It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark
to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as the guide contains important information relating to safety and EMC.
Page 3
Part 1: INTRODUCTION
1.1 Safety and EMC Considerations.....................................................................2
1.2 Before You Begin .............................................................................................2
Information that is especially important to note is identified by the following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the iServer.
CAUTION: Tells you about the risk of electrical shock.
CAUTION: Risk of danger. Tells you of circumstances or practices
that can affect the instrument’s functionality and must refer to
accompanying documents.
TIP: Provides you helpful hints.
!
•Two Temperature Channels
•Web Server
•Virtual Chart Recorder
•Two Relay Alarms
•Two Contact Closures
•2GB SD Flash Memory Card
•Password Protection
•Email Alarms
•Data Logging
•Real Time Clock
•Accurate Readings
•SNMP Trap
•LCD Display
•Back-up Battery 9Vdc
1
Page 8
!
1.1 Safety and EMC Considerations
Refer to the CE Approvals Section.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use twisted-pair wires for signal connections.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
1.2 Before You Begin
Inspecting Your Shipment: Remove the packing slip and verify that you have received
everything listed. Inspect the container and equipment for signs of damage as soon as
you receive the shipment. Note any evidence of rough handling in transit. Immediately
report any damage to the shipping agent. The carrier will not honor damage claims
unless all shipping material is saved for inspection. After examining and removing the
contents, save the packing material and carton in the event reshipment is necessary.
Customer Service: If you need assistance, please contact the Customer Service
Department nearest you.
Manuals, Software: The latest Operation Manual as well as free configuration software
(iConnect) and datalogging software (iLog) are available at the website listed on the
cover page of this manual or on the CD-ROM enclosed with your shipment.
1.3 Description
Monitor Temperature over the Internet -- The iSD provides Web-based temperature
monitoring in critical equipment and locations such as computer server rooms, clean
rooms, laboratories, museums, warehouses, or any remote facility.
View and record temperature on two independent thermocouple channels, over an
Ethernet network or the Internet with no special software—just a Web browser.
Email Alarms -- The device can trigger an alarm if temperature goes above or below a
set point that you determine. Your alarm can be sent by email to a single user or to a
group distribution list, including text messages to cell phones and PDA’s.
Physical Threats -- The iSD-TC includes screw terminals for two contact closures that
work with common alarm sensors. You can instruct the iSD monitor to send an alarm if a
door is opened, a window is broken, or a fire sprinkler goes off.
Power Failure -- The iSD monitor can trigger an alarm if the AC power fails. The iSD-TC
will continue to collect data for two days powered by a standard 9 Volt alkaline battery
(included). A failure on the Ethernet network will not interrupt data recording.
Local Alarms -- The iSD monitor includes two 1.5 Amp output relays that are controlled
by the alarm conditions you select. The relays can trigger flashing lights and a siren for
example to alert personnel near the scene.
With the easy Web-based setup page, the two relays can be programmed for two
temperature inputs, and high or low set points, as well as alarm conditions triggered by
contact closures. The relays can also be programmed to turn off when conditions return
to normal, or programmed to remain latched and require a manual reset.
2
Page 9
1.3 Description (continued)
View Charts and Graphs on the Web -- The iSD serves Active Web Pages to display
real time readings, display charts of temperature, or log data in standard data formats for
use in a spreadsheet or data acquisition program such as Excel or Visual Basic.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over
the LAN or Internet in real time. With the iSD, there is no need to invest time and money
learning a proprietary software program to log or chart the data.
Chart scales are fully adjustable on the fly. For example, the chart can display one
minute, one hour, one day, one week, one month or one year. Temperature can be
charted across the full span or within any narrow range. The iSD can display and chart
absolute measurements in two locations and a differential measurement between the two
locations.
The iSD can take thermocouple types J, K, T, E, R, S, B, C, N, and L measuring
temperatures up to 1,820°C (3,308°F). The iSD includes a pair of type K thermocouples.
Link to Web CAM or IP Camera -- The Web page includes a link to a “Web Cam” or “IP
camera” (not included). If you get a message about an alarm condition, you can quickly
click on the link to view the actual scene over the Internet.
SD Flash Memory Card -- The iServer comes complete with a removable 2 GB SD
Flash Memory card that can store up to seven years of readings taken at ten second
intervals. The data is recorded on widely available SD (Secure Digital) flash cards. The
format is a simple text file that is easily imported to spreadsheets and other programs. It
can be read on a PC or MAC with a USB card reader. You can also download the data
remotely over an Ethernet network or the Internet.
Installation and operation of the iServer requires no special training, tools, or software.
The device connects to any Ethernet network with standard cable and is powered by a
universal 100 to 240 Vac adapter which is supplied with the product.
Award-Winning Technology -- The iSD is simple to install and use, and features the
award-winning iServer technology that requires no special software except a Web
Browser. The iSD connects to an Ethernet Network with a standard RJ45 connector and
sends data in standard TCP/IP packets. It is easily configured with a simple menu using
a Web Browser and can be password protected. From within an Ethernet LAN or over
the Internet, the user simply types its IP address or an easy to remember name such as
"Cleanroom 5" or "Midwest Server Room" in any Web Browser, and the iSD-TC serves a
Web Page with the current readings.
Example:
A standard web browser can be used to monitor and chart temperature. The browser can
also be used to configure the device’s IP address, passwords for access and all
configuration parameters. An iLD Big Display can display the temperature values
received from an iServer over the Ethernet or the Internet.
The following example (see Figure 1.1) illustrates how you can hookup an iServer and
iLD to your network:
3
Page 10
1.3 Description (continued)
COL
ON
TX
RX
COMPUTER with
Standard Web Browser
SMTP SNMP Server
Temperature 1
Temperature 2
88.1 [3.47]
33.3
[1.31]
130.2 [5.13]
RECORDING
DHCP
LINK/ACT
100 BASE-T
C/ F TIME/IP BKLT
DUAL TEMPERATURE
Figure 1.1 iServer and iLD Big Display on the Ethernet Network
#
2.1 Dimensions
Dimensions are in mm
with inches in [ ].
Figure 2.1 Dimensions
4
If unit is to be mounted on a flat
surface, you may take the
bottom rubber feet off the unit.
Page 11
2.2 Wall Mounting
14.9 [0.59]
46.1 [1.81]
38.1 [1.50]
130.2 [5.13]
38.1 [1.50]
6.1 [0.24]
23.8 [0.94]
88.1 [3.47]
34.4 [1.36]
REAR WIRE
ENTRY AREA
ADDITIONAL MOUNTING OPTIONTO RETAIN UNIT TO MOUNTING BRACKET
USE #4 X 1/4" LONG SELF-TAPPING SCREW
DRILL 3.17 [0.125]
USE TWO, #4
FLAT HEAD SCREWS
TO MOUNT BRACKET
UNIT OUTLINE
CLIPS (3)
29.5 [1.16]
Position unit where required. Mark and drill the two #4 screw holes.
After bracket is mounted on the wall, align back of unit over the three bracket clips, once
engaged, slide downward, the unit will snap in place.
It is recommended that you ground your unit by connecting a wire to the
Return/Ground position of the relay connector, see Figure 2.6.
Dimensions are in mm
Figure 2.2 Wall Mounting
with inches in [ ].
5
Page 12
2.3 Parts of the iServer Unit
C/ F TIME/IP BKLT
RST
ETHERNET
9-12 Vdc
dc Power Input
SD Flash
Memory
Card
Standby
Button
Cover
Screw
(2 plcs)
SD Flash
Memory
Card
32 Digit LCD Display
Buttons
1
8
9Vdc Battery
(under cover)
iServer LEDs
Removable Plug
Connector for
Input and Outputs
(under cover)
1
614
TOP VIEW
+-
100 BASE-T
LINK/ACT
DHCP
RECORDING
STBY
The 9V battery
is the back-up
power for the
recording
function only.
Table 2.1 Parts of iServer Unit
ETHERNETRJ45 interface for 10/100BASE-T connection.
RESETButton: Momentary (Push and Release) resets power on unit; Push and Hold for
100 BASE-TLED (Green) On: Indicates 100 Mbps; LED Off: Indicates 10 Mbps.
LINK/ACTLED (Green) On/Blinking: Indicates good network link and network activities
RECORDINGLED (Green) Blinking Fast: Indicates that the unit is recording. LED Blinking:
TIME/IPButton: Press repeatedly to change LCD display from: 1) Date and Time;
Figure 2.3 Parts of the iServer Unit
10 seconds to reset unit to factory defaults and reset power.
(receiving or sending packets).
DHCPLED (Yellow): When DHCP is enabled, once the iServer receives the IP
parameters from the DHCP server this LED will turn Solid yellow.
during back-up battery operation according to sampling rate, or recording interval
if recording is ON.
°C/°FButton: Press to change LCD display units of measurement between °C and °F.
Press and Hold along with TIME/IP button during power-on, this will enable
DHCP mode.
2) iServer’s IP address; 3) Temperature1, Temperature 2. Press and Hold
along with °C/°F button during power up, this will enable DHCP mode.
6
Page 13
2.3 Parts of the iServer Unit (continued)
MOUNTING
SCREWS (2)
SD FLASH
CARD
COVER
RELAY
CONNECTOR
TRAY
I/O CONTACT
CONNECTOR
ETHERNET &
DC POWER
CONNECTORS
BATTERY
LOCATION
THERMOCOUPLE
CONNECTORS
BKLTButton: Push and Hold to display Backlight on LCD when it is running on the
STBYButton: 1) Stops the recording; 2) Press before ejecting Flash Card.
2.4 Disassembly Instruction
You may need to open the unit for one of the following reasons:
• To wire relay connector or I/O connector. (Refer to Figure 2.6)
• To connect or replace the battery.
Disconnect the power supply before proceeding.
• Make sure the flash memory card is fully inserted (or removed), before removing the cover.
Remove cover, by removing 2 mounting screws on each side.
back-up battery (backlight is always on while running on the ac adapter).
NOTE: display will show “Safe to Eject SD” after button has been pressed
Press STBY
before ejecting
Flash Card.
NOTE: display will
show “Safe to
Eject SD” after
button has been
pressed.
Figure 2.4 Opening the Unit
7
Page 14
2.4.1 Battery Installation
KEEP INSULATOR COVER
ON BATTERY CLIP
WHEN BATTERY IS NOT
BEING USED
TRAY
REMOVE BATTERY CLIP
INSULATOR COVER AND
STORE AGAINST BATTERY
WHEN BATTERY IS BEING USED.
INSULATOR COVER
9 VDC BATTERY
Figure 2.5 Battery Installation
2.5 Network Communication Interfaces
2.5.1 10/100 BASE-T RJ-45 Pinout
The 10/100BASE-T Ethernet network
system is used in the iServer for
network connectivity. The 10 Mbps or
100 Mbps twisted-pair Ethernet system
operates over two pairs of wires. One
pair is used for receiving data signals
and the other pair is used for
transmitting data signals. This means
that four pins of the eight-pin connector
are used.
PinNameDescription
1+Tx+ Transmit Data
2-Tx- Transmit Data
3+RX+ Receive Data
4N/CNot Connected
5N/CNot Connected
6-Rx- Receive Data
7N/CNot Connected
8N/CNot Connected
Figure 2.6 RJ45 Pinout
For CE compliance at 100 Mbps: use shielded cable, opposite end of cable must
be grounded.
2.5.2 Connecting iServer to PC/Hub/Switch/Router
The iServer’s Ethernet interface can automatically detect the Rx and Tx lines on a
twisted pair Ethernet cable (MDI/MDIX Auto Cross). Therefore, to connect an iServer to a
PC/Hub/Switch/Router, either a straight-through or a cross-over cable can be used.
