Omega Products LDP63100-AC User Manual

Extra Large Display Meter
For Temperature and Process Inputs
LDP63100-E shown smaller than actual size.
LDP63100
U Large 101 mm (4") LED
Display Readable to 180'
U Various Input Types
Available
U Alarms, Analog Outputs,
and Communication
U Custom Units Label
with Backlight
U Programmable
User Inputs
U Universal AC Powered U NEMA 4 (IP65) U Field Installable Output
Cards (Optional)
The LDP63100 Series is a versatile display that can increase productivity by offering the plant floor or production area a large visual display of their current status. Whether your measurement needs are for temperature, voltage, current or process information, the LDP63100
can satisfy your requirements. The LDP63100 accepts various analog inputs which allow the unit to adapt to most any application. Additional plug-in option cards add alarms, analog outputs, and communication/ bus capabilities, making the LDP63100 an “intelligent” panel meter. The unit has a large display, designed to be remotely mounted, therefore the unit does not have a programming keypad. Unit programming can be accomplished through the use of external switches that can be wired via the terminal block; a minimum of 3 switches is required. An optional programming remote option provides a 10' interconnecting cable and programming box. The remote buttons make programming the display easy.
Specifications
Display: 101 mm (4") red LED, 5-digit,
-19999 to 99999 Power Requirements: 85 to 250 Vac,
50/60 Hz, 18 VA
Environmental Conditions: Storage Temperature Range:
-40 to 60°C (-40 to 140°F) Operating and Storage Humidity:
0 to 85% max RH (non-condensing) Altitude: Up to 2000 meters
Mounting Requirements:
Max Panel Thickness: 9.5 mm (0.375") Min Panel Thickness [NEMA 4
(IP65) Sealing]: 1.52 mm (0.060") Terminal Block Wiring:
Wire Strip Length: 7.5 mm (0.3") Wire Gage: 30-12 AWG copper wire Maximum Torque: 0.58 to 0.81 N-m
(5 to 7 in-lb) Construction: Aluminum front panel,
enclosure, and rear cover with textured black polyurethane paint for scratch and corrosion resistance protection; sealed front panel meets NEMA 4 (IP65) specifications for indoor use when properly installed—Installation Category II, Pollution Degree 2, panel gasket and keps nuts included
Weight: 2.25 kg (5 lb) Readout:
Resolution: Variable—0.1, 0.2, 0.5, or 1, 2, or 5°
Scale: °F or °C Offset Range: -19,999 to 99,999
display units
LDP63100-AC Isolation For All 4 Cards:
Isolation To Sensor Common: 1400 Vrms for 1 min
Working Voltage: 125V Isolation To User Input Common:
500 Vrms for 1 min Working Voltage: 50V
M
M-100
Thermocouple Inputs
Thermocouple Inputs:
Input Impedance: 20 MΩ Lead Resistance Effect: 0.03 µV/Ω
Max Continuous Overvoltage: 30V
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 60°C)
T -200 to 400°C (-328 to 752°F)
-270 to -200°C (-454 to -328°F) 1.2°C** 2.1°C E -200 to 871°C (-328 to 1600°F)
-270 to -200°C (-454 to -328°F) 1.0°C** 2.4°C J -200 to 760°C (-328 to 1400°F) 1.1°C 2.3°C K -200 to 1372°C (-328 to 2502°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.4°C R -50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C S -50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C B 100 to 300°C (100 to 572°F) 3.9°C 5.7°C
300 to 1820°C (572 to 3308°F) 2.8°C 4.4°C N -200 to 1300°C (-328 to 2372°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.1°C C 0 to 2315°C (32 to 4199°F) 1.9°C 6.1°C
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
