Omega Products BB19-AV1 Installation Manual

omega.com
TM
®
BB19 & BB200 Bare Bones Series
INSTRUCTION
SHEET
OMEGA’s Bare Bones (BB) Series meters are designed for low cost OEM applications.The BB19 Series gives OEM buyers an easy-to-use digital indicator for current, voltage, and line frequency which can be incorporated into the design of machines or systems.
Units feature convenient screw terminal connections for quick hook-up of sensor input and power.
BB19 Series meters have a compact size and wide ambient operating range, so they can be used in a variety of applications.
The ac voltage units (BB19-AV1, BB19-AV2) can be used to monitor line power to make sure that the correct level of voltage is being used in the application.For example, you may want to monitor the voltage that is being applied to equipment to verify that the ac signal is within specifications.It is also important to monitor the level of current draw. Current draw that is too high may cause damage to equipment.The BB19 ac current meters give the user a low cost means of monitoring line current.
Line frequency monitors (BB19-F1 or BB19-F2) can be used in situations where it is necessary to verify that the frequency of the power source falls within specifications.
DC voltage and dc current meters (BB19-DC series and BB19-DV series) can be used in process measurement and control applications as a secondary source to monitor signals that are being sent by temperature, pressure or flow transducers.
These meters can also be used as a troubleshooting device to assist the user who believes that transducers are not functioning properly.
In addition to BB19 series, the BB200 series measure thermocouple and process inputs. The BB201 and BB202 models are can be ordered with either thermocouple types: J, K, T or RTD with 0.1 or 1 degree resolution. The BB211 and BB212 universal process meters accept inputs from pressure and flow sensors with voltage or milliamp outputs. They can be scaled to display in engineering units up to 1500 counts.
UNPACKING INSTRUCTIONS
Remove the Packing List and verify that all equipment has been received. Make sure that the following is in the box: a BB19 and an operator's manual. If there are any questions about the shipment, please contact the OMEGA Engineering Customer Service Department.
Note: The carrier will not honor any claims unless all shipping material is saved for their examination. After examining and removing contents, save packing material and carton in the event reshipment is necessary.
Current, Voltage, Line Frequency & Temperature Meters
BB19 & BB200 Features
U NEMA-4 and IPC55
(Splash Proof, Hose Down)
U
1
8 DIN Panel Cutout
U Low Cost U Shallow Depth (Only 1" Deep) U Screw T erminals U High Impact Polycarbonate
Case
U Red or Green Backlit Display U Wide Operating Temperature
-4 to 140°F (-20 to 60°C)
U User Selectable
Decimal Points
BB19 Features
Current and Voltage Monitor Features
U Overrange Indication U AC Voltage and Current
(Average Response)
U Ideal for Line Monitoring U Input Signal Can Be
Used to Power Meter
U Multiple Ranges Available for
Use with External Current Transformers
Line Frequency Monitor Features
U 0.1 Hz or 1.0 Hertz Resolution U Overrange Indication
BB200 Features
U Thermocouple Input:
J, K, or T
U RTD Input: Pt.385, 2-,3-Wire,
0.1° or 1° DisplayResolution
BB19 & BB200 Series
Specifications Display: 31⁄2-digit, 7-segment backlit
LCD; 13 mm (0.5") height
Polarity: Automatic (-) displayed Warmup:10 minutes Environment Operating Range: -20 to 60°C (-4 to
140°F) Storage Range: -30 to 70°C (-22 to 159°F)
Performance Conversion Rate: 2.5 per second
Normal Mode Rejection:
40 db 50-60 Hz
Common Mode Rejection:
100 db 50-60 Hz, except isolated
Zero Adjustment: Automatic
FCC Compliance: Complies with class B
limits of FCC rules and regulations, part 15, subpart J for conducted and radiated emissions
Panel Cutout:
BB200 Series:1⁄ 8 DIN, 45 H x 92 mm W (1.772 x 3.622");
Weight: 2 oz (56.7 g)
