rugged proven technology of a direct reading, type, variable area flowmeter, with a solid state switching module This combination aids themachine designer/troubleshooter by providingtaneous flow-rate
The
1.plastic. Polysulfone is a strong remains very stable to precautions must be observed to ensure properperformance.
a)
b)
cl
dJ
FL9000-AC
READ INSTRUCTIONS THOROUGHLY BEFORE INSTALLING FLOWMETER
FL9000-AC
The meter will melt, crack or distort if exposed toan open flame or excessive heat. Therefore, DO
sweatfit
NOT mounted to the plastic flowmeter body.
Pipe dope MUST NOT CONTACT the plasticflowmeter body. Some pipe dope formulas willreact adversely with Polysulfone. If a sealingmaterial is necessary, use of Teflon tape is
recommended.Do not over-tighten the threads on the plastic
flowmeter body. Overtightening NPT pipethreads may cause fracturing of the plasticflowmeter body.
Piping on the inlet and outlet of the flowmetermust be aligned. Pay special attention to this
Flowmeter combines the
piston-
hermeticaiy
indrcation,
Flowmeter is made of polysulfone
brass fittings into a system while
coupled with the
?hermoplastic,
21O’F.
However, some
sealed,
instan-
IMPORTANT
and
s
electronic signal module, which automatically alerts theoperator. or controller if an incorrect flow rate is detected.
verification, pump testing, etc
2.
3.
4.
5.
.
Uses of this product include cooling indication and verification, lubrication oil indication and
when high temperature, high pressure, or acombination of both may be encountered.
e)
Check the compatibility of the fluid in the systemwith the materials used in the flowmeter.
FL9000-AC
The straight pipe at the inlet or outlet to stabilize the flowthrough the meter.
FL9000-AC
The orientation. Its design allows the designer/installer tomount the flowmeter in horizontal piping, or verticalpiping, without affecting meter accuracy.
FL9000-AC
The normally jam valves and other flow controls. Ifparticulate will be encountered, a 200 mesh or 74micron filter is recommended.
Notice the “Flow Direction” arrow located on theflowmeter scale The valve to flow moving against the arrow.
DOES NOT require lengths of
can be mounted in any plane of
will tolerate particles that will
FL9000-AC
water/Glycol
will act as a check
Page 3
FLOW ALARM ASSEMBLY
RETAINING
(Fig. 1)
After the Flow Meter is installed, loosen the cap screwon the electronic alarm assembly (see Figure 1). Adjustthe assembly so that the retaining band centersapproximately at the desired flow alarm position. Then,retighten
cap screw securely. The module turns “on” as
BAND
flow exceeds preset. The separate four conductor female connector. To solderwires onto the connector, it will have to be disassembled,as shown in Figure 2.
J
FL9000-AC comes with a
SOLDER LUG
GASKET
(Fig. 2)
LOOSEN STRAIN RELIEFNUT AND RUN
WIRES IN HERE
STRAIN RELIEF NUT
2
Page 4
The connector has fourOn the FL9000
3 and 4 are not used. On the
unit with the VAC flow alarm, terminals
flow alarm, terminal
solder lugs labeled
FL9DCKl
3 is not used. It should be noted
1.2.3
and 4.
unit with the VDC
before reassembly, which wire is connected to which
-
solder lug.see
Color coding, or labeling the
6gures
3a
and
3b
wires is advised.
STRAIN RELIEF NUT
POlARlPl
(Fig.
After securing wires to solder lugs, a determination of theorientation that the body of the connector should face.needs to be into the connector body, see Figure 4 below,
mada
PIN
3al
Before snapping the conductors back
4
After choosing orientation A, B or C, snap connectorback together, pull excess wires out of strain relief, andtighten strain nut. Plug into electric housing and securewith screw.
r
INLET OF FLOWMETER
-
ELECTRONIC
STRAIN RELIEF NUT
POLARITY PIN
(Fig.