On certain devices (like iServer), it is possible for the hardware to automatically
correct errors in cable selection, making the distinction between a “straightthrough” cable and a “cross-over” cable unimportant. This capability is known as
“Auto MDI/MDIX”.
8
Page 15
2.6 Relay and I/O Wiring Connections
To access the Relay and I/O Connectors you must remove the cover, refer to Section 2.4.
It is recommended that you ground your unit by connecting a wire to the
Ground/Return position of the relay connector or by wrapping a wire around the
case’s bottom screw. Refer to Figure 3.1 for location.
Figure 2.7 Relay and I/O Contact Connections
9
Page 16
FIRMWARE
VERSION #
MAC ADDRESS LABEL
IN HEX CODE
REMOVE DEFAULT IP ADDRESS LABEL
AND PUT NEW CUSTOMER'S IP ADDRESS
1
SCREW FOR
GROUNDING UNIT
#!
3.1 Network Protocols
The iServer can be connected to an Ethernet network communicating through standard
IP protocols including TCP, UDP, SNMP, SMTP, ARP, HTTP (WEB access), DNS, DHCP,
ICMP, SNTP, and Telnet.
3.2 Ethernet (MAC) Address
MAC (Media Access Control) address is a unique hardware number for Ethernet devices
like computers, network switches, print servers, etc. When you're connected to an
Ethernet LAN using a computer you can see a table of IP addresses called “ARP table”
stored on that computer. The ARP table relates IP addresses of devices on a network to
their corresponding MAC addresses. The MAC address can be found on a label
attached to your Ethernet device and it contains 6 bytes (12 characters) of hexadecimal
numbers XX:XX:XX:XX:XX:XX hex
For example: 0A:0C:3D:0B:0A:0B
Remove the small label with the default IP address of 192.168.1.200 and there
will be room to put your IP address. See Figure 3.1
Figure 3.1 Labeling
101011
Page 17
3.3 DHCP
DHCP, Dynamic Host Configuration Protocol, enables computers and network devices to
receive their IP configurations from a DHCP server.
If DHCP is enabled on your iServer, as soon as the iServer that is connected to the
network is powered on, there will be an exchange of information between the iServer and
the DHCP server. As a result, the DHCP server will assign an IP address, a Gateway
address, a Subnet Mask, and a DNS address to the iServer. Note that the DHCP server
must be correctly configured to make such assignments.
If fixed or static IP address is desired, the DHCP function must be disabled.
The iServer is shipped with DHCP disabled (factory default).
The DHCP can be enabled by accessing the iServer’s web server and selecting Network
menu (refer to Section 4.4.2) or by pressing and holding the two front buttons °C/°F and
TIME/IP during power-on (refer to Section 2.3).
It’s very important to communicate with the network administrator in order to
understand DHCP and its existing configurations on the host server before
enabling DHCP on the iServer.
The iServer is shipped with a default static IP address of 192.168.1.200 and
Subnet Mask of 255.255.255.0.
3.4 DNS
DNS, Domain Name System, enables computers and devices to be recognized over a
network based on a specific name instead of IP addresses.
For example, instead of having to use http://192.168.1.200 (IP address), you would use
http://isdb870 or any name up to sixteen alphanumeric characters defined as a Host
Name in the iServer’s web server.
The default Host Name for an iServer is "isd" followed by the last four digits of the MAC
address of that iServer unit.
On Windows servers where DHCP and DNS are separate functions it is very
important to configure the DHCP server to communicate with DNS in order for
the iServer’s Host Name to correctly respond. If you cannot access the iServer
using its Host Name, please contact your network administrator to make sure
DHCP and DNS servers are linked together.
If DNS server address is setup, all Host Names reported during weblink configuration
(i.e. SMTP server IP, SNTP server IP, SNMP trap server IP, etc.) will be translated into IP
addresses.
3.5 IP Address
Every active device connected to the TCP/IP network must have a unique IP address.
This IP address is used to build a connection to the iServer.
All network devices like computers that use TCP/IP protocol to communicate with each
other should have a unique 32-bit address called IP address. The IP address is divided
into two portions, the network ID and the host ID. For instance, every computer on the
same network uses the same network ID. At the same time, all of them have different
host IDs. For more details about the IP address see Appendix B.
Page 18
3.6 Port Number
All TCP connections are defined by the IP address and a port number. A port number is
an internal address that provides a TCP/IP interface between an application software on
a computer and a device on the network or between two devices on the network.
There are two default TCP port (socket) numbers assigned to the iServer:
1) Port 2000: Once a TCP connection is made to the iServer using port 2000 or any
port number that is configured on the iServer for Local Port (see Network menu,
Section 4.4.2), the iServer can then be polled for variables like temperature,
humidity, etc. using commands. For the list of commands see Section 4.9.1.
2) Port 2002: This port is the iServer’s network console port for reading or changing
the settings within the iServer. For the list of settings refer to Section 4.8.1. For both
of the above cases, for example, a Telnet application can be used.
Depending on user’s preference and network setup, the iServer can be configured in
several ways:
Using the latest versions of Web browsers like Internet Explorer, Firefox, Opera, or
Safari (iPhone) the iServer’s Web server can be accessed, see Section 4.2.
It can also be configured using a TCP connection to port 2002 using a command line
interface, see Section 4.8.1.
The iCONNECT Configuration Software can also be used to find and configure the
iServer over the Ethernet, see Section 4.1.2.
Before you configure the iServer, you will need to assign an IP address to the
unit. Refer to Section 4.1.1, 4.1.2 or 4.1.3.
4.1 IP Address Assignment
4.1.1 DHCP (Method 1)
The DHCP server will assign an IP address, see Section 3.3.
4.1.2 ARP HTTPget Commands (Method 2)
You can download the HTTPget program from our web site to use it for this section.
1. From the Command line (DOS prompt) where you keep the HTTPget.exe file, type the
following:
arp -s 128.100.101.76 00-03-34-00-b8-70press the <Enter> key
128.100.101.76, for example, is the IP address that you want to assign to your iServer
and 00-03-34-00-b8-70 is the MAC address of your iServer labeled on the bottom of the
unit.
2. From the same prompt, type the following HTTPget command:
httpget -r -S “00000000” 128.100.101.76:1press the <Enter> key
00000000 is the default ADMINISTRATOR password in your iServer unit and
128.100.101.76:1 is the IP address that your iServer will accept on TCP port 1. At this
point, you have successfully assigned 128.100.101.76 IP address to your iServer.
Continued on the following page.
12
Page 19
4.1.2 ARP HTTPget Commands (Method 2) (continued)
C:\>arp -s 128.100.101.76 00-03-34-00-b8-70
C:\>httpget -r -S “00000000” 128.100.101.76:1
New IP is assigned. The unit will reset in 10 seconds.
C:\>
The above IP address of 128.100.101.76 is an example to show how these
commands work. To get a valid IP address on your network you need to consult
with your IT department.
Figure 4.1 shows the screen shot of an actual DOS window with the above commands
executed.
Figure 4.1 ARP and HTTPget Commands on a DOS Window
4.1.3 Direct Connection (Method 3)
The iServer is shipped with a default IP address of 192.168.1.200 and Subnet Mask of
255.255.255.0.
To start, connect your iServer directly to your PC using a straight or cross-over Ethernet
cable and power it on.
Make sure that the Network LINK/ACT LED on the iServer and your Ethernet switch is
solid ON. Refer to Figure 4.2.
If you are going to use a Web browser or Telnet program to access the iServer using its
default IP address of 192.168.1.200, you need to make sure that the PC from which
you’re establishing the connection has an IP address that is in the same range as the
iServer’s IP address.
For example, you can assign your PC an IP address of 192.168.1.x, where x is any
number from 1 to 254.
Your PC’s IP address cannot be the same as the iServer’s IP address.
You also need to make sure that your PC’s subnet mask is 255.255.255.0.
This is a good way to access the iServer over the network and make any configuration
changes needed.
Changing your PC’s IP address is temporary and it’s only for the purpose of accessing
the iServer for initial configurations like assigning a new IP address, subnet mask, etc.
Once the iServer is configured you can put your PC back to its original IP settings.
If 192.168.1.200 is already in use on your network, connect the iServer directly to your
computer using a CAT5 Ethernet cable (either straight or cross-over cable will be detected
by the iServer) and proceed as described below.
13
Page 20
4.1.3 Direct Connection (Method 3) (continued)
100 BASE-T
LINK / ACT
DHCP
RECORDING
Ethernet Cable
After connecting the
iServer to computer, power it on.
LINK/ACT LED should be
SOLID green
Computer’s
Ethernet Port
(RJ45
connection)
Plug in the
Power Adapter
iServer with
default IP address
of 192.168.1.200
Figure 4.2 Connecting Computer Directly to iServer
1) Click on your Windows “Start” menu and select
“Control Panel” from the list options.
Double click on the “Network Connections” icon
Figure 4.3 Network Connections
2) You now have “Network Connections”
window opened.
The “Local Area Connection” icon has
all the settings for your ethernet
connection.
Double click on this icon.
Figure 4.4 Local Area Connection
14
Page 21
4.1.3 Direct Connection (Method 3) (continued)
http://192.168.1.200Address
iSD-TC Welcome Page
ReadingsChart
SetupWeb Link
Fill out the fields for the IP
3) Click on “Properties”
button
Figure 4.5 Changing TCP/IP Properties on Your Computer
4) Now you may need to reboot your computer.
5) Once your PC is back up, open your browser and type the iServer’s default IP
address of 192.168.1.200 in the “Address” window of your browser and press the
Enter key.
You will soon be inside the Welcome page (see
server and from there you can access all the menus.
Select “Internet Protocol(TCP/IP)” and click on
“Properties” button
Figure 4.6)
address 192.168.1.100 and
Subnet mask 255.255.255.0
as indicated below. Press
OK and also on all the other
remaining windows.
of the iServers WEB
Figure 4.6 iServer Welcome Page
15
Page 22
4.1.3 Direct Connection (Method 3) (continued)
C:\>ping 192.168.1.200
Pinging 192.168.1.200 with 32 bytes of data:
Reply from 192.168.1.200: bytes=32 time=15ms TTL=64
Reply from 192.168.1.200: bytes=32 time=8ms TTL=64
Reply from 192.168.1.200: bytes=32 time=8ms TTL=64
Reply from 192.168.1.200: bytes=32 time=8ms TTL=64
Pinging statistics for 192.168.1.200:
Packets: Sent=4, Received=4, Lost=0 (0% loss)
Approximate round trip times in milli-seconds:
Minimum=8ms, Maximum=15ms, Average=9ms
To verify a good connection to the iServer, from a DOS prompt on your computer
type "ping 192.168.1.200" and press Enter.
You should get a reply as shown in Figure 4.7.
If you don’t receive a reply it means that you do not have a network connection
between your PC and the iServer.
Check your IP address, subnet mask, and gateway address.
Figure 4.7 Pinging the iServer from MS-DOS Prompt
16
Page 23
4.1.4 iConnect Software
(Method 4)
The iServer can be assigned an IP Address by using the iConnect software.
a)Download the iConnect software from the website listed on the cover of this manual
(software section).
b)Install iConnect software on a networked PC. This software is compatible with
Windows 95, 98, NT, 2000, and XP.
c)Use iConnect to assign an IP address to the iServer and access its web pages for
configuration.
You can also use any standard web browser to access the iServer’s web pages.
Consult with your IT department for obtaining an IP address.
Figure 4.8 Assigning an IP Address using iConnect
1)Place the IP address in this box.
2)Take the MAC address from the label attached to the bottom of the iServer and
place it in this box.
3)Click here to send the above IP address to the iServer.
4)After the IP address is assigned to the iServer, click here to access it’s web pages.
5)Click here to Ping the iServer whose IP address is shown in the IP address box.