The accuracy over the interval -270 to -200°C (-454 to -328°F) is a function of temperature, ranging from 1°C at -200°C and degrading to
**
7°C at -270°C. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
RTD Inputs
Type: 3- or 4-wire, 2-wire can be compensated for
lead wire resistance Excitation Current:
100 Ω Range: 165 µA 10 Ω Range: 2.6 mA
Lead Resistance: 100 Ω Range: 10 Ω/lead max 10 Ω Range: 3 Ω/lead max Max Continuous Overload: 30V
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C) 100 Ω Pt alpha = 0.00385 -200 to 850°C 100 Ω Pt alpha = 0.003919 -200 to 850°C 120 Ω Nickel alpha = 0.00672 -80 to 260°C 10 Ω Copper alpha = 0.00427 -100 to 260°C
After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and
*
accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
(-328 to 1562°F) (-328 to 1562°F)
(-112 to 1562°F)
(-148 to 500°F)
0.4°C 1.6°C
0.4°C 1.6°C
0.2°C 0.5°C
0.4°C 0.9°C
Custom Ranges
Custom Ranges: Up to 16 data point pairs Input Range: -10 to 65 mV
0 to 400 Ω: High range 0 to 25 Ω: Low range
Display Range: -19999 to 99999
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C)
Custom mV Range -10 to 65 mV (1 µV res) 0.02% of rdg + 4µV 0.12% of rdg + 5 µV Custom 100 Ω Range 0 to 400 Ω (10 MΩ res) 0.02% of rdg + 0.04 Ω 0.12% of rdg + 0.05 Ω Custom 10 Ω Range 0 to 25 Ω (1 MΩ res) 0.04% of rdg + 0.005 Ω 0.20% of rdg + 0.007 Ω
M-101
Process Inputs— Excitation Power:
Transmitter Power: 24 Vdc, ±5%,
regulated, 50 mA max
Reference Voltage: 2 Vdc, ± 2% Compliance: 1 kΩ load min (2 mA max)
Max
Input Accuracy* Accuracy* Impedance/ Continuous Display
Temperature Coefficient:
40 ppm/°C max
Reference Current: 1.75 mAdc, ± 2% Compliance: 10 kΩ load max Temperature Coefficient:
40 ppm/°C max
Range (18 to 28°C) (0 to 50°C) Compliance Overload Resolution
20 mA 0.03% of rdg 0.12% of rdg (-2 to 26 mA) + 2 µA + 3 µA 20 Ω 150 mA 1 µA
10 Vdc 0.03% of rdg 0.12% of rdg (-1 to 13 Vdc) + 2 mV + 3 mV 500 kΩ 300V 1 mV
After 20 minute warm-up. Accuracy is specified in 2 ways: accuracy over an 18 to 28°C
*
(64 to 82°F) with a 10 to 75% RH environment and accuracy over a 0 to 50°C (32 to 122°F) with a 0 to 85% RH (non-condensing environment). Accuracy over the 0 to 50°C (32 to 122°F) range includes the temperature coefficient effect of the meter.
True RMS—Excitation Power:
Transmitter Power: 24 Vdc,
±5%, regulated, 50 mA max
True RMS AC Voltage/Current Isolation To Option Card Commons and User Input Commons: 125 Vrms
Isolation To AC Power Terminals:
250 Vrms
Maximum Crest Factor (Vp/VRMS):
5 @ FS input
Input Coupling: AC, or AC and DC Input Capacitance: 10 pF Common Mode Voltage:
125 Vac working
Common Mode Rejection (DC to 60 Hz): 100 dB
True RMS Voltage/Current Inputs
Input Max DC Impedance Continuous
Range Accuracy* Blocking (60 Hz) Overload Resolution
200 mV
+ 0.4 mV
2V
+ 2 mV
20V
+ 20 mV
300V
+ 0.3V
200 µA
+ 0.4 µA
2 mA
+ 2 µA
20 mA
+ 20 µA
200 mA
+ 0.2 mA
5 A
+ 5 mA
Conditions for accuracy specification: 20 minutes warm-up, 18 to 28°C (64 to 82°F)
*
temperature range, 10 to 75% RH non-condensing, 50 Hz to 400 Hz sine wave input, 1% to 100% of range. Add 0.1% reading + 20 counts error over 0 to 50°C (32 to 122°F) range, add
0.2% reading + 10 counts error for crest factors up to 3, add 1% reading up to 5, add 0.5% reading + 10 counts of DC component and add 1% reading + 20 counts error over 20 Hz to 10 KHz range.
Non-repetitive surge rating: 15 A for 5 seconds.
**
Inputs are directly coupled to the input divider and shunts. Input signals with high DC
***
component levels may reduce the usable range.
