It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark
to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as the guide contains important information relating to safety and EMC.
This device is marked with the international caution symbol. It is important
to read this manual before installing or commissioning this device as it
contains important information relating to Safety and EMC (Electromagnetic
Compatibility).
This instrument is a panel mount device protected in accordance with EN
61010-1:2001, electrical safety requirements for electrical equipment for
measurement, control and laboratory. Installation of this instrument should
be done by qualified personnel. In order to ensure safe operation, the
following instructions should be followed.
This instrument has no power-on switch. An external switch or circuitbreaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch or
circuit-breaker shall meet the relevant requirements of IEC 947–1 and IEC
947-3 (International Electrotechnical Commission). The switch shall not be
incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn
from the main supply in case of a fault in the equipment, an overcurrent
protection device shall be installed.
•Do not exceed voltage rating on the label located on the top of the
instrument housing.
•Always disconnect power before changing signal and power
connections.
•Do not use this instrument on a work bench without its case for safety
reasons.
•Do not operate this instrument in flammable or explosive atmospheres.
•Do not expose this instrument to rain or moisture.
•Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
•Use electrical wires with adequate size to handle mechanical strain and
power requirements. Install without exposing bare wire outside the
connector to minimize electrical shock hazards.
EMC Considerations
•Whenever EMC is an issue, always use shielded cables.
•Never run signal and power wires in the same conduit.
•Use signal wire connections with twisted-pair cables.
•Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
Failure to follow all instructions and warnings may result in injury!
This is a Class A ITE product. In a domestic environment this product may
cause radio interference in which case the user may be required to take
adequate measures.
1
1.2 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as soon
as you receive the shipment. Note any evidence of rough handling in
transit. Immediately report any damage to the shipping agent. The carrier
will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing
material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation Manual as well as free configuration software
(iConnect) are available from the website listed on the cover pagesof this manual, or on the CD-ROM enclosed with your shipment.
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
NOTE: Provides you with information that is important to successfully
setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances
or practices that can effect the instrument’s functionality and must
refer to accompanying documents.
TIP: Provides you helpful hints.
1.3 Description
The wi®Series wireless monitoring and control system features meters compatible
with a large and growing number of wireless sensors: UWTC “Universal Wireless
Thermocouple” Type J, K, T, E, R, S, B, N, and C, UWRTD “Universal Wireless
RTD” , and UWIR “Universal Wireless Infrared Temperature Sensor”. For more
information about the UWTC, UWRTD, and UWIR, refer to the separate manual for
these products.
2
1.3 Description (continued)
The wireless sensors transmit up to four hundred feet 400’ (approx. 120 meters-without obstructions or interference) to a wiSeries meter connected directly to an
Ethernet network and the Internet. The wireless system complies with IEEE 802.15.4
operating at 2.4 GHz. The wiSeries Meter Scanner & Controller can monitor up to
eight (8) wireless sensors.
The Meter also provides error detection mechanism for inactive communication
and diagnostic information including signal strength and data transmission
success rate to help troubleshooting potential wireless system installation issues.
The Meter connects directly to an Ethernet network and the Internet and features
award-winning embedded Web Server. It is easily configured and monitored with a
Web browser over the Ethernet network or the Internet.
CONTROL, MONITOR, AND ALARM: The Meter comes standard with dual outputs
of either Form C relays, SSR’s (solid state relays) or dc Pulses that can be used for
ON/OFF control functions or alarms.
The meter can monitor alarm conditions for any or all of the wireless sensors. For
example, the meter can be set up to trip an alarm if any one of the sensors indicated
that it was above or below a pre-set alarm point.
Analog output is fully scalable and may be configured as an ON/OFF controller or retransmission to follow your readings.
MONITOR AND CONTROL LOCALLY AND OVER THE INTERNET: The wiSeries
wireless monitoring and control system provides local monitoring and control, along
with remote Web-based monitoring of temperature from thermocouples, RTD’s, and
infrared temperature sensors.
