Omega Products FD-400C Installation Manual

MADE
IN U.S.A.
1 YEAR
WARRANTY
Location
QUICK-START OPERATING INSTRUCTIONS
This manual contains detailed operating instructions for all aspects of the FD-400 flow instrument. The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible. This pertains to basic operation of the clamp-on transducer only. If specific instrument features or an alternate transducer style are to be used or if the installer is unfamiliar with this type of instrument, refer to the appropriate section in the manual for complete details.
1. TRANSDUCER LOCATION
A. Determine the appropriate mounting location for the transducers by
referring to Figure 1.1. Pipe must be filled with liquid to ensure proper operation.
Top View of Pipe
Figure 1.1
Transducer Locations
Pipe Preparation and Mounting
2. PIPE PREPARATION AND TRANSDUCER MOUNTING
A. The piping surface, where the transducers are to be mounted,
needs to be clean and dry. Remove loose scale, rust and paint to ensure satisfactory acoustical bonds.
B. Connect the mounting straps around the pipe. Leave the strap
loose enough to slip the transducers underneath.
C. Apply a liberal amount of silicone grease onto the transducer
faces.
D. Place each transducer under the mounting strap, 180° apart on the
pipe. Ensure that the transducer cables are facing the same direction on the downstream side of the flow. See Figure 1.2 on page 1.2.
E. Route the transducer cable back to the FD-400 monitor, avoiding
conduits that contain high voltage AC supply wires.
Rev. 11/09 -1.1- Series FD-400
QUICK-START OPERATING INSTRUCTIONS
Cables point in the direction of flow
Top View of Pipe
Figure 1.2
Transducer Direction
Connections
Startup
3. TRANSDUCER CONNECTIONS
A. Mount FD-400 monitor within the length of the transducer cables.
While transducer cable extension is not generally recommended, if additional transducer cable is required, utilize RG59 75 Ohm coaxial cable and 75 Ohm interconnections such as BNC.
B. Route the transducer cables through the center conduit hole in the
bottom of the FD-400 enclosure and connect to terminal block J4. The terminal blocks are a pluggable type and can be removed to simplify wiring access. A wiring diagram is located on the inner door for reference.
4. INITIAL SETTINGS AND POWER UP
A. Verify that the FD-400 power supply jumper settings are properly
configured for the power supply that will be utilized. A wiring and jumper selection diagram is located on the inner door for reference.
NOTE: Power supply selection is specified during order placement and appropriate jumpers are placed at the factory. If power is changed from AC to DC or vice versa, the fuse requirement will change. Fuse ratings are listed on the transmitter’s door.
B. Route power connections through the conduit hole farthest to the
left and in the FD-400 enclosure. Then connect power to the J2 terminal block. See Figure 3.2 on page 3.4.
C. Apply power.
D. On initial power-up, the FD-400 conducts a series of self-diagnostic
tests and buffering operations that take approximately 30 seconds.
E. Enter pipe internal diameter (Pipe ID), measuring units and output
configuration.
Rev. 11/09 -1.2- Series FD-400
TABLE OF CONTENTS
Quick-Start Operating Instructions
Introduction
General
Applications
Product Specifications
Transducer Installation
Transducer Mounting Locations
Pipe Preparation
Page
1.1
1.5
1.5
1.7
2.1
2.3
Clamp-On Transducer Mounting
Probe Transducer Mounting
Transmitter Installation
Mounting Location
Dimensional Drawing
Transducer Wiring Connections
Power Supply Wiring Connections
Wiring Diagram
Multiple Meter Synchronization
ISO Modules—General Information
4-20 mA Module
2.3
2.6
3.1
3.2
3.3
3.3
3.4
3.7
3.8
3.9
Rev. 11/09 -1.3- Series FD-400
TABLE OF CONTENTS
Control Relay Module
Rate Pulse Output Module
Instrument Programming
Keypad Operation
Totalizer Reset
Measurement Units Selection
Engineering Units Selection
4-20 mA Programming
Rate Pulse Programming
Dual Relay Configuration
Change Password
Advanced Set-up
Page
3.10
3.11
4.1
4.3
4.3
4.4
4.7
4.9
4.10
4.12
4.12
Startup and Troubleshooting
Startup Requirements
Troubleshooting
Appendix
FD-400 Software Map—General Operations
FD-400 Software Map—Output Configurations
Specific Gravity / Fluid Sound Speed Chart
Pipe Dimension Chart: ST, SS, PVC / Cast Iron / Ductile Iron
FPS to GPM Conversion Chart
5.1
5.2
Rev. 11/09 -1.4- Series FD-400
PART 1 - INTRODUCTION
General
Application Versatility
The FD-400 ultrasonic flow meter is designed to measure volumetric flow of solids-bearing or aerated liquid within closed conduit. Trans­ducers are available as non-contacting (FD-400C) or insertion probe (FD-400I) types. FD-400C non-contacting transducers are strapped to the outside of a pipe and are suitable for most installations where the pipe material supports the transmission of ultrasound. Some pipe materials, such as concrete pressure pipe and some plastic lined pipes do not allow ultrasound to penetrate to the liquid inside. For these applications, the FD-400I insertion probe will be needed.
