Economical DIN Rail Signal Conditioners
CCT Series
CCT Series
$
180
Basic Unit
Voltage, Current, Frequency, Resistance,
Potentiometer, Thermocouple, RTD and Strain Gage Input Modules
Integrator Modules Convert Voltage or
Loop Powered Galvanic Isolator
Provides 2 kVeff Isolation Between Input and Output
Compatible with Standard 35 mm DIN Rail
The CCT series DIN rail signal conditioners are designed to accept a broad range of input signals, such as ac and dc voltage and current, frequency, temperature (thermocouple and RTD), and process transducers, and provide standard process outputs of either 0/4 to 20 mA, or 0 to 10 Vdc. The CCT series features a modern housing design, that is easily mounted on standard DIN rails. Connections are safely and securely made, with input and output connections on the opposite sides of the module.
Shown larger than actual size.
Internal Design
The CCT series is designed using an internal plug-in three module system that provides flexibility in selecting and changing the power supply, input signal and output signal. Available power supplies include 110 Vac, 220 Vac, and 24 Vdc.
Isolation
The three internal modules in each signal conditioner (signal input, signal output and power supply) are isolated up to 2 kVeff.
Outputs
Each CCT series signal conditioner is available with current and voltage output (only one may be used at a time). Available output types include 4 to 20 mA or 0 to 20 mA (jumper-selectable) and 0 to 10 Vdc.
Standard outputs are linear and proportional to the signal input. Thermocouple input modules feature special circuitry to linearize the output to the actual temperature, and not to the non-linear signal produced by thermocouple sensors.
H-27
Page 2
A/IN
A/OUT
Integrators
The CCT integrator signal conditioners accept either voltage or current signals, and provide a frequency pulse output. This pulse output can be used as input signals for PLCs or other industrial controls.
Additional Features
Additional models in the CCT series include the FAR power supplies, that can be used with the CCT-80 strain gage transmitter, to provide wheatstone bridge excitation. The loop-powered galvanic isolator model CCT-100 can be used in any application where input to output isolation is required. The CCT-100 provides up to 2 kVeff isolation between the input and output terminals.
Specifications
Power:
(±10% tolerance on all power supplies) Output: 4 to 20 mA and 0 to 10 Vdc standard; 0 to 20 mA via jumper select
110 Vac (standard); 220 Vac or 24 Vdc (optional)
Accuracy: 0.2% or 0.3,%, depending on the model Response Time: 250 ms Isolation: 2 kVeff Ripple: 0.5% Bandpass: 1.5 Hz (-3 dB) Operating Ambient: -10 to 60°C (14 to 140°F) Storage Ambient: -30 to 80°C (-22 to 176°F) Temperature Coefficient: 0.015%/°C Power Consumption: 1.5 VA max Enclosure: Polycarbonate, RAL 7032; UL 94 V-1,
IP40 protection Terminal Housing: Polycarbonate, UL 94-2,
IP20 protection
Max Wire Size: 4 mm Dimensions: 75 H x 45 W x 110 mm D
(2.95" x 1.77" x 4.33")
Weight: 270 g (0.6 lb) Mounting: DIN rail 46277 and EN 50022 (35 x 7.5 mm)
H-28
2
(14 AWG)
H
Page 3
Economical DIN Rail
SIGNAL INPUT 1 Vac
INPUT SIGNAL
1 3 4 5 6 +
INPUT SIGNAL
+
1 3 4 5 6 +
+
SIGNAL INPUT 1 Vac
Signal Conditioners
CCT Series
ac/dc Voltage and Current Input Models
ac/dc Voltage Input
Ranges from 100 mV to 650 V
ac/dc Current Input
Models with 0 to 50 mA or 0 to 5 A
The CCT series of ac and dc input signal conditioners accept analog signals and provide conditioned, isolated analog outputs of 0 to 10 V or 0/4 to 20 mA. The CCT-01 accepts dc voltages, the CCT-08 accepts ac voltages, while the CCT-04 and CCT-32 accept ac and
CCT-01 dc Voltage Input CCT-08 dc Voltage Input
Range 0 to 0 to 0 to 0 to 0 to
100 mV 1 V 10 V 100 V 650 V
Impedance 100 kΩ 100 kΩ 1 MΩ Overvoltage 25 V 75 V 1000 Vdc/750 Vac
Overvoltage Protection
for Voltage Inputs
High Impedance Voltage
Inputs
Low Impedance Current
Inputs
dc current signals, respectively. The CCT-32 also provides 24 Vdc excitation for powering transmitters. All models are powered by 110 Vac (220 Vac or 24 Vdc powered models also available), are mountable on standard 35 mm DIN rail, and are isolated to 2 kVeff.