6)Click here to find all the iServer’s on your network .
7)The IP addresses for the iServer’s found by the iConnect will be listed here.
8)These fields indicate the IP address and the subnet mask of the PC on which the
iConnect is running.
17
Page 24
4.1.4 iConnect Software
(Method 4)
(continued)
d)To access the iServer for Configuration:
Click on the “View Webpage” button, you will access the iServer’s welcome page.
To take advantage of the iServer’s full capability use any standard web browser to
access the iServer’s web pages as described in Section 4.2.
Figure 4.9 Accessing the iServer’s using iConnect
18
Page 25
4.2 Access and Configuration Using a Web Browser
http://192.168.1.200Address
iSD-TC Welcome Page
ReadingsChart
SetupWeb Link
http://192.168.1.200Address
Login
Readings
Chart
Web LinkSetup
Password:
OK
LOGIN
http://192.168.1.200Address
Administrator Login
Readings
Chart
Web LinkSetup
Password:
OK
ADMINISTRATOR
• Start your web browser.
• In the URL field, type http://192.168.1.200 (iServer’s default IP address).
• The Welcome Page, will be displayed.
Figure 4.10 iServer Welcome Page
In order to access the iServer’s web pages, users may be prompted for a
password, as shown below.
4.3 LOGIN and ADMINISTRATOR Passwords
There are 2 different access levels:
1. LOGIN Password is required to access the iServer’s Readings, Chart, and Web Link
pages unless it’s disabled. The default password is 12345678.
2. ADMINISTRATOR Password is required to access the iServer’s Setup menu unless
it’s disabled. The default password is 00000000.
Refer to Section 4.4.5 for Password setup.
Figure 4.11 LOGIN and ADMINISTRATOR Passwords
19
Page 26
4.4 Setup
http://192.168.1.200Address
Overview
Readings
Chart
Web LinkSetup
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Model
Firmware Version
DHCP
MAC Address
IP Address
Subnet Mask
Gateway Address
Hostname
Ethernet Port
Web Server Port
Recording
Uptime
x.x
Disabled
00:03:34:00:b8:70
192.168.1.200
255.255.255.0
0.0.0.0
isdb870
Auto
80
OFF
1 day, 00:00:00 hh:mm:ss
Menu BarMenu Panel
iSD-TC
Clicking the Setup button on the Welcome page (see Figure 4.10) will provide access to
the Menu Panel (see Figure 4.12).
Using this Panel you can configure the iServer entirely.
4.4.1 Overview
Once the Administrator password is entered, the Overview page will appear which
provides a summary of important parameters within the iServer.
All the fields are read-only.
Figure 4.12 Overview
20
Page 27
4.4.2 Network
http://192.168.1.200Address
Network
Readings
Chart
Web LinkSetup
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Save ChangesReset
DHCP
MAC Address
IP Address
Subnet Mask
Gateway Address
DNS Address
Host Name
Protocol
Local Port
Web Server Port
Web Link Title
Web Link Address
This menu provides network configurations including IP parameters and Ethernet
interface options. Fields are described below.
4.4.2.1 IP Configuration
DHCP – If the box is checked the iServer will dynamically request an IP address, a
subnet mask, a gateway address, and a DNS address from the DHCP server. By default
the DHCP option is disabled. For more information about DHCP, see Section 3.3.
MAC Address – This Indicates the hardware address of the iServer and it is nonconfigurable. For more information about MAC Address, see Section 3.2.
IP Address – This indicates the IP address of the iServer. The iServer’s default IP
address is 192.168.1.200. When DHCP is enabled this field will be dimmed. Consult with
your IT department for obtaining an IP address.
Subnet Mask – It’s a 32-bit number that is used to determine which part of the IP
address is the network portion and which part is the host portion. When DHCP is enabled
this field will be dimmed. The iServer’s default Subnet Mask is 255.255.255.0. Consult
with your IT department for obtaining a subnet mask.
DHCP can be enabled by pressing and holding the two front buttons ºC/ºF and
TIME/IP during power-on (refer to Section 2.3).
Figure 4.13 Network: IP Configuration
21
Page 28
4.4.2.1 IP Configuration (continued)
Gateway Address – This points to the router that forwards traffic to a destination
address outside of the subnet on which the iServer resides. This is the IP address of the
router which functions as a gateway. When DHCP is enabled this field will be dimmed.
The iServer’s default Gateway address is 0.0.0.0. Consult with your IT department for
obtaining a gateway address.
DNS Address – In order to use the hostname to access the iServer, the DNS server on
your network must be configured, refer to Section 3.4. iServer plays the role of a DNS
client, in the sense that the iServer will actively query the DNS server for the IP address
associated with a particular domain name. When DHCP is enabled this field will be
dimmed. The iServer’s default DNS address is 0.0.0.0. Consult with your IT department
for obtaining a DNS address.
Host Name – If DHCP is enabled, the iServer will send this name to the DHCP server.
This name is used so that the iServer can be accessed based on a specific name
instead of an IP address. For example, instead of using http://192.168.1.200 (IP
address), you would use http://isdb870 or any name up to sixteen (16) alphanumeric
characters. The default Host Name for an iServer is "isd" followed by the last four digits
of the MAC address of that particular iServer.
On Windows servers where DHCP and DNS are separate functions it’s very
important to configure the DHCP server to communicate with DNS in order for
the iServer’s Host Name to correctly respond. If you cannot access the iServer
using its Host Name, please contact your network administrator to make sure
DHCP and DNS servers are linked together.
Protocol – It’s the network protocol the iServer communicates with the Ethernet
Network. Options are TCP and UDP. The default is TCP.
Local Port – The default port is 2000. Refer to Section 3.6.
Web Server Port – The default port is 80. This is the primary port number for the HTTP
protocol used for communication between internet browsers and web sites/web servers.
Web servers open this port then listen for incoming connections from web browsers.
Similarly, when a web browser is given an IP address (like the iServer’s IP address), it
assumes that the iServer’s web server is listening for connections on port 80. If this port
is changed to anything but 80 then on the browser the new port number must be
indicated with a colon (:) after the IP address. For example, if the Web Server Port is
changed to 500, you will then need to type http://192.168.1.200:500 on the browser to
access the iServer’s web server.
One of the applications where the Web Server Port number may need to change
is when users want to access the iServer’s web server from outside the local
area network (i.e. Internet). By setting up “Port Forwarding” inside a router that
is the gateway to that local area network this task can be accomplished. “Port
Forwarding” technique uses the Web Server Port number to forward the Internet
connection to the iServer on the LAN.
Web Link Title – This is a text field that appears on the button on the iServer’s Web Link
Page, refer to Section 4.7. This can describe the Web Link Address assigned below.
Web Link Address – This provides a link to any TCP/IP node on the network or any
Web link on the Internet. Examples would be www.123abc.com or if you have a device
with an embedded Web server (just like the iServer) once you enter its IP address in this
field and click on the Web Link button on the iServer’s Welcome page you'll be able to
access your device using the same browser interface.
22
Page 29
4.4.2.2 Ethernet Port
http://192.168.1.200Address
Ethernet Port
Readings
Chart
Web LinkSetup
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Save ChangesReset
IP Configuration Ethernet Port
Auto-Negotiation
Speed
Duplex
100 Mbps
Full
10 Mbps
Half
Auto-Negotiation – It is the link, in terms of speed and duplex, between the iServer and
another Ethernet device like an Ethernet switch.
If Auto-Negotiation box is checked, the iServer will auto-negotiate the speed and duplex
with the attached Ethernet device. If any of the other options are selected, the speed and
duplex will be fixed.
It’s important to have the same Ethernet port configuration on the iServer and the
attached Ethernet device. If iServer cannot auto-negotiate with the attached Ethernet
node it will default to 10 Mbps and Half-Duplex. Once Auto-Negotiation is checked, other
fields under this category will be dimmed. By default the Auto-Negotiation is checked.
Figure 4.14 Network: Ethernet Configuration
If the iServer detects the link to be 100 Mbps the 100 BASE-T LED will be solid
green.
4.4.3 Configuration
This menu provides configurations for the real-time clock, server parameters, sensors,
and alarm relays settings. Fields are described below.
4.4.3.1 Date and Time
Current Date – This field indicates the iServer’s real time clock date. The format is
yyyy/mm/dd. When there is no date defined, the iServer will be defaulted to 2099/01/01
and be shown in red to alert you that it has not yet been set..
Current Time – This field indicates the iServer’s real time clock time. The format is
military time (24-hour) and it is entered as hh:mm:ss.
Change Date and Time – By clicking on this option the real data and time can be entered.
23
Page 30
4.4.3.1 Data and Time (continued)
http://192.168.1.200Address
Date and Time
Readings
Chart
Web LinkSetup
Save ChangesCancel
Current Date
Current Time
Change Date and
Time
Date and Time
Network Time Server
NTS Address
Time Zone
(GMT-08:00)Pacific Time(US&Canada)
Time Server
SensorsServerAlarm RelaysContact ClosuresDate and Time
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
2099/01/01 (yyyy/mm/dd)
00:00:00
Network Time Server – If there is a time server on the network or the Internet, the
iServer will get the real date and time once the Network Time Server’s IP address is
provided. Default is unchecked.
NTS Address – The field to enter the Network Time Server’s IP address.
The U.S. National Institute of Standards and Technology (NIST) publishes a list of time
servers on the Internet used by the NIST Internet Time Service (ITS). The list includes
each server’s name, IP address, and location in the United States. As of the publication
date of this manual, links to the list can be found at http://tf.nist.gov.
Time Zone – If Network Time Server option is checked, the correct time zone must be
selected for the correct time display.
Figure 4.15 Configuration: Date and Time
Once the AC adaptor is disconnected from the iServer and there is no battery
back-up, the iServer will lose its date and time settings.
Once the iServer is rebooted from any web page, the iServer will lose its date
and time settings whether or not the back-up battery is installed.
If the iServer is setup to get it’s time from a Network Time Server, then the time
will be re-assigned after the reboot.
24
Page 31
4.4.3.2 Server
http://192.168.1.200Address
Server
Readings
Chart
Web LinkSetup
Save ChangesReset
Server Type
Interval
Disconnect After Data Sent
Time Stamp
Command
5 secs
Server
SensorsServerAlarm RelaysContact ClosuresDate and T ime
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Server Type – Options are Command and Continuous.
If Command is selected the iServer will respond to commands sent from a network host
(for the list of commands refer to Section 4.9.1).
If Continuous is selected the iServer will send temperature 1, temperature 2, differential
values, contact closure and alarm relay status once every time amount selected in the
Interval box.
The Command and Continuous modes operate when a network host opens a TCP
connection to the iServer’s IP address with port 2000.
In UDP Command mode, iServer will respond back with a UDP packet (to the _ address and
port) if a host application sends a UDP command to iServer’s IP address with port 2000.
In UDP Continuous mode, iServer starts sending continuous data if a host application
sends a trigger or UDP packet to iServer’s IP address with port 2000.
Interval – This is the time interval (in seconds) between each data transmission when
the iServer is in Continuous mode. The default value is set to 5 seconds and the
minimum is 2 seconds.
Time Stamp – If checked, the iServer will stamp the data with date and time before
sending it out to a network host. This will apply to Command and Continuous modes.
Default is unchecked.
Disconnect After Data Sent – If checked, once the iServer responds back with data, the
iServer will close the TCP connection that had been made from the network host.
This feature should be used if data acquisition software expects data to be ended by
closing TCP connection from the client.
