Omega Products FL9000-AC Installation Manual

Page 1
FL9000-ACSERIES
Flowmeters
Operators Manual
Page 2
FLWOO-AC
SERIES INSTALLATION
OMEGA@
The
rugged proven technology of a direct reading, type, variable area flowmeter, with a solid state switching module This combination aids the machine designer/troubleshooter by providing taneous flow-rate
The
1. plastic. Polysulfone is a strong remains very stable to precautions must be observed to ensure proper performance.
a)
b)
cl
dJ
FL9000-AC
READ INSTRUCTIONS THOROUGHLY BEFORE INSTALLING FLOWMETER
FL9000-AC
The meter will melt, crack or distort if exposed to an open flame or excessive heat. Therefore, DO
sweatfit
NOT mounted to the plastic flowmeter body.
Pipe dope MUST NOT CONTACT the plastic flowmeter body. Some pipe dope formulas will react adversely with Polysulfone. If a sealing material is necessary, use of Teflon tape is
recommended. Do not over-tighten the threads on the plastic
flowmeter body. Overtightening NPT pipe threads may cause fracturing of the plastic flowmeter body.
Piping on the inlet and outlet of the flowmeter must be aligned. Pay special attention to this
Flowmeter combines the
piston-
hermeticaiy
indrcation,
Flowmeter is made of polysulfone
brass fittings into a system while
coupled with the
?hermoplastic,
21OF.
However, some
sealed,
instan-
IMPORTANT
and
s
electronic signal module, which automatically alerts the operator. or controller if an incorrect flow rate is detected.
verification, pump testing, etc
2.
3.
4.
5.
.
Uses of this product include cooling indication and verification, lubrication oil indication and
when high temperature, high pressure, or a combination of both may be encountered.
e)
Check the compatibility of the fluid in the system with the materials used in the flowmeter.
FL9000-AC
The straight pipe at the inlet or outlet to stabilize the flow through the meter.
FL9000-AC
The orientation. Its design allows the designer/installer to mount the flowmeter in horizontal piping, or vertical piping, without affecting meter accuracy.
FL9000-AC
The normally jam valves and other flow controls. If particulate will be encountered, a 200 mesh or 74 micron filter is recommended.
Notice the “Flow Direction” arrow located on the flowmeter scale The valve to flow moving against the arrow.
DOES NOT require lengths of
can be mounted in any plane of
will tolerate particles that will
FL9000-AC
water/Glycol
will act as a check
Page 3
FLOW ALARM ASSEMBLY
RETAINING
(Fig. 1)
After the Flow Meter is installed, loosen the cap screw on the electronic alar m assemb ly (see Figure 1). Adjust the assembly so that the retaining band centers approxi ma tely at the desired flow alar m position. Then, retighten
cap screw securely. The module turns “on” as
BAND
flo w exceeds preset. The separate four conductor female connector. To solder wires onto the connector, it will have to be disassembled, as shown in Figure 2.
J
FL9000-AC comes w ith a
SOLDER LUG
GASKET
(Fig. 2)
LOOSEN STRAIN RELIEF NUT AND RUN
W IRES IN HERE
STRAIN RELIEF NUT
2
Page 4
The connector has four On the FL9000
3 and 4 are not used. On the
unit with the VAC flow alarm, terminals
flow alarm, terminal
solder lugs labeled
FL9DCKl
3 is not used. It should be noted
1.2.3
and 4.
unit with the VDC
before reassembly, which wire is connected to which
-
solder lug. see
Color coding, or labeling the
6gures
3a
and
3b
wires is advised.
STRAIN RELIEF NUT
POlARlPl
(Fig.
After securing wires to solder lugs, a determination of the orientation that the body of the connector should face. needs to be into the connector body, see Figure 4 below,
mada
PIN
3al
Before snapping the conductors back
4
After choosing orientation A, B or C, snap connector back together, pull excess wires out of strain relief, and tighten strain nut. Plug into electric housing and secure with screw.
r
INLET OF FLOWMETER
-
ELECTRONIC
STRAIN RELIEF NUT
POLARITY PIN
(Fig.