0.1% of rdg
0.1% of rdg
0.1% of rdg
0.2% of rdg
0.1% of rdg
0.1% of rdg
0.1% of rdg
0.1% of rdg
0.5% of rdg
±10V 686 kΩ 30V 0.01 mV
±50V 686 kΩ 30V 0.1 mV
±300V 686 kΩ 300V 1 mV
±300V*** 686 kΩ 300V 0.1V
±15 mA 1.11 kΩ 15 mA 0.01 µA
±50 mA 111 Ω 50 mA 0.1 µA
±150 mA 11.1 Ω 150 mA 1 µA
±500 mA 1.1 Ω 500 mA 10 µA
±7 A*** 0.02 Ω 7 A** 1 mA
Option Boards Specifications RS232/RS485
RS485 Communication Card
Type: RS485 multi-point balanced
interface
Isolation To Sensor and User Input Commons: 500 Vrms for 1 min
Working Voltage: 50V (not isolated from
all other commons)
Baud Rate: 300 to 19.2 K Data Format: 7/8 bits; odd, even, or no parity Bus Address: 0 to 99, max 32 m per line Transmit Delay: Selectable, 2 to 50 ms or
50 to 100 msec
RS232 Communication Card
Type: RS232 half duplex Isolation To Sensor and User Input
(Commons): 500 Vrms for 1 min Working Voltage: 50V (not isolated from all
other commons)
Baud Rate: 300 to 19.2 K Data Format: 7/8 bits; odd, even, or no parity
MODBUS® Specifications
Type: RS485, RTU and ASCII MODBUS
modes
Isolation To Sensor and User Input Commons: 500 Vrms for 1 minute
Working Voltage: 50V, not isolated from all
other commons
Baud Rates: 300 to 38400 Data: 7/8 bits Parity: No, odd, or even Addresses: 1 to 247 Transmit Delay: Programmable, see
transmit delay explanation
Analog Output Card
Types: 0 to 20 mA, 4 to 20 mA and
0 to 10 Vdc
Isolation To Sensor and User Input Commons: 500 Vrms for 1 min
Working Voltage: 50V, not isolated from all
other commons Accuracy: 0.17% of FS (18 to 28°C); 0.4%
of FS (0 to 50°C)
Resolution: 1/3500 Compliance:
10 Vdc: 10 kΩ load minimum 20 mA: 500 Ω (Ω) load max Update Time: 200 ms max to within 99%
of final readout value (digital filter and internal zero correction disabled), 700 ms max (digital filter disabled, internal zero correction enabled)
LDP63100-AC Only: 1 s max to within 99% of final readout value (digital filter disabled)
M
M-102
DC Inputs
183
(7.22)
Max Input Accuracy Accuracy Impedance/ Continuous Range (18 to 28°C) ( 0 to 50°C) Compliance Overload Resolution
±200 µAdc
+ 0.03 µA + 0.04 µA
±2 mAdc
+ 0.3 µA + 0.4 µA
±20 mAdc
+ 3 µA + 4 µA
±200 mAdc
+ 30 µA + 40 µA
±2 Adc
+ 0.3 mA + 0.4 mA
±200 mVdc
+ 30 mV + 40 mV
±2 Vdc
+ 0.3 mV + 0.4 mV
±20 Vdc
+ 3 mV + 4 mV
±300 Vdc
+ 30 mV + 40 mV
100 Ω
+ 30 MΩ + 40 MΩ
1000 Ω
+ 0.3 Ω + 0.4 Ω
10 kΩ
+ 1 Ω + 1.5 Ω
After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over an 18 to 28°C
*
and 10 to 75% RH environment; and accuracy over a 0 to 50°C and 0 to 85% RH (non­condensing environment). Accuracy over the 0 to 50°C range includes the temperature coefficient effect of the meter.