Figure 4.16 Configuration Menu: Server
25
Page 32
http://192.168.1.200Address
Sensors
Readings
Chart
Web LinkSetup
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Save ChangesReset
SensorsServerAlarm RelaysContact ClosuresDate and Time
Description
End Character
0x
C
Temperature 1
Reading 1
UnitDisplay
Data Format
Offset
Adjust by
0D
Description
End Character
0x
Reading 2
0D
Description
End Character
0x
Differential
Reading 3
0D
T0000.0C
Unit
Data Format
T0000.0C
C
Unit
Data Format
D0000.0C
0.0
Reading Low 0.0
Reading High
100.0
Ref. Low
0.0
Ref. High
100.0
Display
Offset
Display
0.0
Reading Low
0.0
Reading High
100.0
Ref. Low
0.0
Ref. High
100.0
Cold Junction
Cold Junction
K T ype
TC T ype
Offset
Adjust by
K T ype
TC T ype
Scale & Offset
C
Temperature 2
4.4.3.3 Sensors
This page is where the Sensor Parameters are defined. Reading 1 is for Thermocouple
Input 1, Reading 2 is for Thermocouple Input 2, and Reading 3 is for the difference
between Input 1 and Input 2.
Description – This can be a name for the sensor or where the sensor is located. This
field is text only and can have up to 16 alphanumeric characters. This description will
appear wherever Reading 1, 2 or 3 is displayed on the web server.
Unit – This is the unit of measurement for temperature. It can be either C for Celsius or F
for Fahrenheit.
Display – If checked, the variable (i.e. Temperature1, Temperature2, Differential) will be
displayed on the Readings and Chart applets, as well as data transmission in
Continuous mode (see Server Type Section 4.4.3.2). The default is checked.
Figure 4.17 Configuration Menu: Sensors
Once the unit is selected, either C or F, it will be a global change throughout the
web server, as well as on the LCD display. If you use the front C/F buttons to
change the unit of temperature it will have no affect on the web pages.
26
Page 33
4.4.3.3 Sensors (continued)
Reading Low 10.0
Reading High
200.0
Ref. Low
12.0
Ref. High
195.0
End Character – The iServer can attach a character (in Hex) to the end of temperature
data packet. This will apply to either Continuous or Command mode. If 00 is entered
there will be no character attached. The default is 0D (Hex representation of <CR>).
Data Format – This indicates the format of the temperature reading being displayed on a
network host when Continuous transmission is used (see Server Type Section 4.4.3.2).
TC Type – This provides a list of thermocouple types to select from.
The types are J, K, T, E, R, S, B, C, N, and DINJ.
If Disabled is selected the display on the iServer and the Reading page will display
Disabled.
The default is K Type. For the list of Thermocouple types and their range and accuracy
see Section 5.
Cold Junction – Click on the link and follow instructions to perform cold junction
compensation for the selected thermocouple channel.
Cold junction compensation will allow you to adjust (calibrate) the thermocouple reading
in reference to 0°C environment.
A correct TC Type must be selected before doing cold junction compensation.
Adjust by – If it’s determined that the reading is slightly off this field can be used to
adjust the reading. The options are Offset and Scale & Offset.
Using the Offset method you can manually assign a numerical value to adjust the
reading. For example if the actual reading is 55 where it should be 54 you can enter -1 in
the Offset field.
The Scale & Offset method uses two points to adjust the reading within the entire
temperature range. For example, if at the lower point the actual reading is 10 where it
should be 12 and at the higher point the actual reading is 200 where it should 195, here
is how the numbers are entered.
The adjusting numbers can be positive or negative with one decimal point.
The adjusting values must be assigned after the Unit of temperature (C or F) is
selected. If the unit of temperature is changed, you must readjust the values for
a correct result.
27
Page 34
4.4.3.4 Contact Closure
http://192.168.1.200Address
Contact Closures
Readings
Chart
Web LinkSetup
Save ChangesReset
Contact 1
Description
End Character 0x
Display
Disable
Contact In1
0D
Contact 2
Description
End Character 0x
Display
Disable
Contact In2
0D
TypeUnlatch
Clear Latch
Record all alarm events on the flash memory
Retrieve
SensorsServerAlarm RelaysContact ClosuresDate and Time
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Contacts
Output
End Character 0x
Display
Active Low
0D
Output
For wiring and pin-outs see Section 2.6. The options for Contact 1 & 2 are Disable,
Normally Open, and Normally Close. Default is Disable.
Normally Open and Normally Close are the initial states of the Contact Closure. For
Contact 1 & 2 – This configures the first and second Contact Closures on the iServer.
example, if it’s set for Normally Open, the iServer will display NORMAL status as long as
the contact is open. Once the contact is closed the iServer will change the status to
ACTIVE.
If Disable option is selected the Contact Closures will be inoperable.
Description – This is a text-only field and can take up to 16 alphanumeric characters.
This can be the name of a device connected to the Contact (i.e. Alarm) or the location.
This name is displayed on the Readings webpage and responded to Command and
Continuous mode connections. Defaults are Contact In1 and Contact In2.
End Character – This means that the iServer will send a character (in Hex) after
sending the state of the Contact Closure in Continuous or Command mode. Default is 0D
(Hex representation of <CR>).
Display – If checked the status of Contacts will be displayed on the Readings webpage
and responded to Command and Continuous mode connections. Default is unchecked.
Output – The options are Active High and Active Low. The Output will be High or Low if
the Contact 1 or Contact 2 status is changed. Default is Active Low.
Figure 4.18 Configuration Menu: Contact Closures
28
Page 35
4.4.3.4 Contact Closure (continued)
http://192.168.1.200Address
Alarm Relays
Readings
Chart
Web LinkSetup
Save ChangesReset
Relay 1
Description
Status
Type
Set Point High
Set Point Low
End Character 0x
Display
Temperature
Alarm Relay 1
Disable
Unlatch
Clear Latch
0.0
0.0
0D
Relay 2
Description
Status
Type
Set Point High
Set Point Low
End Character 0x
Display
SensorsServerAlarm RelaysContact ClosuresDate and Time
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
End Character – This means that the iServer will send a character (in Hex) after sending
the state of the Output in Continuous or Command mode. Default is 0D (Hex
representation of <CR>).
Type – The options are Unlatch and Latch. Default is Unlatch.
If it’s set to Unlatch, once the Contact is back to NORMAL the Output will automatically
change to its original state.
If it’s set to Latch, once the Contact is back to NORMAL the Output will remain
unchanged until the user clicks on the Clear Latch button.
Display – If checked the status of the Output will be displayed on the Readings webpage
and responded to Command and Continuous mode connections. Default is unchecked.
Record contact events on the flash memory – If checked the Output status with
stamped date and time will be recorded into an ASCII file on the flash memory card. By
clicking the Retrieve button the file will be open. Default is unchecked.
4.4.3.5 Alarm Relays
This section would allow the two relays on the iServer to be configured as needed. For
physical connections and pin-outs refer to Section 2.6.
Relay 1 and Relay 2 – This configures the first and second relays on the iServer. The
options for each are temperature 1, temperature 2, and differential.
This means that both Relays can be set for temperature 1 or both Relays can be set for
temperature 2, or one can be set for temperature 1 and one for differential.
Figure 4.19 Configuration Menu: Alarm Relays
29
Page 36
4.4.3.5 Alarm Relays (continued)
Description – This is a text field for naming the device connected to the relay or it could
be the location where the device is installed. This field can take up to 16 alphanumeric
characters. This name will be displayed anywhere on the web pages associated with
alarm relays; for example the Readings applet.
Defaults are Alarm Relay1 and Alarm Relay2.
Status – The options are Disable, Low, High, and Low or High. The default is Disable.
If Low is selected Set Point Low must be given a value and once the sensor reading falls
below that value the relay will change status.
If High is selected Set Point High must be given a value and once the sensor reading
rises above that value the relay will change status.
If Low or High is selected Set Point Low and High must be given values and relay status
will change once the sensor reading is outside that range.
If Disable is selected relays will be deactivated.
Alarm status with the associated set point will be shown on the chart applet as well.
Type – The options are Unlatch and Latch. The default is Unlatch.
If Unlatch is selected and the relay is activated, once the sensor reading goes back
within the Set Point range, the alarm will be deactivated automatically.
If Latch is selected, once the sensor reading goes back within the Set Point range, the
relay will remain active until the user clears it by clicking on the Clear Latch button.
Set Point High – This is the field for the upper Set Point.
Set Point Low – This is the field for the lower Set Point.
End Character – This is the character (in Hex) that the iServer will send along with the
alarm status.
This applies to either Continuous or Command mode described on the Server page,
under the Configuration menu (Section 4.4.3.2).
The default is 0D meaning a Carriage Return character will be sent after the value.
Display – This would indicate whether to display the status of the alarm relays on the
Readings applet as well as the TCP Command and Continuous modes, and any other
related fields.
The default is unchecked.
Record all alarm events on the flash memory – If checked, all the alarm events with
stamped date and time will be recorded on the flash memory card.
By pressing the Retrieve button the ASCII log file will be opened.
The default is unchecked.
Using the web server, the log file can be retrieved if the file size is 32 KB or
smaller. For a larger file size you must use a flash card reader to open the log
file. Refer to Section 4.10.
30
Page 37
4.4.4 Management
http://192.168.1.200Address
Setup
Readings
Chart
Web LinkSetup
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Save ChangesReset
SNMP Response Enabled
SNMP Community
Contact
Location
SNMP Trap Server
Simple Network Management Protocol
SMTP Server
SMTP Server Port
From:
To:
Subject:
Reminder Interval
Transmission Delay
Simple Mail Transfer Protocol
AlarmsSetup
None
0.0.0.0
public
None
0.0.0.0
25
60
1
mins
mins
This page provides the iServer’s email, SNMP and alarm settings. SNMP (Simple
Network Management Protocol) is the protocol used by network management systems to
communicate with network devices that respond to SNMP connections for the purpose of
problem detections and corrections.
If SNMP and/or SMTP features are desired, please make sure iServer’s network setting
as well as SNMP trap server and SMTP mail server are setup properly. Failure to do so
may cause iServer to be unresponsive while waiting for these servers to reply back.
Fields are described below.
4.4.4.1 Setup
Simple Network Management Protocol
SNMP Response Enabled – If this option is checked the iServer will respond to network
nodes broadcasting SNMP requests. The default is unchecked.
Make sure your network is setup properly (gateway, etc) before using SNMP feature
SNMP Community – Every SNMP communication takes place using a community
string. The default is Public.
Contact – This text field specifies the contact person for this node, together with information
on how to contact this person. This field takes up to 16 alphanumeric characters.
Location – This text field specifies the location of the iServer. For example it can be
“control station”, which is the place where the iServer is located. This field takes up to 16
alphanumeric characters.
SNMP Trap Server – This field contains the IP address of the SNMP trap server located
somewhere on the network. The trap server listens for SNMP traps coming from the
iServer when there is an alarm condition (refer to Alarms Section 4.4.4.2 under the
Management page).
Figure 4.20 Management Menu: Setup
31
Page 38
4.4.4.1 Setup (continued)
Simple Mail Transfer Protocol
SMTP Server – This field specifies the IP Address of the SMTP server.
1)You must have an email server (SMTP server) on your network in order to
receive emails generated by the iServer.
2)iServer does not support SMTP server authentication.
SMTP Server Port – This specifies the TCP port used by the SMTP Server. The default is 25.
From – This field specifies the name of the person who sends the email. It can also be
an email address.
To – This field specifies the email address of the recipient. This field can take up to 200
alphanumeric characters; limited to 4 addresses of 50 characters each. Each address
should be separated by a comma, without spaces. Ex: aaa@bbb.com,ccc@ddd.com
You can create a “distribution group address” if you need to have more email
addresses.
Subject – This field specifies the subject of the email. Emails for all the alarms will have
this common subject line. Example of a subject can be “Alarm from iServer”.
