Omega Products AU-1B05UR User Manual

Supplementary CirCuit proteCtorS
ul 1077 for equipment, lighting and Control CirCuitS
UR Series
AU-3B30UR 3-pole
supplementary protector,
DIN Rail Mounted
17.5 mm Width per Pole
Current Limiting
0.5-60A, 480 Y/277 Vac 50/60 Hz
10kA Short Circuit
Interrupting Capacity
Box Clamp or Ring Tongue
Wire Connection
While UL 489 branch circuit breakers protect feeder or branch circuits, UR Series UL 1077 supplementary protectors are made to trip faster than a standard UL 489 circuit breaker, therefore providing additional protection for specific devices. Supplementary protectors provide critical protection in applications where branch circuit protection is not required, or is already provided by a separate device. These breakers are installed on the load side of the branch circuit and are typically used to safeguard control circuits, lighting, business equipment, appliances and a range of other applications.
UR Series supplementary protectors are available in one‑, two‑, and three‑pole configurations and up to 21 different current ratings from 0.5A to 60A and can safely be used in applications up to 480Y/277 Vac with a 10 kA short circuit withstand rating (see table on next page for backup fuse requirements). Three different trip characteristics, including B, C and D curves, give you the ability to configure the exact protection scheme you require. These supplementary protectors are DIN rail mounted and at only 17.5 mm (0.69") wide, they are extremely compact and help to reduce panel size.
Accessories are field mounted on these supplementary protectors for enhanced control and monitoring capabilities. Field mounting kits include all necessary parts and instructions. Accessories can be gang mounted on a single controller (the auxiliary switch in the outside position). The mounting arrangement links the internal latch‑pins for the tripping mechanisms, ensuring simultaneous trips. Handles are linked to simplify manual resetting. Accessories include neutral pole, shunt and undervoltage trip and auxiliary contacts.
30 Amp B-trip curve.
For Terminal
Blocks and Enclosures. Visit omega.com/auto
Applications
B-Trip Protectors
Include business equipment, wiring protection, lighting, appliances, control circuits and some electronic applications. Relatively long thermal trip delay but low magnetic trip point.
C-Trip Protectors
Include lighting, wiring protection, appliances, business equipment, and control circuit applications. Relatively long thermal trip delay and medium magnetic trip point.
D-Trip Protectors
Include control transformers, power supplies and reactive loads. Relatively long thermal trip delay and very high magnetic trip point.
DIN rail sold separately. Visit omega.com/drtb-rail
AU-1B10UR 1-pole supplementary protector, 10Amp B-trip curve.
1
SPECIFICATIONS
3 Pole
35
(1.38)
74.7
(2.94)
93.3
(3.67)
52.5
(2.07)
2 Pole 3 Pole
35
(1.38)
74.7
(2.94)
35
(1.38)
93.3
(3.67)
52.5
(2.07)
68.4 (2.69)
6.5 44 (1.73)
45
(1.77)
Voltage Rating: 480Y/277 Vac Short Circuit Withstand Rating
(UL - Ratings):
0.5-6A (RC): 10kA with no back‑up fuse 8-60A (RC): 10kA with UL‑listed Class J
back‑up fuse; 5kA with no back‑up fuse
Calibration Temperature: 30°C (86°F) Operating Temperature: ‑25 to 55°C
(‑13 to 131°F) Storage Temperature: ‑40 to 70°C
(‑40 to 158°F)
Dimensions: mm (inch)
1 Pole
89.3
(3.52)
2 Pole
SHORT CIRCUIT WITHSTAND RATINGS FOR SUPPLEMENTRY PROTECTORS
UL-Listed Class J FUSE NO BACKUP TRIP CURVE Amp RANGE UP TO 10 kA FUSE REQUIRED
All 0.5 to 10 A 70 A 10kA All 12 to 60 A 4x RC
Up to rated current.
*
Terminal Size Acceptability: Top: 18‑3 AWG
Bottom: 18‑2 AWG Tightening Torque: 25 lb‑in. (2.8 Nm) Terminal Protection Degree: IP20 Vibration Resistance: >15 g (18 to 50 Hz) Mechanical Life: 6000 on/off cycles
3 Pole
BACKUP PROTECTION
* 5kA
Electrical Life: 10,000 on/off cycles Dimensions:
Height: 89.3 mm (3.52") Width:
One Pole: 17.5 mm (0.69") 2 Pole: 35 mm (1.38") 3 Pole: 52.5 mm (2.07")
Depth: 74.9 mm (2.95")
45
(1.77)
17.5
(0.69)
35
(1.38)
52.5
(2.07)
(0.26)
Trip-Characteristics* Applications
Characteristic Trip Boundaries
Thermal Trip
Must not
Trip>100ms
Must Trip
<1hr
B-Characteristics
1.13xRC1.45xRC 3xRC 5xRC
Magnetic Trip
Must not
Trip>100ms
Must Trip
at 100ms
C-Characteristics
1.13xRC1.45xRC 5xRC 10xRC
Lighting
Wiring
Protection
Control
Circuits
Business
Equipment
Appliances
Control
Transformers
6.5
Power
Supplies
Side view
General
Electronics
44 (1.73)
68.4 (2.69)
Reactive
Load
D-Characteristics
1.13xRC1.45xRC 10xRC 20xRC
The value of each characteristic is shown vertically beneath its corresponding heading.
*
Warning!
This information should only be used as a selection guide. The use of a miniature circuit Breaker/supplementary protector in an application with a certain Trip Characteristic always requires prototype testing! It is the responsibility of the circuit design engineer to select the appropriate miniature circuit breaker/supplementary protector for his specific application.