CCT-01 Input Connections
CCT-08 Input Connections
CCT-04 Input Connections
To Order (Specify Model Number)
Model No.
CCT-01-0/100MV $180 0 to 100 mV dc 0 to 10 V or 0/4 to 20 mA CCT-01-0/1V 180 0 to 1 V dc 0 to 10 V or 0/4 to 20 mA CCT-01-0/10V 180 0 to 10 V dc 0 to 10 V or 0/4 to 20 mA CCT-01-0/100V 180 0 to 100 V dc 0 to 10 V or 0/4 to 20 mA CCT-01-0/650V 180 0 to 650 V dc 0 to 10 V or 0/4 to 20 mA CCT-08-0/100MV 180 0 to 100 mV ac 0 to 10 V or 0/4 to 20 mA CCT-08-0/1V 180 0 to 1 V ac* 0 to 10 V or 0/4 to 20 mA CCT-08-0/10V 180 0 to 10 V ac* 0 to 10 V or 0/4 to 20 mA CCT-08-0/100V 180 0 to 100 V ac* 0 to 10 V or 0/4 to 20 mA CCT-08-0/650V 180 0 to 650 V ac* 0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc. *The CCT-08 signal frequency range is 20 Hz to 6KHz.
Ordering Example:
CCT-04 ac Current Input
Range 0 to 50 mA ac 0 to 5 A ac
Impedance 20 Ω 0.02 Ω Overload 100 mA ac 7.5 A ac
Price Input Range Output
CCT-01-0/100 mV dc input signal conditioner with 0 to 100 mVdc range,
$180.
To Order (Specify Model Number)
Model No.
CCT-04-0/50MA $180 0 to 50 mA ac 0 to 10 V or 0/4 to 20 mA CCT-04-0/5A 180 0 to 5 A ac 0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No charge for 220 Vac, add $50 to price for 24 Vdc.
Ordering Example:
Price Input Range Output
CCT-04-0/5A ac current input signal conditioner with 0 to 5 A ac range,
H-29
$180
.
Page 4
dc Current Input Models
A/IN
A/OUT
To Order (Specify Model Number)
Model Number†Price Input Range Output
CCT-32-0/50MA $180 0 to 50 mA dc 0 to 10 V or 0/4 to 20 mA CCT-32-0/5MA 180 0 to 5 mA dc 0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc.
Ordering Example:
CCT32-0/5MA dc current input signal conditioner with 0 to 5 mA range,
Range 0 to 50 mA dc 0 to 5 A dc
Impedance 20 Ω 20 Ω
Shown smaller than actual size
Overload 100 mA dc 100 mA dc
Voltage Excitation for Current Loop: 24 V dc @ 25 mA, supplied by converter
Thermocouple Input Models
Available with J, K, T, E, R
and S Thermocouple Types
Jumper-Selectable
Up or Downscale Break Protection
0.3% AccuracyLinearized
The CCT series of thermocouple input signal conditioners accept J, K, T, E, R or S type thermocouples, and provide conditioned, isolated analog outputs of 0 to 10 V or 0/4 to 20 mA. All models are powered by 110 Vac (220 Vac or 24 Vdc
Range Table
Range Code Range J KTESR
0/200C 0 to 200°C X 0/300C 0 to 300°C XX 0/400C 0 to 400°C XXX 0/500C 0 to 500°C XX 0/600C 0 to 600°C XX 0/700C 0 to 700°C XX 0/800C 0 to 800°C XX 0/900C 0 to 900°C X 0/1000C 0 to 1000°C X 0/1200C 0 to 1200°C X 600/1600C 600 to 1600°C X 850/1700C 850 to 1700°C X
powered models also available), are mountable on standard 35 mm DIN rail, and are isolated to 2 kVeff.
Specifications
Cold Junction Compensation Error: 0.05°C/°C for J, K, T, E and R
calibrations; 0.1°C/°C for type S; at 25°C ambient typical
Max Overvoltage: 75 Vdc Break Protection: Jumper
selectable, upscale (>20 mA) or downscale (<4 mA)
H-30
$180
Input Connections
To Order
(Specify Model No.)
