Potentiometer, Thermocouple, RTD and
Strain Gage Input Modules
⻬ Integrator Modules Convert Voltage or
Current to Frequency
⻬ Loop Powered Galvanic Isolator
Provides 2 kVeff Isolation Between Input
and Output
⻬ Compatible with Standard 35 mm DIN Rail
The CCT series DIN rail signal conditioners are
designed to accept a broad range of input signals, such
as ac and dc voltage and current, frequency,
temperature (thermocouple and RTD), and process
transducers, and provide standard process outputs of
either 0/4 to 20 mA, or 0 to 10 Vdc. The CCT series
features a modern housing design, that is easily
mounted on standard DIN rails. Connections are safely
and securely made, with input and output connections
on the opposite sides of the module.
Shown larger
than actual size.
Internal Design
The CCT series is designed using an internal plug-in
three module system that provides flexibility in selecting
and changing the power supply, input signal and output
signal. Available power supplies include 110 Vac,
220 Vac, and 24 Vdc.
Isolation
The three internal modules in each signal conditioner
(signal input, signal output and power supply) are
isolated up to 2 kVeff.
Outputs
Each CCT series signal conditioner is available with
current and voltage output (only one may be used at a
time). Available output types include 4 to 20 mA or 0 to
20 mA (jumper-selectable) and 0 to 10 Vdc.
Standard outputs are linear and proportional to the
signal input. Thermocouple input modules feature
special circuitry to linearize the output to the actual
temperature, and not to the non-linear signal produced
by thermocouple sensors.
H-27
Page 2
A/IN
A/OUT
Integrators
The CCT integrator signal conditioners accept either
voltage or current signals, and provide a frequency
pulse output. This pulse output can be used as input
signals for PLCs or other industrial controls.
Additional Features
Additional models in the CCT series include the FAR
power supplies, that can be used with the CCT-80
strain gage transmitter, to provide wheatstone bridge
excitation. The loop-powered galvanic isolator model
CCT-100 can be used in any application where input to
output isolation is required. The CCT-100 provides up
to 2 kVeff isolation between the input and output
terminals.
Specifications
Power:
(±10% tolerance on all power supplies)
Output: 4 to 20 mA and 0 to 10 Vdc standard;
0 to 20 mA via jumper select
110 Vac (standard); 220 Vac or 24 Vdc (optional)
Accuracy: ≤0.2% or ≤0.3,%, depending on the model
Response Time: ≤250 ms
Isolation: 2 kVeff
Ripple: ≤0.5%
Bandpass: 1.5 Hz (-3 dB)
Operating Ambient: -10 to 60°C (14 to 140°F)
Storage Ambient: -30 to 80°C (-22 to 176°F)
Temperature Coefficient: ≤0.015%/°C
Power Consumption: 1.5 VA max
Enclosure: Polycarbonate, RAL 7032; UL 94 V-1,
IP40 protection
Terminal Housing: Polycarbonate, UL 94-2,
IP20 protection
Max Wire Size: 4 mm
Dimensions: 75 H x 45 W x 110 mm D
(2.95" x 1.77" x 4.33")
Weight: 270 g (0.6 lb)
Mounting: DIN rail 46277 and EN 50022 (35 x 7.5 mm)
H-28
2
(14 AWG)
H
Page 3
Economical DIN Rail
SIGNAL
INPUT 1 Vac
INPUT SIGNAL
1 3 4 5 6
+
INPUT SIGNAL
+
1 3 4 5 6
+
+
SIGNAL
INPUT 1 Vac
Signal Conditioners
CCT Series
ac/dc Voltage and Current Input Models
⻬ ac/dc Voltage Input
Ranges from 100 mV to
650 V
⻬ ac/dc Current Input
Models with 0 to 50 mA
or 0 to 5 A
The CCT series of ac and dc input
signal conditioners accept analog
signals and provide conditioned,
isolated analog outputs of 0 to 10 V
or 0/4 to 20 mA. The CCT-01
accepts dc voltages, the CCT-08
accepts ac voltages, while the
CCT-04 and CCT-32 accept ac and
dc current signals, respectively.
