IndustrIal Control
transformers
C-Transformers
l Single Phase Transformers
l VA Load for 50 to 500
l Input Voltages 240/480 to 120 Vac
l Input Voltages 208/230/450 to
24/115 Vac
l Models with Integral Fuse Blocks
Transformers provide stepped down voltages
to machine tool control devices enabling
control circuits to be isolated from all power
and lighting circuits. This allows the use of
grounded or ungrounded circuits that are independent of the power or lighting grounds;
greater safety is afforded the operator.
The control transformer line is particularly
adaptable on applications where compact
construction is demanded.
Single-Phase Transformers
How to Select Single-Phase Units
1. Determine the primary (source) voltage
(the voltage presently available).
2. Determine the secondary (load) voltage
(the voltage needed at the load).
3. Determine the VA load:
Select a transformer rating equal to or
greater than the load VA.
VA = Load Volts x Load Amps
C0050E2A
shown smaller
than actual size.
DIMENSIONS: mm (inch)
MODEL NO. VA HEIGHT WIDTH DEPTH
C0050E2A 50 65 (2.56) 76 (3) 76 (3) 1.2 (2.6) 1
C0075E2A 75 65 (2.56) 76 (3) 89 (3.5) 1.6 (3.5) 1
C0100E2A 100 73 (2.875) 86 (3.375) 86 (3.375) 1.9 (4.2) 1
C0150E2A 150 81 (3.187) 95 (3.75) 102 (4) 3 ( 6.7) 1
C0200E2A 200 97 (3.812) 114 (4.5) 102 (4) 3.9 (8.5) 1
C0250E2A 250 97 (3.812) 114 (4.5) 111 (4.375) 10 (4.5) 1
C0300E2A 300 97 (3.812) 114 (4.5) 121 (4.75) 5.1 (11.3) 1
C0500E2A 500 121 (4.75) 133 (5.25) 140 (5.5) 8.7 (19.2) 1
C0050E2AFB 50 100 (3.937) 76 (3) 76 (3) 1.3 (2.8) 1
C0075E2AFB 75 100 (3.937) 76 (3) 89 (3.5) 1.7 (3.7) 1
C0100E2AFB 100 108 (4.25) 86 (3.375) 86 (3.375) 2.0 (4.4) 1
C0150E2AFB 150 116 (4.562) 95 (3.75) 102 (4) 3.1 (6.9) 1
C0200E2AFB 200 132 (5.187) 114 (4.5) 102 (4) 3.9 (8.7) 1
C0250E2AFB 250 132 (5.187) 114 (4.5) 111 (4.375) 4.6 (10.2) 1
C0300E2AFB 300 132 (5.187) 114 (4.5) 121 (4.75) 5.2 (11.5) 1
C0350E2AFB 350 132 (5.187) 114 (4.5) 133 (5.25) 6.3 (13.8) 1
C0500E2AFB 500 156 (6.125) 133 (5.25) 140 (5.5) 8.8 (19.4) 1
C0050E5E 50 65 (2.56) 76 (3) 83 (3.25) 1.5 (3.4) 2
C0100E5E 100 81 (3.187) 95 (3.75) 143 (5.625) 2.7 (5.9) 2
C0150E5E 150 81 (3.187) 95 (3.75) 111 (4.375) 3.6 (7.9) 2
WEIGHT
kg (lbs)
WIRING
DIAGRAM
1
• •
• •
•
•
•
•
•
•
• •
•
•
•
•
•
•
•
•
•
H1 H2 H3 H4
X3 X2 X1
0V
220/230/240V
440/460/480V
200/208V
0V
23/24/25V
110/115/120V
240V
230V
220V
480V
460V
440V
H1 H3 H2 H4 H1 H3 H2 H4
110V
115V
120V
XZ
X1
H1 H3 H2 H4
• •
• •
•
•
•
H1 H2 H3 H4
X3 X2 X1
0V
220/230/240V
440/460/480V
200/208V
0V
23/24/25V
110/115/120V
Wiring Diagram 1
111 (4.375)
SECONDARY
SIDE
133 (5.25)
114 (4.5)
63.5 (2.5)
STACK
98 (3.875)
140 (5.5)
C0050E2AFB
shown smaller
than actual size.
To Order Visit omega.com/c-transformer for Pricing and Details
INDUSTRIAL CONTROL TRANSFORMERS CPT
MODEL NO. DESCRIPTION
C0050E2A 50 VA, 240/480 to 120 Vac
C0075E2A 75 VA, 240/480 to 120 Vac
C0100E2A 100 VA, 240/480 to 120 Vac
C0150E2A 150 VA, 240/480 to 120 Vac
C0200E2A 200 VA, 240/480 to 120 Vac
C0250E2A 250 VA, 240/480 to 120 Vac
C0300E2A 300 VA, 240/480 to 120 Vac
C0500E2A 500 VA, 240/480 to 120 Vac
C0050E5E 50 VA, 208/230/450 to 24/115 Vac
C0100E5E 100 VA, 208/230/450 to 24/115 Vac
C0150E5E 150 VA, 208/230/450 to 24/115 Vac
TRANSFORMERS WITH PRIMARY FUSE BLOCK
C0050E2AFB 50 VA, 240/480 to 120 Vac
C0075E2AFB 75 VA, 240/480 to 120 Vac
C0100E2AFB 100 VA, 240/480 to 120 Vac
C0150E2AFB 150 VA, 240/480 to 120 Vac
C0200E2AFB 200 VA, 240/480 to 120 Vac
C0250E2AFB 250 VA, 240/480 to 120 Vac
C0300E2AFB 300 VA, 240/480 to 120 Vac
C0350E2AFB 350 VA, 240/480 to 120 Vac
C0500E2AFB 500 VA, 240/480 to 120 Vac
Comes complete with instruction sheet.
Ordering Examples: C0050E2A, 50 VA control transformer.
C0050E2AFB, 50 VA control transformer with primary fuse block.
2
Dimensions: mm (inch)
Wiring Diagram 2