Operation:
Note: When connecting a pulse signal, ensure that the input
signal voltage is less than or equal to the rating. The unit may
be damaged if the input voltage exceeds the maximum rating.
Power Input and Analog Output Setup:
To connect the signal input proceed as follows:
1. Connect a DC power supply with an output voltage
between 10 to 32Volt DC to the signal conditioner (J1).
Note: If power supply used has current limiting, it may not
be able to power the signal conditioners if the available output
voltage is around 10Volt, since the peak current may reach 1 to
5 Amps for a few milliseconds.
2. Ensure that if the selected mode or signal source is different
from the default then change them using serial
communication explained later in this manual.
3. Connect the signal input to screw terminal, and ensure that
the screws are tight
4. To view/change the scaling that relates the analog output to
signal input: connect the RS232 output of the signal
conditioner to an available serial port of a computer. The
cable and the DB9 or DB25 connectors are available as an
option.
56
DRN-FP
Frequency/Pulse Signal Conditioner
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI
regulations that apply. OMEGA is constantly pursuing certification of its
products to the European New Approach Directives. OMEGA will add the CE
mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but
OMEGA Engineering, Inc. accepts no liability for any errors it contains, and
reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used
for, patient connected applications.
PATENT AND TRADEMARK NOTICE:
This product is covered by one
or more of the following patents: U.S. Pat. No. Des. 336,895,
5,274,577/ Canada 2052599, 2052600/ Italy 1249456, 1250938/
France Brevet No. 91 12756/ Spain 2039150, 2048066/ UK Patent
No. GB2 249 837, GB2 248 954/ Germany DE 41 34398 C2.
, are trademarks of OMEGA Engineering, Inc.
This device is marked with the international hazard symbol.
It is important to read the Setup Guide before installing or
commissioning this device as it contains important
information relating to safety and EMC.
M2524/0301
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in
materials and workmanship for a period of 13 months from date of
purchase. OMEGA Warranty adds an additional one (1) month grace period
to the normal one (1) year product warranty to cover handling and
shipping time. This ensures that OMEGAs customers receive maximum
coverage on each product.
If the unit should malfunction, it must be returned to the factory for
evaluation. OMEGAs Customer Service Department will issue an Authorized
Return (AR) number immediately upon phone or written request. Upon
examination by OMEGA, if the unit is found to be defective it will be repaired
or replaced at no charge. OMEGA’S WARRANTY does not apply to defects
resulting from any action of the purchaser, including but not limited to
mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the
unit shows evidence of having been tampered with or shows evidence of
being damaged as a result of excessive corrosion; or current, heat, moisture
or vibration; improper specification; misapplication; misuse or other
operating conditions outside of OMEGAs control. Components which wear
are not warranted, including but not limited to contact points, fuses, and
triacs.
OMEGA is pleased to offer suggestions on the use of its various
products. However, OMEGA neither assumes responsibility for any
omissions or errors nor assumes liability for any damages that result
from the use if its products in accordance with information provided
by OMEGA, either verbal or written. OMEGA warrants only that the
parts manufactured by it will be as specified and free of defects.
OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF
ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies
of purchaser set forth herein are exclusive and the total liability of
OMEGA with respect to this order, whether based on contract,
warranty, negligence, indemnification, strict liability or otherwise,
shall not exceed the purchase price of the component upon which
liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it
be used: (1) as a Basic Component under 10 CFR 21 (NRC), used in or with any
nuclear installation or activity; or (2) in medical applications or used on humans.
Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes
no responsibility as set forth in our basic WARRANTY / DISCLAIMER language,
and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless
from any liability or damage whatsoever arising out of the use of the Product(s)
in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer
Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA,
PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the
outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and
proper packaging to prevent breakage in transit.
FOR W
ARRANTY RETURNS, please
have the following information
available BEFORE
contacting OMEGA:
1. P.O. number under which the
product was PURCHASED,
2. Model and serial number of the
product under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-W
ARRANTY REPAIRS,
consult OMEGA for current repair
charges. Have the following
information available BEFORE
contacting OMEGA:
1. P.O. number to cover the COST of
the repair,
2. Model and serial number of
product, and
3. Repair instructions and/or specific
problems relative to the product.
OMEGAs policy is to make running changes, not model changes, whenever an
improvement is possible. This affords our customers the latest in technology
and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2001 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced, translated, or
reduced to any electronic medium or machine-readable form, in whole or in
part, without prior written consent of OMEGA ENGINEERING, INC.
5. Turn on the computer, start Windows 3.0 or higher and run
the Signal Conditioner Configuration Setup Program. If the
program has not been installed, then insert the 3.5Ó floppy
disk in either drive A or B. From the Program Manager
choose File, Run; in the command box type either A: setup or
B: setup according to your drive designation. The program
will create an icon for the signal conditioner. You may start
the program by clicking on this icon.
6. Start the configuration program, you need to indicate which
serial port is to be used for serial communication by checking
the appropriate check box on the opening menu.
Note: It is not necessary to know the serial communication
protocol. i.e. baud rate, parity, 7/8 data bit and stop bit; the
program will determine this information automatically.