The CCT-32 also provides 24 Vdc
excitation for powering transmitters.
All models are powered by 110 Vac
(220 Vac or 24 Vdc powered
models also available), are
mountable on standard 35 mm DIN
rail, and are isolated to 2 kVeff.
CCT-01 Input Connections
CCT-08 Input Connections
CCT-04 Input Connections
To Order (Specify Model Number)
Model No.
CCT-01-0/100MV$1800 to 100 mV dc0 to 10 V or 0/4 to 20 mA
CCT-01-0/1V1800 to 1 V dc0 to 10 V or 0/4 to 20 mA
CCT-01-0/10V1800 to 10 V dc0 to 10 V or 0/4 to 20 mA
CCT-01-0/100V1800 to 100 V dc0 to 10 V or 0/4 to 20 mA
CCT-01-0/650V1800 to 650 V dc0 to 10 V or 0/4 to 20 mA
CCT-08-0/100MV1800 to 100 mV ac0 to 10 V or 0/4 to 20 mA
CCT-08-0/1V1800 to 1 V ac*0 to 10 V or 0/4 to 20 mA
CCT-08-0/10V1800 to 10 V ac*0 to 10 V or 0/4 to 20 mA
CCT-08-0/100V1800 to 100 V ac*0 to 10 V or 0/4 to 20 mA
CCT-08-0/650V1800 to 650 V ac*0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models
add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50
to price for 24 Vdc. *The CCT-08 signal frequency range is 20 Hz to 6KHz.
Ordering Example:
CCT-04 ac Current Input
Range0 to 50 mA ac0 to 5 A ac
Impedance20 Ω0.02 Ω
Overload100 mA ac7.5 A ac
†
PriceInput RangeOutput
CCT-01-0/100 mV dc input signal conditioner with 0 to 100 mVdc range,
$180.
To Order (Specify Model Number)
Model No.
CCT-04-0/50MA$1800 to 50 mA ac0 to 10 V or 0/4 to 20 mA
CCT-04-0/5A1800 to 5 A ac0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add
“-220VAC” or “-24VDC” to the model number. No charge for 220 Vac, add $50 to price for 24 Vdc.
Ordering Example:
†
PriceInput RangeOutput
CCT-04-0/5A ac current input signal conditioner with 0 to 5 A ac range,
H-29
$180
.
Page 4
dc Current Input Models
A/IN
A/OUT
To Order (Specify Model Number)
Model Number†PriceInput RangeOutput
CCT-32-0/50MA$1800 to 50 mA dc0 to 10 V or 0/4 to 20 mA
CCT-32-0/5MA1800 to 5 mA dc0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add
“-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to
price for 24 Vdc.
Ordering Example:
CCT32-0/5MA dc current input signal conditioner with 0 to 5 mA range,
Range0 to 50 mA dc0 to 5 A dc
Impedance20 Ω20 Ω
Shown smaller
than actual size
Overload100 mA dc100 mA dc
Voltage Excitation for Current Loop: 24 V dc @ 25 mA, supplied by converter
Thermocouple Input Models
⻬ Available with J, K, T, E, R
and S Thermocouple
Types
⻬ Jumper-Selectable
Up or Downscale
Break Protection
⻬ 0.3% Accuracy
⻬ Linearized
The CCT series of thermocouple
input signal conditioners accept J,
K, T, E, R or S type thermocouples,
and provide conditioned, isolated
analog outputs of 0 to 10 V or 0/4 to
20 mA. All models are powered by
110 Vac (220 Vac or 24 Vdc
Range Table
Range CodeRangeJ KTESR
0/200C0 to 200°CX
0/300C0 to 300°CXX
0/400C0 to 400°CXXX
0/500C0 to 500°CXX
0/600C0 to 600°CXX
0/700C0 to 700°CXX
0/800C0 to 800°CXX
0/900C0 to 900°CX
0/1000C0 to 1000°CX
0/1200C0 to 1200°CX
600/1600C600 to 1600°CX
850/1700C850 to 1700°CX
powered models also
available), are
mountable on
standard 35 mm DIN
rail, and are isolated
to 2 kVeff.
