OMEGAFLEX TracPipe FLEXIBLE GAS PIPING Installation Manual

FLEXIBLE GAS PIPING
FLEXIBLE GAS PIPING
DESIGN GUIDE
DESIGN GUIDE
and
and
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
December 2005
December 2005
®
RESIDENTIAL • COMMERCIAL • INDUSTRIAL
RESIDENTIAL • COMMERCIAL • INDUSTRIAL
FGP-001, Rev. 12-05
TABLE OF CONTENTS
Chapter 1 Introduction
1.0 User Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1 Listing of Applicable Codes and Standards . . . . . . . . . . . . . . . . . . . . . . 4
TracPipe Specification Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 2 Description of System and Components
2.0 Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Pressure Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Shut-off Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.1 Material Use and Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TracPipe Flexible Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
AutoFlare Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TracPipe Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 3 System Configurations and Sizing
3.1 System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1A Series and Parallel Low-pressure Systems . . . . . . . . . . . . . . . . . . . . . 13
3.1B Dual Presure Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.1C System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.1D System Pressure Choices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Sizing Methods and Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2A Use of Sizing Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2B Sizing Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Low-pressure Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Elevated Pressure Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Medium Pressure Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2C Sizing Hybrid Systems (Combination Steel/TracPipe Systems) . . . . . . 19
3.2D Alternate Sizing Method (Sum of Pressure Loss Calculations) . . . . . . . 21
3.3 Gasbreaker Excess Flow Devices for CSST and
Steel Pipe Gas Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.4 Sizing Instructions for Gasbreaker Devices Used with
CSST/TracPipe Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4A Meter Devices (Series GB-300, GB-400, GB-600) . . . . . . . . . . . . . . . . 26
3.4B Appliance Devices (Series GB-090, GB-120, GB-150) . . . . . . . . . . . . . 26
3.4C Sizing Instructions for Gasbreaker Devices with Steel Pipe Systems . . . . . 26
Chapter 4 Installation Practices
4.1 General Installation Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Minimum Bend Radius . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Debris Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Support- Vertical Runs/ Horizontal Runs . . . . . . . . . . . . . . . . . . . . . . . 32
4.2 Fitting Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Tubing Cutting/End Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Assembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Minimum Tightening Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Re-assembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.2A Trouble Shooting Fitting Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.3 Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Clearance Holes and Notching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.3A Concealed Locations for Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.3B Outdoor Installation Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.4 Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1
4.4A Striker Plate Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Spiral Metal Hose Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Thru-penetration Fire Stop UL Classifications . . . . . . . . . . . . . . . . . . . 40
4.5 Meter Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Termination Mounts/Meter Mounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.6 Appliance Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.6.1 Moveable Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Termination Fittings with Appliance Connectors . . . . . . . . . . . . . . . . . . 42
4.6.2 Fixed Appliance Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.6A Pad Mounted, Roof Top Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.6B Outdoor Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.6C Fireplace Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.7 Manifold Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Allowable Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.8 Pressure Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Vent Limiter Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Vent Line and Sizing Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.8A Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.8B Regulator Capacity and Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.8C Over-Pressurization Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.9 Underground Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.9A Guidelines for Underground Installations . . . . . . . . . . . . . . . . . . . . . . . 52
4.9B TracPipe PS Fitting Attachment Instructions . . . . . . . . . . . . . . . . . . . . 54
4.9C Underground PS with Flexible Poly Tubing . . . . . . . . . . . . . . . . . . . . . . 55
4.9D TracPipe PS-II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.9E TracPipe PS-II Fitting Attachment Instructions . . . . . . . . . . . . . . . . . . . 58
4.10 Electrical Bonding/Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4.10A TracPipe CounterStrike CSST Installations . . . . . . . . . . . . . . . . . . . . . 61
Chapter 5 Inspection Repair and Replacement
5.1 Minimum Inspection Requirements (Checklist) . . . . . . . . . . . . . . . . . . . 63
5.2 Repair/Replacement of Damaged Tubing . . . . . . . . . . . . . . . . . . . . . . . . 64
Chapter 6 Pressure/Leakage Testing
6.0 Pressure Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.1 Pressure Test for Elevated Pressure Systems . . . . . . . . . . . . . . . . . . . . . 65
6.1A Appliance Connection Leakage Check Procedure . . . . . . . . . . . . . . . . . 66
6.1B Regulator Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Chapter 7 Capacity Tables
7 in / 0.5 in WC Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8 in / 2 in WC Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
11 in / 5 in WC Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2 PSI / 1 PSI Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5 PSI / 3.5 PSI Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11 in / 0.5 in WC Drop (LP only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
12-14 in / 2.5 in Drop (LP only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
2 PSI / 1.5 PSI Drop (LP only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.1 Table PD.1 Pressure Drop per foot for TracPipe (Natural Gas) . . . . . . 75
7.2 Steel Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
7.2A Pressure Drop per 100 foot of Steel Pipe . . . . . . . . . . . . . . . . . . . . . . . . . 81
Chapter 8
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Appendix A UL Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Appendix B Manufactured Housing Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
2
CHAPTER 1
INTRODUCTION
!
WARNINGS
SECTION 1.0 — USER WARNINGS
The TracPipe®gas piping material (CSST­Corrugated Stainless Steel Tubing ) must only be installed by a qualified person who has been trained or otherwise qualified through the TracPipe Gas Piping Installation Program. Any installer must also
meet qualifications in accordance with state and/or local requirements as established by the administrative authority which enforces the plumbing or mechanical code where the gas piping is installed. This document provides general instructions for the design and installation of fuel gas piping systems using gas piping material CSST . The guide must be used in conjunction with state and local building codes. Local codes will take precedence in
the event of a conflict between this guide and the local code. In the absence of local
codes, installation must be in accordance with the current edition of National Fuel Gas Code, ANSI
Sound engineering principles and practices must be exercised for the proper design of fuel gas piping systems, in addition to com­pliance with local codes. The installation instructions and procedures contained in this Design Guide must be strictly followed in order to provide a safe and effective fuel gas piping system or system modification. All installations must pass customary inspections by the local official having authority prior to having the gas service turned on. All require­ments of the local natural gas utility or propane supplier must also be met. Only the components provided or specified by OMEGAFLEX as part of the approved piping system are to be used in the installa­tion.
The use of
TracPipe tubing or fittings
with tubing or fittings from other flexi­ble gas piping manufacturers is strict­ly prohibited and may result in serious bodily injury or property damage.
Z223.1/NFP A 54, the National Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1, the International Fuel Gas Code, the Federal Manufactured Home Construction and Safety Standards, ICC/ANSI 2.0 or the Standard on Manufactured Housing, NFPA 501, as applicable
S
I
F
S
I
E
A
D
L
C
U
L
OMEGAFLEX
®
451 Creamery Way Exton, PA 19341-2509 610-524-7272 Fax: 610-524-7282
WARNING !
If this system is used or installed improperly, fire, explosion or asphyxiation may result. The installation instructions and applicable local codes must be strictly followed.
1-800-671-8622 www.omegaflex.com
© Copyright OmegaFlex Inc. 1997, 1998, 2001, 2002,
2003, 2004, 2005
3
SECTION 1.1 — APPLICABLE CODES AND STANDARDS
REGIONAL /MODEL CODES LISTING CSST AS AN ACCEPTABLE GAS PIPING MATERIAL AS OF JULY 2005:
a. ANSI/IAS LC-1 b. CANADA-CSA B149.1 Natural Gas
and Propane Installation Code
c. NFPA 54/ANSI Z 223.1 National Fuel
Gas Code d. ICBO-Uniform Mechanical Code e. BOCA-National Mechanical Code f. CABO-1 and 2 Family Dwelling Code g. SBCCI-Standard Gas Code h. ICC-International Mechanical Code i. IAPMO Listing FILE 3682 j. IAPMO Listing FILE 4665 TracPipe
PS-II
CSA 6.26 Standard
k. ICBO Evaluation Services ER-5412. l. Factory Mutual “Flexible Piping
Systems for Flammable Gases.”
m. California Mechanical and Plumbing
Codes n. ICC-International Fuel Gas Code o. NFPA 58 LP-Gas Code p. UPC-Uniform Plumbing Code 2003 q. UL Through Penetration Firestop
Systems Classified (see Appendix A) r. Tested to Code Requirements per
ASTM E84 (UL 723)
This Design and Installation Guide has been written in accordance with the most current edition of ANSI LC1 CSA 6.26, Fuel Gas Piping Systems using Corrugated Stainless Steel Tubing (CSST).