The flow meter operates by transmitting an ultrasonic sound from its transmitting transducer through the pipe wall or from the probe tip into the moving liquid. The sound will be reflected by useful sonic reflectors1 suspended within the liquid and recorded by the receiving transducer. If the sonic reflectors are moving within the sound transmission path, sound waves will be reflected at a frequency shifted (Doppler frequency) from the transmitted frequency. The shift in frequency will be directly related to the speed of the moving particle or bubble. This shift in frequency is interpreted by the instrument and converted to various user defined measuring units.
1
What makes a good Doppler reflector? The four criteria are:
 The scattering material must have a sonic impedance (sound
speed difference) at least 10% different from the fluid.
 There must be some particles large enough to cause longitudinal
reflection – particles larger than 35 micron.
 For a given pipe size, the longitudinal reflection must have suffi-
cient energy to overcome the Rayleigh (energy wasting) scatter­ing caused by smaller particles.
 The reflecting material must travel at the same velocity as the
fluid for good accuracy.
The FD-400 flow meter can be successfully applied on a wide range of metering applications. The easy to program transmitter allows the standard product to be used on pipe sizes ranging from 1 - 120 inch (25 - 3050 mm) pipe I.D. With the small pipe transducer option, the pipe size range is 0.25 - 1 inch (6 - 25 mm). A variety of liquid applications can be accommodated: raw sewage, river water, plant effluent, mining slurries, sludge, etc. Because the clamp-on transducers are non-contacting and have no moving parts, the flow meter is not affected by system pressure, fouling or wear. Standard transducers are rated to 250 °F (121 °C). Optional high temperature transducers are rated to operate to 400 °F (204 °C).
Rev. 11/09 -1.5- Series FD-400
PART 1 - INTRODUCTION
User Safety
Data Storage
Product Identification
The FD-400 employs modular construction and provides electrical safety for the operator. The enclosure is constructed from rugged polycarbonate plastic with UV inhibitors. The enclosure does not contain any conductive materials that can become energized while the door is closed. The keypad is also manufactured from polycarbonate and is designed for outdoor use. The AC power transformer provides 4,000 Volts of isolation from the power supply mains. The display face contains voltages no greater than 24 Vdc. Output modules are optically isolated from external power supplies and provide a great degree of immunity to ground loops.
The FD-400 product retains all user configuration data and totalizer accumulations in non-volatile FLASH memory indefinitely.
The serial number and complete model number of each FD-400 is located on the inside of the monitor’s front cover. Should technical assistance be required, please provide the Omega Customer Service Department with this information.
Rev. 11/09 -1.6- Series FD-400
PART 1 - INTRODUCTION
Rev. 11/09 -1.7- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
Unpacking
Mounting Locations
After unpacking, it is recommended to save the shipping carton and packing materials in case the instrument is stored or re-shipped. Inspect the equipment and carton for damage. If there is evidence of shipping damage, notify the carrier immediately.
The transducers that are utilized by the FD-400 contain piezoelectric crystals for transmitting and receiving ultrasonic sound energy through the pipe wall in the case of the Series FD-400C transducer and from the probe tip of the Series FD-400I. Placement of the ultrasonic transducer is the most critical step in achieving an accu­rate and reliable flow reading. All flow meters of this type rely on a full-pipe of fluid that is flowing symmetrically (evenly) in the pipe. Flow in partially filled pipes and immediately downstream of elbows, valves and pumps is unstable and will lead to unstable readings and non-linearity.
Figure 2.1 illustrates five possible pipe configurations and recom­mends installation only in locations where it can be guaranteed that the pipe will be filled at all times when flow measurements are required. The two locations illustrated in the top two drawings may allow the meter to operate, but it is unlikely that stable and accurate
Figure 2.1
Pipe Configurations and Installation Recommendations
Rev. 11/09 -2.1- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
flow readings will be realized over a very large range of flow. Since products like the FD-400 have software algorithms that assume a full-pipe of liquid, partially-filled pipes can lead to very large flow measurement errors and should be avoided.
Select a transducer mounting location with adequate straight runs of pipe, both upstream and downstream, to achieve stable readings1. Examples of minimum upstream and downstream requirements are included in Figure 2.2.
1
2
3
4
5
Example
1 24 5
2 14 5
3 10 5
4 10 5
5 10 5
6 24 5
* Upstream
Pipe Diameters
** Downstream
Pipe Diameters
6
Figure 2.2
Upstream/Downstream Pipe Requirements
1
The FD-400 system will provide repeatable measurements on
piping systems that do not meet these requirements, but the accuracy
Rev. 11/09 -2.2- Series FD-400
may be influenced to various degrees.
PART 2 - TRANSDUCER INSTALLATION
Pipe Preparation
Couplant
Before the transducer heads are mounted to the pipe surface, an area slightly larger than the flat surface of the transducer face must be prepared. If pipe insulation is present, it must be peeled back to expose the pipe surface. Typical preparation involves wire brush removal of loose paint, rust, scale or dirt. Paint, if bonded well to the pipe surface, does not need to be removed. The bumps present on ductile iron pipe do not need to be removed. Thoroughly dry the mounting surfaces so that the couplant grease will properly bond to the surface.
NOTE: Small pits in the piping surface typically do not significantly impact ultrasonic transmission or signal reception.
To assure an acoustically conductive path between the transducer face and the prepared piping surface, a coupling compound is employed. Clamp-on ultrasonic meters will not operate without coupling compound mounted between the pipe wall and the trans­ducer face. Enclosed with the FD-400 system is a tube of coupling compound that is adequate for general purpose applications. Omega prefers silicone-based valve grease or RTV (Room Tem­perature Vulcanizing) products or grease for Doppler installations as they operate over a very wide temperature range. In some installa­tions, such as automotive, silicone is not permitted. Alternate petro­leum-based products can be utilized, but verify that the grease is rated not to flow at the maximum surface temperature anticipated on the pipe.
In general, utilize the following couplants with these transducers:
FD-400C Dow 732 or Dow 111 (or equivalent)
FD-400C-HT Dow 112 or Pyrogel Grade 100
FD-400I Not applicable
FD-400C Clamp-On Transducer Mounting
Rev. 11/09 -2.3- Series FD-400
Clamp-on transducers should be mounted on the pipe 180° apart and facing each other on the pipe, with the cables on the down­stream side of the transducers. If the pipe is horizontal, the preferred mounting orientation is 3 and 9 o’clock, with 12 o’clock being the top of the pipe. See Figure 2.3 on page 2.4. Orientation on vertical pipes does not matter. FD-400I insertion probe trans­ducer installation starts on page 2.6.
PART 2 - TRANSDUCER INSTALLATION
Top View of Pipe
Figure 2.3
Transducer Placement
PROCEDURE:
1. Large pipe installations utilize stainless steel straps to secure the transducers to the outside of the pipe. The FD-400 system is shipped with four 36 inch (900 mm) straps, which are suitable for pipes up to 39 inches (1000 mm) diameter. Select the proper number of transducer straps to allow a complete strap to go around the circumference of the pipe. If a pipe is larger than 39 inches (1000 mm), it is recommended that a single strap/buckle arrangement be utilized to reduce the number of strap connec­tions. See Figure 2.4. The straps can be connected together to make a continuous length. Small pipe installations do not utilize straps, but use an integral clamping mechanism built into the transducer.