Reminder Interval – This field sets a reminder interval for email and/or trap to be sent
again. The allowed minimum value is 1 minute. If it’s set to 0 the iServer will not send a
reminder email. The default is 60 minutes.
Power Reset alarm is only sent once, regardless of reminder interval.
Transmission Delay – Once the iServer alarm condition is met, this is the amount of
time the alarm condition is met before iServer sends any email or trap. If it’s set to 0,
email and/or trap will be sent immediately. The default is 1 minute.
4.4.4.1.1 Sending Text Messages to a Cell Phone
In the SMTP To field, you can use the following format to have the iServer send a text
message to your cell phone. Since most cell phones are capable of receiving text
messages you just need to find the correct email format for your cell phone provider.
T-Mobilephone_number@tmomail.net
Virgin Mobilephone_number@vmobl.com
AT&Tphone_number@txt.att.net
Sprintphone_number@messaging.sprintpcs.com
Verizonphone_number@vtext.com
Nextelphone_number@messaging.nextel.com
“phone_number” is your 10 digit cell phone number.
There is text box next
to each event. The
text content will be the
Figure 4.21 Management Menu: Alarms
body of the email.
This includes events or conditions. Once a condition is met the iServer will send an email
or/and an SNMP trap if either one or both are checked. Fields are described below.
Multiple alarm events can be checked and for each event an email and/or a trap
will be sent.
Temperature 1– The options are Low, High, and Low or High.
If Low is selected the Low field must be given a value (lower than that value is an alarm
condition).
If High is selected the High field must be given a value (higher than that value is an
alarm condition).
If Low or High is selected the Low and High fields must be given values (outside the
band is an alarm condition).
Temperature 2 – The same as Temperature 1 defined above.
Differential – The same as Temperature 1 defined above.
There is text box next to each event. The text content will be the body of the
email.
Power Reset – This refers to the iServer being powered off and back on (power reset).
If the option is checked the iServer will automatically send one email or/and an SNMP
trap after rebooting, regardless of reminder interval.
Probe Disconnected – If the probe attached to the iServer is disconnected that is
considered as an alarm condition.
33
Page 40
4.4.4.2 Alarms (continued)
http://192.168.1.200Address
Security
Readings
Chart
Web LinkSetup
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Save ChangesReset
Login Password
Admin Password
Local Port Password
Telnet Console Access
Web Server Access
Secured Readings and Charts
Change
Change
Change
IP Exclusivity
12345678
00000000
1
2
3
4
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
Enable
No
IP Address
Recording Stopped – If the iServer is recording, once the recording is stopped (no
matter what the cause was) an email or/and a trap will be sent.
SD Card 10% Memory Left – An alarm will be triggered if 10% or less memory left on
the flash card.
Low Battery – If the 9V battery lowers to about 7V, the iServer will prompt an alarm.
Relay 1 Activated – If relay 1 is activated the iServer will prompt an alarm. See Alarm
Relays section under the Configuration page (Section 4.4.3.5).
Relay 2 Activated – If relay 2 is activated the iServer will prompt an alarm. See Alarm
Relays section under the Configuration page (Section 4.4.3.5).
Contact 1 Activated – If contact 1 is activated the iServer will prompt an alarm. See
Contact Closures section under the Configuration page (Section 4.4.3.4).
Contact 2 Activated – If contact 2 is activated the iServer will prompt an alarm. See
Contact Closures section under the Configuration page (Section 4.4.3.4).
4.4.5 Security
This page provides security and access settings for the iServer. Fields are described
below.
Figure 4.22 Security Menu
34
Page 41
4.4.5 Security (continued)
Login Password – To access Readings, Chart, and Web Link menus this password is
required. The password length can be up to 16 alphanumeric case-sensitive characters.
To change the password click on Change.
Empty box means no password is required. The default Login Password is 12345678.
Administrator Password – To access Setup menu this password is required. The
password length can be up to 16 alphanumeric case-sensitive characters. To change the
password click on Change.
Empty box means no password is required. The default Administrator Password is
00000000.
This password will also be prompted when Telnet connection to port 2002 is
made. Port 2002 is the Telnet console port that allows users to configure some
of the parameters that can be configured through the web server.
Local Port Password – To access the iServer (via TCP or UDP socket connection to
port 2000) this password is required. The maximum length can be up to 16
alphanumeric case-sensitive characters.
Empty box means no password is required. The default is none.
Telnet Console Access – If it is unchecked, Telnet console connection to port 2002 will
be blocked. The iServer must be rebooted for the change to take place. The default is
checked.
Web Server Access – If it is unchecked, the iServer’s Web server will not be accessed.
The iServer must be rebooted for the change to take place. The default is checked.
When the Web Server Access is not enabled, the iServer needs to be
configured using Telnet console.
If someone needs to access the Web Server again, use the Telnet console to
enable it.
Secured Readings and Charts – If it is checked the Login password will be required to
display Readings and Chart applets. The default is checked.
IP Exclusivity – This table contains the IP addresses that are allowed to communicate
with the iServer over TCP or UDP connection. This means if the table is empty
connections from all IP nodes are allowed to the iServer. If enabled, all packets from IP
addresses not on this list are ignored and thrown away.
Format SD CardStart Recording Status Data Retrieval
Interval(1-3600)seconds
yyyy/mm/dd
yyyy/mm/dd
Start Time
Stop Time
Start Date
Stop Date
hh:mm:ss(24 hours)
hh:mm:ss(24 hours)
Set Date and Time
Mon Tue Wed Thur Fri Sat Sun
Set Weekdays (only for scheduled recording)
Current Date: 2099/01/01 (yyyy/mm/dd) Current Time: 00:00:00
Continuous
Category
Wrap
Type
Quick Start Recording
Title
Start Recording
This section includes all the parameters and settings for data recording, SD flash card
and recording status, data retrieval, and formatting the SD card. Fields are described
below.
4.4.6.1 Start Recording
Interval – This is the time interval between each data. It can be between 1 to 3600
seconds.
Title – This is the header for each recorded data file on the SD flash card.
Quick Start Recording – If this button is clicked recording will start immediately.
Make sure your Current Date and Time are correct.
Type – The options are Wrap and Non-Wrap.
If Wrap is selected once the SD flash card is full the iServer will delete the old data
stored on the card in order to record the new data. Each time a new recording takes
place an old record will be deleted.
If Non-Wrap is selecetd the iServer will stop recording once the SD flash card is full.
Figure 4.23 Recording Menu: Start Recording
36
Page 43
4.4.6.1 Start Recording (continued)
Category – The options are Continuous and Scheduled.
In Continuous recording Start Date and Start Time fields are required. If there is not an
End Date and End Time, the recording will continue non-stop.
In Scheduled recording, any of the days can be selected and the recording will take
place only on those days. Here are some important notes about the Scheduled
recording:
•The Start Date, Start Time, and Stop Time must be defined. The Stop Date does not
apply to Scheduled recording. This means that the Scheduled recording will never
stop until the user decides to stop it.
•If the Start Date is one of the selected days recording will start on that day.
•If the Start Date is not one of the selected days recording will start on the next 1st
selected day.
•The Start Time and the Stop Time apply to every single day that is selected.
•The Start Time is the time that recording will start on those selected days.
•The Stop Time is the time that recording will stop on those selected days.
•The Start Time must be earlier (at least 20 seconds) than the stop time.
•Let’s say today we’re configuring the unit for Scheduled recording. If the Start Time
is earlier than the Current Time (real time clock) and today is one of the selected
days, the recording will start immediately.
•Scheduled recording is suitable for users who want to start and stop recording at
certain times on certain days. Users who want to have continuous recording three
days a week, for instance, this feature can also be used. Just make sure to select
start and stop times that would link the three days together.
For example, we need to have 3 days (72 hrs) a week continuous recording
(Monday, Tuesday, and Wednesday) with recording Interval of 1 minute. The StartTime should be 00:00:00 and the Stop Time should be 23:59:00. This will connect
all 3 days together and it will run on weekly bases.
Start Date – This is the date on which the data recording must start.
Start Time – This is the time that the recording will start. It’s based on a 24-hour format.
The Start Time must be at least twenty seconds after the Current Time (real time).
Stop Date – This is the date on which the data recording will stop. Stop Date does not
apply to Scheduled recording.
Stop Time – This is the time that the recording will stop. It’s based on a 24-hour format.
A failure on the Ethernet network will not interrupt data recording.
37
Page 44
http://192.168.1.200Address
Status
Readings
Chart
Web LinkSetup
Recording
StartDate
StopDate
Category
Interval
OFF
(yyyy/mm/dd)
(yyyy/mm/dd)
StartTime
StopTime
Type
Title
(hh:mm:ss)(24 hours)
(hh:mm:ss)(24 hours)
Recording Status
SD Card Detected
SD Card Write Protected
Total Flash Size
Available Flash Size
YES
NO
1925456(KB)
1925452(KB)
SD Card Status
Check Battery
Battery Status
Current Date: 2099/01/01
Current T
ime: 00:00:00
Uptime0 days,00:00:00 hh:mm:ss
Format SD CardStart Recording Status Data Retrieval
This page can be used to retrieve the recorded data from the SD flash card and save it
into an ASCII file.
Using the Retrieve EndDate field select the date (year, month, and day) that is the end
date for the retrieved data.
Then use Retrieve Period field to identify the duration of the retrieved data; selections
are: 1 Day, 1 Week, 1 Month and 1 Year.
The year, month and day dates are taken from your computer.
Now, you can press on the Start Data Retrieval button to log the data into a file.
The file is a text document with extension .data. It can be opened in Excel or Notepad or
any software package that can read text files.
The fields are separated by a semi-colon ( ; ) see Figure Figure 4.41 for a sample text file.
Refer to Section 4.10.1 for steps that may help you to open the data file
Figure 4.25 Recording Menu: Data Retrieval
in an ASCII or Excel application.
The data recorded on the SD card can be read on a PC or MAC using a USB or
any standard card reader. The file format is text and is easily imported to spread
sheets and other programs. For details see Section 4.10.
39
Page 46
4.4.6.4 Format SD Card
http://192.168.1.200Address
Format SD Card
Readings
Chart
Web LinkSetup
Format SD Card
Formatting SD Card will erase all data.
Allow up to 2 minutes to format.
While card is being formatted, please wait for message:
“SD Card Formatted” before continuing.
Format SD CardStart Recording Status Data Retrieval
Clicking on Format SD Card button will start formatting the flash card inside the iServer.
Formatting the SD card will erase all data on the card. Allow up to 2 minutes for format
to be completed which then it will display "SD Card Formatted".
Figure 4.26 Recording Menu: Format SD Card
4.4.7 System
This menu provides various options to reboot, restore defaults, upgrade firmware and
download/upload configuration for the iServer. Fields are described below.
4.4.7.1 Reboot
Reboot – This option resets the power on the iServer.
If the iServer is recording data the reboot option will stop the recording.
It will also set the real date/time back to default unless the Network Time Server option
Please make sure no other clients are connected to the device.
Consult manual for complete instructions.
Clicking on this button will put the iServer back to its default settings.
Figure 4.28 System: Defaults
4.4.7.3 Upgrade
Upgrade – This option loads a new firmware into the iServer over the network. The
firmware is a binary file with .bin extension. This file must be kept on the same PC from
which the iServer is accessed.
Once the firmware upload is completed the iServer will power reset itself. This typically
takes about 30 seconds.
1. Connect the iServer directly to the PC using a straight or crossed Ethernet cable. This
will also help to have a faster firmware upload.
2. From the “Network” menu, change the Web Server Port, for example, to 500 (default
is 80), save the change, and reset the power on your iServer. The next time you will
access the iServer’s Web server, you must type http://192.168.1.200:500 where
192.168.1.200 is the IP address of the iServer and 500 is the new Web server port
(HTTP port).
