMA 4X
(IP65) Case Construction
RS232/RS485 Serial
Communications
Universally Powered
The LDP63200 Series are versatile large display meters available as a DC volt, current, or process meter with scaling, serial communications and dual relay outputs. The 5-digit displays are available in either 57 mm (2.25") or 101 mm (4") high red LED digits with adjustable display intensities. The 57 mm (2.25") high models are readable up to 39.6 m (130'). The 101 mm (4") high models are readable up to
54.9 m (180'). Both versions are constructed of a NEMA 4X (IP65) enclosure in light weight aluminum. All models also come with dual Form C relay outputs and RS232/ RS485 serial communications.
Specifications
Display: 5-digit, 57 mm (2.25") or
101 mm (4") intensity adjustable red LED (-99999 to 99999)
Power Requirements
AC Power: 50 to 250 Vac 50/60 Hz,
26 VA
DC Power: 21.6 to 250 Vdc, 11 W DC Out: ±24 Vdc at 100 mA if input
voltage is greater than 50 Vac/Vdc ±24 Vdc at 50 mA if input voltage is less than 50 Vdc
Isolation: 2300 Vrms for 1 min to all inputs and outputs
Input Ranges: Jumper selectable
4" High
LEDS
LDP63200-2, $520.
A/D Converter: 16 bit resolution A/D Conversion Rate: 6 readings/sec Display Response Time: 500 msec min
User Input
Software: Selectable pull-up (8.6 K) or
pull-down resistor (3.9 K) that determines active high or active low input logic.
Trigger levels: VIL= 1.0V max; VIH=
2.4V min; V Response Time: 5 msec typ; 50 msec
debounce (activation and release)
Communications
Type: RS485 or RS232 Isolation To Sensor and User Input
Commons: 500 Vrms for 1 min Working Voltage: 50V not isolated from
all other commons
Data: 7/8 bits Parity: No, odd or even Baud Rate: 300 to 38.4 K Bus Address: Selectable 0 to 99,
max 32 m (105') per line (RS485) Memory: Nonvolatile EEPROM retains
all programming parameters and max/min values when power is removed
Output
Type: Single FORM-C relay Isolation to Sensor and User Input
Commons: 1400 Vrms for 1 min Working Voltage: 150 Vrms Contact Rating:
Resistive Load:
5 amps @ 120/240 Vac or 28 Vdc
Inductive Load:
Life Expectancy: 100,000 min operations
MAX
= 28 Vdc
1
8 H.P. @ 120 Vac
M-1
LDP63200-4, $718.
2.25" High LEDS
Both shown smaller
than actual size.
Response Time
Turn On: 4 msec max Turn Off: 4 msec max
Environmental Conditions
Operating Temperature: 0 to 65°C
(32 to 149ºF) Storage Temperature: -40 to 70°C
(-40 to 158ºF)
Operating and Storage Humidity:
0 to 85% max RH (non-condensing)
Vibration According to IEC 68-2-6:
Operational 5 to 150 Hz, in X, Y, Z direction for 1.5 hours, 2 g’s (1 g relay)
Shock According to IEC 68-2-27:
Operational 30 g’s (10 g relay), 11 msec in 3 directions
Altitude: Up to 2000 m (6561') Connections: Internal removable
terminal blocks
Wire Strip Length: 10 mm (0.4") Wire Gage: 24-12 AWG copper wire,
90°C rated insulation only
Torque: 5.3 inch-lbs (0.6 N-m) max Cable Diameter: Outside diameter must
be 4.6 mm (0.181") to 7.9 mm (0.312") to maintain NEMA 4 (IP65) rating of cord grips
Construction: Aluminum enclosure, steel side panels with textured black polyurethane paint for scratch and corrosion resistance protection. Meets NEMA 4X (IP65) specifications. Installation Category II, pollution degree 2
Weight:
LDP63200-2: 2.04 kg (4.5 lb) LDP63200-4: 4.76 kg (10.5 lb)
M
Extended Warranty
Program
SM
X
Z
Y
Air Pressure Stabilization Vent
Dimensions: mm (in)
Model No. X (Length) Y (Height) Z (Center) LDP63200-2 406.4 (16) 101.6 (4) 304.3 (12)
LDP63200-4 660.4 (26) 200 (7.875) 558.8 (22)
D.C. Voltages: 200 mV, 2V, 20V, 200V, 10V
Input Accuracy at 23°C Input Temperature
Range Less than 85% RH Impedance Resolution Coefficient
200 mV 0.1% of span 1.027 M 10 µv 70 ppm/°C
2V 0.1% of span 1.027 M 0.1 mV 70 ppm/°C
20V 0.1% of span 1.027 M 1 mV 70 ppm/°C
200V 0.1% of span 1.027 M 10 mV 70 ppm/°C
10V 0.1% of span 1.027 M 1 mV 70 ppm/°C
D.C. Currents: 200 µA, 2 mA, 20 mA, 200 mA
Input Accuracy at 23°C Input Max Temperature
Range Less than 85% RH Impedance Input Signal Resolution Coefficient
200 µA 0.1% of span 1.111 k 15 mA 10 nA 70 ppm/°C
2 mA 0.1% of span 111 15 mA 0.1 µA 70 ppm/°C
20 mA 0.1% of span 11 15 mA 1 µA 70 ppm/°C
200 mA 0.1% of span 1 15 mA 10 µA 70 ppm/°C
57.15 (2.25)
Comes complete with operator’s manual.
Accessory (Field Installable)
Ordering Example: LDP63200-4, large 102 mm (4") display process meter, $718. OCW-3, OMEGACARE to a total of 5 years ($179), $718 + 179 = $897.
D.C. Process: 4 to 20 mA, 1 to 5 Vdc, 0/1 to 10 Vdc
OMEGACARESMextended warranty program is available for models shown on this page. Ask your sales representative for full details when placing an order. OMEGACARE covers parts, labor and equivalent loaners.
SM
Input Range Select Range
4 to 20 mA Use the 20 mA range
1 to 5 Vdc Use the 10V range
1 to 10 Vdc Use the 10V range
AVAILABLE FOR FAST DELIVERY!
To Order (Specify Model Number)
Model No. Price Description (Display Meter Only, No Outputs) LDP63200-2 $520 Large 57 mm (2.25") display process meter LDP63200-4 718 Large 102 mm (4") display process meter
Model No. Price Description LDP63200-PLUG $5 Plug to seal unused wiring connection ports (for NEMA 4 rating only)
SM
extends standard 2-year warranty
M-2
Loading...