WHILE EVERY EFFORT HAS BEEN MADE TO PREPARE THIS DOCUMENT IN ACCORDANCE WITH THE REGIONAL MODEL CODES IN EFFECT AT ITS PRINTING, OMEGAFLEX CANNOT GUARANTEE THAT THE LOCAL ADMIN­ISTRATIVE AUTHORITY WILL ACCEPT THE MOST RECENT VERSION OF THESE CODES. THE INSTALLER IS ULTIMATELY RESPONSIBLE TO DETERMINE SUITABILITY AND ACCEPTANCE OF ANY BUILDING COMPONENT, INCLUDING GAS PIPING. OMEGAFLEX ASSUMES NO RESPONSIBILITY FOR MATERIALS OR LABOR FOR INSTALLATIONS MADE WITHOUT PRIOR DETERMINATION OF LOCAL CODE AUTHORITY ACCEPTANCE.
4
TracPipe
®
SPECIFICATION DATA SHEET
FGP-SS4-CHART
TracPipe®part no.
FGP-SS4-375 FGP-SS4-500 FGP-SS4-750 FGP-SS4-1000 FGP-SS4-1250 FGP-SS4-1500 FGP-SS4-2000
Size (inch) 3/8" 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" EHD (AGA size) 15 19 25 31 37 46 62 Jacket O.D. (max.) .668 .868 1.108 1.383 1.665 1.920 2.590 Inside Diameter (nom) .440 .597 .820 1.040 1.290 1.525 2.060 Wall Thickness (in.) .01 .01 .01 .01 .012 .012 .012
*EHD (Effective Hydraulic Diameter) A relative measure of Flow Capacity; This number is used to compare individual sizes between different manufacturers. The higher the EHD number the greater flow capacity of the piping.
STRAIGHT AUTO-FLARE FITTINGS
1. ADAPTER – Brass
2. INSERT – Stainless Steel
3. NUT—Brass
4. SPLIT-RINGS – Brass or Stainless Steel
5. FLEXIBLE PIPE – Stainless Steel
Tube size 3/8" 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" NPT Thread 1/2"or 3/8" 1/2"or 3/4" 3/4"or 1/2" 1"or 3/4" 1-1/4" 1-1/2" 2"
AVAILABLE IN SIZES
FLANGE MOUNT AUTO-FLARE FITTINGS
1. ADAPTER – Brass
2. INSERT – Stainless Steel
3. FLANGE NUT – Brass
4. SPLIT-RINGS – Brass or Stainless Steel
5. FLANGE – Malleable Iron/Brass
6. FLEXIBLE PIPE – Stainless Steel
CONSULT FACTORY FOR OTHER TERMINATION METHODS
5
AVAILABLE IN SIZES
Tube Size 3/8" 1/2" 3/4" 1" 1-1/4" NPT Thread 1/2"or 3/8" 1/2" 3/4" 1" 1-1/4"
CHAPTER 2
DESCRIPTION of SYSTEM and COMPONENTS
SECTION 2.0 TracPipe FLEXIBLE GAS PIPING MATERIAL DESCRIPTION
1. TUBING
The TracPipe fuel gas piping system con- sists of corrugated, semi-rigid stainless steel tubing with brass mechanical attach­ment fittings terminating in NPT pipe fit­tings for easy attachment to traditional black iron pipe systems and direct connec­tions to gas appliances. Tubing is available in sizes 3/8 inch, 1/2 inch 3/4 inch, 1 inch, 1-1/4 inch, 1-1/2 inch,and 2 inch. The 300 series stainless steel tubing is jack­eted, with a non-metallic cover which pro­vides ease of running through joists, studs, and other building components. The jacket is marked at one foot intervals with the amount of tubing left on the reel, for quick measure­ment.
2. FITTINGS
Straight NPT pipe fittings are standard and are available in sizes shown above to fit all tubing. Additional fittings include termination mount and flange-mount straight and 90 degree elbow fittings for termination of gas lines near movable appliances; and meter termination accessories for support of TracPipe at utility meter sets on building exteriors and roof pen­etrations. Tee fittings are available for addi­tion of branch lines into tubing runs; reducer tees are available in popular sizes and pipe outlet tees terminate in pipe threads on the outlet leg for size changes utilizing available black iron reducer fittings.
3. ACCESSORIES
Accessories are available for expansion of the flexible piping material and additions to existing fuel gas piping systems. These accessories include:
A. Manifolds — allow parallel installations
with “home runs” to each appliance. 1/2 inch female NPT outlets and 3/4 inch
and 1/2 inch female NPT inlets. Large size manifolds are also available for use with commercial size TracPipe.
B. Pressure Regulators: pounds to inches -
for use in elevated pressure system installations (over 14 inches water column
- one half psi) to reduce pressure to stan­dard low pressure for appli­ances. Available regulators include 1/2 and 3/4 inch sizes for natural and propane use and 1-1/4 inch size for natural gas. Regulators include approved vent limiters except 1-1/4" size.
C. Protection Devices-for use where flexible
piping passes through studs, joists and other building materials and is restricted from moving to avoid nails, screws and other punc­ture threats.
6
There are four striker plate configura­tions made from stamped steel and specially hardened to resist penetration from screws and pneumatic nail guns. These are quarter-striker, half striker full­striker and 6" X 17" flat plate striker. Spiral wound galvanized steel “floppy” conduit is available for use as additional protection.
Some of the special usage features of TracPipe gas piping are outlined below:
1. Flexible gas piping is used to provide safe, efficient, timely installation of fuel gas pip­ing within buildings, residential, commer­cial, and industrial, or for outdoor connec­tions to appliances that are attached or in close proximity to the building.
D. Shut-off Valves-for use in elevated pres-
sure installations: 2 psi up to 5 psi. (Standard gas-cocks should be used at appli­ance stub outs and other low pressure areas of the piping sys­tem.) Brass lever-handle ball valves supplied by OmegaFlex are rated for 5 psi use and are available in 1/2 inch and 3/4 inch sizes.
SECTION 2.1 — MATERIAL USE AND LIMITATIONS
This Design and Installation Guide has been written in accordance with the most current edition of ANSI LC 1 CSA 6.26,
FUEL GAS PIPING SYSTEMS USING COR­RUGATED STAINLESS STEEL TUBING (CSST).
This Design Guide is intended to aid the pro­fessional gas pipe installer in the design, installation and testing of flexible fuel gas pip­ing systems for residential, commercial and industrial buildings. It is not possible for this guide to anticipate every variation in con­struction style, building configuration, appli­ance requirement, or local restriction. This document will not therefore cover every appli­cation. The user should either exercise his own engineering judgment on system design and installation, or seek technical input from other qualified sources. Additional informa­tion pertaining to gas piping systems is avail­able from your local gas utility or propane supplier.
2. Flexible gas piping can be routed in most locations where traditional gas piping materials are installed: inside hollow wall cavities, along or through floor joists in basements, on top of the joists in attics, on roof tops or along soffits or in chases outside of buildings. TracPipe gas piping has been tested and is listed by CSA International for both outdoor and indoor use.
3. TracPipe is listed by CSA International
for fuel gas use in the USA and Canada for pressures up to 25 psi. For local gas utility approved use only, TracPipe has been tested for use up to 125 PSI for sizes 3/8" up to 1-1/4", and for use up to 25 psi for sizes 1-1/2" and 2".
4. In North America, the most common pres­sure for Natural Gas is 6-7 inches water column, standard low pressure. Elevated pressures of either 2 psi or one half psi are also available from utilities in most areas for new residential construction. 5 PSI systems are commonly installed in com­mercial or industrial buildings. Elevated pressures allow the use of smaller diame­ter piping, while providing for increased loads and longer length runs.
5. Flexible gas piping can be used for Natural gas and propane (Liquefied Petroleum gas) and other fuel gases rec­ognized in NFPA 54 National Fuel Gas Code.
6. TracPipe CSST with the yellow polyethyl-
ene jacket has been tested by Underwriters Laboratory to UL723 (ASTM E84) Surface Burning Characteristics with flame spread and smoke density ratings meeting the
7
requirements of ANSI/CSA LC-1 for use in air ducts and plenums. It is mandatory, however, to follow fire and building code requirements in all installations. CounterStrike with black jacket requires removal of the jacket for use in air ducts or plenums.