HOUSING
3b)
3
POLARITY PIN
(Fig. 4)
Page 5
FL9000-AC
The variety of different
is designed to turn “on” or “off” a
115VAC
loads. Examples of loadsinclude: Solenoid valves, warning lights and AC relaycoils. The module can only switch loads that consumebetween 2.5 and 90 watts, or have 5000R to 150Rimpedance respectively. If the load draws less than 2.5watts, a loading capacitor is required. The capacitor’svalue and connection is demonstrated in Figure 5. If the
load draws greater than 90 watts, a power relay is
necessary. Figs. 6 and 7 show typical relay connections.Wiring Configurations:
Conventional Connection: See Fig. 5
1.
3Load limited by relay contacts
3.
The Schematic in Fig. 5 will provide conduction over
15-20% of full scale above, or below the flow rate set
point.
LOADS CAP. MUST BE
RATED
XS’OOV
INWCTlVE
WITH
Fig. 5
foad
1
must draw between 2.5 and 90 watts. For
loads smaller than 2.5 watts, see
#2.
For loads
greater than 90 watts, see Figs. 6 and 7.
2 Loads consuming less than 2.5 watts require a
0.47
PF
capacitor connected as shown. Thiscapacitor will increase the power consumption andensure complete conduction.
2. Conventional Relay Connections: See Fig. 6Fig. 6 demonstrates a SPDT relay with a 115 VAC coil
integrated with a flow alarm module. Thiscombination allows switching of loads up to therating of the relay contacts.
VW
11s
RELAY
1
Y3
:
RELAY CONTACT
RI
I
II
4
I
Fig. 6
latching Relay Systems: See Fig. 7
The Flow Alarm Module can be integrated withlatching type relays, or a simple latching system canbe connected as in Fig. 7.
DPDT
RELAY
W
BUT
f
-1I,
0
TON
“LLA,
0
RELAY CONTACT
LUNIACI
Y,
IF----
The module will turn the relay “on” as flow eitherexceeds, or falls below the flow rate set point. Therelay will remain activated until the reset button isdepressed.
Page 6
Wiring Configurations for VDC Flow Alarm:
1. For relay output:al Relays with coil voltage
between 7 and 24 VDC.
b)
Relays with coil voltage
between 4 and 60 VDC.
TTL/CMOS interface:
2. For
FROM
CONNECTOR
3.Other loads (eg. lamp, buzzer,
.
etc)The load must draw less than
0.5 amps at 7-24 VDC. If theload uses in excess of 0.5amps or 24 VDC, section 1wiring must be used.
Note: See specifications to avoid damage to FET (transistor).
CAUTION: To protect the FET from damage due to inductivecollapse, use a “catch” diode, as demonstrated in section 1 of wiringconfigurations, when switching inductive loads such as solenoidsand relay coils. Connection of Terminal 1 directly to a voltage sourcewill destroy the unit.
74 microns for standardunits; 400 microns forribbed piston watermeters
3h”
1
FL-9200-‘/(a”
FL-9000 and
Length
(‘A”(1’/6”Copper Tubing. FL-9000and Male
Polysulfone
210°F
across flats,
Length;
9100-5%
%”
O.D.) or 1” Nominal
O.D.)
Type M
FL9100-1”
NPT,
*
NominalFL9200-Fits
WETTED PARTS:
ALARM
SETPOINT:
RELAY:
Polysulfone,steel,
barium ferriteProximity switch
triggering a
1 amp over 25% of span, anddrops out above andbelow that. Includesmating connector. Relaynot field installable
Adjustable
stainless
Buna-N,
and
110
Relay pulls in
triac.