Input
Model Number†Price Type
CCT-22-(*) $195 J CCT-23-(*) 195 K CCT-24-(*) 195 T CCT-25-0/800C 195 E CCT-26-600/1600C 195 S CCT-27-850/1700C 195 R
*Specify range code from range table. CCT-25 is only available with 0 to 800°C range, CCT-26 is only available with 600 to 1600°C range
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered unit models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc.
Ordering Example:
conditioner for type K thermocouple input, with 0 to 1200°C range,
CCT-23-0/1200C, signal
$195
.
.
H
Page 5
Economical DIN Rail Signal
A/IN
A/OUT
Conditioners
CCT-20 RTD Input Models
100Ω Pt RTD Element,
0.00385 Curve
2 or 3 Wire Configuration0.2% AccuracyDownscale Break
Protection
1 mA Max Excitation
Current
The CCT-20 signal conditioners accept 100Ω Pt RTD signals, and provide conditioned, isolated
To Order (Specify Model Number)
Model Number†Price Input Range Output
CCT-20-0/100C $190 0 to 100°C 0 to 10 V or 0/4 to 20 mA CCT-20-0/200C 190 0 to 200°C 0 to 10 V or 0/4 to 20 mA CCT-20-0/300C 190 0 to 300°C 0 to 10 V or 0/4 to 20 mA CCT-20-0/400C 190 0 to 400°C 0 to 10 V or 0/4 to 20 mA
Shown smaller than actual size
CCT-20-0/500C 190 0 to 500°C 0 to 10 V or 0/4 to 20 mA CCT-20-0/600C 190 0 to 600°C 0 to 10 V or 0/4 to 20 mA
Ordering Example:
CCT-20-0/200C RTD input signal conditioner with 0 to 200°C range,
CCT Series
outputs of 0 to 10 V or Units are 110 Vac powered (220 Vac or 24 Vdc power also available). Modules are mountable on standard 35 mm DIN rail, and are isolated to 2 kVeff.
CCT-20 Input Connections
0/4 to 20 mA.
$190.
CCT-90 Potentiometer Models
100 Ω Min/1 MΩ Max
Input
Excitation Reference
Voltage Between 1 and 2V
CCT-95 Resistance Input Models
0.2% AccuracyUpscale Break Protection
(>20 mA)
10%FS Min Input Span
See page H-35 for FAR series DIN Rail mount power supply modules.
CCT-90 Input Connections
The CCT-90 potentiometer input modules accept 3-wire potentiometers (such as position sensors) and CCT-95 models accept resistance signals, providing isolated 0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc.
output. Each model is 110 Vac powered (220 Vac or 24 Vdc also available). Models are mountable on standard 35 mm DIN rail, and are isolated to 2 kVeff.
CCT-95 Input Connections
To Order (Specify Model Number)
Model Number†Price Input Range Output
CCT-90 $190 Potentiometer 0 to 10 V or 0/4 to 20 mA CCT-95-0/200 190 0 to 200 Ω 0 to 10 V or 0/4 to 20 mA CCT-95-0/2K 190 0 to 2K Ω 0 to 10 V or 0/4 to 20 mA CCT-95-0/20K 190 0 to 20 kΩ 0 to 10 V or 0/4 to 20 mA CCT-95-0/200K 190 0 to 200 kΩ 0 to 10 V or 0/4 to 20 mA
Ordering Example:
CCT-90 potentiometer input signal conditioner,
$190
.
H-31
Page 6
CCT-05 Frequency Input Models
DI/O
A/OUT
NPN, PNP, NAMUR, Open
Collector, Contact, or TTL Inputs or AC Voltage (100 mV to 400 Vac)
Signal Input Range from
40 Hz to 40 kHz
Excitation for NPN, PNP
and NAMUR Inputs
The CCT-05 signal conditioners accepts inputs from a variety of frequency transducers, including NPN, PNP, NAMUR, open collector,
contact or TTL pulse or AC voltage (100 mV to 400 Vac). Modules are supplied scalable for a minimum and maximum frequency range. The actual range is set by the user via multiturn trimmers, a frequency generator is also required. All units are 110 Vac powered (220 Vac or 24 Vdc power also available), and may be mounted on standard 35 mm DIN rail. Each unit is isolated to 2 kVeff.
To Order (Specify Model Number)
Model No.