7. For underground or under slab burial the flexible gas piping run must be encased in a sleeve of polyethylene, or other approved water resistant material. See Section 4.9, Underground Installations. Sleeved runs under concrete slabs beneath buildings must be installed as required by local codes. Most codes require venting of the sleeves under build­ings to the outdoors. This can be accom­plished using Pre-sleeved TracPipe PS or PS-II with available accessories.
this use when the appliance is free to move for cleaning, etc.
®
11. TracPipe AutoFlare
fittings have been tested by CSA International (formerly the American Gas Association Laboratories ) and are listed for use in concealed loca­tions as defined in NFPA 54 National Fuel Gas Code, The Uniform Plumbing Code, and The International Fuel Gas Code. This facilitates installation of the key valves required for gas fireplaces in many jurisdictions. Concealed fittings are also desirable when adding tees for branch runs in series configurations and in other installation situations where locating a TracPipe fitting in an accessible location is not practical.
8. Flexible gas piping can be used in con­junction with steel pipe (black iron or gal­vanized) in either new construction or ren­ovation and replacement piping installa­tions. All TracPipe fittings terminate in standard NPT male or female pipe threads to interface with appliances, valves, unions and couplings.
9. For retrofit installations, TracPipe can be snaked through hollow wall cavities with­out major restoration as is typical when running rigid pipe through existing con­struction. The replacement or addition of gas appliances, fireplaces, and gas logs is greatly facilitated with flexible piping on reels requiring no special tooling or oily threading equipment.
10.TracPipe gas piping can be run directly
to the shut off valves of most fixed appli­ances without installing an appliance connector. For moveable appliances such as ranges or dryers, the use of an approved flexible appliance connector is required in most jurisdictions. TracPipe cannot be substituted as a connector for
8
SECTION 2.2 — SYSTEM COMPONENTS
®
®
TracPipe Flexible Gas Piping
Component Material Description/Dimensions
Corrugated
TracPipe
Flexible
Gas
Piping
Stainless
Steel
(300 Series)
with
Polyethylene
Jacket
part no.
Size (inch) 3/8" 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" EHD (AGA size) 15 19 25 31 37 46 62 Jacket O.D. (max.) .668 .868 1.108 1.38 1.665 1.920 2.590 Inside Dia. (nom) .440 .597 .820 1.040 1.290 1.525 2.060
*EHD (Effective Hydraulic Diameter) A relative measure of Flow Capacity; This number is used to com­pare individual sizes between different manufacturers. The higher the EHD number the greater flow capacity of the piping.
FGP-SS4-375 FGP-SS4-500 FGP-SS4-750 FGP-SS4-1000 FGP-SS4-1250 FGP-SS4-1500 FGP-SS4-2000
TracPipe
on
Reels
Plywood
Reels
for
packaging
Note: other reel lengths available upon request.
Weight
Pipe Size Standard Reel Length
3/8 inch 250 feet 100 feet 29 pounds 1/2 inch 87 pounds
3/4 inch 55 pounds
1 inch 180 feet 60 pounds
1-1/4 inch 115 pounds
1-1/2 inch 125 pounds
2 inch 150 feet 92 pounds
500 feet 250 feet
100 feet 50 feet
250 feet 100 feet
180 feet 100 feet
250 feet 150 feet
250 feet 150 feet
Long Reel
9
AutoFlare®Fittings
Component Material Description/Dimensions
PS PS-II
TracPipe PS
&
PS-II
Accessories
Black
Polyethylene
Sleeved
TracPipe
Vent Tee
Heat Shrink Cuff
Vent Nut Split Adaptor
Coupling Rings
Straight
Mechanical
Fitting
Reducer
Fitting
Termination
and Flange
Mount
Fittings
Straight
and 90 Elbow
Meter
Termination
Fitting
Stud
Bracket
Brass
Fitting
Autoflare
Insert
Brass
Fitting
Autoflare
Insert
Malleable
Iron or Brass
Flange
Brass Fitting
Autoflare
Insert
Galv. steel
Mounting
Bracket
Sizes: 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2
and 2 inch Note size 3/8 fitting has either 1/2" NPT or 3/8"
NPT Thread
Sizes: 3/8, 1/2, 3/4, 1 inch
and 1-1/4 inches
Note size 3/8 fitting has either
1/2" NPTor 3/8" NPT Thread
Elbow Sizes: 3/8 in. and 1/2 in.
Flange
Mounting
Bracket
Tee
Fitting
&
Coupling
Galv. Steel
Brass Tee
Fitting
& Coupling
Autoflare
Insert
One size fits all:
Size
3/8 through 1-1/4 inches
Sizes: 3/8, 1/2, 3/4 and 1 inch
Reducer tees available for 1/2, 3/4 and 1 inch sizes
10
TracPipe Accessories
Component Material Description/Dimensions
Load
Center
Manifold
Bracket
Multi-
Port
Manifolds
Painted Steel
Galvanized
Steel
Malleable
Iron
Poly Coated
Pressure
Regulators
Shut
Off
Valves
Cast Housing Suitable
for
Outdoor
Use
Brass
Housing
with
Stainless
Steel
Ball
Sizes: 1/2 inch & 3/4 inch & 1-1/4 inch
Regulator includes approved vent lim-
iting device for REG 3 (1/2 in.) and
REG 5A (3/4 in.).
Note: Stainless steel High Pressure tags
are available for use where required by
code
Sizes: 1/2 inch & 3/4 inch
11
TracPipe Accessories
Component Material Description/Dimensions
Full
Striker
Plate
Half
Striker
Plate
Quarter
Striker
Plate
Carbon
Steel
Hardened
size: 3" x 12"
Carbon
Steel
Hardened
size: 3" x 7"
Carbon
Steel
Hardened
size: 3" x 2"
6 x 17
Striker
Plate
Floppy
Strip
Wound
Conduit
Carbon
Steel
Hardened
size: 6" x 17"
Type RW
Galvanized
Steel
sizes: Fits 3/8", 1/2", 3/4", 1", 1-1/4", 1-1/2"
and 2" TracPipe
12
r
CHAPTER 3
SYSTEM CONFIGURATIONS AND SIZING
SECTION 3.1 — SYSTEM CONFIGURATIONS
There are several piping system options available to the installer using TracPipe gas piping material. This flexibility of design is one of the major benefits of CSST.
3.1A — LOW PRESSURE SYSTEMS
1. SERIES: A series layout is the most com­mon arrangement utilized for black iron pipe. This consists of a main run with tees branching off to each appliance.
range
50 CFH
gas meter
163 CFH
water heater
30 CFH
furnace 60 CFH
3.1B — DUAL PRESSURE SYSTEMS
Elevated pressure systems (2 psi for residen­tial and up to 5 psi for commercial installa­tions) are usually piped with one or more house line regulators (pounds-to-inches) fol­lowed by a manifold and runs to each of the appliances. It is possible that these runs to appliances may contain tees branching off to an additional appliance where gas loads per­mit.
range
55 CFH
furnace 80 CFH
E
C
dryer
D
30 CFH
B
water heater
40 CFH
gas mete
A
205 CFH
2 PSI
fireplace
18 CFH
Series Layout
2. PARALLEL: A parallel system consists of a central distribution manifold with branch runs to the appliances. This is usually accomplished by providing a main supply line to a manifold and installing “home runs” to each appliance location. In the parallel system shown below the pressure is not elevated above 1/2 pound and no regulator is required.
range
55 CFH
water heater
1/2 PSI
gas meter
205 CFH
A
dryer
30 CFH
Parallel Layout
40 CFH
C
B
D
furnace
80 CF
H
E
Dual Pressure System Layout
NOTE: HYBRID SYSTEMS – FLEXIBLE GAS PIPE and RIGID BLACK PIPE COMBINA­TIONS.