Input Type Range Accuracy
-10 to 1200°F 2.8°F
-30 to 650°C + 0.1% rdg
-40 to 1500°F 2.5°F
-40 to 800°C + 0.1% rdg
-100 to 600°F 3.5 F
-100 to 350°C + 0.1% rdg
P1 -200 to 600°F 1°F
( ) -100 to 500°C + 0.2% rdg
P2 -100.0 to 199.9°F 0.1F
( )-100.0 to 199.9°C + 0.2% rdg
Order Suffix Description
-230 230 Vac
-LV 12 or 24 Vdc (isolated) power
Order Suffix Description
-GN Green display
To Order
(Specify Model Number)
Model Number Description Range BB19-AV1 ac voltage meter 80 to 130 Vac BB19-AV2 ac voltage meter 80 to 260 Vac BB19-DV1 dc voltage meter 200 mV dc BB19-DV2 dc voltage meter 2 Vdc BB19-DV3 dc voltage meter 20 Vdc BB19-DV4 dc voltage meter 200 Vdc BB19-AC1-(*) ac current meter 0 to 5 Amps ac** BB19-AC2 ac current meter 0 to 50 Amps ac** BB19-DC1 dc current meter 200 mA dc BB19-DC2 dc current meter 2 mA dc BB19-DC3 dc current meter 20 mA dc BB19-DC4 dc current meter 200 mA dc BB19-F1 Line frequency monitor 40 to 440 Hz BB19-F2 Line frequency monitor 40 to 199.9 Hz
Suffix Display Max
-1 2000
-2 1500
-3 1000
-4 600
-5 500
-6 300
-7 200
-8 100
* Enter display max for 0 to 5 Amp ac input meter ** For use with 5 A or 50 A external current transformer (supplied with meter)
Comes complete with operator's manual and panel mount adaptor
Ordering Examples: BB19-DV3, dc voltage meter with range up to 20 Vdc, BB19-AC1-2, ac current meter with range 0 to 5 A with maximum display range 1500, BB19-F1-GN-LVI, line frequency meter with range 40 to 440 Hz, green display,and
12 or 24 Vdc isolated power,
BB19 Power Options
BB19 Display Options
BB19-AC1 Display Max Ordering Suffixes
To Order
(Specify Model Number)
Model No. Description BB201(*)
1
8 DIN temperature meter with green backlit display
BB202(*)
1
8 DIN temperature meter with red backlit display
BB211
1
8 DIN scalable process meter, green backlit display
BB212
1
8 DIN scalable process meter with red backlit display
*Specify Input : J, K,T thermocouple, P1 for 1° resolution RTD, or P2 for 0.1° resolution RTD. To order with optional 230 Vac power, add suffix “-230” to Model Number . Ordering Example: BB201K, temperature meter with type K thermocouple input, green
backlit display and 115 Vac,
BB19 Specifications
DC Input Types and Ranges 200 mV dc & 2 Vdc: BB19-DV1,-DV2
Accuracy: ±(.1% + 1 count) typical;
±(.2% + 1 count) max. Input Resistance:100 M
Overload Protection:
200 V continuous, 300 V intermittent
20 Vdc & 200 Vdc: BB19-DV3,-DV4
Accuracy: ±(.1% + 1 count) typical;
±(.2% + 1 count) max.
Input Resistance: 1 M Overload Protection:
350 V continuous, 500 V intermittent
dc Current: BB19-DC
Accuracy: ±(.1% + 1 count) typical;
±(.2% + 1 count) max. Input Resistance: 200 mV drop full
scale
Overload Protection:
3 times f.s.current
AC Input Types and Ranges ac Voltage: BB19-AV1, -AV2
Accuracy: ±(0.5% + 1 count) Input Resistance: 1 M Overload Protection:
350 V continuous, 500 V intermittent
5 A ac Current: BB19-AC1
Accuracy: ±(0.5% + 1 count) Input Resistance: Current
transformer Overload Protection: 3 times f.s. current
50 A ac Current: BB19-AC2
Accuracy: ±(0.5% + 5 counts) Input Resistance: Current
transformer Overload Protection: 3 times f.s. current
Frequency Input Types and Ranges 40 to 440 Hz: BB19-F1
Accuracy: ±1 Hz
40.0 to 199.9 Hz: BB19-F2 Accuracy: ±.2 Hz (40 to 70 Hz),
±.5 Hz (above 70 Hz)
Distortion: ≤0.1 Hz for up to 20% third harmonic distortion
Power Options 115 V +10%,-15%: 50 to 400 Hz at 2 VA 230 V +10%,-15%: 50 to 400 Hz at 2 VA 12 to 24 Vdc: 150 mA Common Mode Rejection:
dc powered, which is 80 db 50-60 Hz
Display Decimal Point:Three position,
external selection Overload: Three lower digits blank for readings greater than 1999
BB200 Series Specifications
Temperature Input:Type: J, K, T Thermocouple; BB201, BB202
100 RTD Pt 385 2- or 3-wire;
BB201, BB202 Process Input Type and Ranges
200 mVdc,2 Vdc, 10 Vdc, 20 mA:
BB211, BB212 Power Supply Options:
115 Vac or230 Vac ±10%; 50 to 400 Hz
BB200 Series Temperature Input Types and Ranges
JJ
KK
TT
RTDRTD
RTDRTD
Loading...