CCT-05-40/70 $220 0 to 40 Hz 0 to 70 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-70/125 220 0 to 70 Hz 0 to 125 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-125/225 220 0 to 125 Hz 0 to 225 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-225/400 220 0 to 225 Hz 0 to 400 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-400/700 220 0 to 400 Hz 0 to 700 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-700/1250 220 0 to 700 Hz 0 to 1250 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-1250/2250 220 0 to 1250 Hz 0 to 2250 Hz 0 to 10 V or 0/4 to 20 mA CCT-05-2250/4K 220 0 to 2250 Hz 0 to 4 kHz 0 to 10 V or 0/4 to 20 mA CCT-05-4K/7K 220 0 to 4 kHz 0 to 7 kHz 0 to 10 V or 0/4 to 20 mA CCT-05-7K/12.5K 220 0 to 7 kHz 0 to 12.5 kHz 0 to 10 V or 0/4 to 20 mA CCT-05-12.5K/22.5K 220 0 to 12.5 kHz 0 to 22.5 kHz 0 to 10 V or 0/4 to 20 mA CCT-05-22.5K/40K 220 0 to 22.5 kHz 0 to 40 kHz 0 to 10 V or 0/4 to 20 mA
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc. *The output signal is non-linear for input frequencies below 10 Hz.
Price Range Range Output
Min* Max*
Shown smaller than actual size.
Ordering Example:
frequency input signal conditioner with 0 to 70 Hz minimum range and 0 to 125 Hz maximum range,
CCT-05-70/125
$220.
H
H-32
Page 7
Economical DIN Rail
A/IN
A/OUT
Signal Conditioners
CCT Series
Strain Gage/Load Cell Input Models
For Strain Gage Sensors
with 20 mV Output and 10 V Excitation
4 and 6-Wire Bridge
Sensors
350 Ω Sensor ImpedanceCompanion FAR-1 Power
Supply Module Provides Stabilized 10 Vdc Excitation for 4 Modules
FAR Series Power
Supplies Provide Bridge Excitation
FAR-1 10 V, 250 mA power supply with Shown smaller than actual size.
excitation sense capability, $133.
The CCT-80 strain gauge/load cell signal conditioners accept input from 350Ω bridge circuits and provide isolated 0 to 10 V or 0/4 to 20 mA output. The FAR series power supplies can be used to provide signal isolation for bridge circuits and other transducers. The FAR-1 is specifically designed for use with strain gage circuits. All units are 110 Vac powered (220 Vac power also available), and are mounted on standard 35 mm DIN rails.
Power Supply Specifications
Power: 110 Vac, 50-60 Hz Output Adjust (FAR-1 only): ±5%, internal
potentiometer
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc.
To Order (Specify Model Number)
Model No.†Price Description
CCT-80 $190 Strain gage signal conditioner with
FAR-1 133 10 V, 250 mA power supply
FAR-2-5 133 5 V, 225 mA power supply FAR-2-9 133 9 V, 225 mA power supply FAR-2-12 133 12 V, 200 mA power supply FAR-2-15 133 15 V, 100 mA power supply FAR-2-18 133 18 V, 100 mA power supply FAR-2-24 133 24 V, 150 mA power supply
* To order FAR-1 with 230 Vac power, add suffix “-230” to model number at no additional charge.
Ordering Example:
FAR-1 10 V, 250 mA power supply, $190 + 133 =
CCT-80 strain gage signal conditioner with
0-10 V or 0/4 to 20 mA output
with excitation sense capability, 110 Vac power*
$323
.
CCT-80 Input Connections
H-33
Page 8
CCT-55 Signal
A/IN
A/OUT
Integrators
Convert Analog Voltage/Current to
Frequency Output
Source or Sink OutputOutput Ranges From 1 pulse/hour to
10,000 pulses/sec Full Scale
The CCT-55 signal integrators provide conditioned, isolated frequency outputs proportional to the analog input signal. The CCT-55-V accepts voltages from 0-100 mV to 0 to 650 V, while the CCT-55-I accepts from 0 to 5 mA to 0 to 50 mA input. Output ranges are field setable through jumper selection and multiturn trimmers. A calibrator and frequency meter is required for adjustment.