HOUSING
3b)
3
POLARITY PIN
(Fig. 4)
Page 5
FL9000-AC
The variety of different
is designed to turn “on” or “off” a
115VAC
loads. Examples of loads include: Solenoid valves, warning lights and AC relay coils. The module can only switch loads that consume between 2.5 and 90 watts, or have 5000R to 150R impedance respectively. If the load draws less than 2.5 watts, a loading capacitor is required. The capacitor s value and connection is demonstrated in Figure 5. If the
load draws greater than 90 watts, a power relay is
necessary. Figs. 6 and 7 show typical relay connections. Wiring Configurations:
Conventional Connection: See Fig. 5
1.
3 Load limited by relay contacts
3.
The Schematic in Fig. 5 will provide conduction over
15-20% of full scale above, or below the flow rate set
point.
LOADS CAP. MUST BE
RATED
XSOOV
INWCT lVE
WITH
Fig. 5
foad
1
must draw between 2.5 and 90 watts. For
loads smaller than 2.5 watts, see
#2.
For loads
greater than 90 watts, see Figs. 6 and 7.
2 Loads consuming less than 2.5 watts require a
0.47
PF
capacitor connected as shown. This capacitor will increase the power consumption and ensure complete conduction.
2. Conventional Relay Connections: See Fig. 6 Fig. 6 demonstrates a SPDT relay with a 115 VAC coil
integrated with a flow alarm module. This combination allows switching of loads up to the rating of the relay contacts.
VW
11s
RELAY
1
Y 3
:
RELAY CONTACT
RI
I
I I
4
I
Fig. 6
latching Relay Systems: See Fig. 7
The Flow Alarm Module can be integrated with latching type relays, or a simple latching system can be connected as in Fig. 7.
DPDT
RELAY
W
BUT
f
-1 I,
0
TON
“LLA,
0
RELAY CONTACT
LUNIACI
Y,
IF--- -
The module will turn the relay “on” as flow either exceeds, or falls below the flow rate set point. The relay will remain activated until the reset button is depressed.
Page 6
Wiring Configurations for VDC Flow Alarm:
1. For relay output: al Relays with coil voltage
between 7 and 24 VDC.
b)
Relays with coil voltage
between 4 and 60 VDC.
TTL/CMOS interface:
2. For
FROM
CONNECTOR
3. Other loads (eg. lamp, buzzer,
.
etc) The load must draw less than
0.5 amps at 7-24 VDC. If the load uses in excess of 0.5 amps or 24 VDC, section 1 wiring must be used.
Note: See specifications to avoid damage to FET (transistor).
CAUTION: To protect the FET from damage due to inductive collapse, use a “catch” diode, as demonstrated in section 1 of wiring configurations, when switching inductive loads such as solenoids and relay coils. Connection of Terminal 1 directly to a voltage source will destroy the unit.
VCLTAGE
Page 7
SPECIFICATIONS ACCURACY: REPEATABILITY: MAX. TEMP./PRESSURE:
MAXIMUM PARTICLE SIZE:
SIZE:
CONNECTION:
MATERIAL:
f
7% full scale
f
1% full scale
7ooF;@
220 PSI 60
PSI at
74 microns for standard units; 400 microns for ribbed piston water meters
3h”
1
FL-9200- /(a”
FL-9000 and
Length
(A” (1/6” Copper Tubing. FL-9000 and Male
Polysulfone
210°F
across flats,
Length;
9100-5%
%”
O.D.) or 1” Nominal
O.D.)
Type M
FL9100-1”
NPT,
*
NominalFL9200-Fits
WETTED PARTS:
ALARM
SETPOINT:
RELAY:
Polysulfone, steel,
barium ferrite Proximity switch
triggering a
1 amp over 25% of span, and drops out above and below that. Includes mating connector. Relay not field installable
Adjustable
stainless
Buna-N,
and
110
Relay pulls in
triac.