O-100%
VAC
FS
@
Page 8
ONLYOUALlFlEO PERSONNEL. NO WARRANTY EXTENDED HEREIN WILL APPLYIF SUCH UNIT IS INSTALLED ORU
SED BY
UNOUALIFIED PERSOARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED. INCLUDING BUT NOT LIMITED TO THE IMPLIEDWARRANTIES OF MERCHANTABILITY AN0 OF FITNESS FOR A PARTICULAR PURPOSE. OMEGAENGINEERING, INC IS NOT RESPONSIBLE FOR ANV DAMAGES OR LOSSES CAUSED TO OTHEREOUIPMENT. WHETHER DIRECT. INDIRECT. INCIDENTAL. SPECIAL ORPURCHASER MAY EXPERIENCE AS A RESULT OF THE INSTALLATION OR USE OF THE PRODUCT THEBUYER’S SOLE REMEDY FOR ANY BREACH OF THIS AGREEMENT BY OMEGA ENGINEERING. INC OR ANY
OF
ANY
BRV\CHPAID BY THE DIRECTLY AFFECTED BY SUCH BREACH.
EVERY PRECAUTION FOR ACCURACY HAS BEEN TAKEN IN THE PREPARATION OF THIS MANUAL.HOWEVER, OMEGA ENGINEERING. INC. NEITHER ASSUMES ERRORSTHAT
OF THE PRODUCTS IN ACCORDANCE WITH THE INFORMATION CONTAINED IN THE MANUAL.
WARRANTY BY OMEGA ENGINEERING, INC. SHALL NOT EXCEEDTHE PURCHASE PRICE
PURCnASER TO OMEGA ENGINEERING. INC. FOR THE UNIT OR UNITS OR
MAY APPEARNOR ASSUMES
NNEL
. THERE ARE NO WARRANTIES EXCEPT AS STATED HEREIN. THERE
CONSEOUENTIAL. WHICH THE
LIABILITV FOR ANY DAMAGES THAT RESULT FROM THE USE
RESPONSIBILITV FOR ANY OMISSIONS OR
BYTHESE UNITS ARE INHERENTLY DANGEROUS AND ARE INTENDED TO BE INSTALLED AND USED
EOUIPMENT
=OMEGA
,,.One Omega
Slamford,
‘,.“I%
ENGINEERING,INC.
‘rrrbu).“lo
I
Owe.
Box 4047
Connecncu:
““rpy,
ffi907-0047
Call OMEGA Toll Free’.
Sales:
Customer Service: l-600-622-2378
Engineering Assistance:
CT:
(203)
‘In
And
Directtelephone number (203)CONTACT THE OMEGA CUSTOMER SERVICE DEPARTMENT TO OBTAIN AN AUTHORIZEDRETURN (AR) NUMBER. The designated AR number should then be marked on the outside ofthe return package.
359.1660
lnlernabonal
all warranty and
To
1. Returnee’s name,
2. Model end Repalr
3.
OMEGA’s policy is
Thai
possible.
OMEGA” is a
0
Copyright 1990 OMEGA ENGINEERING, INC. All rights reserved including illustrations.
in this manual may be reproduced
without
way our
regls:ered
writlen
1400-TGOMEGA
I
1-600-6246342
140047244361
repalr
delaya,
Serlal
Inrtructlons.
IO
make running changes, not model changes,
cuslomers
l-600-622-BEST
I
l-600-USA-WHEN
CABLE: OMEGATELEX: 996404
Return
requeats/lnqulriea
359.1660. BEFORE RETURNING ANY INSTRUMENT, PLEASE
alao please be
proceaalngrvold
address, and phone number.
numbem.
get the latest
EASYLINK: 62966934
FAX: (203) 3547700
Requests/lnqulrter
to OMEGA Customer Service Department,
sun, to Include:
in technology and
trademark of OMEGA ENGINEERING,
permission
In
any manner,
lrom
OMEGA ENGINEERING,
eflher wholly or
whenever an improvement is
engmeenng.
INC.
In
pan for any purpose whatsoever
INC.
Nolhing
Printed in U.S.A
M1174/0590
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.