The wiSeries system let’s you monitor and record temperature over an Ethernet
network or the Internet without any special software--just your Web Browser.
ETHERNET: The wiSeries meter-controller-scanner is an independent node on the
network sending and receiving data in standard TCP/IP packets. It is easily
configured from a Web Browser and can be password protected. From within an
Ethernet LAN or over the Internet, the user simply types the IP address (such as
192.168.1.200) or an easy to remember name (such as "Oven5" or "Fixture") and
the wiSeries meter serves a Web Page with the current readings.
EMAIL ALARM: The wiSeries meter can trigger an alarm if variables go above or
below a Setpoint that you determine. Your alarm can be sent by email to a single
user or to a group distribution list, including text messages to cell phones and PDA’s.
The "Mail Notifier" software is a free and easy program for this application.
CHARTS AND GRAPHS: The wiSeries system serves Active Web Pages to display
real time readings and charts of temperature. You can also log data in standard data
formats for use in a spreadsheet or data acquisition program such as Excel or Visual
Basic. We offer a free and easy to use program iLog for logging data to Excel.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart
over the LAN or Internet in real time. With the wiSeries system there is no need to
invest time and money learning a proprietary software program to log or chart the
data. Chart scales are fully adjustable on the fly. For example, the chart can display
one minute, one hour, one day, one week, one month or one year.
be charted across the full span or within any narrow range such as (20 to 30°C).
Temperature can
3
1.3 Description (continued)
TC
RTDTC
WIRELESS METER
(Receiver)
END DEVICES
(Transmitters)
COMPUTER
(Datalogging
Software)
COMPUTER
(Standard
Web Browser)
ETHERNET
iLD Large Display Meter
Temperature
wi8xx-U
iR
DATALOGGING: The OPC Server software makes it easy to integrate the wiSeries
wireless sensor system with many popular Data Acquisition and Automation
programs offered by NEWPORT, OMEGA, Wonderware, iConics, Intellution,
Rockwell Automation, and National Instruments, among others.
PROGRAMMABLE COLOR DISPLAY: The wiSeries features patented
programmable color displays. The display can be programmed to change color at
any Setpoint or Alarm point. For example, the meter can be programmed to display
the process value in GREEN during warm-up, switching to AMBER to signal the
normal operating range, and in RED to signal an alarm condition. The changes in
color are quickly seen from a distance, and machine operators can intuitively react to
changing conditions. The colors can be programmed to change back when the value
drops back below the alarm point or to "latch" on until being reset by the operator.
The meter can also be programmed to display only one unchanging color: GREEN,
AMBER, or RED. This is a useful way to let an operator identify, at a glance,
temperature values in three separate locations, or to display three different
measurements.
The following example Figure 1.1 illustrates how you can hookup the Temperature
Wireless System to your network:
The wireless system consists of a single Meter and one or more End Devices /
Transmitters. The End Devices will send data periodically to the Meter where it serves
as a gateway between the users and the End Devices. The users can access the data
through the Meter’s Web Server and provided data acquisition software.
A standard web browser can be used to monitor and chart temperature. The browser
can also be used to configure the meter’s IP address, passwords for access and
overall configuration parameters.
Figure 1.1 Temperature Wireless Monitor and
Control System on the Ethernet Network
4
PART 2
1
2
C
F
12
%RH
D
12CF
Upper Display:
Temperature Values
Lower Display:
Wireless Transmitter ID#
01 thru 08
HARDWARE
2.1 Physical Characteristics and Mounting
2.1.1 Front Panel
Figure 2.1 Front Panel Display
Table 2.1 Front Panel Enunciators
1
Output 1 / Setpoint 1 / Alarm 1 indicator
2
Output 2 / Setpoint 2 / Alarm 2 indicator
°C
°F
°C unit indicator for Temperature
°F unit indicator for Temperature
Changes display to Configuration Mode and advances through menu
items. Make sure to presstwice (Stand-by) followed by pressing
(stop communication) before entering the Configuration mode.
Used in Configuration Mode to change values. In Run Mode, it’s used
to lock the display to the next sensor reading.
Used in Configuration Mode to change values. It’s also used to
resume scrolling sensors.
Accesses submenus in Configuration Mode
For complete Front Panel Pushbutton procedures, refer to the
Supplemental Guide.
The rear panel connections are shown in Figure 2.2.
Use copper conductors
only for power connections
Figure 2.2 Rear Panel Power and Output Connections
Table 2.2 Rear Panel Connector
POWERAC/DC Power Connector: All models
OUTPUT 1Based on one of the following models:
Relay SPDT
Solid State Relay (SSR)
Pulse
Analog Output (Voltage and Current)
OUTPUT 2Based on one of the following models:
Relay SPDT
Solid State Relay (SSR)
Pulse
Network Communication Interface Section:
ETHERNET RJ45 interface for 10BASE-T connection.
RESETButton: Used for power reseting the Ethernet board.
ACTIVITYLED (Red) Blinking: Indicates network activities (receiving or
sending packets).
NET LINKLED (Green) Solid: Indicates good network link.
TXLED (Yellow) Blinking: Indicates transmitting data to the serial port.
RXLED (Green) Blinking: Indicates receiving data on the serial port.
6
2.1.3 Dimensions
3.780 [96.00]
1.890
[48.00]
0.700 [17.78]
4.325
[109.85]
1
2
C
F
12
%RH
D
12CF
PANEL THICKNESS
0.25 (6.4) MAX
0.03 (0.6) MIN
PANEL CUTOUT
1/8 DIN
Figure 2.3 Mounting Dimensions
7
2.1.4 Assembly and Mounting
Front Bezel
Gasket
Case
Panel
Thumbnuts
Sleeve
Model No.
Label
2.1.4.1 Panel Mounting Instruction
1. Using the dimensions from the panel cutout in Figure 2.3, cut an opening in
the panel.
2. Remove sleeve from the rear of the case by removing thumbnuts.
3. Insert the case into the opening from the front of the panel, so the gasket seals
between the bezel and the front of the panel.
4. Slip the sleeve over the rear of the case.
5. Tighten the thumbnuts to hold the unit firmly in the panel.
Figure 2.4 Panel Mounting
8
2.1.4.2 Antenna Mounting Instruction
METER MOUNTED
IN NON-METALIC
ENCLOSURE.
METER MOUNTED
IN A METALIC
ENCLOSURE.
For best reception: connect the antenna directly to the rear of the meter, if the
meter is not installed in a metal panel or enclosure.
If the rear of the meter is behind a metal panel or in a cabinet, use a coaxial
cable to position the antenna outside of the enclosure in the open air.
Use the shortest cable that can reach a suitable location. The antenna on this
Meter and any End Devices should be installed in a vertical position, pointing
towards the sky.
Metallic structure should be kept at least 0.8" (2 cm), although 2.4" (6 cm)
is recommended away from the antenna.
Any casing that encloses the antenna should be plastic. In addition, it is
also wise to avoid plastic case with dark fillers or colorants.
Refer to Section 5 for more Environmental / Operating Conditions.
Figure 2.5 Antenna Mounting
9
2.1.4.3 Disassembly Instruction
Gasket
If necessary, the board assembly may be removed from the front of the case
housing.
Warning: Disconnect ac power from the unit before proceeding.
1. Remove the board assembly from the case by pulling at the sides of the bezel.
2. The bezel, along with the board assembly will unlatch from the case housing.
•
Depending on the size of your Ethernet connector, you may need to
disconnect it from the RJ45 jack on the rear of the meter.
•
Depending on the length of your antenna cable, you may need to
disconnect it from the rear of the meter.
Figure 2.6 Accessing the Main Board Assembly
10
2.1.5 Electrical Installation
24 Vac or
20 to 36 Vdc
90 to 240 Vac 110 to 375 Vdc
OR
2.1.5.1 Power Connections
Warning: Do not connect ac power to your meter until you have
completed all output connections. This meter must only be installed by a
specially trained electrician with corresponding qualifications. Failure to
follow all instructions and warnings may result in injury!
Connect the main power connections as shown below.
Use copper
conductors only for
power connections
Figure 2.7 Main Power Connections
Table 2.3 Fuse Requirement (See Specifications Section)
FUSEConnectorOutput TypeFor 115Vac For 230VacDC
FUSE 1
FUSE 2
For the low voltage power option, in order to maintain the same degree of
protection as the standard high voltage input power units (90 - 240 Vac),
always use a Safety Agency Approved DC or AC source with the same
Overvoltage Category and pollution degree as the standard AC unit (90 240 Vac).
The Safety European Standard EN61010-1 for measurement, control,
and laboratory equipment requires that fuses must be specified based on
IEC127. This standard specifies for a Time-lag fuse, the letter code “T”.
The above recommended fuses are of the type IEC127-2-sheet III. Be
aware that there are significant differences between the requirements
listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a
result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse is
approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to
consult the manufacturer’s data sheets for a cross-reference.
PowerN/A 100 mA(T) 100 mA(T)100 mA(T)
Power
N/A N/AN/A400 mA(T)
11
2.1.5.2 Wiring Outputs
This meter has two factory installed outputs. The SPDT Mechanical Relay, SPST
Solid State Relay, Pulse and Analog Output Connection are shown below.
Use copper
conductors only for
power connections
Figure 2.8
a) Mechanical Relay and SSRb) Pulse and Analog
Outputs Wiring HookupOutputs Wiring Hookup
12
2.1.5.2 Wiring Outputs (continued)
TEMPERATURE
CONTROLLER
CONTROL
SIDE
dc INPUT
SSR
ac INPUT
SSR
ac INPUT
SSR
LOAD
SIDE
HEATER
Vac
Vac
dc CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH dc VOLTAGE SSR DRIVER OUTPUT
FAST BLOW
FUSE
0 or 5 Vdc,
TYPICALLY
4
3
1
2
TEMPERATURE
CONTROLLER
CONTROL
SIDE
LOAD
SIDE
HEATER
Vac
Vac
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT
FAST BLOW
FUSE
Vac
DRIVING
SSR
4
3
1
2
TEMPERATURE
CONTROLLER
CONTROL SIDE
LOAD
RESISTOR
LOAD
SIDE
HEATER
Vac
Vac
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT
FAST BLOW
FUSE
Vac
DRIVING
SSR
4
3
1
2
Figure 2.9 Typical Applications
13
2.1.5.3 Jumper Settings for Display Color Setup
1
4
3
2
ON
1
ON
RED
GREEN
S1
8
GREEN
RED
S1
AMBER
S1 (Open)
S1
Display Board
To change the color of the lower display follow the instructions below:
1.
The unit should be removed from the panel and opened.
Refer to Section 2.1.4.3 for assembly and disassembly instructions.
2.
Locate S1 jumper, on the back side of the display board. Select the
position for your color choice of Red, Green or Amber.
Figure 2.10 Location of S1 Jumper
To change the color of the upper Display, see Section 4.3.7.5.
14
2.1.5.4 Dip Switches
1
4
3
2
OFF
ON
1
4
3
2
OFF
ON
1
ON
OFF
S1
8
4 Position
DIP Switch on
Ethernet Board
8 Position
DIP Switch on
Wireless Board
OFF
ON
1
8
To change the DIP switches, follow the instructions below:
1.
The unit should be removed from the panel and opened.
Refer to Section 2.1.4.3 for assembly and disassembly instructions.
2.
Locate the 4 and 8 position DIP switches, on the top board.
The Meter is shipped with all DIP switches in "OFF" position
To set the Wireless and Ethernet settings to Factory Default, Refer to
Section 7.
1To change the
2-8N/A
Wireless settings to
Factory Default
Figure 2.11 Location of DIP Switches
1 N/A
2 To change the Ethernet settings to
Factory Default
3 To enable/disable DHCP
4 N/A
15
2.2 Network Communication Interfaces
2.2.1 10Base-T RJ-45 Pinout
The 10BASE-T Ethernet network (RJ-45) system is used in the Meter for
network connectivity. The 10 Mbps twisted-pair Ethernet system operates over
two pairs of wires. One pair is used for receiving data signals and the other pair
is used for transmitting data signals. This means that four pins of the eight-pin
connector are used.
PinNameDescription
1+Tx+ Transmit Data
2-Tx- Transmit Data
3+RX+ Receive Data
4N/CNot Connected
5N/CNot Connected
6-Rx- Receive Data
7N/CNot Connected
8N/CNot Connected
Figure 2.12 RJ45 Pinout
2.2.2 10Base-T Crossover Wiring
When connecting the iServer directly to the computer, the transmit data pins of
the computer should be wired to the receive data pins of the Meter, and vice
versa. The 10Base-T crossover cable with pin connection assignments are
shown below.
Figure 2.13 10Base-T Crossover Cable Wiring
Use straight through cable for connecting the Meter to an Ethernet hub.
The ports on the hub are already crossed.
16
PART 3
NETWORK CONFIGURATION
3.1 Ethernet (MAC) Address
MAC (Media Access Control) address is your computer's unique hardware
number. When you're connected to the LAN from your computer, a
correspondence table relates your IP address to your computer's physical (MAC)
address. The MAC address can be found on the label of your meter (see Figure
2.4 and 3.1) and contains 6 bytes (12 characters) of hexadecimal numbers
XX:XX:XX:XX:XX:XX For Example
Remove the small label with the default IP address and there will be room to put
your IP address.
: 0A:0C:3D:0B:0A:0B
Figure 3.1 Label Detail
3.2 Network Protocols
The Meter can be connected to the network using standard TCP/IP protocols. It
also supports ARP, HTTP (Web Server), DHCP, DNS and Telnet protocols.
3.3 DHCP
DHCP, Dynamic Host Configuration Protocol enables individual computers or
devices to extract their IP configurations from a server (DHCP server).
If the DHCP is enabled on your Meter, as soon as the Meter is connected to the
network, there is an exchange of information between DHCP server and the
Meter. During this process the IP address, the Gateway address, and the Subnet
Mask will be assigned to the Meter by the DHCP server. Note that the DHCP
server must be configured correctly to do such assignment.
17
3.3 DHCP (continued)
The Meter is shipped with DHCP disabled (factory default).
If fixed or static IP address is desired, the DHCP must be disabled.
The DHCP can be enabled by setting the DIP switch # 3 to the "ON" position
Figure 3.2 4 Position DIP Switch
Setting the Meter’s IP address to 0.0.0.0 will also enable DHCP.
3.4 DNS
DNS, Domain Name System enables individual computers and devices to be
recognized over a network based on a specific name instead of an IP address.
For example, instead of having to use http://192.168.1.200 (IP address), you
would use only http://wis03ec or any eight character name stored as Host
Name under "Access Control" page from the Wireless System Home Page.
The default DNS name for the Meter is "wis" followed by the last four digits of
the MAC address of that particular Meter.
1. It is very important to communicate with the network administrator in
order to understand the DHCP and its existing configurations on the
host server, before enabling the DHCP on the Meter.
2. The Meters are shipped with a default static IP address of
192.168.1.200 and Subnet Mask of 255.255.255.0.
3. On Windows servers where the DCHP and DNS are separate
functions it is very important to configure the DHCP server to
communicate with the DNS in order for the iServer’s Host Name to
correctly respond. If you cannot access the iServer using its Host
Name, please contact your network administrator to make sure the
DHCP and DNS servers are linked together.
18
3.5 IP Address
Every active device connected to the TCP/IP network must have a unique IP
address. This IP address is used to establish a connection to the Meter. Every
computer using TCP/IP should have a unique 32-bit address which is divided
into two portions, the network ID and the host ID. For instance, every computer
on the same network uses the same network ID. At the same time, all of them
have a different host ID. For more details about the IP address see Appendix B.
3.5.1 Default IP Address
The Meter is shipped with a default IP address of 192.168.1.200 and Subnet
Mask of 255.255.255.0. If you are going to use a Web browser or Telnet
program to access the Meter using its default IP address, make sure that the PC
from which you’re establishing the connection has an IP address that is in the
same range as the Meter’s IP address (192.168.1.x, where x can be any number
from 1 to 254). See Section 3.5.2.
Your PC’s IP address cannot
You also need to make sure that your PC’s Subnet Mask is 255.255.255.0. This
is a good way to access the Meter over the network and make any configuration
changes needed. If 192.168.1.200 is already in use on your network, use an
Ethernet crossover cable between your computer and the Meter to change the IP
address or any other settings within the Meter.
be the same as the Meter’s IP address.
19
3.5.2 Changing TCP/IP Properties on Your Computer
Go to your computer’s Control Panel then Network Connections.
Pick the network with the proper Ethernet card. Right click and choose
Properties
Look for Internet Protocol, click on it
and press Properties
Figure 3.3 Network Connections
Setup the IP address (in this case, 192.168.1.1) as shown below and press OK
You can access the Meter’s Web
Server via any internet browser
using IP address of 192.168.1.200.
Once you log into the Meter’s Web
Server, you will be able to change its
IP configuration according to
Section 4.2.
After you configure the
Meter’s IP configurations,
you should go back and set
your PC’s previous IP
settings.
.
Figure 3.4 Network Connections
20
PART 4
NETWORK OPERATIONS
This Meter can be used and configured in several ways, depending on user’s
preference and network setup. It can be configured using a Web browser, like
Internet Explorer. It can also be configured using the iConnect Configuration
Software.
If DHCP and DNS servers are configured to exchange information, the
connection will be very simple. All you need to do is to enable DHCP on the
Meter (see Section 3.3) and use a straight through network cable to connect the
Meter to an Ethernet hub or switch and power it up. Now, you can use the
Meter’s default Host (Domain) Name, which is wisxxxx (where xxxx are the last
four characters of its MAC address) to access the Meter’s Web Server.
If DHCP is not the preferred method, you can configure your PC’s network
connection with an IP address of 192.168.1.x that is in the same range as the
Meter’s default IP address (192.168.1.200) and connect to the Meter using a
cross-over network cable between your PC’s network port and the Meter. After
you’re done with configuring the Meter, you can always set your PC back to its
original settings. See Section 3.5.2 for more details.
On your computer, from the MS-DOS Prompt window type "ping 192.168.1.200
and press Enter. If DHCP and DNS servers are used type "ping wisxxxx", where
xxxx are the last four digits of the Meter’s MAC address, located on the meter. You
should get a reply as shown in Figure 4.1.
You can use the host name (wisxxxx) instead of the IP address only if your
DHCP server is configured to communicate with your DNS. Please consult
with your IT department for details.
4.0 Testing the Connection
"
Figure 4.1 Pinging the Meter from MS-DOS Prompt
This proves that the connection is proper and you can get into configuration or
run mode using the Telnet or Web browser.
21
4.1 iConnect Software
The Meter may also be assigned an IP Address by using the iConnect software.
a)Download the iConnect software from the website listed in this manual.
b)Install iConnect software on a networked PC. This software is compatible
with Windows 95, 98, NT, 2000, and XP.
c)Use iConnect to assign an IP address to the Meter and access its web
pages for configuration. You can also use any standard web browser to
access the Wireless System’ web pages. Consult with your IT department
for obtaining an IP address.
Figure 4.2 Assigning an IP Address using iConnect
1)Place the IP address in this box.
2)Take the MAC address from the label attached to the bottom of the Meter
and place it in this box.
3)Click here to send the above IP address to the Meter.
4)After the IP address is assigned to the Meter, click here to access it’s web
pages.
5)Click here to Ping the Meter whose IP address is shown in the IP address box.
6)Click here to find all the Meters on your network .
7)The IP addresses for the Meters found by the iConnect will be listed here.
8)These fields indicate the IP address and the subnet mask of the PC on
which the iConnect is running.
22
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.