Specifications
Cold Junction Compensation
Error: 0.05°C/°C for J, K, T, E and R
calibrations; 0.1°C/°C for type S; at
25°C ambient typical
*Specify range code from range table. CCT-25 is
only available with 0 to 800°C range, CCT-26 is only
available with 600 to 1600°C range
† 110 Vac powered units supplied standard.
To order 220 Vac or 24 Vdc powered unit models
add “-220VAC” or “-24VDC” to the model number.
No additional charge for 220 Vac, add $50 to price
for 24 Vdc.
Ordering Example:
conditioner for type K thermocouple input, with 0 to
1200°C range,
The CCT-20 signal conditioners
accept 100Ω Pt RTD signals, and
provide conditioned, isolated
To Order (Specify Model Number)
Model Number†PriceInput RangeOutput
CCT-20-0/100C$1900 to 100°C0 to 10 V or 0/4 to 20 mA
CCT-20-0/200C1900 to 200°C0 to 10 V or 0/4 to 20 mA
CCT-20-0/300C1900 to 300°C0 to 10 V or 0/4 to 20 mA
CCT-20-0/400C1900 to 400°C0 to 10 V or 0/4 to 20 mA
Shown smaller
than actual size
CCT-20-0/500C1900 to 500°C0 to 10 V or 0/4 to 20 mA
CCT-20-0/600C1900 to 600°C0 to 10 V or 0/4 to 20 mA
Ordering Example:
CCT-20-0/200C RTD input signal conditioner with 0 to 200°C range,
CCT Series
outputs of 0 to 10 V or
Units are 110 Vac powered
(220 Vac or 24 Vdc power also
available). Modules are mountable
on standard 35 mm DIN rail, and
are isolated to 2 kVeff.
CCT-20 Input Connections
0/4 to 20 mA.
$190.
CCT-90
Potentiometer
Models
⻬ 100 Ω Min/1 MΩ Max
Input
⻬ Excitation Reference
Voltage Between
1 and 2V
CCT-95 Resistance
Input Models
⻬ 0.2% Accuracy
⻬ Upscale Break Protection
(>20 mA)
⻬ 10%FS Min Input Span
See page H-35
for FAR series
DIN Rail mount
power supply
modules.
CCT-90 Input Connections
The CCT-90 potentiometer input
modules accept 3-wire
potentiometers (such as position
sensors) and CCT-95 models
accept resistance signals, providing
isolated 0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add
“-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to
price for 24 Vdc.
output. Each model is 110 Vac
powered (220 Vac or 24 Vdc also
available). Models are mountable on
standard 35 mm DIN rail, and are
isolated to 2 kVeff.
CCT-95 Input Connections
To Order (Specify Model Number)
Model Number†PriceInput RangeOutput
CCT-90$190Potentiometer0 to 10 V or 0/4 to 20 mA
CCT-95-0/2001900 to 200 Ω0 to 10 V or 0/4 to 20 mA
CCT-95-0/2K1900 to 2K Ω0 to 10 V or 0/4 to 20 mA
CCT-95-0/20K1900 to 20 kΩ0 to 10 V or 0/4 to 20 mA
CCT-95-0/200K1900 to 200 kΩ0 to 10 V or 0/4 to 20 mA
Ordering Example:
CCT-90 potentiometer input signal conditioner,
$190
.