Either one of the above options will make you the only user on that iServer.
Figure 4.29 System: Upgrade
When doing firmware upgrade on the iServer, there should be NO other ongoing or new Web server (HTTP) connections made to the device; otherwise,
the iServer will not upgrade the firmware. You can do either of the following to
prevent this from happening:
After you have successfully upgraded your device, you can verify the firmware
version number on the “Overview” page (see Section 4.4.1).
It’s recommended to set the iServer to default settings after the firmware is upgraded.
See above Section 4.4.7.2 on how to set the iServer to default settings.
Applying default settings will change the iServer’s settings to factory defaults.
If those settings are important to you and you do not want to reconfigure the iServer, you
will need to do the following steps.
From the “System” menu:
1) “Download” the iServer’s configuration settings, Section 4.4.7.4.
2) “Upgrade” the iServer with the new firmware, Section 4.4.7.3.
3) Set the iServer to “Default” settings. The iServer’s IP address is now
192.168.1.200.
4) “Upload” the same configuration you obtained from step 1 onto the iServer,
Section 4.4.7.5.
4.4.7.4 Download Configuration
Clicking on this button will download the configuration file that contains all the settings
stored in the iServer and use it as a reference.
Please make sure no other clients are connected to the device.
http://192.168.1.200Address
Diagnostics
Readings
Chart
Web LinkSetup
Ethernet ReceivedTransmitted
Packets44376073
Reset Counter
Overview
Network
Configuration
Management
Security
Recording
System
Diagnostics
Log Out
Figure 4.31 System: Upload Configuration
Upload Configuration – Using this option to upload the configuration file into the
iServer. It is recommended to download and store a working copy of this configuration
file in case the device is configured improperly.
You can set the iServer to its default settings and upload the configuration file
back into the iServer.
4.4.8 Diagnostics
This page provides the number of Ethernet packets received or transmitted. Pressing the
Reset Counter button will set the counts to zero.
4.4.9 Log Out
Once you click on Log Out, you will be logged out, and taken back to the Welcome page.
Figure 4.32 Diagnostics
43
Page 50
4.5 Readings
http://192.168.1.200Address
Readings
Temperature 1
Temperature 2
Differential
23.0 C
47.3 C
11.0 C
ACTIVE LOW
Contact2ACTIVE
RecordingON
Output
Contact1NORMAL
Readings
Chart
Web LinkSetup
JavaHTML
Auto Update
Seconds
2
Refresh
This page displays temperature 1, temperature 2, differential, and the status of the alarm
relays and recording.
It can be displayed either as an HTML page or a Java applet.
4.5.1 HTML
Refresh – Adding a time value in seconds will automatically update the HTML page with
fresh readings.
Figure 4.33 Readings: HTML
44
Page 51
4.5.2 Java
Help[?]
http://192.168.1.200Address
Readings
Readings
Chart
Web LinkSetup
JavaHTML
Auto Update
Seconds
2
Refresh
Temperature 1
Temperature 2
Differential
23.0 C
47.3 C
11.0 C
ACTIVE LOW
Contact2ACTIVE
RecordingON
Output
Contact1NORMAL
If Java option is chosen installation of Java Runtime is required (refer to Appendix G).
Data Logging – This option will require the Java Policy file to be setup.
Press on Help[?] for details.
An alternate way to set up the Java Policy can be found in Appendix G.
Once the Java Policy file is completed, click on Data Logging button to log the data
displayed on this page into a file. The file is in comma separated values (.csv) format,
which can be opened in Excel or as ASCII. The fields are separated by a comma ( , ).
When the button is ACTIVE it means that the data is currently being logged into a file.
The value in seconds in the Refresh box determines how often the data is being logged.
The default is 2 seconds.
“Java and the Java Coffee Cup Logo are trademarks or registered trademarks of Sun Microsystems, Inc. in the U.S. and other countries."
If you want to access the “Chart” and/or the “Readings” applet from outside your
local network on which the iServer is connected, you must allow ports 1001
(Readings) and 2003 (Chart) on your Router.
If a blank screen appears without any “java application running” or image of a
“Java logo”, please verify you have the latest Java Runtime Environment installed
and configured according to the instructions (refer to Appendix G). If you do not
have Java Runtime Environment installed, you may download it from our website
(in the software section) or contact the Customer Service Department nearest you.
This page charts the temperature1, temperature 2, and differential, in real-time across
the full span or within any narrow range (such as 20 to 30ºC). The time-base can display
one minute, one hour, one day, one week, one month or one year.
If a blank screen appears without any “java application running” or image of a
“Java logo”, please verify you have the latest Java Runtime Environment
installed and configured according to the instructions (refer to Appendix G).
If you do not have Java Runtime Environment, you may download it from our
website (in the software section) or contact the Customer Service Department
nearest you.
High / Low – If Alarm Relays are enabled (in the Configuration menu), the set point
values for High and Low alarms will be listed and graphed on the chart.
Max. / Min. – This shows the maximum and minimum values for each variable indicated
on the Y-axis.
Figure 4.35 Adjustable Chart
46
Page 53
4.6 Chart (continued)
http://192.168.1.200Address
Web Link
Readings
Chart
Web LinkSetup
Web Link
Data Source – The options are Live and Recorded.
If Live is selected the real-time data will be charted for the time indicated on the X-axis.
If Recorded is selected the stored data on the SD card will be charted for the time
indicated on the X-axis.
Alarm Relay Set Points – This option will hide or chart (normal) the set point values.
The bold option will thicken the displayed set point lines.
If Alarm Relays are disabled (in the Configuration menu) the set points for High
and Low alarms will not be graphed or displayed on the chart.
X-axis – This indicates the time, options includes one minute, one hour, one day, one
week, one month or one year.
Y-axis – The left Y-axis is dedicated to temperature 1. Either temperature 2 or
differential can be selected for the right Y-axis.
Style – This option will hide or chart (normal) the graph of the variables (temperature 1,
temperature 2, and differential). The bold option will thicken the displayed graphs.
Save Chart – Save the current graph in PNG (Portable Network Graphics) format. The
filename has extension .png. This option will require the Java Policy file to be setup.
Press on Help[?] for details. An alternate way to set up the Java Policy can be found in
Appendix G.
Print Chart – The displayed chart will be printed once the button is clicked.
If you want to access the “Chart” and/or the “Readings” applet from outside your
local network on which the iServer is connected, you must allow ports 1001
(Readings) and 2003 (Chart) on your Router.
4.7 Web Link
This page is configured from the Network menu under IP configuration.
Refer to Section 4.4.2.1.
Figure 4.36 Web Link
47
Page 54
4.8 Telnet Setup
192.168.1.200
UNSPEC
Host:TCP/IP:
S
erial:
2002TCP p
ort#:
Protocol:
COM1: Communications Port {COM1
Te
lnet
Tera T erm: New Connection
CancelH
elpOK
With a telnet program, you can connect to the iServer using its IP address and TCP Port
2000. In Continuous mode (refer to Configuration:Sensors page Section 4.4.3.2), the
telnet session will receive continuous data (temperature 1, temperature 2, and differential)
from the iServer. In Command mode, a command can be sent to query the iServer.
Refer to Section 4.9.1 for list of commands. (temperature 1, temperature 2, and
differential)
4.8.1 Telnet Connection
Telnet stands for Telecommunications Network, it is a protocol that provides a way for
users to connect to a node with a valid IP address anywhere on an Ethernet network or
the Internet . You can open a Telnet session using a terminal emulation programs like
Tera Term (downloadable from the internet), which is a free software for Windows.
You can initiate a telnet connection by typing the IP address of the iServer, and Port
2002 for logging into the iServer’s telnet consol port (see Figure 4.37). By telneting to
Port 2000, you will be able to access temperature 1, temperature 2, and differential,
readings.
The default password for Telnet Login is 00000000 and can be changed if
desired.
Once the connection is established you will be prompted for an Administrator Password
(default is 00000000). Telnet console port (2002) allows users to configure some
parameters within the iServer. Figure 4.39 shows the parameters that can be changed.
After connecting to the iServer, you can use the following commands to read, modify, and
get help.
pdisplays the current settings (Figure 4.38)
?displays all the available options as well as an example on how to enter a
sset a new configuration (see the example in Figure 4.39), sending the
RESETrestart the iServer.
FACTORY set the iServer to it’s factory default settings, the RESET command is
command (Figure 4.39)
command c is required to permanently store the new settings
required after the FACTORY command
cpermanently store the new settings
qquit the telnet session
Telnet to Port 2002 – p commandTelnet to Port 2002 – ? command
4.9 HTTPget Program
The HTTPget software is used to send a single HTTP or TCP request to an iServer
product. In contrast, the telnet or Hyperterminal programs allow a continuous
connection with multiple requests to be sent to the iServer product.
Generally HTTPget is used for simply programming an IP address to the iServer or for
quickly obtaining a reading of from a device.
The iServer product must be configured from the configuration web page so that the
"Server Type" value is set to "Command", refer to Section 4.4.3.2.
49
Page 56
4.9.1 HTTPget using Port 2000
You can setup and read the information from the iServer by using the HTTPget program.
The following program can be used to read data from the iServer by using TCP port
2000. The command string is sent to this TCP port, then the response can be read back
from the same socket.
The HTTPget.exe file is used to setup and read information from the iServer. This file can
be downloaded from the website listed on the cover of this manual (software section).
Notes on using HTTPget :
The HTTPget.exe program should be installed to the windows directory (usually c:\winnt
or c:\windows)
1. Open up a command window (or have a DOS window)
a) Click on start menu
b) Click on "Run"
c) In the dialog box that appears, type "cmd" or "command" and click on "OK" button.
d) A command window should now appear.
2. If you now type "httpget" and press the "enter" key, the program options should be
displayed.
3. Next run HTTPget with the options displayed below
httpget -r -S “*SRTC\r” 192.168.1.200:2000
where:
-r –S are parameters needed for the command string
*SRTC is the command as the following:
*SRTCRead the temperature in C, celcius (Channel 1)
*SRTFRead the temperature in F, fahrenheit (Channel 1)
*SRHCRead the temperature in C (Channel 2)
*SRHFRead the temperature in F (Channel 2)
*SRDCRead the differential in C
*SRDFRead the differential in F
*SRA1Read alarm set points for relay 1
*SRA2Read alarm set points for relay 2
*SRBRead the temperature in C and humidity
*SRBFRead the temperature in F and humidity
*SRYSIndicate AC or DC power and battery status
*SRYRSTReset Power on
*SR_XD1Disable alarm condition check for relay 1
*SR_XD2Disable alarm condition check for relay 2
50
Page 57
4.9.1 HTTPget using Port 2000 (continued)
*SR_XC1Reset relay 1 latch condition
*SR_XC2Reset relay 2 latch condition
*SR_XE1Re-enable alarm condition check for relay 1 (must be
executed after *SR_XD1)
*SR_XE2Re-enable alarm condition check for relay 2 (must be
executed after *SR_XD2)
*SR_XP1Close relay 1 for < 200 mSec
*SR_XP2Close relay 2 for < 200 mSec
*SR_XH1Close relay 1
*SR_XH2Close relay 2
*SR_XL1Open relay 1
*SR_XL2Open relay 2
*SR_XR1Read current state of relay 1
*SR_XR2Read current state of relay 2
*SRT2Status of Contact 1 (Disable, Normal, Active)
*SRH2Status of Contact 2 (Disable, Normal, Active)
*SRD2Status of the Output associated with the Contacts
(Active High, Active Low)
\r is the carriage return termination character
192.168.1.200 is an IP address
2000 is a socket port number
Response:
076.6 (in Deg.F format)
4.10 Flash Card Reader
The data recorded on the SD card can be read on a PC or MAC with a USB or any
standard card reader.