2. Wrap the strap around the pipe in the area where the
Pipe Sizes Straps Required
1" to 9" 25 to 225 mm 1
10" to 19" 250 to 480 mm 2
20" to 29" 500 to 740 mm 3
30" to 39" 760 to 1000 mm 4
Figure 2.4
Straps Required vs. Pipe Size
Rev. 11/09 -2.4- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
transducers are to be mounted. Leave the strap loose enough to allow the transducers to be placed underneath. If multiple straps are being used, it can be beneficial to wrap electrical tape around all but one screws in place.
3. Spread an even layer of coupling compound, approximately inch (3mm) thick, to the prepared transducer mounting areas of the pipe.
4. Spread an even layer of coupling compound, approximately inch (3mm) thick, to the flat face of the two transducers.
5. Place each transducer under the strap with the flat face – amber plastic window – positioned towards the pipe. The notch on the back of the transducer will provide a mounting surface for the strap. The transducer cables must be facing in the same direction and downstream of the transducers for proper operation.
strap connection to secure the strap worm
NOTE: Large pipes may require two people for this procedure.
6. Tighten the strap strong enough to hold the transducers in place, but not so tight that all of the couplant squeezes out of the gap between the transducer face and pipe. Ensure that the transducers are squarely aligned on the pipe and 180° apart. If RTV is utilized, avoid moving the transducers during the curing time – typically 24 hours – as bubbles may form between the transducer and pipe that can reduce ultrasonic signal transmis­sion to unsatisfactory levels.
7. Route the transducer cables back to the area where the transmitter will be mounted, avoiding high voltage cable trays and conduits. While transducer cable extension is not generally recommended, if additional transducer cable is required, utilize RG59 75 Ohm coaxial cable and 75 Ohm interconnections such as BNC terminations. Failure to use proper cables can lead to improper operation of the FD-400 flow meter. Excess cable may be coiled to take up extra length or cutoff.
8. If the transducers are to be permanently mounted using Dow 732, the RTV must be completely cured before proceeding to Instrument Start-up. Ensure that no relative motion between the transducer and pipe occurs during the 24 hour curing process. If Dow 111 grease was used for temporary operation of the FD­400 system, proceed with the Instrument Start-up procedures.
Rev. 11/09 -2.5- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
A
FD-400I Probe Transducer Mounting
The FD-400I insertion transducer that is utilized by the FD-400 contains piezoelectric crystals for transmitting and receiving ultrasonic sound energy. The black Ultem® plastic tip of the FD-400I contains these crystals, which are designed to be inserted just into the path of the flowing liquid.
Select a transducer mounting location that will be completely filled with liquid when flow measurements are to be made – See Figure
2.1 on page 2.1 – and with adequate straight runs (without
disturbances) of pipe, both upstream and downstream, to achieve stable and accurate readings. Examples of minimum upstream and downstream requirements are included in Figure 2.2 on page 2.2. Note that if adequate straight piping cannot be provided, the FD­400 system will operate repeatably, but will probably not achieve ideal accuracy.
When installing the FD-400I transducer in a horizontal pipe, the preferred orientation is at least 20 degrees from the top or bottom of the pipe – See Figure 2.5. Ensure that the mounting location allows for adequate clearance to install and retract the probe fully from the pipe.
TOP V IEW
OF PIPE
20°
I
N
S
T
A
L
L
Figure 2.5
Acceptable
Installation Locations
20°
Install Doppler Probe between 1 o’clock
INSTALL MAGPROBE
BETWEEN 1 O’CLOC K
and 5 o’clock on the pipe
ND 5 OCLOCK ON THE PIPE
A
T
I
O
N
R
A
N
G
E
The instructions cover hot tapped installations (installations where it is required to install or remove the transducer probe without shutting down the process pressure). If the product is being installed without an isolation valve, ignore the steps that pertain to its installation. Figure 2.6 on page 2.7 illustrates an exploded view of an isolation valve assembly and names the various components.
Rev. 11/09 -2.6- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
Figure 2.6
Hot Tap Installation
If FD-400I-BV or FD-400-SSV accessory kits were ordered with the FD-400I probe, a hot tapped installation can be completed. The kits include an isolation valve assembly and are designed for installation in pipes under pressure, up to 700 psi (48 bar) at 70 F (21º C).
All items required for installation are provided with the kit, except for the 1-½" NPT weld coupling or service saddle and the drilling and welding equipment. These instructions call for the use of a drilling machine designed for operations under pressure (for example, Muller Co., Decatur, Illinois).