H-31
Page 6
CCT-05 Frequency Input Models
DI/O
A/OUT
⻬ NPN, PNP, NAMUR, Open
Collector, Contact, or TTL
Inputs or AC Voltage
(100 mV to 400 Vac)
⻬ Signal Input Range from
40 Hz to 40 kHz
⻬ Excitation for NPN, PNP
and NAMUR Inputs
The CCT-05 signal conditioners
accepts inputs from a variety of
frequency transducers, including
NPN, PNP, NAMUR, open collector,
contact or TTL pulse or AC
voltage (100 mV to 400 Vac).
Modules are supplied scalable
for a minimum and maximum
frequency range. The actual
range is set by the user via
multiturn trimmers, a frequency
generator is also required. All
units are 110 Vac powered
(220 Vac or 24 Vdc power also
available), and may be
mounted on standard 35 mm
DIN rail.
Each unit is isolated to 2 kVeff.
To Order (Specify Model Number)
Model No.
CCT-05-40/70$2200 to 40 Hz0 to 70 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-70/1252200 to 70 Hz0 to 125 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-125/2252200 to 125 Hz0 to 225 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-225/4002200 to 225 Hz0 to 400 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-400/7002200 to 400 Hz0 to 700 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-700/12502200 to 700 Hz0 to 1250 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-1250/22502200 to 1250 Hz0 to 2250 Hz0 to 10 V or 0/4 to 20 mA
CCT-05-2250/4K2200 to 2250 Hz0 to 4 kHz0 to 10 V or 0/4 to 20 mA
CCT-05-4K/7K2200 to 4 kHz0 to 7 kHz0 to 10 V or 0/4 to 20 mA
CCT-05-7K/12.5K2200 to 7 kHz0 to 12.5 kHz0 to 10 V or 0/4 to 20 mA
CCT-05-12.5K/22.5K2200 to 12.5 kHz0 to 22.5 kHz0 to 10 V or 0/4 to 20 mA
CCT-05-22.5K/40K2200 to 22.5 kHz0 to 40 kHz0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add
“-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price
for 24 Vdc. *The output signal is non-linear for input frequencies below 10 Hz.
†
PriceRangeRangeOutput
Min*Max*
Shown smaller
than actual size.
Ordering Example:
frequency input signal conditioner with
0 to 70 Hz minimum range and 0 to
125 Hz maximum range,
CCT-05-70/125
$220.
H
H-32
Page 7
Economical DIN Rail
A/IN
A/OUT
Signal Conditioners
CCT Series
Strain Gage/Load Cell Input Models
⻬ For Strain Gage Sensors
with 20 mV Output and
10 V Excitation
⻬ 4 and 6-Wire Bridge
Sensors
⻬ 350 Ω Sensor Impedance
⻬ Companion FAR-1 Power
Supply Module Provides
Stabilized 10 Vdc
Excitation for 4 Modules
⻬ FAR Series Power
Supplies Provide Bridge
Excitation
FAR-1 10 V, 250 mA power supply with
Shown smaller
than actual size.
excitation sense capability, $133.
The CCT-80 strain gauge/load cell signal conditioners
accept input from 350Ω bridge circuits and provide
isolated 0 to 10 V or 0/4 to 20 mA output. The FAR series
power supplies can be used to provide signal isolation for
bridge circuits and other transducers. The FAR-1 is
specifically designed for use with strain gage circuits. All
units are 110 Vac powered (220 Vac power also
available), and are mounted on standard 35 mm DIN rails.
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc
powered models add “-220VAC” or “-24VDC” to the model number.
No additional charge for 220 Vac, add $50 to price for 24 Vdc.
To Order (Specify Model Number)
Model No.†PriceDescription
CCT-80$190Strain gage signal conditioner with
FAR-113310 V, 250 mA power supply
FAR-2-51335 V, 225 mA power supply
FAR-2-91339 V, 225 mA power supply
FAR-2-1213312 V, 200 mA power supply
FAR-2-1513315 V, 100 mA power supply
FAR-2-1813318 V, 100 mA power supply
FAR-2-2413324 V, 150 mA power supply
* To order FAR-1 with 230 Vac power, add suffix “-230” to model
number at no additional charge.