However, it is good practice to mark the protocols used on the
signal conditioner label if different from default.
7. Once the program starts it will automatically detect the
signal conditioner configuration and will display a window of
available options. To view the signal input click on the
display on/off.
8. To change analog output scaling choose analog output
scaling and enter the desired values.
9. Once the custom scaling is finished, ensure that Send
Configuration is clicked, otherwise the changes will not take effect.
10. The input/output scaling may be fine tuned, while both
communication and analog output are active. You may make
a change to the analog output in the configuration program,
and watch the DVM connected to analog output of the signal
conditioner follow the new settings.
11. You may save or print a particular configuration by
selecting the file menu. ItÕs always a good practice to both
print and save the scaling of each signal conditioner.
12. If the program is not able to establish communication then
an error message is displayed. This happens either when the
wrong serial port is specified or when the cable is
disconnected.
®
omega.com
®
®
®
OMEGAnet¨ On-Line Service
www.omega.com
Servicing North America:
USA:•• One Omega Drive, P.O. Box 4047
ISO 9001 Certified• Stamford CT 06907-0047
•• TEL: (203) 359-1660•• FAX: (203) 359-7700
•• e-mail: info@omega.com
Canada:•• 976 Bergar
•• Laval (Quebec) H7L 5A1
•• TEL: (514) 856-6928•• FAX: (514) 856-6886
•• e-mail: info@omega.ca
For immediate technical or application assistance:
USA and Canada:• Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
•• Customer Service: 1-800-622-2378 / 1-800-622-BEST
•• Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
•• TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
Mexico and • TEL: (001)800-TC-OMEGA
Latin American:• En Espa
•• e-mail: info@omega.com.mx
–ol: (001) 203-359-7803•
Servicing Europe:
Benelux:•• Postbus 8034, 1180 LA Amstelveen, The Netherlands
•• TEL: +31 20 3472121•• FAX: +31 20 6434643
•• Toll Free in Benelux: 0800 0993344•
•• e-mail: nl@omega.com
Czech Republic:• RudŽ arm‡dy 1868, 733 01 Karvin‡ 8
•• TEL: +420 69 6311899• FAX: +420 69 6311114
•• e-mail: czech@omega.com
France:•• 9, rue Denis Papin, 78190 Trappes
•• TEL: +33 130 621 400• FAX: +33 130 699 120
•• Toll Free in France: 0800406342
••
Germany/Austria:• Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
•• TEL: +49 7056 9398-0• FAX: +49 7056 9398-29
•• Toll Free in Germany: 0800 TC-OMEGA
•• e-mail: germany@omega.com
United Kingdom:• One Omega Drive
ISO 9002 Certified• River Bend Technology Centre
•• Northbank, Irlam Manchester M44 5EX United Kingdom
•• TEL: +44 161 777 6611• FAX: +44 161 777 6622
•• Toll Free in England: 0800 488 488
•• e-mail: sales@omega.co.uk
e-mail: france@omega.com
Internet e-mail
info@omega.com
¨
¨
¨
• FAX: (001) 203-359-7807
¨
¨
DRN-FP
FREQUENCY/PULSE INPUT
General Description:
The DRN Series of DIN rail-mountable signal conditioners are
available for Thermocouple, RTD, Strain, Process, AC Voltage,
AC Current and Pulse/Totalizer input types.
The factory calibrated signal conditioners are ideal for all
process and power monitoring applications, they feature 3way isolation, high accuracy input, programmable outputs,
and are excellent front end interfaces for programmable logic
controllers or data acquisition systems. For maximum user
configurability the signal conditioners allow complete inputoutput scaling via a RS-232 connection to any PC or PLC.
Software Description:
The signal conditioner configuration program is a MS
DOS/Windows program (this manual is for the Windows
version). It is designed especially for the DRN Series Signal
Conditioner. This program will run on any PC with Windows
application and will start automatically.
Free Serial Communication software and ActiveX Controls are on the
CD-ROM enclosed with this shipment. To download the latest
software release (or request a free CD-ROM) please go to:
www
.omega.com/software
What You need:
¥Your choice of the signal conditioner
¥IBM PC or compatible
¥Windows software 3.1 or higher, or Windows 95/98
¥RJ12 connector with telephone cable
¥Adapter (DB9 or DB25 to RJ12)
Setting up your System
INPUT TYPE:
Min. Low level signal input (magnetic
pickups) : From 0 mV to 120 mV
Open Collector NPN (Use software to
set: 3 K½ pull up to 5V): Max. current
source = 1.66 mA
Open Collector PNP (Use software to set: 1K½ pull down to
RTN): Max. current sink = 12.5 mA
Introduction:
The frequency/pulse signal conditioners are high
performance instruments which operates in 4 different modes.
Input can be programmed to read different signal sources
including low level pulse, open collector and TTL/CMOS
signals. Key features are: programmable excitation and input;
operates as a rate meter, totalizer with reset, A-B totalize and
Quadrature; scalable analog output and a simple RS232
interface for scaling analog output and range selection. The
RS232 interface may also be used for digital transmission of
the input signal to a computer or a PLC. Additional features
include three way isolation between DC power, signal input
and analog output/RS232.
