2.3 FILTER INSTALLATION
It is recommended that a filter with a rating of two (2) microns
be installed on the inlet side of the meter. This filter will reduce
the amount of foreign matter that could impair operation of
meter.
2.4 INSTALLATION OF METER
a. Check the control valve is fully closed.
b. Check the valve body is fully seated in meter
frame. Finger tighten if necessary.
c. Slowly tip meter back and forth and check that
float has freedom to move.
d. Remove dust covers from the inlet and outlet connections.
e. Install inlet and outlet line connections. Inlet
connection is at the zero end of the meter
.
2.5 CONTROL VALVE REPOSITIONING PROCEDURE
The user may desire to change the control valve from
the inlet side of the meter to the outlet side. If meter
is installed in the line, make sure that flow is stopped
to the meter. Failure to do this may result in a safety
hazard.
a. Disconnect inlet and outlet lines to meter.
b. Remove metering tube and seal spindle. Refer to
paragraph 4.3
c. Remove check ball from inside seal spindle.
Retain check ball for future use.
d. Install seal spindle in meter body. Refer to
paragraph 4.4
e. Turn meter 180
°
from original position so control
valve is now on outlet and seal spindle is on inlet.
f. Install metering tube. Refer to paragraph 4.4
g. Connect inlet and outlet lines to meter.
SECTION 3 OPERATION
3.1 GENERAL
After the meter has been installed it is ready for
operation. During operation make sure that meter
temperature and pressure specifications are not exceeded,
as stated in paragraph 1.2
When the valve stem knob is turned counterclockwise to
the stop, the valve is fully open. Flow indication is
measured using the center of the float as the reference
point. A check valve is incorporated within the seal
spindle. The check valve prevents reverse flow through
the meter when upstream flow is stopped. When the
control valve is installed on the outlet of the meter, the
check valve is not included.
SECTION 4 MAINTENANCE
4.1 GENERAL
No periodic maintenance, oiling, or cleaning is required
for the meter or meter components when it is used in
normal applications. It may be necessary to remove the
metering tube and components for cleaning when various
liquids have stained or left a deposit.
It is recommended that the meter and meter components
be ultrasonically cleaned if possible. If ultrasonic cleaning
is not available, use a suitable solvent. Tube and float may
be cleaned with a pipe cleaner or similar accessory.
4.2 SERVICE INFORMATION
Should this equipment require repair or adjustment,
contact OMEGA ENGINEERING Customer Service
Department at (203) 359-1660.
It is important that servicing be performed only by
trained and qualified service personnel. If this
equipment is not properly serviced, serious personal
injury and/or damage to the equipment could result.
4.3 DISASSEMBLY PROCEDURE (SEE FIGURE 5.1)
a. Remove shield (8) by squeezing sides at top and
bottom, and pulling forward.
b. Hold metering tube (1), and rotate seal spindle (4)
to the right until the stop is reached. Remove
metering tube.
c. Using tweezers, remove outlet float stop (2).
Remove float from metering tube. Be careful not
to drop float. Remove inlet float stop (2). If float is
stuck in metering tube, a rod (wooden dowel or
pipe cleaner preferred) may be inserted through
the inlet end of the tube, and the float pushed
through. Care must be taken not to score or
scratch the tube.
d. Depress seal spindle retainer tab. Rotate seal
spindle (4) to the left until it is disengaged from
the meter. Be careful not to drop the check ball (6)
from inside the seal spindle. Remove check ball.
e. Remove control valve (9) from meter body.
4.4 ASSEMBLY PROCEDURE (SEE FIGURE 5.1)
After the meter and the meter components have been
cleaned or checked, the following assembly procedures
should be followed. A separate assembly procedure
for the control valve is given in paragraph 4.6
a. Insert control valve body into meter frame and
finger tighten to secure.
b. Insert check ball (6) into seal spindle (4). Check for
freedom of movement.
c. Depress seal spindle retainer tab. Insert seal
spindle (4) into end fitting, and turn to the right
until fully seated. Release seal spindle retainer.
d. Insert inlet float stop (2) through outlet end of
metering tube. Using a rod (wooden dowel or
pipe cleaner preferred) push inlet float stop
through metering tube until it is approximately
1
/16 to 1/32 inch from end of metering tube.
(See Figure 4.2).
e. Insert float into metering tube.
f. Insert outlet float stop (2). Push float stop into
metering tube, until it is seated approximately
1
/16 to 1/32 inch from end of tubes. (See Figure 4.2).
Figure 4.2 Float Stop Installation Diagram