In low or medium pressure systems, it is often advantageous to use both corru­gated stainless steel tubing and rigid pipe in the same system. This is the case when a larger diameter main branch is required to provide for the total appliance load in a paral-
lel system. TracPipe is certified for use in
combination with black iron pipe and copper tube gas piping systems. For additional infor­mation on Hybrid Systems see examples showing the method for sizing hybrid systems
using both TracPipe and black iron pipe
These are included in the SIZING EXAMPLES section of this manual. Refer to Section 3.2C
13
SECTION 3.1C — SYSTEM DESIGN
1. Prepare a sketch or layout of the gas pip­ing system you are about to install. The information you will need is the location of each appliance, the point of delivery (location of utility meter or second stage LP regulator), appliance load demands, and possible pipe routing locations. The load demand data is usually available on the appliance manufacturer’s nameplate, or can be provided by the builder.
2. Determine local piping restrictions prior to installing flexible gas piping. The major code bodies in North America have written Corrugated Stainless Steel Tubing into the latest revisions of their mechanical codes, but local and state adoption of these codes often lags behind. CONFIRM THA THE LOCAL CODE AUTHORITY HAS ACCEPTED THE USE OF FLEXIBLE GAS PIPING. Your TracPipe distributor should be able to provide that information but confirmation by the installer should be made where there is a question.
SECTION 3.1D — SYSTEM PRESSURE CHOICES
1. NATURAL GAS-Determine the delivery pressure provided by the Local Distribution Utility where the piping will be installed.
ances manufactured for use in the US
and Canada are designed to operate up to a maximum of 14 inches water column.
c. ELEVATED PRESSURE-2 PSI -Is the
highest natural gas pressure usually supplied within residential buildings in North America. This pressure always requires the installation of a pounds­to-inches house line regulator between the utility meter set and the appli­ances.
2. PROPANE (LP GAS)-Is typically supplied within residential buildings at 11 inches water column, set at the second stage reg-
T
ulator mounted outside the building. Propane can also be utilized at medium­pressure, with the use of a 13-14 inch set­ting. For 2 PSI Propane elevated pressure the Maxitrol regulator used is FGP-REG­3P.(which is factory set at 11 inches water column.) A second stage regulator which reduces 10 psi from the tank to 2 psi must be used. (e.g. Fisher model R312E).
NOTE: TracPipe has been tested by CSA
International (formerly AGA Laboratories) for a working pressure of 125 PSI for sizes 3/8" through 1-1/4" and 25 PSI for sizes 1-1/2 & 2".
a. LOW PRESSURE-6 to 7 inches water
column-equivalent to 4 ounces or 1/4 pound is the standard pressure sup­plied by natural gas utilities in the USA and Canada.
b. MEDIUM PRESSURE-1/2 POUND-12
to 14 inches water column-Is available from many natural gas utilities as an enhanced pressure supply. The increase in pressure provides for reductions in
pipe size and does not require a pres­sure regulator. Most natural gas appli-
PRESSURE CONVERSION CHART
1/4 PSI = 7" w.c. = 4 oz. 1/2 PSI = 14" w.c. = 8 oz.
1 PSI = 28" w.c. = 16 oz. 2 PSI = 56" w.c. = 32 oz.
14
SECTION 3.2 SIZING METHODS and EXAMPLES
low pressure
gas meter
100 CFH
water heater
35 CFH
furnace 65 CFH
B
A
C
SECTION 3.2A — USE OF SIZING TABLES
This Chapter includes flexible gas piping siz­ing procedures for both low pressur e and ele­vated pressure systems. Every piping system introduces pressure loss to the fluid flowing within. The amount of loss depends on the piping size and the gas flow, expressed in cubic feet per hour (and converted to BTU’s). The object of the sizing exercise is to deter­mine the smallest size piping which will intro­duce the allowed pressure loss or drop with­in the length of piping required. Sizing Tables (Capacity Charts) provide the maximum flow capacity for a given length of run for each pipe size. A different sizing table is used for each system pressure and pressure drop combination.
1. The low pressure series system (standard arrangement) is sized in the same way as a conventional low pressure black iron pipe system using TracPipe sizing tables or tables found in National Fuel Gas Code NFPA 54. This method is known as the “Branch Length Method”. Pressure drop in a low pressure system is usually limited to 1/2 inch water column over the system.
This part of the system is sized the same as a low pressure system, except that a special table N-3 is used allowing 3 inches of water column drop. These lines are typ­ically sized for only one appliance load installed as a “home run” from the mani­fold.
SECTION 3.2B — SIZING EXAMPLES BRANCH LENGTH METHOD
To size each of the following systems, deter­mine the required size for each section and outlet. To size each section of the system, determine both the total gas load for all appli­ances and the maximum distance (longest length) in which a particular section delivers gas.
EXAMPLE 1 LOW PRESSURE SYSTEM SERIES ARRANGEMENT
2. Elevated pressure systems incorporate two
operating pressures downstream of the util­ity meter set. The first pressure, set by the service regulator at the meter, is usually 2 PSI. This part of the system is sized sepa­rately and ends at the pounds-to-inches reg­ulator. The allowable pressure loss for this part of the system must be added to the effect of the regulator to determine the avail­able pressure at the regulator outlet. The chart in Section 4.8B shows pressure losses for maximum loads through the regulator.
3. For a 2 PSI system, the proper drop is usu-
ally 1 PSI for this part of the system; this allows for the approximate 3/4 PSI regula­tor drop downstream and provides the 1/4 PSI (6-7 inches w.c.) necessary for appli­ances. The regulator reduces the pressure from pounds to 8 inches water column.
Figure 3-1
manifold
LENGTH OF RUNS A = 10 Feet
pressure regulator
B = 10 Feet C = 15 Feet
line shut-off
appliance shut-off
Supply pressure 6 inches w.c. Allowable drop 0.5 inches w.c.
1. The system presented in figure 3-1 is typi­cal of a single family installation in which there are a limited number of appliances located in one general area. The supply pressure is 6 inches water column and the allowable drop is 1/2 inch.
15
2. To size section A, determine the longest run from the meter that includes section A and the total gas load it must deliver:
• Meter to Furnace is 20 ft. (A+B)
parallel. The MEDIUM PRESSURE SYSTEM (1/2 PSI ) allows a higher pressure drop (6 inches Water column) than is available with low pressure systems.
• Meter to Water Heater is 25 ft. (A+C). This is the longest run.
• Determine the maximum load trans­ported by Section A
• Furnace plus Water Heater = 100 cfh (100,000 BTU)
• Select Table N-1 “Low Pressure 6 inches- 1/2 inch w.c. drop"
• Using the longest run method, select the column showing the measured length, or the next longest length if the table does not give the exact length. Referring to table N-1 the column for 25 feet of piping shows that sizes 3/8 and 1/2 are too small and the next available size is 3/4 supplying 132 cfh.
• The correct size is 3/4".
3. To size Section B, determine the length of run from the meter to the Furnace and the load delivered:
• Length is 20 ft (A+B) and load is 65 cfh (65,000 BTU)
• Table N-1 shows that size 1/2" supplies 67 cfh
• The correct size is 1/2".
4. To size Section C, determine the length of run from the meter to the Water Heater and the load delivered:
• Length is 25 ft (A+C) and load is 35 cfh (35,000 BTU)
• Table N-1 shows that size 1/2" is required, because size 3/8" only sup­plies 27 cfh (27,000 BTU)
• The correct size is 1/2"
EXAMPLE 2 MEDIUM PRESSURE 12-14 INCHES W.C. (1/2 PSI)
1. The system shown in Figure 3-2 is typical of a single family installation with several appliances. The arrangement chosen is
range
55 CFH
water heater
1/2 PSI gas meter 205 CFH
dryer
30 CFH
40 CFH
C
B
A
D
furnace 80 CF
H
E
Figure 3-2
LENGTH OF RUNS
manifold
A = 10 Feet B = 20 Feet
pressure regulator
C = 10 Feet D = 40 Feet
line shut-off
appliance shut-off
E = 10 Feet
Supply pressure 1/2 PSI (12"-14" w.c.) Allowable drop: 6" w.c.
2. To size SECTION A, determine the LONGEST RUN from the meter to the fur­thest appliance.
• Meter to dryer is 50 feet (10+40) A+D
• Determine maximum load transport­ed by section A
• Dryer + Range + Water heater + Furnace = 205 cfh ( 205,000 BTU)
• Select table N-4 “Medium Pressure 1/2 PSI with 6 inch drop“. Table N-4 shows that 1/2" size is too small for 205 cfh at 50 ft. but 3/4" can handle 315 cfh.
