HIGH TEMPERATURE
L
B
C
M
D
A
H
E
4"
Airflow
Direction
DimensionsTypical Installation
Air
Air
Duct opening is
Hairpin elements
K
AIR DUCT HEATERS
ADH and ADHT Series
Starts at
$
1050
⻬ Series ADH Outlet
Air Temperatures
to 426°C (800°F)
⻬ Series ADHT Outlet
Air Temperatures
to 648°C (1200°F)
⻬ 5 to 270 kW
⻬ 480V, 3 Phase
⻬ 0.475" Dia. Tubular
Elements
APPLICATIONS
Heating air for various drying/
curing operations up to 648°C
(1200°F) air temperature, heat
treating, re-heating or
dehumidification, and other
similar air heating applications.
FEATURES
Rugged construction. Sturdy 0.475"
diameter tubular elements mounted
to a heavy
Terminal housing made of 18 gage
aluminized steel. Element support
plates of 16 gage aluminized steel are
held in place by stainless steel support
rods. High temperature units have the
To Order
1
⁄4 or 3⁄8" thick steel flange.
(Specify Model Number)
ADH-005/480V/3P, $1050
shown smaller than actual size
additional feature of stainless steel
material for the 3" insulation housing
and element support plate—all of which
provides superior rigidity, strength and
reliability.
MOST POPULAR MODELS HIGHLIGHTED!
3-1⁄2"
J
Long life metal sheath tubular
elements—Corrosion/oxidation
resistant sheath. High grade
Incoloy sheath material for excellent
corrosion/oxidation resistance at high
operating temperatures.
ADH-Low-Medium Temperature (30 W/in2)
kW ABCDEHKLMElem. Circ. Model No. Price lbs
100 435⁄8 203⁄8 281⁄4 423⁄8 53⁄8 31⁄2 111⁄8 91⁄2 60 5 ADH-100/480V/3P 6350 175
162 395⁄8 35 427⁄8 383⁄8 47⁄8 31⁄2 111⁄8 91⁄2 54 6 ADH-162/480V/3P 9800 185
216 275⁄8 35 427⁄8 263⁄8 41⁄2 37⁄8 20 183⁄8 72 6 ADH-216F/480V/3P 15,950 240
270 335⁄8 35 427⁄8 323⁄8 51⁄2 37⁄8 20 183⁄8 90 8 ADH-270F/480V/3P 19,200 300
Ordering Example: ADH-035/480V/3P, 21-element, 3-phase, 480V high temperature air duct heater, $3250.
Refer to J-5 for application data.
Dimensions - Inches
555⁄8 201⁄8 281⁄8 4
10 75⁄8 203⁄8 281⁄8 6
15 9
20 115⁄8 203⁄8 281⁄8 101⁄4 23⁄4 31⁄2 111⁄8 91⁄2 12 1 ADH-020/480V/3P 1900 35
25 135⁄8 203⁄8 281⁄8 121⁄4 31⁄4 31⁄2 111⁄8 91⁄2 15 1 ADH-025/480V/3P 2300 40
30 15
35 175⁄8 203⁄8 281⁄4 163⁄8 41⁄4 31⁄2 111⁄8 91⁄2 21 1 ADH-035/480V/3P 3250 65
40 195⁄8 203⁄8 281⁄4 183⁄8 43⁄4 31⁄2 111⁄8 91⁄2 24 2 ADH-040/480V/3P 3700 70
45 215⁄8 203⁄8 281⁄4 203⁄8 51⁄4 31⁄2 111⁄8 91⁄2 27 2 ADH-045/480V/3P 4158 80
50 235⁄8 203⁄8 281⁄4 203⁄8 53⁄4 31⁄2 111⁄8 91⁄2 30 2 ADH-050/480V/3P 4550 90
60 275⁄8 203⁄8 281⁄4 263⁄8 41⁄2 31⁄2 111⁄8 91⁄2 36 2 ADH-060/480V/3P 5100 105
5
⁄8 203⁄8 281⁄8 8
5
⁄8 203⁄8 281⁄4 143⁄8 33⁄4 31⁄2 111⁄8 91⁄2 18 1 ADH-030/480V/3P 2750 55
1
⁄4 21⁄2 31⁄2 111⁄8 91⁄2 31ADH-005/480V/3P $1050 8
1
⁄4 31⁄2 31⁄2 111⁄8 91⁄2 61ADH-010/480V/3P 1250 15
1
⁄4 33
1
⁄2 111⁄8 91⁄2 91ADH-015/480V/3P 1450 25
No. No. Wt.
J-3
L
B
C
M
D
A
H
E
4"
3-1/2"
3-5/8"
Airflow
Direction
DimensionsTypical Installation
Air
Air
Sheet Metal
Duct
Thermocouple
Terminal Box
Insulated
Standoff
Collar
Insulation
(3" max.)