TTL/CMOS Input: (Use software to set: no pull up/down).
Low <= 0.8 V , High >= 3.5 V (For Input: 0.2 Hz to 16 KHz)
Low <= 0.8 V , High >= 12 V ( For Input: 0.2 Hz to 50 KHz )
NAMUR Sensors (Use software to set: 1K½ pull down to RTN
and 8.2V Excitation.)
For measuring a low level signal riding on top of a large DC
signal, connect a 0.1 uF capacitor. See Detail.
Use software to set 1K½ pull down to RTN.
OPERATING MODES:
Frequency: Range = 0.2 Hz to 50 KHz
Max. Input Frequency: 30 KHz. for Input
Level: 0-5 V
Max. Input Frequency: 50 KHz. for Input Level: 0-12 V
FREQUENCY RESOLUTION
0 to 9.99999 Hz 0.00001 Hz
10 to 99.9999 Hz 0.0001 Hz
100 to 999.999 Hz 0.001 Hz
1000 to 9999.99 Hz 0.01 Hz
10000 to 50000.0 Hz 0.1 Hz
0 to 50000 Hz 1 Hz
Totalize with Reset: Range = 0 to 999999*, if reading is larger
than 999999, then reading is converted to floating point
number, i.e. 9.99E9 (maximum).
Max. Input Frequency: 30 KHz. for Input Level: 0-5 V
Max. Input Frequency: 50 KHz. for Input Level: 0-12 V
A-B Totalize (Reset input used as +A input): Range = -99999
to 999999*, if reading is larger than 999999, then reading is
converted to floating point number, i.e. -9.99E9 (minimum),
9.99E9 (maximum).
Max. Input Frequency: 30 KHz. for Input Level: 0-5 V
Max. Input Frequency: 25 KHz. for Input Level: 0-12 V
Quadrature (Reset input used as second input): Range =
-99999 to 999999*, if reading is larger than 999999, then
reading is converted to floating point number, i.e. -9.99E9
(minimum), 9.99E9 (maximum).
Max. Input Frequency: 30 KHz. for Input Level: 0-5 V
Max. Input Frequency: 25 KHz. for Input Level: 0-12 V
* Resolution is 1 count.
ISOLATION:
Dielectric strength to 1000 Vrms transient per 1 minute test
based on EN 61010 for 50 Vdc or Vrms working voltage.
Three way Isolation:
¥ Power to input
¥ Power to analog output/communication
¥ Input to analog output/communication
COMMON MODE REJECTION:
100 dB
INPUT IMPEDANCE:
Input: 1M½ to +EXC Reset: 100K to +5V
INPUT OVER-VOLTAGE PROTECTION:
With 1K pull down: 14V With 3K pull up: 20V
Without pull up/down: 60V
START HERE
2
3
EXCITATION:
5, 8.2 or 12.5V at 25mA, programmable
ACCURACY AT 25 ¡C:
± 0.1% of Full scale Crystal time base accuracy: ± 50 ppm
TEMPERATURE STABILITY:
± 50 ppm/¡C typical Time base stability: ± 1ppm/¡C
STEP RESPONSE FOR RS232 OUTPUT:
0.1 second to 99% of the final value
(Filter time constant = 0, Gate time = 0.05 Sec)
RESPONSE TIME:
To verify the response time, check the carriage return <CR>,
it will be sent at the end of the response. You can send
another command after you receive the <CR>.
i.e. send: *X01 response: X01<DATA><CR>
Note: Only for reading (X01 command).
Frequency mode: response time is controlled by the
gate time. If gate time is increased then response
time is longer.
Other modes: response time is not controlled by the
gate time.
ANALOG OUTPUT STEP RESPONSE TIME:
2 Seconds to 99% of the final value
WARM UP TO RATED ACCURACY:
30 minutes
ANALOG OUTPUT SIGNAL TYPE:
Voltage: 0-10 Volt, maximum current 10mA
Current: 0-20 mA or 4-20 mA, maximum compliance
voltage 10 Volts (maximum loop resistance 500½)
ANALOG OUTPUT LINEARITY:
0.1% of FS
INPUT POWER:
10 to 32 Volt DC
POWER CONSUMPTION:
3 Watts (125mA at 24V DC)
OPERATING AMBIENT:
-5 to +55 ¡C
STORAGE TEMPERATURE:
-40 to +85 ¡C
RELATIVE HUMIDITY:
90% at 40 ¡C
non-condensing
DIMENSIONS:
4
J4
O
34
N/C
U
U
PWR
R
S
2
3
2
C
J2
W
J2
T
P
T
D
C
P
R
J2
Frequency Mode/
Totalize Mode
with Reset (example)
Excitation
NPN open
Collector
Quadrature Mode
Excitation
Quadrature
Encoder
EXC
EXC
+EXC
+IN
RST
RTN
+EXC
A
+IN
RST
B
RTN
+EXC
A
B
VI
J3
1 2
SIGNAL INPUT
+
-
J1
1 2 3 4
1 2 3 4
+IN
RST
RTN
Totalize (A-B) Mode