The DRG-AR Series modules are a family of DIN rail mount limit alarms with dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. Modules are available for a variety of input types including thermocouples, RTDs, DC and AC current and voltages.
Each module can be set to a number of input ranges via an input selector switch. The alarm points and dead band are adjusted by potentiometers.
Model Price Input Type
DRG-AR-AC $289 AC Voltage and Current DRG-AR-DC 289 DC Voltage and Current DRG-AR-RTD 289 RTD DRG-AR-TC 289 Thermocouple
Diagnostic LEDs
All modules are equipped with 3 front panel LEDs. The first is a dual function LED labeled input. This green LED indicates line power and input signal status. Two red LEDs indicate the relay state for each setpoint. An illuminated red LED indicates the tripped condition.
Output
The DRG-AR Series modules are equipped with two SPDT relays, rated at 120 Vac or 28 Vdc at 5 amperes. Each of these relays is independently controlled by the field configurable setpoint and deadband.
Operation
The field configurable limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe operation. Each of the setpoints has a respective HI or LO deadband. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the low deadband. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-fail-safe). In the fail-safe mode, a power failure results in an alarm state output.
A/IN DI/O
A/OUT
ALL MODELS AVAILABLE FOR FAST DELIVERY!
H-30
H
Specifications
DRG-AR-AC Range (Voltage Mode):
100 mV to 200 Vac
Impedance (Voltage Mode):
>100KΩ
Overload (Voltage Mode):
300 Vac, max.
Range (Current Mode):
10 mA to 100 mAAC
Impedance (Current Mode):
20Ω, typical
Overcurrent (Current Mode):
200 mAAC
Overvoltage (Current Mode):
60V peak
Frequency Range: 40 to 400 Hz Limit Differentials (Deadbands):
>50 mV/5 mA: 0.25% to 5% of span <50 mV/5 mA: 1% to 5% of span
Setpoint Repeatability (Constant Temperature): 0.2% of full scale
DRG-AR-DC Range (Voltage Mode):
10 mV to ±200 V
Impedance (Voltage Mode):
>100KΩ
Overload (Voltage Mode):
200 VRMS, max.
Range (Current Mode):
1 mA to ±100 mA
Impedance (Current Mode):
20Ω, typical
Overcurrent (Current Mode):
170 mA RMS max.
Overvoltage (Current Mode):
60 Vdc
Limit Differentials (Deadbands):
>50 mV/5 mA: 0.25% to 5% of span <50 mV/5 mA: 1% to 5% of span
Setpoint Repeatability (constant temp):
>50 mV/5 mA: 0.1% of full scale <50 mV/5 mA: 0.2% of full scale
Excitation:
24 Vdc, 20 mA maximum
321
654
17,7 (.70)
90.0
(3.54)
88.5
(3.48)
105.2
(4.14)
35 mm RAIL
110.2
(4.34)
32 mm RAIL
DIMENSIONS ARE IN MM (INCHES)
Dynamic DeadBand
LSI circuitry in the DRG-AR Series prevents false trips by repeatedly sampling the input. The input must remain beyond the setpoint for 100 milliseconds to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This, effectively, results in a dynamic deadband.
DRG-SC-RTD: Sensor Types: RTD, Pt100, Pt500,
Pt1000 (= 0.00385); Cu10, Cu100, Ni 120, Ni Fe 604
Sensor Connection: 3 wire Range: See Range Table Excitation Current: <2 mA for
Pt100, Pt500, Pt1000; <5mA for Cu100, Ni 120 or Ni Fe 604
Lead Wire Resistance: 40% of base sensor resistance or 100Ω (whichever is less), max. per lead
Lead Wire Effect: Less than 1% of the maximum input temperature span
Limit Differentials (Deadbands):
1.0 to 5% of span
Setpoint Repeatability (Constant Temperature): ±0.2% of full scale
DRG-SC-TC Ranges: See Range Table Bias Current (Burnout Detection):
<1.5 microamp
Impedance: >1MΩ Overvoltage: ±10 V differential Limit Differentials (Deadbands):
0.25 to 5% of span
Setpoint Repeatability (Constant Temperature): 0.2% for temp
> 0°C. 0.3% for temp < 0°C
SPECIFICATIONS COMMON TO ALL MODULES
Relay Contacts
2 SPDT (2 form C) Relays 1 Relay per setpoint Current Rating: 120 Vac: 5A, 240 Vac: 2A, 28 Vdc: 5A Material: Silver-Cadium Oxide Electrical Life: 10
5
operations
Isolation: 1800 Vdc between input, contacts and power
RESPONSE TIME Dynamic Deadband: Relay status
will change when proper setpoint condition exists for 100 msec
Normal Mode (Analog Filtering):
<250 msec, (10-90%) Mounting: Standard 32mm
or 35mm DIN rail Wire Termination: Screw:
Termination for 12-22 AWG ESD Susceptibility: Meets IEC
801-2, Level 2 (4 KV)
Humidity (Non-Condensing):
Operating: 15 to 95% (@45°C), Soak: 90% for 24 hours (@65°C)
Temperature Range: Operating: 0 to 55°C (32 to 131°F), Storage: -25 to 70°C (-13 to 158°F)
Power: 9-30 Vdc, 1.5 W typical,
2.5 W max