The format is a simple “.txt” text file that is easily imported in MS Excel or MS WordPad
or any software package that can read text files (see Figure 4.41).
The entire recording session is saved into a file kept in the root directory.
The name of this file is S followed by the date the recording was started , so for example:
S20100401.txt is April 1st, 2010.
The same recording data is also saved into daily files located in a series of month and
year directories in which the recording took place (see Figure 4.40).
1. Right-click on the data file and select Open with Wordpad. This will display the ASCII
data in WordPad.
2. From the Edit menu select the Replace option to replace all the ; (semicolons)
with , (commas).
3. From the File menu select Save As and save the file with an extension .csv (Comma
Separated Value).
4. This .csv file can now be opened in Excel with the correct format.
Alternatively, you can do the following--
1 Open Excel. Go to File, Open, select Files of Type: Choose Text files (*.prn, *.txt,
*.csv), and then select the data file you wish to open.
2. A Text Import Wizard should pop-up.
Select Delimited type of file, then Next.
Click on semicolon as the Delimiter type, then Next.
The screen should show how the file is being divided into columns, click on Finish.
3 From the File menu select Save As and save the file with an extension .csv.
The next time you open this file it will open in Excel automatically.
You may remove the letters C or F and D from the recorded values (using the
Replace option of Excel or Wordpad). This will enable you to create charts of the data.
Figure 4.41
Example of data recorded on the
SD card, standard text (.txt) file format
52
Page 59
4.11 iLog Software
This is an Excel application software that can log temperature, humidity and dewpoint
from the iServer over the local network (Ethernet) or the internet.
a)Download the iLog software from the website listed on the cover of this manual
(software section).
b)Install iLog software on a networked PC. This software is compatible with Windows
95, 98, NT, 2000, XP, and Vista.
c)If you have Excel 2007 or higher, when installing iLog choose “Custom” installation
option and on the next window check the box for “Excel 2007 Apps” and continue
the installation to the end.
d)For complete information of how to use the iLog software, click on the HELP button.
e)There is a list of Error Messages in Appendix F.
Figure 4.42 iLog Software Logging Data
The Options button will let you select the product model.
Choose iSE-TC from the Model Selection pull-down menu (from General tab).
The iLog application actually consists of several Excel files, though most supported
devices can be accessed by the main iLog program. The main program is listed as
"iLog", plus a version number, under the Start Menu program links (those links available
by clicking the Start button on the Windows taskbar).
In the following table, the iLog File column shows how many sensors are logged by the
main iLog file. If more than 3 sensors are available, then the Alternate column shows
how many sensors the device can support. Devices with more than 3 sensors will have
their own Excel file. For these files, click on the model device found in the Start Menu.
The "Auto" column shows number of columns per remote device that are possibly
displayed.
The Full column shows number of columns allocated per device for the "Full"
spreadsheet, which will be able to display all data for all active devices.
Networked ProductAutoFull
zSeries Receiver and Remotes1 to 4 column / device4 column / 32 device
wiSeries with zED Remotes1 to 2 column / device2 column / 32 device
UWTC REC-3 and Remotes1 or 2 column / device2 column / 32 device
wiSeries with UWTC Remotes1 to 2 column / device2 column / 32 device
The active wireless devices, when shown in the Excel application, will be shown with
the device number and the units returned.
54
Page 61
Thermocouple Input
Temperature Range: refer to Thermocouple Chart
Temperature Accuracy: refer to Thermocouple Chart
Resolution: 1°/0.1°
Temperature Stability: 0.08°C/°C
Thermocouple Cold End Tracking: 0.05°C/°C
Thermocouple Lead Resistance: 100 ohm max.
Thermocouple Type (ITS 90): J, K, T, E, R, S, B, C, N, L
Input TypeRangeAccuracy
Iron - Constantan-210 to 760°C / -346 to 1400°F0.4°C / 0.7°F
®
CHROMEGA
- ALOMEGA
Copper - Constantan
®
CHROMEGA
- Constantan
Pt / 13%Rh-Pt
Pt / 10%Rh-Pt
30%Rh-Pt / 6%Rh-Pt
-260 to -160°C / -160 to 1372°C1.0°C / 0.4°C
®
-436 to -256°F / -256 to 2502°F1.8°F / 0.7°F
-270 to -190°C / -190 to 400°C1.0°C / 0.4°C
-454 to -310°F / -310 to 752°F1.8°F / 0.7°F
-270 to -220°C / -220 to 1000°C1.0°C / 0.4°C
-454 to -364°F / -364 to 1832°F1.8°F / 0.7°F
-50 to 40°C / 40 to 1768°C1.0°C / 0.5°C
-58 to 104°F / 104 to 3214°F1.8°F / 0.9°F
-50 to 100°C / 100 to 1768°C1.0°C / 0.5°C
-58 to 212°F / 212 to 3214°F1.8°F / 0.9°F
600 to 1820°C1.0°C
1112 to 3308°F1.8°F
5%Re-W / 26%Re-W0 to 2320°C / 32 to 4208°F0.4°C / 0.7°F
LED Indicators: 100 BASE-T, Network Link and Activity, DHCP, Recording
LCD Display:32 digits, 4.8 x 9.7mm (0.19 x 0.38”)
Memory Data Flash Card:2 GB SD Flash Card for 8 months of data storage at
1 second recording intervals, or 7 years at 10 seconds
Relay Outputs: Two relays 1.5 A @ 30 Vdc
Alarm I/OsTwo contact inputs TTL 0.5 mA with 10K pull-up;
one open collector output 150 mA @ 30 Vdc
Auto MDI/MDIX
Sample Rate:16 samples/second max.
Management: Device configuration and monitoring through embedded
WEB server
Embedded WEB Server: Serves WEB pages containing real-time data and live
updated charts within definable time intervals.
POWER
Power Input:9 to 12 Vdc
Consumption:4W
Safety Qualified
ac Power Adapter (included)Nominal Output: 9 Vdc @ 0.5 A
Input: 100 to 240 Vac, 50/60Hz
Back-up Battery: 9 Vdc, alkaline. 30 hours at 10 second recording intervals,
or 60 hours at 1 minute intervals
ENVIRONMENTAL
Operating Temperatures
iServer Unit:0 to 60°C (32 to 140°F)
Battery:-18 to 55°C (-0.4 to 131°F)
ac Power Adapter:0 to 40°C (32 to 104°F)
Industrial Cable:-40 to 125°C (-40 to 257°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Material:SS 304 case with wall mount bracket
iServer Housing Dimensions:88.1H x 130.2W x 33.3D mm (3.47 x 5.13 x 1.31”)
Weight:462 g (1.02 lbs.), including battery
GENERAL
Agency Approvals: FCC-B, CE
Software: Compatible with Windows operating systems
Firmware upgrade from Ethernet
OPC Server
iConnect: Configuration software for the Ethernet interface
iLog: Macro for automatic data logging in MS Excel
56
Page 63
33)1(-9$
User of this manual should be familiar with following definitions:
ARP (Address Resolution Protocol) is a protocol for mapping an Internet Protocol address
(IP address) to a physical machine address that is recognized in the local network. For example,
the IP address in use today is an address that is 32-bits long. In an Ethernet local area network,
however, addresses for attached devices are 48-bits long. (The physical machine address is
also known as a Media Access Control or MAC address.) A table, usually called the ARP cache,
is used to maintain a correlation between each MAC address and its corresponding IP address.
ARP provides the protocol rules for making this correlation and providing address conversion in
both directions.
Ethernet is a network protocol defined by the IEEE 802.3 standard. Ethernet-based
networks use MAC Address rather then IP Address to exchange data between computers. By
using ARP and adding TCP/IP support, Ethernet devices may be connected as part of the
Internet. An Ethernet LAN typically uses coaxial cable or special grades of twisted pair wires.
The most commonly installed Ethernet systems are called 10BASE-T and provide transmission
speeds up to 10 Mbps. Devices are connected to the cable and compete for access using a
Carrier Sense Multiple Access with Collision Detection (CSMA/CD) protocol.
IP (Internet Protocol) is the method or protocol by which data is sent from one computer to
another on the Internet.
IP address (Internet Protocol address) is a 32-bit number that identifies each sender or
receiver of information that is sent in packets across the Internet.
IP Netmask is a 32-bit pattern of bits used to determine which part of the IP address is the
network portion and which part is the host portion.
MAC (Media Access Control) Address is your computer's unique hardware number. When
you're connected to the Internet from your computer, a correspondence table relates your IP
address to your computer's physical (MAC) address on the LAN.
Ping is a utility that tests the network connectivity. It is used to determine if the host is capable
of exchanging information with another host.
Port number/Socket number is a way to identify a specific process to which an Internet or
other network message is to be forwarded when it arrives at a server. It is a predefined address
that serves as a route from the application to the Transport layer or from the Transport layer to
the application of the TCP/IP system.
Sockets are a method for communication between a client program and a server program in a
network and defined as "the endpoint in a connection." Information transferred across the
Internet primarily occurs between sockets.
SMTP Simple Mail Transfer Protocol is an Internet standard for electronic mail (email) transfer
across the Internet. SMTP clients usually use SMTP to send email messages by specifying the
SMTP server. The email server uses SMTP to both send and receive email messages.
SNMP Simple Network Management Protocol is a network monitoring protocol to monitor
devices connected to an Ethernet Network.
TCP/IP (Transmission Control Protocol/Internet Protocol) is the basic communication
language or protocol of the Internet. When you are set up with direct access to the Internet, your
computer is provided with a copy of the TCP/IP program just as every other computer that you
may send messages to or get information from also has a copy of TCP/IP. TCP/IP often is used
as a general term to indicate generic access to the Internet.
UDP/IP (User Datagram Protocol/Internet Protocol) is the TCP/IP standard protocol that
allows an application program on one machine to send a datagram to an application program on
another. The UDP can be either in Broadcast or Directed form. The Broadcast UDP transmits
data to every node on the same network. The Directed UDP transmits data to one node only.
57
Page 64
33)1(-9((4)55
An IP address is a unique 32-bit address assigned to a computer and includes:
• A network ID number identifying a network.
• A host ID number identifying a computer on the network.
All IP addresses have been divided into three smaller groups (classes) A, B and C
• Class A addresses have 8-bits of network ID and 24-bits of host ID. They can support
a large number of hosts, approximately 2 = 16,777,216 computers per network.
The IP addresses range in binary from 00000001.xxxxxxxx.xxxxxxxx.xxxxxxxx
to 01111111.xxxxxxxx.xxxxxxxx.xxxxxxxx
The IP addresses range in decimal from 1.x.x.x to 127.x.x.x
Class A network ID’s support a very large number of hosts.
• Class B addresses have 16-bits of network ID and 16-bits of host ID. They can
support approximately 216= 65,536 computers per network.
The IP addresses range in binary from 10000000 00000000.xxxxxxxx.xxxxxxxx
to 10111111 11111111.xxxxxxxx.xxxxxxxx
The IP addresses range in decimal from 128.0.x.x TO 191.255.xxx.xxx
Class B network ID’s support a medium number of hosts.
• Class C addresses have 24-bits of network ID and 8-bits of host ID. They can support
approximately 28= 256 computers per network.
The IP addresses range in binary from 11000000.00000000.00000000.xxxxxxxx
to 11011111.11111111.11111111.xxxxxxxx
The IP addresses range in decimal from 192.0.0.xxx to 223.255.255.xxx
Class C network ID’s support a small number of hosts.
The rest of the addresses are divided into two classes, D and E.
Class D networks are not assigned to the host. They are used for multicasting.
The address range from 224.x.x.x to 239.x.x.x
Class E networks are experimental or reserved addresses.