O-100%
VAC
FS
@
Page 8
ONLY OUALlFlEO PERSONNEL. NO WARRANTY EXTENDED HEREIN WILL APPLY IF SUCH UNIT IS INSTALLED OR U
SED BY
UNOUALIFIED PERSO ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED. INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AN0 OF FITNESS FOR A PARTICULAR PURPOSE. OMEGA ENGINEERING, INC IS NOT RESPONSIBLE FOR ANV DAMAGES OR LOSSES CAUSED TO OTHER EOUIPMENT. WHETHER DIRECT. INDIRECT. INCIDENTAL. SPECIAL OR PURCHASER MAY EXPERIENCE AS A RESULT OF THE INSTALLATION OR USE OF THE PRODUCT THE BUYER S SOLE REMEDY FOR ANY BREACH OF THIS AGREEMENT BY OMEGA ENGINEERING. INC OR ANY
OF
ANY
BRV\CH PAID BY THE DIRECTLY AFFECTED BY SUCH BREACH.
EVERY PRECAUTION FOR ACCURACY HAS BEEN TAKEN IN THE PREPARATION OF THIS MANUAL. HOWEVER, OMEGA ENGINEERING. INC. NEITHER ASSUMES ERRORSTHAT
OF THE PRODUCTS IN ACCORDANCE WITH THE INFORMATION CONTAINED IN THE MANUAL.
WARRANTY BY OMEGA ENGINEERING, INC. SHALL NOT EXCEEDTHE PURCHASE PRICE
PURCnASER TO OMEGA ENGINEERING. INC. FOR THE UNIT OR UNITS OR
MAY APPEAR NOR ASSUMES
NNEL
. THERE ARE NO WARRANTIES EXCEPT AS STATED HEREIN. THERE
CONSEOUENTIAL. WHICH THE
LIABILITV FOR ANY DAMAGES THAT RESULT FROM THE USE
RESPONSIBILITV FOR ANY OMISSIONS OR
BYTHESE UNITS ARE INHERENTLY DANGEROUS AND ARE INTENDED TO BE INSTALLED AND USED
EOUIPMENT
=OMEGA
,,. One Omega
Slamford,
,.“I%
ENGINEERING,INC.
rrrbu).“lo
I
Owe.
Box 4047
Connecncu:
““rpy,
ffi907-0047
Call OMEGA Toll Free .
Sales:
Customer Service: l-600-622-2378
Engineering Assistance:
CT:
(203)
In
And
Direct telephone number (203) CONTACT THE OMEGA CUSTOMER SERVICE DEPARTMENT TO OBTAIN AN AUTHORIZED RETURN (AR) NUMBER. The designated AR number should then be marked on the outside of the return package.
359.1660
lnlernabonal
all warranty and
To
1. Returnee s name,
2. Model end Repalr
3.
OMEGA s policy is
Thai
possible.
OMEGA” is a
0
Copyright 1990 OMEGA ENGINEERING, INC. All rights reserved including illustrations.
in this manual may be reproduced
without
way our
regls:ered
writlen
1400-TGOMEGA
I
1-600-6246342
140047244361
repalr
delaya,
Serlal
Inrtructlons.
IO
make running changes, not model changes,
cuslomers
l-600-622-BEST
I
l-600-USA-WHEN
CABLE: OMEGA TELEX: 996404
Return
requeats/lnqulriea
359.1660. BEFORE RETURNING ANY INSTRUMENT, PLEASE
alao please be
proceaalng rvold
address, and phone number.
numbem.
get the latest
EASYLINK: 62966934
FAX: (203) 3547700
Requests/lnqulrter
to OMEGA Customer Service Department,
sun, to Include:
in technology and
trademark of OMEGA ENGINEERING,
permission
In
any manner,
lrom
OMEGA ENGINEERING,
eflher wholly or
whenever an improvement is
engmeenng.
INC.
In
pan for any purpose whatsoever
INC.
Nolhing
Printed in U.S.A
M1174/0590
Loading...