Specifications
dc Voltage Input Ranges: 0 to 0.1 Vdc, 0 to 1 Vdc,
0 to 10 Vdc, 0 to 100 Vdc, 0 to 650 Vdc; jumper select
Current Input Ranges: 0 to 5 mA, 0 to 50 mA; jumper select Output: 15 Vdc @ 5 mA source or 100 mA sink with 24 Vdc
external supply Output Ranges: 1 pulse/hr to 10,000 pulses/sec full scale;
jumper select and poteniometer adjustment Pulse Ratio: 50% or fixed 100 ms
CCT 100 Galvanic Isolator
Provides 2 kV Input to
Output Isolation
0 to 50 mA Input and
Output Ranges
Loop Powered
Specifications
INPUT Input/Output Ratio: 1:1; signal
output = signal input
Input Current: 0 to 50 mA dc Input Voltage: 18 Vdc max Voltage Drop: 3 Vdc max Max Load: 50 mA dc
Model CCT-100 Galvanic Isolator
To Order (Specify Model Number)
Model Number Price Description
CCT-100 $140 Loop powered galvanic isolation module
Ordering Example:
CCT-100 galvanic isolator,
OUTPUT Output Current: 0 t 50 mA dc
Ripple: 0.5% @ 3 kHz
$140
.
Shown smaller than actual size.
To Order (Specify Model Number)
Model Number†Price Description
CCT-55-V $255 Voltage Input CCT-55-I 255 Current Input
† 110 Vac powered units supplied standard. To order 220 Vac or 24 Vdc powered models add “-220VAC” or “-24VDC” to the model number. No additional charge for 220 Vac, add $50 to price for 24 Vdc.
Ordering Example:
Load: 0 to 750 Ω Response Time: 50 ms Accuracy: 0.1% at 25°C Temperature Coefficient: 0.01%
each 10°C from 10 to 60°C
Dimensions: 75 x 22.5 x 98.5 mm
Weight: 100 g (0.2 lb)
CCT-55-V voltage input,
(2.95 x 0.89 x 3.88")
$255
.
H
H-34
Page 9
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com
EPG05
www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488
UNITED STATES
www.omega.com
1-800-TC-OMEGA
Stamford, CT.
CANADA
www.omega.ca
Laval(Quebec)
1-800-TC-OMEGA
GERMANY
www.omega.de
Deckenpfronn, Germany
0800-8266342
Karviná, Czech Republic
FRANCE
www.omega.fr
Guyancourt, France
088-466-342
CZECH REPUBLIC
www.omegaeng.cz
596-311-899
BENELUX
www.omega.nl
Amstelveen, NL 0800-099-33-44
More than 100,000 Products Available!
Temperature
Calibrators, Connectors, General Test and Measurement Instruments, Glass Bulb Thermometers, Handheld Instruments for Temperature Measurement, Ice Point References, Indicating Labels, Crayons, Cements and Lacquers, Infrared Temperature Measurement Instruments, Recorders Relative Humidity Measurement Instruments, RTD Probes, Elements and Assemblies, Temperature & Process Meters, Timers and Counters, Temperature and Process Controllers and Power Switching Devices, Thermistor Elements, Probes and Assemblies,Thermocouples Thermowells and Head and Well Assemblies, Transmitters, Wire
Flow and Level
Air Velocity Indicators, Doppler Flowmeters, Level Measurement, Magnetic Flowmeters, Mass Flowmeters, Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Flowmeters, Vortex Shedding Flowmeters
pH and Conductivity
Conductivity Instrumentation, Dissolved Oxygen Instrumentation, Environmental Instrumentation, pH Electrodes and Instruments, Water and Soil Analysis Instrumentation
Data Acquisition
Auto-Dialers and Alarm Monitoring Systems, Communication Products and Converters, Data Acquisition and Analysis Software, Data Loggers Plug-in Cards, Signal Conditioners, USB, RS232, RS485 and Parallel Port Data Acquisition Systems, Wireless Transmitters and Receivers
Pressure, Strain and Force
Displacement Transducers, Dynamic Measurement Force Sensors, Instrumentation for Pressure and Strain Measurements, Load Cells, Pressure Gauges, Pressure Reference Section, Pressure Switches, Pressure Transducers, Proximity Transducers, Regulators, Strain Gages, Torque Transducers, Valves
Heaters
Band Heaters, Cartridge Heaters, Circulation Heaters, Comfort Heaters, Controllers, Meters and Switching Devices, Flexible Heaters, General Test and Measurement Instruments, Heater Hook-up Wire, Heating Cable Systems, Immersion Heaters, Process Air and Duct, Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
click here to go to the omega.com home page
Loading...