The address range from 240.x.x.x to 247.x.x.x
58
Page 65
33)1(-9200&1(5
C:\>arp - 192.168.1.96
No ARP Entries Found
C:\>ping 192.168.1.96
Pinging 192.168.1.96 with 32 bytes of data:
Reply from 192.168.1.96=bytes=32 time=5ms TTL=32
Reply from 192.168.1.96=bytes=32 time=3ms TTL=32
Reply from 192.168.1.96=bytes=32 time=3ms TTL=32
Reply from 192.168.1.96=bytes=32 time=4ms TTL=32
C:\>arp -a 192.168.1.96
Interface: 192.168.1.118
Internet Address Physical Addresss Type
192.168.1.9600-03-34-00-00-23 dynamic
C:\>arp -s 192.168.1.96 00-03-34-00-00-23
C:\>arp -a 192.168.1.96
Interface: 192.168.1.118
Internet Address Physical Addresss Type
192.168.1.9600-03-34-00-00-23 static
C:\>arp -d 192.168.1.96
C:\>arp -a 192.168.1.96
No ARP Entries Found
C:\>
ARP is the Internet layer protocol responsible for matching or obtaining the MAC
(hardware) address that corresponds to a particular IP address. The ARP command
allows the user to view the current contents of the ARP cache of the local computer
(residing on the same network). Microsoft includes the ARP.EXE utility for viewing and
modifying the ARP cache with its Windows products. The following ARP commands can
be used to view cache entries:
• arp –a fi Use this command to view all ARP cache entries.
• arp –a plus IP address fi Use this command to view ARP cache entries associated
with one particular interface on a network with multiple adapters.
• arp –g fi Same as arp –a.
• arp –N fi Use this command to display ARP entries for specific network interface.
• arp – s plus IP address plus Physical address fi Use this command to manually
add a permanent static entry to the ARP cache.
• arp –d fi Use this command to manually delete a static entry.
Ping the destination computer using IP address first before using the arp -a
command.
The following window shows examples of arp commands and responses.
• Your computer has an IP address of 192.168.1.118
• The destination computer has an IP address of 192.168.1.96
Figure C.1 ARP Commands and Responses
59
Page 66
33)1(-9)60&5.
IP Netmask or Subnet Mask is a 32-bit pattern of ones and zeros used to determine
network portion of an IP address from the host portion of the IP address. Subnet mask is
a network ID that is created by borrowing bits from host portion of IP address and using
them as part of a network ID. The table below shows a default subnet mask for address
Classes A, B, and C. Each bit that is set to "1" in the subnet mask corresponds to the bit
in the IP address that is to be used as the network ID. Each bit that is set to "0" in the
subnet mask corresponds to a bit in the IP address that is to be used as the host ID.
Address ClassMask Binary Value Mask Decimal Value
or Dotted Notation
Class A255.0.0.0
Class B255.255.0.0
Class C255.255.255.0
11111111
11111111
11111111
00000000
11111111
11111111
00000000
00000000
11111111
00000000
00000000
00000000
If your network requires more network ID’s, you can extend the default subnet mask to
include additional bits from the host ID. This allows for additional network ID’s within the
network. The table below shows some examples of subnet masks and bits moved from
the hosts ID to create a new subnet.
To determine the number of valid hosts ID’s remaining after subnetting, use the following
equation: 2n– 2, where n is the number of octet digits left after the subnet mask.
-10005 Failed to find the iServer.Ethernet cable is disconnected,
iServer is powered off, connections
across the firewall require longer
“connection to socket time out”
setting.
-10006 Windows socket was closed.
-10007 Windows socket error.Wrong IP or wrong Port number
was used.
-10008 The iServer failed to respond to a request.Wrong IP or wrong Port number
was used.
-10011Response came empty.No data was sent.
-10012 Device responded with Possibly the iLog is configured for
"Serial Time Out" string.wrong product model.
-10014 Terminal Server Mode when the Port isTry to set “disconnect after data
configured to disconnect after sending data.sent” under Configuration/Server
-15100 Error on obtaining the temperature reading.Possibly the iLog is configured for
wrong product model.
-1Device responded with Possibly the iLog is configured for
"Command not found" string.wrong product model.
63
Page 70
33)1(-9&8&716-0)18-4210)16)673
Java (TM) Plug-in Control Panel
AdvancedBasicProxiesBrowserCertificatesCacheAbout
Update
Enable Caching
Cache Settings
ViewClear
Location
Size
Jar Compression
MB
Unlimited
C:\Documents and Settings\AppData\Sun\Java\Deploymentcache\java
NoneHigh
ApplyResetHelp
Maximum
50
If your computer does not have Java installed, please download from
http://java.sun.com. You can change the Java setting by clicking its icon in Control Panel.
To load the applet, you have to enable the web browser and disable cache.
1. Go to your computer's Control Panel. Open the Java Plug-in
2. Select the "Cache" Tab
Un-check the "Enable Caching" box
3. Select the "Proxy" Tab. Follow these Browser Proxy Selection instructions
below. (Generally, un-check the box if accessing iServer on your local network
and check the box for access from your internal network to the internet.)
4. Refresh or restart the webpage.
To disable cache setting:
For Java Version 1.4.2.x it is found under the CACHE TAB.
1. Go to your computer's Control Panel. Open the Java Plug-in
2. Click on "Settings" & "View Applets" in the "General" tab.
3. Select the "Settings" button on the General Tab
Un-check the "Enable Caching" box. Then close dialog box to show the General
Tab again
4. Select the "Network Settings" button on the General Tab.
Proceed to the Browser tab. Follow the Browser Proxy Selection instructions
below.You should either select the "Use Browser Settings" option or the "Direct
Connection" option depending on the network connections between your
computer and the iServer. (Generally, select "Direct Connection" if accessing
iServer on your local network and select "Use Browser Settings" option for access
from your internal network to the internet.)
5. Refresh or restart the webpage.
For Java Version 1.5.x.x it is found under "General" > "Settings" > "View Applets" and
then at the bottom there is the Checkbox to REMOVE CACHE .
Figure G.2 Java 1.5.x.x. Screen Shots
For Java 1.6.x.x it is similar to Java 1.5.x.x but there is no need to remove
CACHE.
65
Page 72
G.3 Browser Proxy Selection
Accessing iServer within your internal network
•Usually when the computer and iServers are on an internal network, you will not use
Proxy server access.
•You should un-check the "Use Browser Settings" option on the "Proxy" tab.
Accessing iServers units using the internet
•Often the web browser will use Proxy server access to the internet. In such cases,
the default Java runtime settings on the "Proxy" tab should suffice. The default
setting is the "Use Browser Settings" option.
•If the default proxy setting doesn't work, then you may have a situation where the
proxy settings of the web browser are incorrect.
Diagnostics:
If the web page of the iServer appears, then the HTTP Proxy is working fine.
If the data isn't updated on the iServer upon selecting the "Readings" or "Chart" web
page, there may be a problem with access through a winsock proxy server. In such
cases your network administrator will need to provide the winsock proxy server and port
#s. .
These values should be entered into the Socks line on the "Proxy" tab (of the Java
Plugin control panel) or into the "connections" tab on the View,Internet Options dialog
and make sure that the Proxy tab shows that the "Use Browser Settings" option is not
selected (i.e. when you specify proxy connections in the Java Plugin control panel).
Accessing iServer units over Peer-to-Peer network
A simple peer-to-peer network is setup by disconnecting from the main network (as users
will often do when trying to do initial setup of the iServer) and then connecting the
iServer to another computer using an ethernet hub, an ethernet switch, or a Cross-over
cable connection.
Often when using a peer-to-peer network, the Java plugin and the web browser (such as
Internet Explorer) have internet connections configured to connect through proxy
servers. In such case, you will need to simply assign the final IP address on this peer to
peer network and then view the iServer charts after connecting the iServer into the
regular network. Otherwise you can disable the Java plug-in's "Use Browser Settings"
temporarily and then reconfigure the Java plug-in settings for regular network access
after testing the iServer chart access on your peer-to-peer network.
The "Use Browser Settings" should not be selected. And the HTTP and Socks proxy
entries should be blank. Also, setup the internet browser so that proxy servers are disabled.
66
Page 73
33)1(-9&8&2/-':
To activate data retrieval and to save charts from the Java applets, it is necessary to
create a Java Policy file and copy it onto a folder.
1)Open a Notepad file and using the IP address of the iServer type the following:
grant codeBase "http://192.168.1.200/"
{
permission java.security.AllPermission "*", "*";
};
This file should have the IP address of the iServer; in this case the default IP
address is 192.168.1.200.
If the IP address is changed, then the IP address shown in the file needs to be
changed; otherwise, it will not work.
If DHCP/DNS is enabled, the unique iServer’s name using DNS should replace
the IP address.
Example: "http:\\iTHXTEST". Make sure the DHCP server updates the DNS
table to keep track of the iServer’s name and IP addresses (consult with your
network administrator).
2)Save the file as java_policy.txt.
3)Create a folder in your C: drive called "0_JAVAPOLICY".
4)Place the java_policy.txt file into the "0_JAVAPOLICY" folder.
Figure H.1 Java Policy
Java Policy instructions continued on next page.
67
Page 74
&8&2/-': (continued)
Java Runtime Settings
Control Panel
Java Control Panel
Control Panel
Address
CommentsName
JavaJava(TM) Control Panel
General UpdateSecurity AdvancedJava
Java Applet Runtime Settings
Runtime settings are used when an applet is executed in the browser.
If you have multiple Java Runtime Versions listed, add this line to the version
that you are using; if you update your Java, you will need to add this line again.
c.Click OK on the Java Runtime Settings window.
d.Click Apply on the Java Control Panel window and then OK.
6) Close all opened Web browsers.
The "Data Logging" button on the "Readings" page, "Save Chart" button on the
"Chart" page, and the "Retrieve" button on the "Recording Data Retrieval" page
Figure H.2 Java Policy
will not be active if the instructions explained in the above are not followed.
68
Page 75
33)1(-9
Table J-1 SNMP MIB-2
Version: SNMPv1 Private Enterprise Number: .1.3.6.1.4.1.34089
MIB-2 (RFC 1213) supported: System Group
Object Identifier ObjectDescriptionAccessDefault
(OID)
.1.3.6.1.2.1.1.1sysDescrThe name and versionRead-onlyiSD-TC/ X.XX
.1.3.6.1.2.1.1.2sysObjectID The authoritative identification Read-only.1.3.6.1.4.1.34089.X.X
.1.3.6.1.2.1.1.3sysUpTime The time since the system Read-only
.1.3.6.1.2.1.1.4sysContact The contact person for this Read-writeNone
.1.3.6.1.2.1.1.5sysNameThe hostname of this node.Read-writeisdXXXX
.1.3.6.1.2.1.1.6sysLocation The physical location of Read-writeNone
.1.3.6.1.2.1.1.7sysServices The set of services that thisRead-only76
identification of the productX.XX is the
firmware version
of the network management X.X is the product
subsystem contained in the system object ID
product. This value is allocated
within the SMI enterprises
subtree (1.3.6.1.4.1).
was last re-initialized.
node, together with
information on how to
contact this person.
XXXX are the last
4 characters of the
MAC address
this node.
product primarily offers.Services include
The value is a sum of network application, end-to-end
layer services implemented.and internet
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year
from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty
period for one (1) additional year if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found
to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which
wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the
parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESE NTATIONS OF ANY KIND WHATSOEV ER, EX PRE SS OR IMPLIED, EXCEPT THAT OF TI TLE , AN D ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”
under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on
humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on
humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage
whatsoever arising out of the use of the Product(s) in such a manner.
!! !
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR
number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
2. Model and serial number of the product under warranty,
and
3. Repair instructions and/or specific problems relative to
the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.