Low watt density resistor wire. Watt
density on the heating coil is designed
for low watt density operation by
increasing the coil diameter, gage
and length of resistance wire to give
maximum surface area and low
operating coil surface temperature—
providing longer coil life.
Easy element replacement. Individual
elements are mechanically fastened to
the flange permitting convenient, easy
replacement.
Low wiring compartment
temperatures. Made possible by the
addition of a one-inch thick blanket of
insulation in the terminal box—allows
use of low temperature field wiring
instead of expensive high temperature
busbars and wire. High temperature
units include additional three inches
of insulation to help reduce duct heat
losses.
Easy access to simplified field
wiring terminals. Terminal housing
is completely removable for maximum
access to field wiring terminals.
Individual terminal blocks with threaded
stud type terminals are provided for
each circuit to permit quick positive
attachment of circuit wiring conductors.
Dirt/dust resistant terminal housing.
Terminal housing made of solid heavy
gauge aluminized steel rather than
perforated metal to resist dirt and
dust accumulation on the electrical
connections and thus provide longer
service life.
Flange mounting gasket. Packed
separately with each duct heater to
ADHT-005/480V/3P, $1463
shown smaller than actual size
minimize leakage between the
flange and air duct.
MOST POPULAR MODELS HIGHLIGHTED!
To Order
ADHT-High Temperature (20 W/in2)
kW ABCDEHKLMElem. Circ. Model No. Price lbs
555⁄8 201⁄8 281⁄8 4
10 75⁄8 203⁄8 281⁄8 6
15 95⁄8 203⁄8 281⁄8 8
20 115⁄8 203⁄8 281⁄8 101⁄4 23⁄4 31⁄2 111⁄8 91⁄2 12 1 ADHT-020/480V/3P 2350 40
25 135⁄8 203⁄8 281⁄8 121⁄4 31⁄4 31⁄2 111⁄8 91⁄2 15 1 ADHT-025/480V/3P 2650 50
30 155⁄8 203⁄8 281⁄4 143⁄8 33⁄4 31⁄2 111⁄8 91⁄2 18 1 ADHT-030/480V/3P 3150 65
35 175⁄8 203⁄8 281⁄4 163⁄8 41⁄4 31⁄2 111⁄8 91⁄2 21 1 ADHT-035/480V/3P 3800 80
40 195⁄8 203⁄8 281⁄4 183⁄8 43⁄4 31⁄2 111⁄8 91⁄2 24 2 ADHT-040/480V/3P 4300 90
45 215⁄8 203⁄8 281⁄4 203⁄8 51⁄4 31⁄2 111⁄8 91⁄2 27 2 ADHT-045/480V/3P 4850 100
50 235⁄8 203⁄8 281⁄4 223⁄8 53⁄4 31⁄2 111⁄8 91⁄2 30 2 ADHT-050/480V/3P 5300 110
60 275⁄8 203⁄8 281⁄4 263⁄8 41⁄2 31⁄2 111⁄8 91⁄2 36 2 ADHT-060/480V/3P 5900 130
80 355⁄8 203⁄8 281⁄4 343⁄8 43⁄8 31⁄2 111⁄8 91⁄2 48 4 ADHT-080/480V/3P 6700 175
90 395⁄8 203⁄8 281⁄4 383⁄8 47⁄8 31⁄2 111⁄8 91⁄2 54 5 ADHT-090/480V/3P 7050 200
100 435⁄8 203⁄8 281⁄4 423⁄8 53⁄8 31⁄2 111⁄8 91⁄2 60 5 ADHT-100/480V/3P 7400 220
120 275⁄8 35 427⁄8 263⁄8 41⁄2 31⁄2 111⁄8 91⁄2 36 4 ADHT-120/480V/3P 9350 205
160 355⁄8 35 427⁄8 343⁄8 43⁄8 31⁄2 111⁄8 91⁄2 48 8 ADHT-160/480V/3P 11250 270
180 395⁄8 35 427⁄8 383⁄8 47⁄8 31⁄2 111⁄8 91⁄2 54 6 ADHT-180/480V/3P 12300 305
240 275⁄8 35 427⁄8 263⁄8 41⁄2 37⁄8 20 183⁄8 72 8 ADHT-240F/480V/3P 20000 400
Ordering Example: ADHT-020/480V/3P is a 12-element, 3-phase, 480V high temperature air duct heater, $2350.
Refer to J-5 for application data. All ADHT models come with K type overtemp thermocouple.
(Specify Model Number)
Dimensions - Inches
1
⁄4 21⁄2 31⁄2 111⁄8 91⁄2 31ADHT-005/480V/3P $1650 10
1
⁄4 31⁄2 31⁄2 111⁄8 91⁄2 61ADHT-010/480V/3P 1800 20
1
⁄4 33
No. No. Wt.
1
⁄2 111⁄8 91⁄2 91ADHT-015/480V/3P 1950 30
J-4