Omega Products LDP63000-DC-LV User Manual

M-95
Large Display Meter
LDP63000
Starts at
$
475
Large 38 mm (1.5") LED
Various Input Types
Available
Alarms, Analog Outputs,
and Communication
Custom Units Label
with Backlight
Programmable
User Inputs and Function Keys
Universal AC/DC
Powered
NEMA 4 (IP65) Field Installable Output
Cards (Optional)
Specifications
Display: 38 mm(1.5") red LED, 5-digit,
(-19999 to 99999)
Power Requirements:
AC Modules: 85 to 250 Vac,
50/60 Hz, 18 VA DC Modules: 11 to 36 Vdc or 24 Vac
±10%, 50/60 Hz, 14 W
Input: Accepts analog input modules Keypad: Five tactile membrane
switches integrated into the front panel
Environmental Conditions:
Operating Temperature Range:
Determined by the input module
Storage Temperature Range:
-40 to 60°C (-40 to 140°F)
Operating and Storage Humidity:
0 to 85% max RH (non-condensing)
Altitude: Up to 2000 meters Mounting Requirements:
Max Panel Thickness: 9.5 mm (0.375") Min Panel Thickness [NEMA 4
(IP65) Sealing]: 1.57 mm (0.060")
Connections: All wiring connections
are made to the input module via high-compression, cage-clamp terminal blocks
Construction: Steel front panel, enclosure, and rear cover with textured black polyurethane paint for scratch and corrosion resistance protection; sealed front panel meets NEMA 4 (IP65) specifications for indoor use when properly installed—Installation Category II, Pollution Degree 2, panel gasket and keps nuts included
Weight: 1.2 kg (2.7 lbs) (less module) Readout:
Resolution: Variable—0.1, 0.2, 0.5,
or 1, 2, or 5°
Scale: °F or °C Offset Range: -19,999 to 99,999
display units
The LDP63000 Series is a versatile display that can increase productivity by offering the plant floor or production area a large visual display of their current status. Whether your measurement needs are for temperature or process information, the LDP63000 can satisfy your requirements. With the use of a units label and backlighting, the display can be tailored to show the actual engineering unit. The LDP63000 display accepts various analog inputs through the use of input modules which allow the unit to adapt to most any application. Additional plug-in option cards can add alarms, analog output, and communication/bus capabilities, making the LDP63000 an “intelligent” panel meter.
LDP63000-E, $475, shown smaller than actual size.
M-96
M
Thermocouple Inputs
Thermocouple Inputs:
Input Impedance: 20 MΩ Lead Resistance Effect: 0.03µV/Ω Max Continuous Overvoltage: 30 V
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 60°C)
-200 to 400°C (-328 to 752°F)
-270 to -200°C (-454 to -328°F) 1.2°C** 2.1°C
-200 to 871°C (-328 to 1600°F)
-270 to -200°C (-454 to -328°F) 1.0°C** 2.4°C
-200 to 760°C (-328 to 1400°F) 1.1°C 2.3°C
-200 to 1372°C (-328 to 2502°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.4°C
-50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C
-50 to 1768°C (-58 to 3214°F) 1.9°C 4.0°C 100 to 300°C (100 to 572°F) 3.9°C 5.7°C
300 to 1820°C (572 to 3308°F) 2.8°C 4.4°C
-200 to 1300°C (-328 to 2372°F)
-270 to -200°C (-454 to -328°F) 1.3°C** 3.1°C 0 to 2315°C (32 to 4199°F) 1.9°C 6.1°C
* After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
** The accuracy over the interval -270 to -200°C (-454 to -328°F) is a function of temperature, ranging from 1°C at -200°C and degrading to 7°C at -270°C. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C) Custom mV Range -10 to 65 mV (1 µV res) 0.02% of rdg + 4µV 0.12% of rdg + 5 µV Custom 100 Ω Range 0 to 400 Ω (10 MΩ res) 0.02% of rdg + 0.04 Ω 0.12% of rdg + 0.05 Ω Custom 10 Ω Range 0 to 25 Ω (1 MΩ res) 0.04% of rdg + 0.005 Ω 0.20% of rdg + 0.007 Ω
Custom Ranges
Custom Ranges: Up to 16 data point pairs Input Range: -10 to 65 mV
0 to 400 Ω: High range 0 to 25 Ω: Low range
Display Range: -19999 to 99999
* After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
Input Type Range Accuracy* (18 to 28°C) Accuracy* (0 to 50°C) 100 Ω Pt alpha = .00385 -200 to 850°C
(-328 to 1562°F)
0.4°C 1.6°C
100 Ω Pt alpha = .003919 -200 to 850°C
(-328 to 1562°F)
0.4°C 1.6°C
120 Ω Nickel alpha = .00672 -80 to 260°C
(-112 to 1562°F)
0.2°C 0.5°C
10 Ω Copper alpha = .00427 -100 to 260°C
(-148 to 500°F)
0.4°C 0.9°C
RTD Inputs
Type: 3- or 4-wire, 2-wire can be compensated for
lead wire resistance
Excitation Current:
100 Ω Range: 165 µA 10 Ω Range: 2.6 mA
* After 20 minute warm-up. Accuracy is specified in 2 ways—accuracy over an 18 to 28°C (64 to 82°F) in a 15 to 75% RH environment and accuracy over a 0 to 50°C (32 to 122°F) in a 0 to 85% RH (non-condensing) environment. Accuracy specified over the 0 to 50°C (32 to 122°F) operating range includes meter tempco and ice point tracking effects. The specification includes the A/D conversion errors, linearization conformity, and thermocouple ice point compensation. Total system accuracy is the sum of meter and probe errors. Accuracy may be improved by field calibrating the meter readout at the temperature of interest.
Lead Resistance:
100 Ω Range: 10 Ω/lead max 10 Ω Range: 3 Ω/lead max
Max Continuous Overload: 30 V