ul 1077 for equipment, lighting
and Control CirCuitS
UR Series
AU-3B30UR 3-pole
supplementary protector,
• DIN Rail Mounted
• 17.5 mm Width per Pole
• Thermal Magnetic,
Current Limiting
• 0.5-60A, 480 Y/277 Vac 50/60 Hz
• 10kA Short Circuit
Interrupting Capacity
• Box Clamp or Ring Tongue
Wire Connection
While UL 489 branch circuit breakers protect
feeder or branch circuits, UR Series UL 1077
supplementary protectors are made to trip
faster than a standard UL 489 circuit breaker,
therefore providing additional protection for
specific devices. Supplementary protectors
provide critical protection in applications
where branch circuit protection is not required,
or is already provided by a separate device.
These breakers are installed on the load side
of the branch circuit and are typically used to
safeguard control circuits, lighting, business
equipment, appliances and a range of
other applications.
UR Series supplementary protectors are
available in one‑, two‑, and three‑pole
configurations and up to 21 different current
ratings from 0.5A to 60A and can safely
be used in applications up to 480Y/277
Vac with a 10 kA short circuit withstand
rating (see table on next page for backup
fuse requirements). Three different trip
characteristics, including B, C and D curves,
give you the ability to configure the exact
protection scheme you require. These
supplementary protectors are DIN rail
mounted and at only 17.5 mm (0.69") wide,
they are extremely compact and help to
reduce panel size.
Accessories are field mounted on these
supplementary protectors for enhanced
control and monitoring capabilities. Field
mounting kits include all necessary parts
and instructions. Accessories can be
gang mounted on a single controller (the
auxiliary switch in the outside position). The
mounting arrangement links the internal
latch‑pins for the tripping mechanisms,
ensuring simultaneous trips. Handles are
linked to simplify manual resetting.
Accessories include neutral pole, shunt and
undervoltage trip and auxiliary contacts.
30 Amp B-trip curve.
For Terminal
Blocks and
Enclosures. Visit
omega.com/auto
Applications
B-Trip Protectors
Include business equipment, wiring
protection, lighting, appliances, control
circuits and some electronic applications.
Relatively long thermal trip delay but low
magnetic trip point.
C-Trip Protectors
Include lighting, wiring protection,
appliances, business equipment, and control
circuit applications. Relatively long thermal
trip delay and medium magnetic trip point.
D-Trip Protectors
Include control transformers, power supplies
and reactive loads. Relatively long thermal
trip delay and very high magnetic trip point.
DIN rail sold separately.
Visit omega.com/drtb-rail
One Pole: 17.5 mm (0.69")
2 Pole: 35 mm (1.38")
3 Pole: 52.5 mm (2.07")
Depth: 74.9 mm (2.95")
45
(1.77)
17.5
(0.69)
35
(1.38)
52.5
(2.07)
(0.26)
Trip-Characteristics*Applications
Characteristic Trip Boundaries
Thermal Trip
Must not
Trip>100ms
Must Trip
<1hr
B-Characteristics
1.13xRC1.45xRC3xRC5xRC
Magnetic Trip
Must not
Trip>100ms
Must Trip
at 100ms
C-Characteristics
1.13xRC1.45xRC5xRC10xRC
Lighting
Wiring
Protection
Control
Circuits
Business
Equipment
Appliances
Control
Transformers
6.5
Power
Supplies
Side view
General
Electronics
44 (1.73)
68.4 (2.69)
Reactive
Load
D-Characteristics
1.13xRC1.45xRC10xRC20xRC
The value of each characteristic is shown vertically beneath its corresponding heading.
*
Warning!
This information should only be used as a selection guide. The use of a miniature circuit Breaker/supplementary protector in an application
with a certain Trip Characteristic always requires prototype testing! It is the responsibility of the circuit design engineer to select the appropriate
miniature circuit breaker/supplementary protector for his specific application.
The following accessories can be field
mounted on the UR Series supplementary
protectors for enhanced control and
monitoring capabilities. Field mount kits
include all necessary parts and instructions.
Accessories can be gang mounted on a single
controller with the auxiliary switch on the
outside position. The mounting arrangement
links the internal latch‑pins for the tripping
mechanisms, ensuring simultaneous trips.
The handles are linked to simplify manual
resetting. Undervoltage trip units are available
in AC and DC and will come assembled and
calibrated to the protector.
AU-3B30UR 3-pole
supplementary protector,
30 Amp B-trip curve.
To Order Visit omega.com/circuit-breakers for Pricing and Details
Insert “B” for b-curve, “C” for c-curve and “D” for d-curve.
(*)
Ordering Examples: AU-1B05UR, one pole supplementry protector rated for 0.5 Amps B-trip curve.
AU-2D2UR, two pole supplementry protector rated for 2 Amps D-trip curve.