• The correct size is 3/4"
3. To size SECTION B, the distance from the meter to the range is 30 ft (10+20) A+B
• Load is 55 cfh ( 55,000 BTU )
• Table N-4 shows that 3/8" size can handle 90cfh
• The correct size for section B is 3/8"
4. To size SECTION C, the distance from the meter to the water heater is 20 ft (10+10) A+C
• Load is 40 cfh ( 40,000 BTU )
• Table N-4 shows that that 3/8" size
16
can handle 112cfh
r
• The correct size for section C is 3/8"
5. To size SECTION D, the distance from the meter to the dryer is 50 ft (10+40) A+D
• Load is 30 cfh ( 30,000 BTU )
• Table N-4 shows that that 3/8" size can handle 69cfh at 50 feet
• The correct size for section D is 3/8"
6. To size SECTION E, the distance from the meter to the furnace is 20 ft (10+10) A+E
• Load is 80 cfh ( 80,000 BTU )
• Table N-4 shows that that 3/8" size can handle 112cfh at 20 feet
• The correct size for section E is 3/8"
EXAMPLE 3 ELEVATED PRESSURE 2 PSI SYSTEM PARALLEL ARRANGEMENT
1. The system shown in figure 3-3 is adapted for multifamily or single family application with an extended (100 feet) tubing run from the meter to the regulator The 2 PSI system is well adapted to handle the long runs required in multifamily buildings with central­ized meter banks.
• furnace + water heater + dryer + range = 80 cfh + 40 cfh + 30 cfh + 55cfh = 205 cfh (205,000 BTUH) Select Table N-5 “Elevated Pressure 2 PSI with 1 PSI drop’’ This is the standard table chosen to stay within the Maxitrol 325-3 regula­tor capacity. See note below.
• Length is 100 ft.
• Table N-5 shows that 3/8" size is too small for 205 cfh but 1/2" can handle 222cfh.
• The correct size is 1/2"
3. To size each of the other sections: Select Table N-3 “ Regulator Outlet 8.0
inches w.c with a dr op of 3.0 inches w.c
• Section B is 15 feet with a 40 cfh load
3/8" has a capacity of 90 cfh
• Section C is 10 feet with a 80 cfh load
3/8" has a capacity of 112 cfh
• Section D is 25 feet with a 30 cfh load
3/8" has a capacity of 69 cfh
• Section E is 20 feet with a 55 cfh load
3/8" has a capacity of 78 cfh
• The correct size for all these runs is 3/8"
2. To size section A determine the entire gas load it will deliver
range
55 CFH
furnace 80 CFH
E
C
dryer
D
30 CFH
B
water heater
40 CFH
2 PSI
gas mete
A
205 CFH
Figure 3-3
LENGTH OF RUNS
manifold
A = 100 Feet B = 15 Feet
pressure regulator
line shut-off
appliance shut-off
C = 10 Feet D = 25 Feet E = 20 Feet
Supply pressure 2 PSI Allowable drop: 1 PSI up to reg. 3 inches w.c.-reg. to appliance
NOTE: at 250 cfh gas flow the FGP-REG-3 regulator contributes 3/4 PSI drop to the system. (see chart below). The low pressure part of the system downstream of the regulator requires the standard 1/4 PSI to power appliances. Deducting the 3/4 psi drop and the 1/4 psi load the maximum allow­able drop for the meter run is 1 psi. Start with 2 PSI - 3/4 drop for regulator - 1/4 left for Appliance = 1 PSI drop for section A.
Capacities and Pressure Drop
Pressure Drop through Regulator
Based on flow in cubic feet per hour
P/N 7" w.c. 1/2 psi 3/4 psi 1 psi
FGP-REG-3
FGP-REG-5A
FGP-REG-7L
145 204 250 289
338 476 583 673
690 972 1191 1375
17
EXAMPLE 4 MEDIUM PRESSURE 12-14 INCHES W.C. 1/2 PSI) PARALLEL SYSTEM WITH A SERIES BRANCH
1. The system shown in Figure 3-4 has a bar­beque installed nearby the range. A paral­lel arrangement was chosen for the medi­um pressure system (12 inch W.C. with 6 inches W.C. drop) with a single run feeding both range and barbeque in series.
D
1/2 PSI
gas meter
260 CFH
C
A
E
F
B
G
3. To size SECTION B, the line from the mani­fold serves both the range and the barbeque.
• Total load is 105 CFH (105,000 BTUH)
• Longest length is 75 feet (A+B+C) from the meter to the barbeque
• Table N-4 shows that size 1/2" can handle 116 CFH at 80 ft
• The correct size is 1/2"
4. To size SECTION C, the distance from the meter to the barbeque is 75 ft (A+B+C)
• Load is 55 CFH (55,000 BTUH).
• Table N-4 shows that size 3/8" can only handle 54 CFH at 80 ft
• The correct size is 1/2"
5. To size SECTION D, the distance from the meter to the range is 65 ft (A+B+D)
• Load is 50 CFH (50,000 BTUH).
• Table N-4 shows that size 3/8" can handle 58 CFH at 70 ft
• The correct size is 3/8"
Figure 3-4
LENGTH OF RUNS
A = 20 Feet B = 35 Feet C = 20 Feet D = 10 Feet E = 10 Feet F = 10 Feet
G = 15 Feet
2. To size SECTION A, determine the length of the longest run from the meter and the entire gas load it must deliver:
• Range + Barbeque + Water heater + Furnace +Dryer = 260 CFH (260,000 BTUH).
• Meter to barbeque is 75 ft (A+B+C) This is the longest length
• Select Table N-4 Medium Pressure. Table N-4 shows that 1" is required for 260 CFH at 75 ft (using next longer dis­tance 80 ft column)
• The correct size is 1"
6. To size SECTION E, the distance from the meter to the water heater is 30 ft (A+F)
• Load is 40 CFH (40,000 BTUH).
• Table N-4 shows that size 3/8" can handle 81 CFH at 70 ft
• The correct size is 3/8"
7. To size SECTION F, the distance from the meter to the furnace is 30 ft (A+E)
• Load is 80 CFH (80,000 BTUH).
• Table N-4 shows that size 3/8" can handle 81 CFH at 30 ft
• The correct size is 3/8"
8. To size SECTION G, the distance from the meter to the dryer is 35 ft (A+G)
• Load is 35 CFH (35,000 BTUH).
• Table N-4 shows that size 3/8" can handle 78 CFH at 40 ft
• The correct size is 3/8"
18
SECTION 3.2C — SIZING HYBRID SYSTEMS
(Black Iron and TracPipe Combination)
To size a commercial or a residential system with a rigid black iron trunk line and flexible TracPipe branches feeding the appliances, you will need both the standard gas piping capacity tables for black iron printed in many plumbing and mechanical codes (and con­tained in both National and International Fuel Gas Code) and the TracPipe Capacity Tables printed later in this manual.
B
A
Low-pressure
gas meter
715 CFH
B1
A1
Radiant Heater 175 CFH
LENGTH OF RUNS A = 15 Feet C = 20 Feet A1 = 45 Feet C1 = 5 Feet B = 15 Feet D1 = 20 Feet
B1 = 10 Feet
EXAMPLE 5 LOW PRESSURE HYBRID SYS­TEM (Black Iron and TracPipe Combination) SERIES ARRANGEMENT
1. The system shown in figure 3-5 is a typical commercial building with 4 appliances. The gas pressure for this example is standard low pressure with 6-inch supply pressur e and 0.5­inch pressure drop.
2. To determine rigid pipe size (section A) determine the longest run from the meter to the furthest appliance:
Meter to Water Heater Add A + B + C + D1 = 70 ft. Total Load is 715 CFH (715,000 BTU)
C
C1
Unit heaters
2 x each 250 CFH
Figure 3-5
Section A correct size is 1 1/2 inch black pipe
3. To determine rigid pipe size (section B) reduce load by the load carried in section A1 to Radiant Heater (175 CFH). Use same number for length: 70 ft. is longest run. Load for this section is 540 CFH Section B correct size is 1 1/2 inch black pipe
4. To determine rigid pipe size (section C) reduce load further by the load carried in
section B1 to first unit heater (250 CFH). Use same number for length: 70 ft. is longest run. Load for this section is 290 CFH Section C correct size is 1 1/4 inch black pipe
D1
Water heater
40 CFH
5. To determine TracPipe sizing for the branch runs the length to be used is the total length of black pipe plus TracPipe from the meter to that appli­ance. The load used is the load of the individual piece of equipment.
6. To determine the size of TracPipe (section D1) the length is 70 ft and the load is 40 CFH. Using Table N-1: Section D correct size is 3/4 inch
7. To determine the size of TracPipe (section C1) the length is 55 ft and the load is 250 CFH. Using Table N-1: Section C1 correct size is 1 1/2 inch
8. To determine the size of TracPipe (section B1) the length is 40 ft and the load is 250 CFH. Using Table N-1: Section B1 correct size is 1 1/4 inch
9. To determine the size of TracPipe (section A1) the length is 60 ft and the load is 175 CFH. Using Table N-1: Section A1 correct size is 1 1/4 inch
19
EXAMPLE 6 LOW PRESSURE HYBRID SYS­TEM (Black Iron and TracPipe Combination) SERIES ARRANGEMENT
Water heater
Low
pressure
meter
230 CFH
40 CFH
Furnace
70 CFH
A=40 ft
G=25 ft
D=10 ft C2=6 ft
C1=6 ft
F=30 ft
35 CFH
B=20 ft
E=20 ft
H=40 ft
I=30 ft
Dryer
Figure 3-6
Fireplace
30 CFH
Range 55 CFH
5. Section C1, the longest run is 120 ft and load is reduced to 105. Correct size is 1".
6. Section C2, the longest run is 120 ft and load is reduced to 70. Correct size is 3/4".
7. Section D, the longest run is 120 ft and load is reduced to 30. Correct size is 1/2".
8. Section E, length is 60 ft and the load is 55 CFH. From Table N-1 the correct size is 3/4".
9. Section F, length is 90 ft and the load is 70 CFH. From Table N-1 the correct size is 3/4".
1. The system presented in figure 3-6 is a typical residence with 5 appliances. The supply pressure is 7 inches w.c. The allowable drop is 1-inch w.c. total. (black iron drop is 0.5 in. w.c. and TracPipe drop is 0.5 in. w.c.) Note: Check with your local inspection department and/or gas utility before sizing any low-pressure sys­tem with a total drop of more than 0.5 in. w.c.
2. The black iron trunk line (A+B+C1+C2+D) will first be sized for a drop of 0.5 in., w.c. in accordance with the standard method (longest total run) and each TracPipe branch run to an appliance will then be sized for 1.0 in w.c. drop based on the length from that appliance back to the meter. The maximum pressure drop to each appliance will be 1.0-inch w.c.
3. The longest total run is 120 ft. (total length of all black iron sections and TracPipe section to the furthest appliance). The total load is 70+40+55+35+30=230 CFH. Correct size for A is 1-1/4"
10. Section G, length is 95 ft and the load is 40 CFH. From Table N-1 the correct size is 3/4".
11.Section H, length is 120 ft and the load is 30 CFH. From Table N-1 the correct size is 3/4".
12.Section I, length is 95 ft and the load is 35 CFH. From Table N-1 the correct size is 3/4".
EXAMPLE 7 LOW PRESSURE HYBRID STEEL PIPE AND TRACPIPE-PARALLEL ARRANGE­MENT-MANIFOLD-USING THE LONGEST RUN METHOD
1. The system presented in figure 3-7 is typ­ical of a residential installation with four appliances. The supply pressure is 7-8 inches water column. The system will be sized with 0.5 inches w. c. drop for the steel pipe trunk line and 1 inch w.c. drop for the TracPipe branches. (Note: con- firm that pressure drops larger than 0.5 inches water column are permitted in your jurisdiction)
4. Section B, the longest run remains 120 ft but the load is reduced to 175 CFH. Correct size is 1".
20
D=30 ft
Fireplace
Range 55 CFH
E=25 ft
B=10 ft C=10 ft
Figure 3-7
B
30 CFH
Water heater 35 CFH
C
Furnace 75 CFH
A=20 ft
Low pressure
gas meter
195 CFH
2. To size the steel pipe trunk line, determine the longest run from the meter to any appliance and the total load. The longest run is to the fireplace.
• Meter to fireplace is 50 ft (A + D)
• Total load is 195 CFH (75 + 35 + 30 + 55) Using steel pipe Table SP-1 (page 77) fol­lowing the 50 ft column down, the correct size for the steel pipe is 1".
3. To determine the size of the TracPipe run “C” to the furnace use the load through that branch (75 CFH) and calculate the length from the meter to the furnace.
• Meter to furnace is 30 ft (A + B)
• Furnace load is 75 CFH Using Table N-2A the 1.0-inch w.c. pres­sure drop chart for TracPipe. Follow the 30 ft column down, the correct size for the furnace branch line “C” is 1/2".
4. To determine the size of the TracPipe run “B” to the water heater use the load through that branch (35 CFH) and calcu­late the length from the meter to the water heater.
• Meter to water heater is 30 ft (A + C)
• Water heater load is 35 CFH Using Table N-2A the 1.0-inch w.c. pres­sure drop chart for TracPipe. Follow the 30 ft column down, the correct size for the water heater branch line “B” is 1/2".
5. To determine the size of the TracPipe run “D” to the fireplace use the load through that branch (30 CFH) and calculate the length from the meter to the fireplace.
• Meter to fireplace is 50 ft (A + D)
• Fireplace load is 30 CFH Using Table N-2A the 1.0-inch w.c. pres­sure drop chart for TracPipe. Follow the 50 ft column down, the correct size for the fireplace branch line “D” is 1/2".
6. To determine the size of the TracPipe run “E” to the range use the load through that branch (30 CFH) and calculate the length from the meter to the range.
• Meter to range is 45 ft (A + E)
• Range load is 55 CFH Using Table N-2A the 1.0-inch w.c. pres­sure drop chart for TracPipe. Follow the 50 ft column down, the correct size for the range branch line “D” is 1/2".
SECTION 3.2D — ALTERNATE SIZING METHOD: SUM OF PRESSURE LOSS CALCULATIONS
1. In addition to the longest run sizing method, there is another approach to pipe sizing, which yields results closer to the actual friction loss results (obtained from testing) for each section of an installed gas piping system. This engineered approach “Sum of Pressure Loss Calculations” avoids the simplified, con­servative approximations of the longest run method. Mechanical engineers who design piping systems understand that placing a building’s entire load (theoreti­cally) at the farthest equipment outlet is not only inaccurate but will often yield pipe sizes which are larger than neces­sary . The longest run method was devised at a time when gas utilities could not always guarantee a constant pressure at every meter during times of high demands; it is a conservative approach and, although it is the customary sizing approach in North America, other engi­neered calculations are permitted by most codes.
21
2. Pressure Loss Calculations which sum up friction losses in each section of a gas piping system can provide a system design with more accurate and possibly smaller piping diameters than the tradi­tional longest run method. These calcula­tions utilize pressure loss charts for each size of CSST, which have been developed from actual test results. The maximum flow capacity is predicted with more pre­cision than with the longest run method. The Sum of Pressure Loss method is described below with tables providing pressure loss per foot based upon the total load supplied by that length of pipe with all appliances operating.
3. The system designer has simply to deter­mine the load and the length for each run. A tentative size is chosen and pressure loss in that leg is determined by multiplying the loss per foot (inches w.c. from the chart) by the length. Starting at the meter and work­ing outward the pressure loss for each leg is then summed up until the farthest appli­ance is reached. The total calculated loss is then compared with the allowable loss, which must not be exceeded from the meter to the farthest appliance. The allow­able pressure loss for each system is the responsibility of the system designer, based on model codes and on the available pres­sure at the meter set (or second stage reg­ulator) and the pressure required for each appliance (usually found on the manufac­turer's data plate.) Current language in many model codes states: The allowable loss under maximum probable flow condi­tions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appliance is greater that the "minimum inlet pressure" as stated on the appliance manufacturers data plate. If the initial proposed design cal­culation yields a total pressure loss, which is higher than allowed, simply go back and calculate again with larger sizes, starting from the meter.
USING SUM OF PRESSURE LOSS METHOD
Furnace
65 CFH
B=10 ft
Water Heater
35 CFH
Dryer
35 CFH
EXAMPLE 8 LOW PRESSURE SYSTEM SERIES ARRANGEMENT
C2=10 ft
C1=5 ft A=10 ft
D=15ft
Figure 3-8
1. The system presented in figur e 3-8 is similar to that in 3-1, a single-family installation with the addition of one more appliance, a dryer. The supply pressure is 6 inches water col­umn and the allowable pressure drop is 1/2 inch.
2. To size section A, calculate the load car­ried by that section:
•Furnace plus Water Heater plus Dryer = 135 CFH (135,000 BTU) Using Table PD-1 find pressure loss at 135 MBTU load through 3/4"TracPipe Average of .019 and .022 is .021. Drop per foot is
0.021; multiply by length 10 feet = 0.21 drop
3. To size section B find the drop per foot for the load carried by that section: 65 CFH (MBTU)
Using Table PD-1 find pressure loss at 65 MBTU through 1/2" TracPipe Use the average of loss between 60 and 70 MBTU: Average of .019 and .027 is .023 ; Drop per foot is 0.023 Multiply by length 10 feet = 0.23 drop Sum pressure loss meter to Furnace 0.21 + 0.23 = .44 inches w.c This leg is sized properly at 1/2" because sum of loss is less than .5 in. w.c.
22
4. To size section C1 find the drop per foot for the load carried by that section:
70 CFH (MBTU) Using Table PD-1 find pressure loss at 70 MBTU load through 1/2"
TracPipe
Drop per foot is .027; length is 5 ft; 5 X .027 is .135
5. To size section C2 find the drop per foot for the load carried by that section:
35 CFH (MBTU)
Low
Low
Pressure
Pressure
Meter
Meter
230 CFH
230 CFH
Using Table PD-1 find pressure loss at 35 CFH load through 1/2"
TracPipe
Average of .008 and .004 is .006; length is 10 ft; 10X .006 is .06 Sum pressure loss to water heater
0.21 + .135 + .06 = .405 inches w.c This leg is sized properly at 1/2" because sum of loss is less than .5 in. w.c.
6. To size section D find the drop per foot for the load carried by that section: 35 CFH (MBTU)
Using Table PD-1 find pressure loss at 35 MBTU through 1/2" TracPipe Drop per foot is .006 (see number 4 above); Multiply by length 15 feet = .09 Sum pressure loss to dryer 0.21 + 0.135 + .09 = .435 inches w.c. This leg is sized properly at 1/2" because sum of loss is less than .5 in. w.c.
The sum of pressure loss method allows the addition of an appliance without increasing trunk line size.
EXAMPLE 9 LOW PRESSURE HYBRID SYS­TEM (Steel Pipe and TracPipe Combination) SERIES ARRANGEMENT USING SUM OF PRESSURE LOSS METHOD
1. The system presented in figure 3-9 is identical to that in Figure 3-6: a single­family installation with 5 appliances. Low pressure 6-7 inches and a pressure drop of 0.5 inches water column. NOTE: in
Example 6 this system was sized using the longest run method. Here we will use the sum of pressure loss method dis­cussed in section 3.2D.
Water Heater
40 CFH
G=25 ft
Furnace 70 CFH
A=40 ft
D=10 ft
C2=5 ft C1=5 ft
F=30 ft
B=20 ft
Figure 3-9
H=40 ft
Dryer
35 CFH
E=30 ft
I=30 ft
Fireplace
30 CFH
Range
55 CFH
2. Begin by using pipe sizes determined in Example 6 and determine if these are cor­rect with this method. It is possible that smaller pipe sizes may be sufficient; this will be determined by calculating the sum of pressure losses from the meter to each appliance. To use this method a tentative size will be assigned to each run and this size will be confirmed or revised by the calculation. The sum total loss of a run from the meter to the appliance cannot exceed the allowable pressure loss.
3. To determine pressure loss through sec­tion A (steel pipe trunk), use the load through that section (230 CFH) and find pressure loss per foot from the steel pipe Schedule 40 Pressure Drop Curves Graph Table SP-1. The 11/4 inch pipe diameter line intersects the 230 CFH line at a pres­sure drop of .18 inches w.c. per 100 feet of length. Multiply the length: 40 feet by the loss per foot: 0.0018. The pressure loss for this section is 0.072.
4. To determine pressure loss through section B we use the load through that section (175 CFH). Find pressure loss for 1" size from the steel pipe graph in Table SP-1
- 0.6 per 100 feet. Multiply the length: 20 feet by the loss per foot: 0.006. The pres­sure loss for this section is 0.12.
23
5. To determine pressure loss through sec­tion C1 we use the load through that sec­tion (105 CFH). Find pressure loss for 1" size from the steel pipe graph - 0.2 per 100 feet. Multiply the length: 5 feet by the loss per foot: 0.002. The pressure loss for this section is 0.01.
6. To determine pressure loss through sec­tion C2 we use the load through that sec­tion (70 CFH). Find pressure loss for 3/4" size from the steel pipe graph - 0.38 per 100 feet. Multiply the length: 5 feet by the loss per foot: 0.0038. The pressure loss for this section is 0.019.
7. To determine pressure loss through sec­tion D we use the load through that sec­tion (30 CFH). Find pressure loss for 1/2" size from the steel pipe graph - 0.31 per 100 feet. Multiply the length: 10 feet by the loss per foot: 0.0031. The pressure loss for this section is 0.031.
8. To determine pressure loss through sec­tion E (TracPipe drop to the range), use the load through that section (55 CFH) and find pressure loss from Table PD-1 Pressure Drop per Foot for TracPipe. Trying the 3/4 inch column we find .004 inches per foot length (there is no 55 CFH load listed, so we use 60 CFH). Multiply the length: 30 feet by the loss per foot .004. The pressure loss for this section is
0.12. Add the loss of section A to the loss of section E for total loss from the meter to range. 0.072 + 0.12 = 0.192. Since this is less than the 0.5 allowable drop the cor­rect size for section E is 3/4".
9. To determine pressure loss through sec­tion F (TracPipe drop to the furnace), use the load (70 CFH) and find pressure loss from Table PD-1. In the 3/4" column we find 0.005. Multiply the length: 30 feet by 0.005. The pressure loss for this sec­tion is 0.15.
Add the loss of sections A + B to the loss of section F for total loss from meter to furnace. 0.072 + 0.12 + 0.15 = 0.342. The correct size for section F is 3/4".
10. To determine pressure loss through sec­tion G (TracPipe drop to the water heater), use the load (40 CFH) and find pressure loss from Table PD-1. In the 1/2" column we find 0.008. Multiply the length: 25 feet by 0.008. The pressure loss for this section is 0.20. Add the loss of sections A + B + C1 + C2 to the loss of section G for total loss from meter to furnace. 0.072 +
0.12 + 0.01 + 0.019 + 0.20 = 0.421. The correct size for section G is 1/2".
11. To determine pressure loss through sec­tion H (TracPipe drop to the fireplace), use the load (30 CFH) and find pressure loss from Table PD-1. In the 1/2" column we find 0.004. Multiply the length: 40 feet by 0.004. The pressure loss for this sec­tion is 0.16. Add the loss of sections A + B + C1 + C2 + D to the loss of section H for total loss from meter to furnace. 0.072 +
0.12 + 0.01 + 0.019 + 0.031 + 0.16 =
0.412. The correct size for section H is 1/2".
1
2. To determine pressure loss through sec­tion I (TracPipe drop to the dryer), use the load (35 CFH) and find pressure loss from Table PD-1. In the
0.006. Multiply the length: 30 feet by
0.006. The pressure loss for this section is
0.18. Add the loss of sections A + B + C1 to the loss of section I for total loss from meter to dryer. 0.072 + 0.12 + 0.01 + 0.18 = 0.382. The correct size for section I is 1/2"
. Using the Sum of Pressure Loss Method we calculate that three of the five TracPipe sections (when compared with the longest length method) can utilize reduced sizes to deliver the necessary load with a pressure loss equal to or less than the allowable 0.5 inches water col­umn. This enables the installer to use TracPipe on all but the furnace and range drops, which remain
1/2"
column we find
3/4"
.
1/2"
24
SECTION 3.3 — GASBREAKER
®
EXCESS FLOW DEVICES FOR CSST AND STEEL PIPE GAS SYSTEMS
GasBreaker excess flow devices protect against residential and commercial gas line breaks. GasBreakers work in conjunction with TracPipe and other brands of CSST at the gas meter as well as at the appliance manifold. GasBreakers should be connected directly to the manifold at the point between the manifold and the appliance gas lines, which will offer increased safety for the build­ing occupants. The charts used to size CSST systems below are for use with TracPipe flex­ible gas piping only. (For other CSST brands, size the piping by assuming that the load for that section of pipe is the maximum load of the excess flow device chosen).
1. GASBREAKER LOW PRESSURE
EXCESS FLOW DEVICES FOR PROPANE AND NATURAL GAS SERVICE. An excess flow device is a pro-
tective device to help control the dis­charge of fuel gas in the event of a com­plete breakage of pipe lines or flex con­nector rupture. Excess Flow Devices have been of help in limiting gas loss in many incidents involving breakage of piping. Thus, they do provide a useful safety func­tion in gas systems. This section explains
what protection Excess Flow Devices can offer, points out conditions which can inter­fere with that protection, and offers sugges­tions for effective Excess Flow Device installation.
2. INSTALLATION OF GASBREAKER DEVICES ON GAS METERS. The GasBreaker device can be installed down­stream of the gas company meter and bypass tee outlet using standard pipe fit­tings and procedures. GasBreaker Meter Devices must be installed within 5 degrees of the vertical position with the flow arrow pointing upwar
d in the direction of flow.
3. INSTALLATION OF GASBREAKER APPLIANCE DEVICES. GasBreaker devices should be connected directly to the manifold at the point between the manifold and the gas appliance lines. If there is no manifold, the devices could be located at the tee or fitting where the appli­ance drop attaches to the trunk line. All GasBreaker devices except series 120 appliance device must be installed in the vertical position (within 5 degrees) with the flow arrow pointing upward in the direction of flow. The series 120 appliance device can be installed in a vertical or horizontal position with the flow arrow pointing in the direction of flow.
HARD PIPE SYSTEM CSST SYSTEM
(Corrugated Stainless
Steel Tubing)
GASBREAKER METER DEVICES ARE INSTALLED IMMEDIATELY AFTER (DOWNSTREAM OF) THE
GASBREAKER METER DEVICES ARE INSTALLED IMMEDIATELY AFTER (DOWNSTREAM OF) THE BY-PASS TEE
GASBREAKER APPLIANCE SAFETY DEVICES ARE INSTALLED WHERE THE HARD PIPE CONNECTS TO THE APPLIANCE GAS FLEX LINES
FOR MAXIMUM PROTECTION, ALL GAS APPLIANCES SHOULD HAVE A GASBREAKER SAFETY DEVICE
GAS FLEX CONNECT LINE
TO OTHER GAS APPLIANCES
CSST LINES DROP DOWN TO GAS APPLIANCES
CSST Termination Fittings
GASBREAKER
APPLIANCE DEVICES CONNECT TO THE MANIFOLD IN ATTIC
or other location
GAS FLEX CONNECT LINE
25
BY­PASS TEE
SECTION 3.4 — SIZING INSTRUCTIONS FOR GASBREAKER DEVICES USED WITH CSST/TRACPIPE SYSTEMS
SECTION 3.4A — METER DEVICES (SERIES FGP-GB300, FGP-GB400, FGP-GB600)
1. Choose the GasBreaker Meter Device from Table 3.1 based on the total capacity of the gas piping system served by that meter.
2. Using the appropriate GasBr eaker Capacity Chart “Table N-1GB GasBreaker Low Pressure” or “Table N-5GB GasBreaker (2­psi system)” based upon system pressure; determine the size of CSST, which will sup­ply the necessary total capacity of that meter. This size of CSST is designed to allow the GasBreaker device to act as a safety shut-off device in the event of a com­plete breakage of the main downstream trunk line piping. Note: GasBreakers installed at the meter are not designed to protect against breakage of piping down­stream that has been reduced from the initial size or appliance branch piping.
SECTION 3.4B — APPLIANCE DEVICES (SERIES FGP-GB090, FGP-GB120, FGP-GB150)
2. Series System Low Pressure a. When there is no manifold, the devices
should be located at the tee or fitting where the appliance drop attaches to the trunk line. If this is a concealed location, follow local codes.
b. Choose the appropriate size device
(“Max. Load Capacity (BTU/hr)” column) for each appliance from Table 3.1. Select a device with sufficient capacity to supply the appliance(s) connected to that drop.
c. Using GasBreaker Capacity Chart “Table
N-1GB GasBreaker Low Pressure” deter­mine size of TracPipe CSST which will carry the required load for the distance from the meter to the appliance(s). This size of CSST is designed to allow the GasBreaker device to act as a safety shut-off device in the event of a complete downstream breakage of pipe lines or flex connector rupture.
SECTION 3.4C — SIZING INSTRUCTIONS FOR GASBREAKER DEVICES WITH STEEL PIPE SYSTEMS
1. Choose the GasBreaker Device (Appliance
or Meter) from Table 3.1, based upon either the capacity of the appliance or the total capacity of the gas piping system served by the meter.
1. Elevated Pressure 2 PSI system (Manifold with parallel arrangement)
a. Choose the appropriate size device
(“Max. Load Capacity (BTU/hr)” column) for each manifold outlet from Table 3.1. Select a device with sufficient capacity to supply the appliance(s) connected to the outlet.
b. Using GasBreaker Capacity Chart “Table
N-3GB GasBreaker Dual Pressure System” determine size of TracPipe CSST which will carry the required load for the distance from the manifold to the appli­ance(s). This size of CSST is designed to allow the GasBreaker device to act as a safety shut-off device in the event of a complete breakage of downstream pipe lines or flex connector rupture.
2. Using GasBreaker Capacity Chart “Table SP-1GB GasBreaker Steel Pipe Low Pressure” determine the size of CSST, which will supply the necessary capacity of that appliance or meter. This size of CSST will allow the GasBreaker device to act as a safety shut-off device in the event of a complete downstream breakage of pipe lines or flex connector rupture.
Gas Breaker’s published limitations, based upon black pipe sizing (Pipe break open to atmosphere) are:
Series 300: For up to 60' of 3/4" and 190'
of 1" pipe.
Series 400: For up to 200' of 1 1/4" pipe
and 500' of 1 1/2" pipe.
Series 600
26
TABLE 3.1
Low Pressure Excess Flow Devices
GasBreaker Models
Valve Maximum
Inlet x Max. Load Device
Product TracPipe Outlet Capacity Closure Flow
Name Part # Male - NPT (BTU/hr) Rate (SCFH)
GasBreaker FGP-GB090-075 3/4 x 3/4 70,000 100 GasBreaker FGP-GB120-050 1/2 x 1/2"Flare 90,000 125 GasBreaker FGP-GB120-075 3/4 x 5/8"Flare 90,000 125 GasBreaker FGP-GB150-075 3/4 x 3/4 125,000 160 GasBreaker FGP-GB300-075 3/4 x 3/4 275,000 320 GasBreaker FGP-GB300-100 1 X 1 275,000 320 GasBreaker FGP-GB400-100 1 X 1 375,000 450 GasBreaker FGP-GB600-100 1 X 1 500,000 660
Notes:
1) Flow Rates given for 0.6 Specific Gravity Natural Gas with an avg. heating value of 1000 BTU / cu. ft.
2) Abbreviations: “w.c. = inches water column SCFH = Standard Cubic Feet per Hour
3) Equivalent length pipe calculations MUST use the Maximum P across device at Trip AND the Maximum
Device Closure Flow Rate to insure that the GasBreaker EFD will act as a safety shut-off device (“Trip“ or “Close“) under a given set of design conditions. Other P values may be found in TABLE 3.2.
TABLE 3.2
Low Pressure Excess Flow Devices
Pressure drop P(“w.c.) at Flow Rates*
FLOW GasBreaker MODEL
(SCFH) GB090 GB150 GB300 GB400 GB600
50 0.1 60 0.2 0.1 70 0.4 0.2 80 0.6 0.3
90 0.7 0.4 100 0.5 0.2 110 0.7 120 0.8 130 1.0 140 1.2 150 1.3 0.4 200 0.7 0.1 0.1 250 1.1 0.3 300 1.7 0.5 0.5 350 0.8 400 1.3 1.0 500 1.8 600 2.7
*Note: When calculating pipe lengths use TABLE 3.1 to insure
that the EFD will operate as a safety shut-off device.
27
Loading...
+ 67 hidden pages