Procedures are as follows:
1. Verify that the pipe’s line pressure is within the rated limits of
the pressure drilling machine to be used.
2. Grind off paint or other coatings from the pipe in the area where
the FD-400I Probe Assembly is to be installed.
3. Tack weld a 1-½" NPT weld coupling to the pipe or install a
service saddle according to the supplier’s instructions. The coupling or saddle must be aligned perpendicular to the pipe axis and square to its plane.
Rev. 11/09 -2.7- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
4. Complete welding. A water tight, 0.25" minimum weld bead is
recommended.
5. Install the close nipple (supplied with assembly) into the weld
coupling. Use appropriate pipe sealants.
6. Install the isolating ball valve on the close nipple. Verify that the
valve is in fully open position.
7. Install drill bit and adapter into the pressure drilling machine.
Then attach the machine to the isolation valve.
8. Drill through the pipe wall in accordance with the instructions
supplied with the drilling machine.
9. Withdraw the drill bit through the isolating valve. Close the
valve and remove the drilling machine. Check for leakage at valve and connections.
10. Place pipe sealant on the 1-½" NPT threads of the insertion
fitting assembly. Screw the assembly into the isolation valve and tighten with a 2-½" pump wrench.
PROBE INSERTION
Before inserting the FD-400I probe into the piping system, it is necessary to calculate the probe insertion depth that will place the measuring electrodes at the proper position in the pipe. In order to complete this calculation, some knowledge of the piping system must be known. Refer to the paragraphs that follow and Figure 2.7 on page 2.10 for information regarding this process. The variables required are:
 The overall probe length  Pipe internal diameter (I.D.)  Pipe wall thickness  The length of the valve stack  Amount of straight pipe diameters in the system
Using this information and referring to Figure 2.7, proper insertion depth can be determined.
Rev. 11/09 -2.8- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
Measurement A — The typical depth that the FD-400I probe tip is inserted into the piping system is (12.5%) of the pipe internal diameter.
Measurement B — Pipe wall thickness. This information can be obtained from standard pipe wall charts (See the Appendix of this manual) or ideally can be measured using an ultrasonic wall thick­ness gauge.
Measurement C — Measure the distance that is going to be taken up by the pipe tap, nipple, full-flow ball valve and the insertion fitting. FD-400I probes utilize 1-½" NPT hardware and the insertion fitting is approximately 2.5 inches in height.
Measurement E — This is the overall length of the probe measured from the black measurement tip to the top flange on the probe.
Measurement D — This is the length of FD-400I probe that will be protruding from the insertion fitting after it is inserted to the proper depth in the fluid stream.
1. Lubricate the O-rings located within the FD-400I probe seal fitting so that the seals are not damaged during probe insertion.
2. Run the lower jam nuts down to a point that approximates the final insertion position or at least far enough to allow insertion into the insertion fitting. Using the threaded rods as a guide, position the probe in the insertion fitting. Continue to insert the probe as far into the isolation assembly as possible. The probe tip will come in contact with the closed “ball” in the isolation valve.
CAUTION: Do Not Force the Probe Tip Against the “Ball”, as damage to the probe tip may result.
3. Replace the upper jam nuts (2 on each rod) and the cotter pins. The nuts should be run down to the top side of the retaining collar and the cotter pins replaced. Orient the probe in the direction of flow as indicated by the FLOW direction arrow located on the top of the probe flange. See Figure 2.8 on page
2.12. Lock the probe in position with the enclosed allen wrench.
CAUTION: The nuts on both ends of the retaining rods must always be in place as a safety measure to prevent possible probe blow out. Inserting cotter pins is a further safety measure.
Rev. 11/09 -2.9- Series FD-400
PART 2 - TRANSDUCER INSTALLATION
TO CALCULATE INSERTION DEPTH
Measure and record the following linear distances:
E = PROBE LENGTH = _______
C = SEAL FITTING TO PIPE WALL
= _______
B = PIPE WALL THICKNESS
= _______
A = 0.125 × PIPE ID = _______
D = INSERTION DEPTH = _______
D = E - C - B - A
Figure 2.7
Installation Measurements
Rev. 11/09 -2.10- Series FD-400
Loading...
+ 43 hidden pages