0.03% of rdg 0.12% of rdg
0.03% of rdg 0.12% of rdg
0.03% of rdg 0.12% of rdg
0.05% of rdg 0.15% of rdg
0.5% of rdg 0.7% of rdg
0.03% of rdg 0.12% of rdg
0.03% of rdg 0.12% of rdg
0.03% of rdg 0.12% of rdg
0.05% of rdg 0.15% of rdg
0.05% of rdg 0.2% of rdg
0.05% of rdg 0.2% of rdg
0.05% of rdg 0.2% of rdg
1.11 kΩ 15 mA 10 nA
111 Ω 50 mA 0.1 µA
11.1 Ω 150 mA 1 µA
1.1 Ω 500 mA 10 µA
0.1 Ω 3 A 0.1 mA
1.066 MΩ 100V 10 µV
1.066 MΩ 300V 0.1 mV
1.066 MΩ 300V 1 mV
1.066 MΩ 300V 10 mV
0.175V 30V 0.01 Ω
1.75V 30V 0.1 Ω
17.5V 30V 1 Ω
183
(7.22)
629
(24.77)
91.5
(3.60)
154.7 (6.09)
118
Dimensions: mm (inch)
(4.65)
M-103
Setpoint Output Cards:
Type: Four types of field-installable cards Response Time: 200 ms max to within
99% of final readout value (digital filter and internal zero correction disabled), 700 ms max (digital filter disabled, internal zero correction enabled)
LDP63100-AC Only: 1 s max to within 99% of final readout value (digital filter disabled)
LDP63100-T Only: 200 ms typical, 700 ms max (digital filter disabled)
Dual Relay Card (LDP6-CDS10)
Type: Two form “C” relays Isolation to Sensor and User Input
Commons: 2000 Vrms for 1 minute Working Voltage: 250 Vrms Contact Rating:
1 Relay Energized: 5 A @ 120/240 Vac or 28 Vdc (resistive load), 120 Vac (inductive load); total current with both relays energized not to exceed 5 A
Life Expectancy: 100 K cycles min at full load rating; external RC snubber extends relay life for operation with inductive loads
1
8 HP @
Quad Relay Card (LDP6-CDS20)
Type: Four form “A” relays Isolation to Sensor and User Input
Commons: 2300 Vrms for 1 minute Working Voltage: 250 Vrms Contact Rating:
1 Relay Energized: 3 A @ 250 Vac or 30 Vdc (resistive load), 120 Vac (inductive load); total current with all 4 relays energized not to exceed 4 A
Life Expectancy: 100 K cycles min at full load rating; external RC snubber extends relay life for operation with inductive loads
1
10 HP @
Quad-Sinking Open Collector (LDP6-CDS30)
Type: Four isolated sinking
NPN transistors
Isolation To Sensor and User Input Commons: 500 Vrms for 1 min
Working Voltage: 50V, not isolated from
all other commons Rating: 100 mA max @ Vsat = 0.7V max,
Vmax = 30V
Quad-Sourcing Open Collector (LDP6-CDS40)
Type: Four isolated sourcing PNP
transistors
Isolation to Sensor and User Input Commons: 500 Vrms for 1 min
Working Voltage: 50V, not isolated from
all other commons Rating:
Internal Supply: 24 Vdc ± 10% , 30 mA max total for all 4
External Supply: 30 Vdc max, 100 mA max each output
LDP63100-E shown smaller than actual size.
To Order Visit omega.com/ldp63100 for Pricing and Details
Model No. Description (Display Meter Only, No Outputs) LDP63100-T Large display meter, temperature inputs, 85 to 250 Vac power LDP63100-E Large display meter, process Inputs, 85 to 250 Vac power LDP63100-DC Large display meter, universal DC inputs, 85 to 250 Vac power LDP63100-AC Large display meter, true RMS AC voltage/current inputs, 85 to 250 Vac power
Optional Plug-in Output Cards (Field Installable) Model No. Description
Optional Plug-in Output Cards (Field Installable)
Setpoint Alarms (Only 1 Alarm Card Can Be Installed Into Base Meter) LDP6-CDS10 Dual setpoint relay output card LDP6-CDS20 Quad setpoint relay output card LDP6-CDS30 Quad setpoint sinking open collector output card LDP6-CDS40 Quad setpoint sourcing open collector output card Analog Output LDP6-CDL10 Analog output card Communications (Only 1 Communications Card Can Be Installed Into Base Meter)* LDP6-CDC10 RS485 serial communications output card with terminal block LDP6-CDC1C Extended RS485 serial communications output card with dual RJ11 connector LDP6-CDC20 RS232 serial communications output card with terminal block LDP6-CDC2C Extended RS232 serial communications output card with 9-pin D connector LDP6-CDC40 MODBUS communications card LDP6-CDC4C Extended MODBUS communications card with dual RJ11 connector
M
Accessories (Field Installable) Model No. Description LDP6-PGM Programming remote for LDP63100 with 10' cable LDP6-ENC12 NEMA 4 (IP65) enclosure LDP631-SHR Shroud LDP6-EN/SH NEMA 4 (IP65) enclosure and shroud
Free software download available at omega.com/ldp63100 Comes complete with operator’s manual. Note: Adding option cards—meters can be fitted with up to 3 optional plug-in cards, however, only 1 card from each function type can be installed
at a time. The function types include setpoint alarms, analog output and communications. The cards can be installed initially or at a later date. Each optional plug-in card is shipped with installation and programming instructions.
Ordering Examples: LDP63100-E, large display meter, process inputs, 85 to 250 Vac power, LDP6-CDL10 analog output card. LDP63100-T, large display meter, temperature inputs, 85 to 250 Vac power.
M-104
Loading...