Omega Products LDP63100-AC User Manual

Extra Large Display Meter
For Temperature and Process Inputs
LDP63100-E shown smaller than actual size.
LDP63100
U Large 101 mm (4") LED
Display Readable to 180'
U Various Input Types
Available
U Alarms, Analog Outputs,
and Communication
U Custom Units Label
with Backlight
U Programmable
User Inputs
U Universal AC Powered U NEMA 4 (IP65) U Field Installable Output
Cards (Optional)
The LDP63100 Series is a versatile display that can increase productivity by offering the plant floor or production area a large visual display of their current status. Whether your measurement needs are for temperature, voltage, current or process information, the LDP63100
can satisfy your requirements. The LDP63100 accepts various analog inputs which allow the unit to adapt to most any application. Additional plug-in option cards add alarms, analog outputs, and communication/ bus capabilities, making the LDP63100 an “intelligent” panel meter. The unit has a large display, designed to be remotely mounted, therefore the unit does not have a programming keypad. Unit programming can be accomplished through the use of external switches that can be wired via the terminal block; a minimum of 3 switches is required. An optional programming remote option provides a 10' interconnecting cable and programming box. The remote buttons make programming the display easy.
Specifications
Display: 101 mm (4") red LED, 5-digit,
-19999 to 99999 Power Requirements: 85 to 250 Vac,
50/60 Hz, 18 VA
Environmental Conditions: Storage Temperature Range:
-40 to 60°C (-40 to 140°F) Operating and Storage Humidity:
0 to 85% max RH (non-condensing) Altitude: Up to 2000 meters
Mounting Requirements:
Max Panel Thickness: 9.5 mm (0.375") Min Panel Thickness [NEMA 4
(IP65) Sealing]: 1.52 mm (0.060") Terminal Block Wiring:
Wire Strip Length: 7.5 mm (0.3") Wire Gage: 30-12 AWG copper wire Maximum Torque: 0.58 to 0.81 N-m
(5 to 7 in-lb) Construction: Aluminum front panel,
enclosure, and rear cover with textured black polyurethane paint for scratch and corrosion resistance protection; sealed front panel meets NEMA 4 (IP65) specifications for indoor use when properly installed—Installation Category II, Pollution Degree 2, panel gasket and keps nuts included
Weight: 2.25 kg (5 lb) Readout:
Resolution: Variable—0.1, 0.2, 0.5, or 1, 2, or 5°
Scale: °F or °C Offset Range: -19,999 to 99,999
display units
LDP63100-AC Isolation For All 4 Cards:
Isolation To Sensor Common: 1400 Vrms for 1 min
Working Voltage: 125V Isolation To User Input Common:
500 Vrms for 1 min Working Voltage: 50V
M
M-100
Thermocouple Inputs
Thermocouple Inputs:
Input Impedance: 20 MΩ Lead Resistance Effect: 0.03 µV/Ω
Max Continuous Overvoltage: 30V
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 60°C)
T -200 to 400°C (-328 to 752°F)
-270 to -200°C (-454 to -328°F) 1.2°C** 2.1°C E -200 to 871°C (-328 to 1600°F)
-270 to -200°C (-454 to -328°F) 1.0°C** 2.4°C J -200 to 760°C (-328 to 1400°F) 1.1°C 2.3°C K -200 to 1372°C (-328 to 2502°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.4°C R -50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C S -50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C B 100 to 300°C (100 to 572°F) 3.9°C 5.7°C
300 to 1820°C (572 to 3308°F) 2.8°C 4.4°C N -200 to 1300°C (-328 to 2372°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.1°C C 0 to 2315°C (32 to 4199°F) 1.9°C 6.1°C
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
The accuracy over the interval -270 to -200°C (-454 to -328°F) is a function of temperature, ranging from 1°C at -200°C and degrading to
**
7°C at -270°C. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
RTD Inputs
Type: 3- or 4-wire, 2-wire can be compensated for
lead wire resistance Excitation Current:
100 Ω Range: 165 µA 10 Ω Range: 2.6 mA
Lead Resistance: 100 Ω Range: 10 Ω/lead max 10 Ω Range: 3 Ω/lead max Max Continuous Overload: 30V
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C) 100 Ω Pt alpha = 0.00385 -200 to 850°C 100 Ω Pt alpha = 0.003919 -200 to 850°C 120 Ω Nickel alpha = 0.00672 -80 to 260°C 10 Ω Copper alpha = 0.00427 -100 to 260°C
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
(-328 to 1562°F) (-328 to 1562°F)
(-112 to 1562°F)
(-148 to 500°F)
0.4°C 1.6°C
0.4°C 1.6°C
0.2°C 0.5°C
0.4°C 0.9°C
Custom Ranges
Custom Ranges: Up to 16 data point pairs Input Range: -10 to 65 mV
0 to 400 Ω: High range 0 to 25 Ω: Low range
Display Range: -19999 to 99999
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C)
Custom mV Range -10 to 65 mV (1 µV res) 0.02% of rdg + 4µV 0.12% of rdg + 5 µV Custom 100 Ω Range 0 to 400 Ω (10 MΩ res) 0.02% of rdg + 0.04 Ω 0.12% of rdg + 0.05 Ω Custom 10 Ω Range 0 to 25 Ω (1 MΩ res) 0.04% of rdg + 0.005 Ω 0.20% of rdg + 0.007 Ω