Omega Products IP-413 Installation Manual

Electropneumatic Transducer
IP-411 and IP-413
M2073/0303
SPECIFICATIONS
Accur acy*: ± 1%
Maximum Supply Pressure: 40
Pressure Differential: 0.1
Supply Voltage: 18 to 28
Supply Current: 150 M
Enclosure: 18 Ga. C.R. steel chassis
Finish: Baked on enamel PMS2GR88B
Conformance: EMC standards EN50082-1(1992),
EN55014(1993)/EN60730-1(1992)
Compensated Temperature Range: 25°F to 150°F (4°C to 65°C)
T. C . Er ro r : ± 0.025%/°F (.03%/°C)
Media Compatibility: Clean dry air or any inert gas
Port Connection: ¼-inch O.D. poly tubing
Environmental: 10 to 90% RH non-condensing
Te rm in a ti o n: Screw terminal block
Wire Size: 12 Ga. maximum
Input Impedance: 301 ohms (4 - 20 MA); 10K ohms
(0 - 5 or 0 - 10
Weight: 1.0 lb. (.45 kg)
Includes nonlinearity, hysteresis, and non-repeatability.
*
VDC
FS
PSIG
(supply to branch)
PSIG
or
VAC
VDC
A
)
3. Pull wires through the bottom of the transducer and make the necessary connections.
4. Make the pneumatic connections.
WIRING
Use maximum 12 ¼-inch O.D. poly tubing for main and branch pneumatic connection s. The elect ropneumat ic transdu cer can be powered with a 18 to 28
1. Connect the power supply voltage wire to the supply [+] termina l and the power suppl y common to the common [-] terminal.
2. Connect the controller output wire to the input [I] terminal and the controller common wire to the common [-] terminal.
wire for wiring terminals and flexible
AWG
or
supply.
VAC
VDC
JUMPER CONFIGURATIONS
Jumper configuration varies by output type: MA or
VDC
.
CALIBRATION
All electropneumatic transducers are factory calibrated to meet or exceed published specifications. If field adjustment is necessary, follow these instructions:
1. Connect air to the Main port.
2. Connect an accurate gauge to the Branch port using a
minimum of 6 to 10 feet (1.8 to 3.0 m) of tubing.
3. Connect an 18 to 28 VAC or VDC power source to the [+] and [-] terminals. The maximum supply voltage should not exceed 30
4. Apply a low input signal to the [-] and [I] terminals (0
or 4 MA).
VDC
5. Adjust [Z] to obtain the desired low output pressure.
6. Apply a high input signal to the [-] and [I] terminals (5/
10
or 20 MA).
VDC
7. Adjust [S] to obtain the desired high output pressure.
8. Repeat steps 4 through 7 until the transducer is fully
calibrated.
VAC/VDC
.
DIMENSIONS
INSTALLATION PRECAUTIONS
Do not use on an oxygen service, in an explosive or hazardous environment, or with flammable or combustible material.
Disconnect the power supply before installing the transducer. Failure to do so can result in electrical shock and equipment damage.
Make all connections in accordance with the job wiring diagram and national and local electrical codes. Use only copper conductors.
Use electrostatic discharge precautions such as wrist straps when installing and wiring the transducer.
Do not exceed ratings for the transducer.
This transducer contains a half-wave rectifier power supply and must not be powered fro m transforme rs powering other devices with non-isolated full-wave rectifier power supplies.
Verify that the main supply pressure does not exceed 40
Ensure a minimum of 6 to 10 feet (1.8 to 3.0 m) of tubing between the transducer and the actuator.
For a 24 neutral are not reversed. If more than one transducer is being powered from the same transformer, the hot and neutral should be the same for each transducer.
supply voltage, make sure that the hot and
VAC
PSIG
MOUNTING
The electropneumatic transducer must be mounted in an upright posi tion so that th e main and bra nch ports face upwards and the gauge can be read easily.
1. Select the mounting location.
2. Mount the transducer on a vertical surface with three
#8 self-tapping screws (not provided).
.
CHECKOUT
To verify proper operation of the transducer, adjust the input signal to obtain a maximum output pressure for the appropriate range. The output should be 15 or 20 adjust the input signal to obtain a minimum output pressure. The output sho uld be 0 or 3
PSIG
.
PSIG
. Next,
Manual REVISION