Ordering Example:
FAR-1 10 V, 250 mA power supply, $190 + 133 =
CCT-80 strain gage signal conditioner with
0-10 V or 0/4 to 20 mA output
with excitation sense capability,
110 Vac power*
$323
.
CCT-80 Input
Connections
H-33
Page 8
CCT-55 Signal
A/IN
A/OUT
Integrators
⻬ Convert Analog Voltage/Current to
Frequency Output
⻬ Source or Sink Output
⻬ Output Ranges From 1 pulse/hour to
10,000 pulses/sec Full Scale
The CCT-55 signal integrators provide conditioned, isolated
frequency outputs proportional to the analog input signal.
The CCT-55-V accepts voltages from 0-100 mV to 0 to 650 V,
while the CCT-55-I accepts from 0 to 5 mA to 0 to 50 mA
input. Output ranges are field setable through jumper
selection and multiturn trimmers. A calibrator and frequency
meter is required for adjustment.
Specifications
dc Voltage Input Ranges: 0 to 0.1 Vdc, 0 to 1 Vdc,
0 to 10 Vdc, 0 to 100 Vdc, 0 to 650 Vdc; jumper select
Current Input Ranges: 0 to 5 mA, 0 to 50 mA; jumper select
Output: 15 Vdc @ 5 mA source or 100 mA sink with 24 Vdc
external supply
Output Ranges: 1 pulse/hr to 10,000 pulses/sec full scale;
jumper select and poteniometer adjustment
Pulse Ratio: 50% or fixed 100 ms
CCT 100
Galvanic Isolator
⻬ Provides 2 kV Input to
Output Isolation
⻬ 0 to 50 mA Input and
Output Ranges
⻬ Loop Powered
Specifications
INPUT
Input/Output Ratio: 1:1; signal
output = signal input
Input Current: 0 to 50 mA dc
Input Voltage: 18 Vdc max
Voltage Drop: 3 Vdc max
Max Load: 50 mA dc
† 110 Vac powered units supplied standard. To order
220 Vac or 24 Vdc powered models add “-220VAC” or
“-24VDC” to the model number. No additional charge for
220 Vac, add $50 to price for 24 Vdc.
Ordering Example:
Load: 0 to 750 Ω
Response Time: 50 ms
Accuracy: 0.1% at 25°C
Temperature Coefficient: 0.01%
Calibrators, Connectors, General Test and Measurement
Instruments, Glass Bulb Thermometers, Handheld Instruments
for Temperature Measurement, Ice Point References,
Indicating Labels, Crayons, Cements and Lacquers, Infrared
Temperature Measurement Instruments, Recorders Relative
Humidity Measurement Instruments, RTD Probes, Elements
and Assemblies, Temperature & Process Meters, Timers and
Counters, Temperature and Process Controllers and Power
Switching Devices, Thermistor Elements, Probes and
Assemblies,Thermocouples Thermowells and Head and Well
Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level
Measurement, Magnetic Flowmeters, Mass Flowmeters,
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel
Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area
Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen
Instrumentation, Environmental Instrumentation, pH
Electrodes and Instruments, Water and Soil Analysis
Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems,
Communication Products and Converters, Data
Acquisition and Analysis Software, Data Loggers
Plug-in Cards, Signal Conditioners, USB, RS232, RS485
and Parallel Port Data Acquisition Systems, Wireless
Transmitters and Receivers
Band Heaters, Cartridge Heaters, Circulation Heaters,
Comfort Heaters, Controllers, Meters and Switching
Devices, Flexible Heaters, General Test and Measurement
Instruments, Heater Hook-up Wire, Heating Cable
Systems, Immersion Heaters, Process Air and Duct,
Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters