It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark
to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as the guide contains important information relating to safety and EMC.
This device is marked with the international caution symbol. It is important
to read this manual before installing or commissioning this device as it
contains important information relating to Safety and EMC (Electromagnetic
Compatibility).
This instrument is a panel mount device protected in accordance with EN
61010-1:2001, electrical safety requirements for electrical equipment for
measurement, control and laboratory. Installation of this instrument should
be done by qualified personnel. In order to ensure safe operation, the
following instructions should be followed.
This instrument has no power-on switch. An external switch or circuitbreaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch or
circuit-breaker shall meet the relevant requirements of IEC 947–1 and IEC
947-3 (International Electrotechnical Commission). The switch shall not be
incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn
from the main supply in case of a fault in the equipment, an overcurrent
protection device shall be installed.
•Do not exceed voltage rating on the label located on the top of the
instrument housing.
•Always disconnect power before changing signal and power
connections.
•Do not use this instrument on a work bench without its case for safety
reasons.
•Do not operate this instrument in flammable or explosive atmospheres.
•Do not expose this instrument to rain or moisture.
•Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
•Use electrical wires with adequate size to handle mechanical strain and
power requirements. Install without exposing bare wire outside the
connector to minimize electrical shock hazards.
EMC Considerations
•Whenever EMC is an issue, always use shielded cables.
•Never run signal and power wires in the same conduit.
•Use signal wire connections with twisted-pair cables.
•Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
Failure to follow all instructions and warnings may result in injury!
This is a Class A ITE product. In a domestic environment this product may
cause radio interference in which case the user may be required to take
adequate measures.
1
Page 8
1.2 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as soon
as you receive the shipment. Note any evidence of rough handling in
transit. Immediately report any damage to the shipping agent. The carrier
will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing
material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation Manual as well as free configuration software
(iConnect) are available from the website listed on the cover pagesof this manual, or on the CD-ROM enclosed with your shipment.
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
NOTE: Provides you with information that is important to successfully
setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances
or practices that can effect the instrument’s functionality and must
refer to accompanying documents.
TIP: Provides you helpful hints.
1.3 Description
The wi®Series wireless monitoring and control system features meters compatible
with a large and growing number of wireless sensors: UWTC “Universal Wireless
Thermocouple” Type J, K, T, E, R, S, B, N, and C, UWRTD “Universal Wireless
RTD” , and UWIR “Universal Wireless Infrared Temperature Sensor”. For more
information about the UWTC, UWRTD, and UWIR, refer to the separate manual for
these products.
2
Page 9
1.3 Description (continued)
The wireless sensors transmit up to four hundred feet 400’ (approx. 120 meters-without obstructions or interference) to a wiSeries meter connected directly to an
Ethernet network and the Internet. The wireless system complies with IEEE 802.15.4
operating at 2.4 GHz. The wiSeries Meter Scanner & Controller can monitor up to
eight (8) wireless sensors.
The Meter also provides error detection mechanism for inactive communication
and diagnostic information including signal strength and data transmission
success rate to help troubleshooting potential wireless system installation issues.
The Meter connects directly to an Ethernet network and the Internet and features
award-winning embedded Web Server. It is easily configured and monitored with a
Web browser over the Ethernet network or the Internet.
CONTROL, MONITOR, AND ALARM: The Meter comes standard with dual outputs
of either Form C relays, SSR’s (solid state relays) or dc Pulses that can be used for
ON/OFF control functions or alarms.
The meter can monitor alarm conditions for any or all of the wireless sensors. For
example, the meter can be set up to trip an alarm if any one of the sensors indicated
that it was above or below a pre-set alarm point.
Analog output is fully scalable and may be configured as an ON/OFF controller or retransmission to follow your readings.
MONITOR AND CONTROL LOCALLY AND OVER THE INTERNET: The wiSeries
wireless monitoring and control system provides local monitoring and control, along
with remote Web-based monitoring of temperature from thermocouples, RTD’s, and
infrared temperature sensors.
The wiSeries system let’s you monitor and record temperature over an Ethernet
network or the Internet without any special software--just your Web Browser.
ETHERNET: The wiSeries meter-controller-scanner is an independent node on the
network sending and receiving data in standard TCP/IP packets. It is easily
configured from a Web Browser and can be password protected. From within an
Ethernet LAN or over the Internet, the user simply types the IP address (such as
192.168.1.200) or an easy to remember name (such as "Oven5" or "Fixture") and
the wiSeries meter serves a Web Page with the current readings.
EMAIL ALARM: The wiSeries meter can trigger an alarm if variables go above or
below a Setpoint that you determine. Your alarm can be sent by email to a single
user or to a group distribution list, including text messages to cell phones and PDA’s.
The "Mail Notifier" software is a free and easy program for this application.
CHARTS AND GRAPHS: The wiSeries system serves Active Web Pages to display
real time readings and charts of temperature. You can also log data in standard data
formats for use in a spreadsheet or data acquisition program such as Excel or Visual
Basic. We offer a free and easy to use program iLog for logging data to Excel.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart
over the LAN or Internet in real time. With the wiSeries system there is no need to
invest time and money learning a proprietary software program to log or chart the
data. Chart scales are fully adjustable on the fly. For example, the chart can display
one minute, one hour, one day, one week, one month or one year.
be charted across the full span or within any narrow range such as (20 to 30°C).
Temperature can
3
Page 10
1.3 Description (continued)
TC
RTDTC
WIRELESS METER
(Receiver)
END DEVICES
(Transmitters)
COMPUTER
(Datalogging
Software)
COMPUTER
(Standard
Web Browser)
ETHERNET
iLD Large Display Meter
Temperature
wi8xx-U
iR
DATALOGGING: The OPC Server software makes it easy to integrate the wiSeries
wireless sensor system with many popular Data Acquisition and Automation
programs offered by NEWPORT, OMEGA, Wonderware, iConics, Intellution,
Rockwell Automation, and National Instruments, among others.
PROGRAMMABLE COLOR DISPLAY: The wiSeries features patented
programmable color displays. The display can be programmed to change color at
any Setpoint or Alarm point. For example, the meter can be programmed to display
the process value in GREEN during warm-up, switching to AMBER to signal the
normal operating range, and in RED to signal an alarm condition. The changes in
color are quickly seen from a distance, and machine operators can intuitively react to
changing conditions. The colors can be programmed to change back when the value
drops back below the alarm point or to "latch" on until being reset by the operator.
The meter can also be programmed to display only one unchanging color: GREEN,
AMBER, or RED. This is a useful way to let an operator identify, at a glance,
temperature values in three separate locations, or to display three different
measurements.
The following example Figure 1.1 illustrates how you can hookup the Temperature
Wireless System to your network:
The wireless system consists of a single Meter and one or more End Devices /
Transmitters. The End Devices will send data periodically to the Meter where it serves
as a gateway between the users and the End Devices. The users can access the data
through the Meter’s Web Server and provided data acquisition software.
A standard web browser can be used to monitor and chart temperature. The browser
can also be used to configure the meter’s IP address, passwords for access and
overall configuration parameters.
Figure 1.1 Temperature Wireless Monitor and
Control System on the Ethernet Network
4
Page 11
PART 2
1
2
C
F
12
%RH
D
12CF
Upper Display:
Temperature Values
Lower Display:
Wireless Transmitter ID#
01 thru 08
HARDWARE
2.1 Physical Characteristics and Mounting
2.1.1 Front Panel
Figure 2.1 Front Panel Display
Table 2.1 Front Panel Enunciators
1
Output 1 / Setpoint 1 / Alarm 1 indicator
2
Output 2 / Setpoint 2 / Alarm 2 indicator
°C
°F
°C unit indicator for Temperature
°F unit indicator for Temperature
Changes display to Configuration Mode and advances through menu
items. Make sure to presstwice (Stand-by) followed by pressing
(stop communication) before entering the Configuration mode.
Used in Configuration Mode to change values. In Run Mode, it’s used
to lock the display to the next sensor reading.
Used in Configuration Mode to change values. It’s also used to
resume scrolling sensors.
Accesses submenus in Configuration Mode
For complete Front Panel Pushbutton procedures, refer to the
Supplemental Guide.
The rear panel connections are shown in Figure 2.2.
Use copper conductors
only for power connections
Figure 2.2 Rear Panel Power and Output Connections
Table 2.2 Rear Panel Connector
POWERAC/DC Power Connector: All models
OUTPUT 1Based on one of the following models:
Relay SPDT
Solid State Relay (SSR)
Pulse
Analog Output (Voltage and Current)
OUTPUT 2Based on one of the following models:
Relay SPDT
Solid State Relay (SSR)
Pulse
Network Communication Interface Section:
ETHERNET RJ45 interface for 10BASE-T connection.
RESETButton: Used for power reseting the Ethernet board.
ACTIVITYLED (Red) Blinking: Indicates network activities (receiving or
sending packets).
NET LINKLED (Green) Solid: Indicates good network link.
TXLED (Yellow) Blinking: Indicates transmitting data to the serial port.
RXLED (Green) Blinking: Indicates receiving data on the serial port.
6
Page 13
2.1.3 Dimensions
3.780 [96.00]
1.890
[48.00]
0.700 [17.78]
4.325
[109.85]
1
2
C
F
12
%RH
D
12CF
PANEL THICKNESS
0.25 (6.4) MAX
0.03 (0.6) MIN
PANEL CUTOUT
1/8 DIN
Figure 2.3 Mounting Dimensions
7
Page 14
2.1.4 Assembly and Mounting
Front Bezel
Gasket
Case
Panel
Thumbnuts
Sleeve
Model No.
Label
2.1.4.1 Panel Mounting Instruction
1. Using the dimensions from the panel cutout in Figure 2.3, cut an opening in
the panel.
2. Remove sleeve from the rear of the case by removing thumbnuts.
3. Insert the case into the opening from the front of the panel, so the gasket seals
between the bezel and the front of the panel.
4. Slip the sleeve over the rear of the case.
5. Tighten the thumbnuts to hold the unit firmly in the panel.
Figure 2.4 Panel Mounting
8
Page 15
2.1.4.2 Antenna Mounting Instruction
METER MOUNTED
IN NON-METALIC
ENCLOSURE.
METER MOUNTED
IN A METALIC
ENCLOSURE.
For best reception: connect the antenna directly to the rear of the meter, if the
meter is not installed in a metal panel or enclosure.
If the rear of the meter is behind a metal panel or in a cabinet, use a coaxial
cable to position the antenna outside of the enclosure in the open air.
Use the shortest cable that can reach a suitable location. The antenna on this
Meter and any End Devices should be installed in a vertical position, pointing
towards the sky.
Metallic structure should be kept at least 0.8" (2 cm), although 2.4" (6 cm)
is recommended away from the antenna.
Any casing that encloses the antenna should be plastic. In addition, it is
also wise to avoid plastic case with dark fillers or colorants.
Refer to Section 5 for more Environmental / Operating Conditions.
Figure 2.5 Antenna Mounting
9
Page 16
2.1.4.3 Disassembly Instruction
Gasket
If necessary, the board assembly may be removed from the front of the case
housing.
Warning: Disconnect ac power from the unit before proceeding.
1. Remove the board assembly from the case by pulling at the sides of the bezel.
2. The bezel, along with the board assembly will unlatch from the case housing.
•
Depending on the size of your Ethernet connector, you may need to
disconnect it from the RJ45 jack on the rear of the meter.
•
Depending on the length of your antenna cable, you may need to
disconnect it from the rear of the meter.
Figure 2.6 Accessing the Main Board Assembly
10
Page 17
2.1.5 Electrical Installation
24 Vac or
20 to 36 Vdc
90 to 240 Vac 110 to 375 Vdc
OR
2.1.5.1 Power Connections
Warning: Do not connect ac power to your meter until you have
completed all output connections. This meter must only be installed by a
specially trained electrician with corresponding qualifications. Failure to
follow all instructions and warnings may result in injury!
Connect the main power connections as shown below.
Use copper
conductors only for
power connections
Figure 2.7 Main Power Connections
Table 2.3 Fuse Requirement (See Specifications Section)
FUSEConnectorOutput TypeFor 115Vac For 230VacDC
FUSE 1
FUSE 2
For the low voltage power option, in order to maintain the same degree of
protection as the standard high voltage input power units (90 - 240 Vac),
always use a Safety Agency Approved DC or AC source with the same
Overvoltage Category and pollution degree as the standard AC unit (90 240 Vac).
The Safety European Standard EN61010-1 for measurement, control,
and laboratory equipment requires that fuses must be specified based on
IEC127. This standard specifies for a Time-lag fuse, the letter code “T”.
The above recommended fuses are of the type IEC127-2-sheet III. Be
aware that there are significant differences between the requirements
listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a
result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse is
approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to
consult the manufacturer’s data sheets for a cross-reference.
PowerN/A 100 mA(T) 100 mA(T)100 mA(T)
Power
N/A N/AN/A400 mA(T)
11
Page 18
2.1.5.2 Wiring Outputs
This meter has two factory installed outputs. The SPDT Mechanical Relay, SPST
Solid State Relay, Pulse and Analog Output Connection are shown below.
Use copper
conductors only for
power connections
Figure 2.8
a) Mechanical Relay and SSRb) Pulse and Analog
Outputs Wiring HookupOutputs Wiring Hookup
12
Page 19
2.1.5.2 Wiring Outputs (continued)
TEMPERATURE
CONTROLLER
CONTROL
SIDE
dc INPUT
SSR
ac INPUT
SSR
ac INPUT
SSR
LOAD
SIDE
HEATER
Vac
Vac
dc CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH dc VOLTAGE SSR DRIVER OUTPUT
FAST BLOW
FUSE
0 or 5 Vdc,
TYPICALLY
4
3
1
2
TEMPERATURE
CONTROLLER
CONTROL
SIDE
LOAD
SIDE
HEATER
Vac
Vac
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT
FAST BLOW
FUSE
Vac
DRIVING
SSR
4
3
1
2
TEMPERATURE
CONTROLLER
CONTROL SIDE
LOAD
RESISTOR
LOAD
SIDE
HEATER
Vac
Vac
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT
FAST BLOW
FUSE
Vac
DRIVING
SSR
4
3
1
2
Figure 2.9 Typical Applications
13
Page 20
2.1.5.3 Jumper Settings for Display Color Setup
1
4
3
2
ON
1
ON
RED
GREEN
S1
8
GREEN
RED
S1
AMBER
S1 (Open)
S1
Display Board
To change the color of the lower display follow the instructions below:
1.
The unit should be removed from the panel and opened.
Refer to Section 2.1.4.3 for assembly and disassembly instructions.
2.
Locate S1 jumper, on the back side of the display board. Select the
position for your color choice of Red, Green or Amber.
Figure 2.10 Location of S1 Jumper
To change the color of the upper Display, see Section 4.3.7.5.
14
Page 21
2.1.5.4 Dip Switches
1
4
3
2
OFF
ON
1
4
3
2
OFF
ON
1
ON
OFF
S1
8
4 Position
DIP Switch on
Ethernet Board
8 Position
DIP Switch on
Wireless Board
OFF
ON
1
8
To change the DIP switches, follow the instructions below:
1.
The unit should be removed from the panel and opened.
Refer to Section 2.1.4.3 for assembly and disassembly instructions.
2.
Locate the 4 and 8 position DIP switches, on the top board.
The Meter is shipped with all DIP switches in "OFF" position
To set the Wireless and Ethernet settings to Factory Default, Refer to
Section 7.
1To change the
2-8N/A
Wireless settings to
Factory Default
Figure 2.11 Location of DIP Switches
1 N/A
2 To change the Ethernet settings to
Factory Default
3 To enable/disable DHCP
4 N/A
15
Page 22
2.2 Network Communication Interfaces
2.2.1 10Base-T RJ-45 Pinout
The 10BASE-T Ethernet network (RJ-45) system is used in the Meter for
network connectivity. The 10 Mbps twisted-pair Ethernet system operates over
two pairs of wires. One pair is used for receiving data signals and the other pair
is used for transmitting data signals. This means that four pins of the eight-pin
connector are used.
PinNameDescription
1+Tx+ Transmit Data
2-Tx- Transmit Data
3+RX+ Receive Data
4N/CNot Connected
5N/CNot Connected
6-Rx- Receive Data
7N/CNot Connected
8N/CNot Connected
Figure 2.12 RJ45 Pinout
2.2.2 10Base-T Crossover Wiring
When connecting the iServer directly to the computer, the transmit data pins of
the computer should be wired to the receive data pins of the Meter, and vice
versa. The 10Base-T crossover cable with pin connection assignments are
shown below.
Figure 2.13 10Base-T Crossover Cable Wiring
Use straight through cable for connecting the Meter to an Ethernet hub.
The ports on the hub are already crossed.
16
Page 23
PART 3
NETWORK CONFIGURATION
3.1 Ethernet (MAC) Address
MAC (Media Access Control) address is your computer's unique hardware
number. When you're connected to the LAN from your computer, a
correspondence table relates your IP address to your computer's physical (MAC)
address. The MAC address can be found on the label of your meter (see Figure
2.4 and 3.1) and contains 6 bytes (12 characters) of hexadecimal numbers
XX:XX:XX:XX:XX:XX For Example
Remove the small label with the default IP address and there will be room to put
your IP address.
: 0A:0C:3D:0B:0A:0B
Figure 3.1 Label Detail
3.2 Network Protocols
The Meter can be connected to the network using standard TCP/IP protocols. It
also supports ARP, HTTP (Web Server), DHCP, DNS and Telnet protocols.
3.3 DHCP
DHCP, Dynamic Host Configuration Protocol enables individual computers or
devices to extract their IP configurations from a server (DHCP server).
If the DHCP is enabled on your Meter, as soon as the Meter is connected to the
network, there is an exchange of information between DHCP server and the
Meter. During this process the IP address, the Gateway address, and the Subnet
Mask will be assigned to the Meter by the DHCP server. Note that the DHCP
server must be configured correctly to do such assignment.
17
Page 24
3.3 DHCP (continued)
The Meter is shipped with DHCP disabled (factory default).
If fixed or static IP address is desired, the DHCP must be disabled.
The DHCP can be enabled by setting the DIP switch # 3 to the "ON" position
Figure 3.2 4 Position DIP Switch
Setting the Meter’s IP address to 0.0.0.0 will also enable DHCP.
3.4 DNS
DNS, Domain Name System enables individual computers and devices to be
recognized over a network based on a specific name instead of an IP address.
For example, instead of having to use http://192.168.1.200 (IP address), you
would use only http://wis03ec or any eight character name stored as Host
Name under "Access Control" page from the Wireless System Home Page.
The default DNS name for the Meter is "wis" followed by the last four digits of
the MAC address of that particular Meter.
1. It is very important to communicate with the network administrator in
order to understand the DHCP and its existing configurations on the
host server, before enabling the DHCP on the Meter.
2. The Meters are shipped with a default static IP address of
192.168.1.200 and Subnet Mask of 255.255.255.0.
3. On Windows servers where the DCHP and DNS are separate
functions it is very important to configure the DHCP server to
communicate with the DNS in order for the iServer’s Host Name to
correctly respond. If you cannot access the iServer using its Host
Name, please contact your network administrator to make sure the
DHCP and DNS servers are linked together.
18
Page 25
3.5 IP Address
Every active device connected to the TCP/IP network must have a unique IP
address. This IP address is used to establish a connection to the Meter. Every
computer using TCP/IP should have a unique 32-bit address which is divided
into two portions, the network ID and the host ID. For instance, every computer
on the same network uses the same network ID. At the same time, all of them
have a different host ID. For more details about the IP address see Appendix B.
3.5.1 Default IP Address
The Meter is shipped with a default IP address of 192.168.1.200 and Subnet
Mask of 255.255.255.0. If you are going to use a Web browser or Telnet
program to access the Meter using its default IP address, make sure that the PC
from which you’re establishing the connection has an IP address that is in the
same range as the Meter’s IP address (192.168.1.x, where x can be any number
from 1 to 254). See Section 3.5.2.
Your PC’s IP address cannot
You also need to make sure that your PC’s Subnet Mask is 255.255.255.0. This
is a good way to access the Meter over the network and make any configuration
changes needed. If 192.168.1.200 is already in use on your network, use an
Ethernet crossover cable between your computer and the Meter to change the IP
address or any other settings within the Meter.
be the same as the Meter’s IP address.
19
Page 26
3.5.2 Changing TCP/IP Properties on Your Computer
Go to your computer’s Control Panel then Network Connections.
Pick the network with the proper Ethernet card. Right click and choose
Properties
Look for Internet Protocol, click on it
and press Properties
Figure 3.3 Network Connections
Setup the IP address (in this case, 192.168.1.1) as shown below and press OK
You can access the Meter’s Web
Server via any internet browser
using IP address of 192.168.1.200.
Once you log into the Meter’s Web
Server, you will be able to change its
IP configuration according to
Section 4.2.
After you configure the
Meter’s IP configurations,
you should go back and set
your PC’s previous IP
settings.
.
Figure 3.4 Network Connections
20
Page 27
PART 4
NETWORK OPERATIONS
This Meter can be used and configured in several ways, depending on user’s
preference and network setup. It can be configured using a Web browser, like
Internet Explorer. It can also be configured using the iConnect Configuration
Software.
If DHCP and DNS servers are configured to exchange information, the
connection will be very simple. All you need to do is to enable DHCP on the
Meter (see Section 3.3) and use a straight through network cable to connect the
Meter to an Ethernet hub or switch and power it up. Now, you can use the
Meter’s default Host (Domain) Name, which is wisxxxx (where xxxx are the last
four characters of its MAC address) to access the Meter’s Web Server.
If DHCP is not the preferred method, you can configure your PC’s network
connection with an IP address of 192.168.1.x that is in the same range as the
Meter’s default IP address (192.168.1.200) and connect to the Meter using a
cross-over network cable between your PC’s network port and the Meter. After
you’re done with configuring the Meter, you can always set your PC back to its
original settings. See Section 3.5.2 for more details.
On your computer, from the MS-DOS Prompt window type "ping 192.168.1.200
and press Enter. If DHCP and DNS servers are used type "ping wisxxxx", where
xxxx are the last four digits of the Meter’s MAC address, located on the meter. You
should get a reply as shown in Figure 4.1.
You can use the host name (wisxxxx) instead of the IP address only if your
DHCP server is configured to communicate with your DNS. Please consult
with your IT department for details.
4.0 Testing the Connection
"
Figure 4.1 Pinging the Meter from MS-DOS Prompt
This proves that the connection is proper and you can get into configuration or
run mode using the Telnet or Web browser.
21
Page 28
4.1 iConnect Software
The Meter may also be assigned an IP Address by using the iConnect software.
a)Download the iConnect software from the website listed in this manual.
b)Install iConnect software on a networked PC. This software is compatible
with Windows 95, 98, NT, 2000, and XP.
c)Use iConnect to assign an IP address to the Meter and access its web
pages for configuration. You can also use any standard web browser to
access the Wireless System’ web pages. Consult with your IT department
for obtaining an IP address.
Figure 4.2 Assigning an IP Address using iConnect
1)Place the IP address in this box.
2)Take the MAC address from the label attached to the bottom of the Meter
and place it in this box.
3)Click here to send the above IP address to the Meter.
4)After the IP address is assigned to the Meter, click here to access it’s web
pages.
5)Click here to Ping the Meter whose IP address is shown in the IP address box.
6)Click here to find all the Meters on your network .
7)The IP addresses for the Meters found by the iConnect will be listed here.
8)These fields indicate the IP address and the subnet mask of the PC on
which the iConnect is running.
22
Page 29
4.1 iConnect Software (continued)
WIRELESS SENSOR HOME PAGE
d)To access the Wireless System for Configuration:
Click on the "View Webpage" button, you will access the Wireless System’s
home page, refer to Section 4.3 for details.
Figure 4.3 Accessing the Wireless System for Configuration
23
Page 30
4.2 Setting a New IP Address over the Network
ACCESS CONTROL
ACCESS CONTROL
http://192.168.1.200
Address
Main Menu
Login Password 12345678
Admin Password
00000000
IP Address 192.168.1.200
Gateway Address
0.0.0.0
Subnet Mask
255.255.255.0
MAC Address 00:03:03:00:21:D9
Host Name wis21d9
Save Reset
Network Reset
Besides using the iConnect software, you may use the Meter’s default IP
address to access it and assign a new IP address to it.
The Meter is shipped with a default IP address of 192.168.1.200 and Subnet Mask
of 255.255.255.0. You can configure your PC’s Network connection with an IP
address that is in the same range as the Meter’s IP address (192.168.1.x) and
connect to the Meter using a crossover network cable between your PC and the
Meter.
With this completed, you can go to the DOS-Prompt and ping 192.168.1.200. If
you receive responses back (Figure 4.1), you can go to the Web browser and
type in http://192.168.1.200
Page.
Selectbutton, you’ll be asked for the password. You should be
Access Control
on the Access Control page were you can simply type in the desired Static IP
address, and click Save.
For more details about the
and it will take you to the Wireless System’ Home
"
Access Control"page refer to Section 4.3.10.
For the IP address to take effect, the Meter needs to be turned OFF and ON
using the "Network Reset" button. Pressing the physical button marked "RESET"
on the Meter does the same thing.
You can now connect the Meter to an Ethernet hub using a straight through
cable, power it up, and follow the ping routine mentioned in the previous section.
Figure 4.4 Access Control
24
Page 31
4.3 Meter’s Configurations and Operations
Using a web browser, you should be able to view the Meter’s homepage.
• Start your web browser.
• From the browser you type http://wisxxxx
MAC address label located on the Meter (see Figure 3.1), if DHCP and DNS
are used. If a static IP address is used, then simply type http://x.x.x.xx.x.x.x is the Meter’s IP address.
• The Home Page, will be displayed.
using the last four-digits from the
, where
Figure 4.5 Wireless System Home Page Menu
In order to access certain menu items of the Home Page, users may be
prompted for a password, as shown in the two following figures.
25
Page 32
4.3 Meter’s Configurations and Operations (continued)
ADMINISTRATOR
ADMINISTRATOR
LOGIN
LOGIN
http://192.168.1.200http://192.168.1.200
Figure 4.6 LOGIN and ADMINISTRATOR Passwords
There are 2 different access levels:
1. ADMINISTRATOR Password
(administrator) allows certain groups and
individual users to access and modify parameters without any restrictions.
The default password is 00000000. This password can be up to 16
alphanumeric case-sensitive characters.
2. LOGIN Password
(operator) allows users to access and modify all of the
parameters, except "Access Control" which requires an Administrator
password.
The default password is 12345678. This password can be up to 16
alphanumeric case-sensitive characters.
4.3.1 Power Up Meter
For instructions on how to power the Meter, refer to Section 2.1.5.
To verify that an End Device is working before deploying remotely, install the
battery and power it on right next to the Meter. When the End Device is powered
on, the green LED (TX) will blink periodically. This indicates the End Device is
broadcasting its data to the Meter on channel 12 defined by IEEE 802.15.4.
The LED will blink only when the End Device sends data to the Meter. If the
Meter is not powered on, or it’s out of reach, the End Device will not receive the
acknowledgment packet from the Meter and therfore to save battery power it will
go to sleep.
The sleeping period can be defined by the users via the USB port (PC
Configuration software) on the End Device. The End Device sends new data for
a short period of time after every sleep period is over, until it can establish the
connection back with the Meter.
When there are two End Devices with the same Device ID/address, both
will be transmitting data every sampling period with their LEDs blinking.
The Meter will receive data from both End Devices and will display their
verify that the Meter is displaying the correct data.
data alternately. To avoid this, turn the End Device on one by one and
Once you see the End Device’s LED blinking periodically, it means it is sending
data which will appear on the "Readings" page. To view the data in a chart
format, you can use the "Chart" page.
Click on from the Home Page, the following page will appear, showing
updates of the Process and Ambient Temperature.
Readings
Figure 4.7 Readings
While accessing the "Readings" page, If a blank screen appears without
any "java application running" or image of a "Java logo", please verify you
have the latest Java Runtime Environment installed and configured
according to the Section 4.3.3.1. If you do not have Java Runtime
Environment, you may download it from our website or contact the
Customer Service Department nearest you.
The "Readings" fields are defined as follows:
Title
: Meter’s name, assigned in Network Setup Menu.
Name
: End Device’s name, assigned in End Device Setup Menu.
Reading Values
: The order from left to right is Process Temperature, then Ambient.
First Reading: Process - process temperature reading with temperature unit.
Second Reading: Ambient - built-in sensor temperature reading with
temperature unit.
Reading "Open" indicates that no sensing device is detected.
27
Page 34
4.3.2 Get Readings from the End Device (continued)
ID: End Device ID/address
Sequence
The Sequence number is incremented for each newly received data. Therefore,
it indicates if the sensor is transmitting data successfully.
Strength
Success
battery lifetime and high network traffic.
Battery
gets to 3.0V, the batteries should be replaced.
Update
Running/Lost
Device. It displays "Lost" if the Meter has not received data from the End Device.
Data Logging
activate data logging, a file browser pops up to ask for which file data will be
saved. Data is in Comma Separated Value (csv) format, which can also be
opened in Excel. Please name file with .csv extension.
: Sequence number [0-255 ].
: It is the radio signal strength (0-100%), the higher the better.
: 0-100%, a low success rate indicates a longer data delay, shorter
: The total voltage of the battery in the End Device. Once the voltage
: The time interval the Meter received data from the End Device.
: It displays "Running" if the Meter is receiving packages from the End
: Press to activate/de-activate data logging. When it is pressed to
Figure 4.8 Comma Separated Value Format
Columns from left to right: Date and time, Device ID, Device name, Reading 1,
Unit 1, Reading 2, Unit 2, Sequence number, Signal strength, Success rate,
Battery voltage, Status, Update, Next Device ID, Next Device name (up to 8 End
Devices).
ACTIVE data is currently being logged in the specified file.
INACTIVE data logging is not executed.
Refresh
: How often the current applet asks for data from the embedded server.
See Section 4.3.4 before activating data logging.
28
Page 35
4.3.3 Java Runtime Environment Setup
If your computer does not have Java installed, please download from
java.sun.com. You can change the Java setting by clicking its icon in Control
Panel. To load the applet, you have to enable the web browser and disable
cache.
1. Go to your computer's Control Panel. Open the Java Plug-in
2. Click on "Settings" & "View Applets" in the "General" tab.
3. Select the "Settings" button on the General Tab
Un-check the "Enable Caching" box. Then close dialog box to show the
General Tab again
4. Select the "Network Settings" button on the General Tab.
Proceed to the Browser tab. Follow the Browser Proxy Selection
instructions below.You should either select the "Use Browser Settings"
option or the "Direct Connection" option depending on the network
connections between your computer and the Meter. (Generally, select
"Direct Connection" if accessing the Meter on your local network and
select "Use Browser Settings" option for access from your internal
network to the internet.)
5. Refresh or restart the webpage.
For Java Version 1.5.x.x it is found under "General" > "Settings" > "View Applets"
and then at the bottom there is the Checkbox to REMOVE CACHE .
Figure 4.9 Java 1.5.x.x. Screen Shots
29
Page 36
For Java 1.6.x.x it is similar to Java 1.5.x.x but there is no need to
Java (TM) Plug-in Control Panel
AdvancedBasicProxiesBrowserCertificatesCacheAbout
Update
Enable Caching
Cache Settings
ViewClear
Location
Size
Jar Compression
MB
Unlimited
C:\Documents and Settings\AppData\Sun\Java\Deploymentcache\java
1. Go to your computer's Control Panel. Open the Java Plug-in
2. Select the "Cache" Tab
Un-check the "Enable Caching" box
3. Select the "Proxy" Tab. Follow these Browser Proxy Selection
instructions below. (Generally, un-check the box if accessing the Meter
on your local network and check the box for access from your internal
network to the internet.)
4. Refresh or restart the webpage.
To disable cache setting:
For Java Version 1.4.2.x it is found under the CACHE TAB.
Figure 4.10 Java 1.4.2.x Screen Shot
30
Page 37
4.3.3.3 Browser Proxy Selection
Accessing Meter units within your internal network
•Usually when the computer and Meters are on an internal network, you will
not use Proxy server access.
•You should un-check the "Use Browser Settings" option on the "Proxy" tab.
Accessing Meter units using the internet
•Often the web browser will use Proxy server access to the internet. In such
cases, the default Java runtime settings on the "Proxy" tab should suffice.
The default setting is the "Use Browser Settings" option.
•If the default proxy setting doesn't work, then you may have a situation where
the proxy settings of the web browser are incorrect.
Diagnostics:
If the web page of the Wireless System appears, then the HTTP Proxy is
working fine.
If the data isn't updated on the Wireless System upon selecting the "Readings"
page, there may be a problem with access through a winsock proxy server. In such
cases your network administrator will need to provide the winsock proxy server and
port #s. (The TCP ports the Meter uses for Java applets are 1000 and 2003).
These values should be entered into the Socks line on the "Proxy" tab (of the
Java Plugin control panel) or into the "connections" tab on the View,Internet
Options dialog and make sure that the Proxy tab shows that the "Use Browser
Settings" option is not selected (i.e. when you specify proxy connections in the
Java Plugin control panel).
Accessing Meter units over Peer-to-Peer network
A simple peer-to-peer network is setup by disconnecting from the main network
(as users will often do when trying to do initial setup of the Meter) and then
connecting the Meter to another computer using an ethernet hub, an ethernet
switch, or a Cross-over cable connection.
Often when using a peer-to-peer network, the Java plugin and the web browser
(such as Internet Explorer) have internet connections configured to connect
through proxy servers. In such case, you will need to simply assign the final IP
address on this peer to peer network and then view the Wireless System’s charts
after connecting the Meter into the regular network. Otherwise you can disable
the Java plug-in's "Use Browser Settings" temporarily and then reconfigure the
Java plug-in settings for regular network access after testing the Wireless
System’s chart access on your peer-to-peer network.
The "Use Browser Settings" should not be selected. And the HTTP and Socks
proxy entries should be blank. Also, setup the internet browser so that proxy
servers are disabled.
Java and the Java Coffee Cup Logo are trademarks or registered trademarks of Sun Microsystems, Inc. in the U.S. and
other countries."
31
Page 38
4.3.4 Java Policy
To activate data logging and save graphs from the Java applets, it is necessary
to create a Java Policy file and copy it onto a folder.
1)Open a Notepad file and using the IP address of the Meter type the
following:
grant codeBase "http://192.168.1.200/"
{
permission java.security.AllPermission "*", "*";
};
This file should have the IP address of the Meter; in this case the default
IP address is 192.168.1.200. If the IP address is changed, then the IP
address shown in the file needs to be changed; otherwise, it will not work.
If more than one Meter is being monitored from the same computer, it is
necessary to repeat the above for each of the Meters in the same
"java_policy.txt" file.
If DHCP/DNS is enabled, the unique Meter’s name using DNS should replace
the IP address. Example: "http:\\zSrvTEST". Make sure the DHCP server
updates the DNS table to keep track of the Meter’s name and IP addresses
(consult with your network administrator).
2)Save the file as java_policy.txt.
3)Create a folder in your C: drive called "0_JAVAPOLICY".
4)Place the java.policy.policy file into the "0_JAVAPOLICY" folder.
Figure 4.11 Java Policy
32
Page 39
4.3.4 Java Policy (continued)
Java Runtime Settings
Control Panel
Java Control Panel
Control Panel
Address
CommentsName
JavaJava(TM) Control Panel
General UpdateSecurity AdvancedJava
Java Applet Runtime Settings
Runtime settings are used when an applet is executed in the browser.
c.Click OK on the Java Runtime Settings window.
d.Click Apply on the Java Control Panel window and then OK.
6) Close all opened Web browser.
Figure 4.12 Java Policy
The "Data Logging" and "Save Current Graph" buttons in the "Readings"
and "Chart" pages will not be active if the instructions explained in the
above Section 4.3.4 are not followed.
33
Page 40
4.3.5 Chart
wiSeries
Main Menu
CHART
(2 Seconds/Div)
1 Minute
1 Minute
1 Day
1 Week
1 Month
1 Year
0
5
C/Div
50
1200
300
100%
0%
10
%/Div
90
hPa/Div
ChPa
Tue Feb 5 10:19:10 PDT 2008Tue Feb 5 10:18:10 PDT 2008
http://192.168.1.200
Min/Max Temperature
48.0/41.0
P1 Process
P2 Sensor 2
P3 Process
P4 Process
P5 Process
P6 Process
P7 Process
P8 Sensor 8
A1 Ambient
A2 Sensor 2
A3 Ambient
A4 Ambient
A5 Ambient
A6 Ambient
A7 Ambient
A8 Sensor 8
Save Current Graph
Click on from the Home Page, the following page will appear.
The Java™ Applet graph displays Process Temperature and Ambient
Temperature. It can be charted across the full span or within any narrow range
(such as 20 to 30ºC).
Chart
If a blank screen appears without any "java application running" or image
of a "Java logo", please verify you have the latest Java Runtime
Environment installed and configured according to the instructions (refer
to Section 4.3.3.1). If you do not have Java Runtime Environment, you
may download it from our website or contact the Customer Service
Department nearest you.
Figure 4.13 Chart
34
Page 41
4.3.5 Chart (continued)
Title: Meter’s name, assigned in "Network Setup" page.
Save Current Graph: Save the current graph in PNG (Portable Network
Graphics) format. The filename has the extension .png.
Max/Min Temperature: Maximum and minimum temperature of the current
graph.
If a sensor is selected (trend line and sensor name turns bold), its most current
temperature reading is shown here.
Reading "Open" indicates that no sensing device is detected.
Temperature Unit: Temperature unit to be used, either ºC or ºF.
P# button (Process): P# shows the sensor name (assigned in the End Device
Setup Menu) and controls the process sensor readings.
When clicked once, it turns bold, highlights the process sensor trend line and
displays current sensor readings.
When clicked twice, it turns white and the trend line will disappear.
When clicked again, it comes back to normal operation.
Chart Area: Display the trend lines of the sensors.
Range of temperature can be controlled by the upper and lower boxes on the
left.
A# button (Ambient): A# shows the sensor name (assigned in the End Device
Setup Menu), displays error messages [Lost] and controls the ambient sensor
readings.
When clicked once, it turns bold, highlights ambient sensor trend line and
displays current sensor readings.
When clicked twice, it turns white and the trend line will disappear.
When clicked again, it comes back to normal operation.
Applet Start Date and Time: Activates when the "Chart" page opens up.
X-axis Drop-down List: Time scale for the chart.
The chart area can be shown based on 1 min, 1 hour, 1 day, 1 week, 1 month, or
1 year time intervals.
Last Update Date and Time: The last date and time when data arrived.
35
Page 42
4.3.6 Controller Setup
Please refer to local regulations for the allowed maximum transmission power
Transmission Power
PID 13106 (version x.x)
iSeries Firmware Version x.x
Input
Setpoints & On/Off
Alarm 2
Alarm 1
Passcode ID
Display
Permanent Store
Enable Standby Mode Before Configuring Unit
Scrolling
Main Menu
CONTROLLER SETUP
Setup
Transmission Power
Misc.
Monitor
CONTROLLER SETUP
http://192.168.1.200Address
Update
Update
20dBm
End Device ID -
Reset Controller
Disable Standby
Enable Standby
Channel 12
Input
Setpoints & On/Off
Alarm 2
Analog Out
CONTROLLER SETUP
Setup
CONTROLLER SETUP
http://192.168.1.200Address
The Meter has two modes of operations. One is through the Front Panel Buttons
(please refer to Front Panel Supplement for more details), and the other is by
using the browser to configure the settings. Click on from the Home
Page. In a few seconds the following page will appear.
A
B
Controller
This portion of
the menu will
be different
only if you have the
Analog Output Option
installed in your Meter.
C
D
Figure 4.14 Controller Setup
Please refer to
local
regulations for
the maximum
allowed transmission
power.
36
Page 43
4.3.6 Controller Setup (continued)
Below are the definitions of terms used in the Controller Setup page.
A) Setup:
Clicking on the options shown, allows user to modify the different parameters
shown under this menu (see Section 4.3.7. Setup Page for more details)
B) Monitor:
Scrolling: If checked, the Meter will display data from all the End Devices.
Otherwise, it only displays data from the End Device specified on Device ID.
End Device ID: Address/ID of the End Device that will be display on the Meter.
C) Transmission Power:
Channel 12: The Meter communicates in a fixed channel. Operation channel
#12 defined in IEEE 802.15.4 for the sensor network.
Transmission Power: This determines the signal power transmitted by the
Meter. The options are 10 dBm and 20 dBm.
Please refer to local regulations for the allowed maximum transmission
power.
For additional details, please refer to Appendix F
D) Miscellaneous:
PID 13106 (version): The Personal Network ID is fixed to 13106. In parenthesis
is the firmware version of the radio module. The firmware version is also shown
on a label attached to the Meter (see Figure 3.1).
iSeries Version: The firmware version of the Meter. The firmware version is
also shown on a label attached to the Meter (see Figure 3.1)
37
Page 44
4.3.7 Setup
Temperature Unit
F
Filter
4
Control End Device ID:
for Retransmission and On/Off
5
Main Menu
SETUP
Input
SETUP
http://192.168.1.200Address
Cancel
Update
This section is used to configure the Meter online. Click on the specific settings
to change the parameters on that section
4.3.7.1 Input
Control End Device ID: Insert the End Device ID number that will be used as
input to control
Filter: This option allows the user to specify the number of readings stored in
the Digital Averaging Filter. Choice of: 1, 2, 4, 8, 16, 32, 64, 124.
Temperature Unit: Unit of temperature readings, [ ºC or ºF ].
Figure 4.15 Input
38
Page 45
4.3.7.2 Setpoints & On/Off Control
Auto Setpoint Deviation: If "enabled", allows changes to Setpoint 1 to be
made automatically to Setpoint 2. This mode is very helpful if the Temperature
changes often.
In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts
away from SP1--this relation remains fixed when SP1 is changed.
For instance:
Setting SP1=200 and SP2=20 and enabling SP Deviation means that the
absolute value of SP2=220.
Moving SP1 to 300, the absolute value of SP2 becomes 320.
Setpoint 1: This setpoint controls Output 1
Setpoint 2: This setpoint controls Output 2
Permanent Store: Check to save Setpoints in the Meter’s permanent storage.
On/Off 1 and On/Off 2: To enable and disable On/Off Control. Enabling On/Off
Controls will disable the Alarms, and vice versa.
DeadBand: The Dead Band or neutral zone, is the number of degrees counts
around Setpoint 1 (or Setpoint 2 if On/Off 2) which the temperature value must
pass above or below the Setpoint before the output changes state.
Action: Choice of direct or reverse. The error that results from the
measurement of the Process Variable may be positive or negative since it may
be greater or smaller than the Setpoint.
If a positive error should cause the Meter output to increase (i.e. cooling), it
would be called Direct Acting.
If a negative error should cause the output to increase (i.e. heating), it would be
called Reverse Acting.
39
Page 46
4.3.7.2 Setpoints & On/Off Control (continued)
Setpoint 2
Permanent Store
100
DeadBand
DeadBand
On/Off 1
On/Off 2
Auto Setpoint Deviation
Disabled
Disabled
Disabled
Direct
0
Setpoint 1
0
Action
Action
Reverse
0
Main Menu
SETUP
Setpoints & On/Off Control
SETUP
http://192.168.1.200
Address
Cancel
Update
Figure 4.16 Setpoints & On/Off Control
40
Page 47
4.3.7.3 Alarms 1 & 2
Alarm 1 (or 2) Relay: to enable or disable (no alarm function) the alarms .
Alarm 1 (or 2) Low: editable box for the low alarm value.
Alarm 1 (or 2) High: editable box for the high alarm value.
Active: If Above, Alarm condition triggered when the process variable is greater
than the Alarm Hi Value (Low value ignored).
If Below, Alarm condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
If Hi/Low, Alarm condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
If Band, Alarm condition triggered when the process variable is above or below
the "band" set around the Setpoint. Band equals Hi Value (Low Value ignored).
A "band" is set around the Setpoint only in the "Deviation" Mode.
Normally: if Open, then the relay is "energized" only when an alarm condition
occurs.
If Closed, this is "Fail Safe" Mode. Relay is energized under "normal" conditions
and becomes de-energized during alarm or power failure.
Latch: if Latched, Alarm remains "latched" until reset.
If Unlatched, Alarm remains latched only as long as the alarm condition is true.
Absolute: if Absolute, this allows Alarms to function independently from their
respective Setpoints. If the process being monitored does not change often, then
"Absolute" Mode is recommended.
If Deviation, this allows changes to Setpoints to be made automatically to their
corresponding Alarms. Deviation Mode is typically the ideal mode if the process
temperature changes often. In Deviation Mode, set Alarm 1 a certain number of
degrees or counts away from Setpoints, this relation remains fixed even if
Setpoints are changed.
Alarm at Power On: If the alarm is enabled at Power On, the alarm will be
active right after reset for all the End Devices (given the conditions are met),
except the End Device designated in the "Input" menu of the Web Server.
If the alarm is disabled at Power On, the alarm will become enabled when the
process value enters the non alarm area. The alarm is not active while the
process value is approaching the Setpoints.
Errors indicating "lost" or "open" sensor condition can trigger the alarm if
the alarm is set for "active high" above 9000 degrees.
41
Page 48
4.3.7.3 Alarms 1 & 2 (continued)
Normally
Alarm at Power On:
Alarm could be
triggered immediately by non-controlling
end device at startup.
Absolute
Active
Alarm 1 Relay
Alarm 1 Low
Enabled
0
Above
Absolute
Enabled
Alarm 1 High
100
Latch
Unlatched
Open
Main Menu
SETUP
Alarm 1
SETUP
http://192.168.1.200
Address
Cancel
Update
Figure 4.17 Alarms 1 & 2
42
Page 49
Input High
Output Low
Retransmission
Voltage/Current
Enabled
Voltage
0.00
Input Low
0
Output High
10.00
Min. 0V
Max. 10V
1000
Main Menu
SETUP
Analog Output Retransmission
SETUP
http://192.168.1.200
Address
Cancel
Update
4.3.7.4 Analog Output Retransmission
This menu will appear only if you have the Analog Output Option installed
in your Meter.
Figure 4.18 Analog Output Retransmission
Retransmission: When enabled, the input data will be scaled based on Input
Low and Input High and will be outputted. If the input reaches high value the
output will be 10V or 20mA. If the input reaches low value, the output will be
0V or 0mA.
Voltage/Current: Select the output to be Voltage (0-10V) or Current (0-20mA).
Input Low: The minimum input value scaled for Output Low.
Output Low: Output Voltage or Current represented by Input Low.
Input High: The minimum input value scaled for Output High.
Output High: Output Voltage or Current represented by Input High.
43
Page 50
4.3.7.5 Display
Screen Update (seconds)
3
Normal
Green
Alarm 1
Red
Alarm 2
Amber
Main Menu
SETUP
Display
SETUP
http://192.168.1.200
Address
Cancel
Update
This submenu allows the user to select the color of the display--green, red,
amber.
Screen Update: Editable box to enter the display time in seconds between each
End Device.
Normal: Choose the display color of temperature when it is in the normal stage.
Alarm 1: Choose the display color of temperature when alarm 1 is true.
Alarm 2: Choose the display color of temperature when alarm 2 is true.
In order to display one color, set the same display color on all three
submenus.
If user wants the Display to change color every time when both Alarm 1
and Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Figure 4.19a Display Menu
44
Page 51
4.3.7.5 Display (continued)
Screen Update (seconds)
3
Normal
Green
Alarm 2
Amber
Main Menu
SETUP
Display
SETUP
http://192.168.1.200
Address
Cancel
Update
This version of the menu will appear only if you have the Analog Output
Option installed in your Meter.
Figure 4.19b Display Menu (if Analog Output Option)
45
Page 52
4.3.7.5.1 Display Color Examples
Example 1:
Output 1 & Output 2
Alarm Setup
Alarm 1 HI Value "
"Color Display" Setup
Alarm 1 Color "
To prevent unauthorized tampering with the setup parameters, the Meter
provides protection by requiring the user to enter the ID Code before allowing
access to subsequent menus of the Meter’s front panel. If the ID Code entered
does not match the ID Code stored, the Meter responds with an error message
and access to subsequent menus will be denied.
Setpoint ID: If enabled, ID Code is set to Setpoint ID Security Level and if a
user attempts to enter the Configuration Menu, using the Front Panel Buttons,
they will be prompted to enter an ID Code.
Full ID: If enabled, ID Code is set to Full Security Level and if a user attempts to
enter the Main Menu, using the Front Panel Buttons, they will be prompted to
enter an ID Code.
ID: editable box to enter the 4 digit ID Code. Default is 0000.
Figure 4.20 ID Code
48
Page 55
4.3.8 Network Setup
Remote IP Address
Remote Port
0.0.0.0
02000
Remote Access
Disable
TCP/UDP
Server Type
TCP
Command
Forward CR
Disable
Secured Applet
Title
wiSeries
Number of Connections
1
Port
02000
Main Menu
NETWORK SETUP
General
Terminal Server
Remote Access (Tunneling)
NETWORK SETUP
http://192.168.1.200Address
Update
Click on from the Home Page, the following page will appear.
A
B
Network Setup
C
Figure 4.21 Network Setup
49
Page 56
4.3.8 Network Setup (continued)
A) General
Secured Applet: If checked, the LOGIN password is required to open
"Readings" and "Chart" pages.
Title: Meter’s name [maximum of 16 alphanumeric characters], shows on the
"Chart" and "Reading" pages.
B) Terminal Server
TCP/UDP*: The Meter supports TCP and UDP protocols (default is TCP). If UDP
is selected, it can be configured either for Broadcast UDP or Directed UDP. In case
of Broadcast UDP, the Meter will transmit the data to every node on the network.
This can be accomplished if the Remote IP Address is set to 255.255.255.255.
The Broadcast UDP is a practical solution when one Meter needs to communicate
with multiple nodes over the network. In the case of directed UDP, the Meter will
transmit the data to a specific node on the network. This can be accomplished if
the Remote IP Address is set to the IP address of that specific node.
Server Type: Continuous mode sends the temperature to the Ethernet, every
two seconds. It is mainly used to send readings to a remote display. Command
mode (default) needs a command to query the Meter to send the response back
to querying device.
Forward CR: Forward CR can be enabled and disabled. If enabled the Meter will
forward a <CR> along with the data to a network host in Command mode
Number of Connections: The range is from 0 to 5. If 0 is selected, the Terminal
Server feature is disabled. This means that no network connection can be made
to the Meter. If 1 is selected, only one network connection can be made to the
Meter. Any number more than 1 would allow that number of network hosts to read
from the Meter simultaneously (default is 5).
Port: Port number for TCP connections. Invalid ports: <500, >65536, 1000, 2002,
2003, and 7011.
C) Remote Access
Remote IP Address: The Meter can establish a connection to a remote device
(e.g. an iLD Remote Display with an Ethernet embedded board) with this IP.
Remote Port: (default 2000) the remote port number for the connection.
Ports 1000 (used for HTTPget, refer to Section 4.5), 2002, 2003, and 7011 are
reserved for internal use.
Remote Access: ** Remote Access can be enabled and disabled. If enabled,
the Meter can send its data to a remote node on the same network (the "Remote
IP address" and "Remote Port" must be entered).
* TCP/UDP: when UDP mode and Continuous are selected, Remote Access
should be disabled and Remote IP and Port are the UDP remote listening IP and
Port. If the Remote IP is set to 255.255.255.255, the UDP packet becomes a
broadcasting packet which will allow any device listening to the Remote port to
receive the packet.
** If Remote Access is enabled, Terminal Server is automatically disabled.
Update: Saves and Updates any changes on the "Network Setup" page.
Name Update Network Units Remote Format EndChar Display Alarm
Click on End Device ID to modify Sensor Parameters.
Network: Access Data from Network/Applet
Display: Display Reading during Scrolling
Alarm: Enable to Trigger Controller Alarm
Address
Click on from the Home Page, the following page will appear.
End Device
Figure 4.22 End Device Setup
51
Page 58
4.3.9 End Device Setup (continued)
The End Device Setup Page is for configuring the End Device parameters such
as Name and Update Rate.
#: End Device ID/address configured on the End Device. Click on the number
(1 to 8) to view device and modify End Device Parameters.
Name: Name of an End Device, shows on the "Readings" and "Chart" pages.
It is modified on the "End Device Parameters" page.
Update: How often the Meter is expected to receive data from an End Device.
It is modified on the "End Device Parameters" page.
Network: Each check box controls whether or not readings from the End Device
will be outputted.
If unchecked, the reading from the End Device will not be displayed on the
"Readings" and "Chart" pages nor it will be reported through Telnet.
Each End Device has two boxes assigned: the first is for the process sensor, and
the second is for the ambient sensor.
Units: Type of data and the corresponding units [ºC or ºF].
Units of measurement from sensors inside an End Device that has joined the
network will be displayed.
It is modified on the Controller Setup "Input" page.
Remote Format: Modified on the "End Device Parameters" page.
End Char: Modified on the "End Device Parameters" page.
Display: Modified on the "End Device Parameters" page.
Alarm: Modified on the "End Device Parameters" page.
Update: After checking/unchecking the boxes, make sure this is clicked to save
the changes.
Readings: This will take you to the "Readings" page.
Chart: This will take you to the "Chart" page.
4.3.9.1 End Device Parameters
Device Name: Name of this End Device, this is a text field and can take up to
16 alphanumeric characters.
52
Page 59
4.3.9.1 End Device Parameters (continued)
Remote Display Format:
Remote End Char(Hex): 0x
0000000F
0D
Offset(xxxx):C
0
Remote Display Format:
Remote End Char(Hex): 0x
0000000F
0D
Offset(xxxx):C
0
Device Name:
Update:
Sec
ABCDEFGH
120
Display:Alarm
Main Menu
END DEVICE PARAMETERS
End Device 1
END DEVICE PARAMETERS
http://192.168.1.200Address
Update
Cancel
Device Reset
Sensor2
Sensor1
Figure 4.23 End Device Parameters
53
Page 60
4.3.9.1 End Device Parameters (continued)
Engr Lab
75F
75F
Server Room
75F
77F
Clean Room
73F
75F
Engr Lab
75F
75F
Server Room
Tera Term - 206.29.25.27 VT
File Edit Setup Control Window Help
Update (Seconds): How often this End Device is sending its data to the Meter.
The default shown "update second" is 120 seconds. This update corresponds to
the sampling rate configured by using the Configuration Wizard. For detailed
steps on how to configure the sampling rate, please refer to Section 4.1 of theUWTC Manual. Non zero update rate will enable success calculation and lost
detection features. Update rate should reflect the actual blinking interval in order
to enhance the accuracy of success calculation and lost detection.
Update on the webpage means how often the Meter expects a reading
coming from a End Device. The Meter uses this Update to detect lost
condition and calculate success rate. It is purely used by the Meter only,
and the End Device does not recognize the Update on the webpage.
Therefore, changing Update will not change the actual sample rate
stored on the End Device.
For a more accurate success rate and lost packet information, it is
necessary to keep the "Update" time, the same as the "Sampling Rate"
of the UWTC End Device.
Sensor 1
This is the field to modify the parameters for the process sensor.
Remote Display Format: Remote display format is for Server Type continuous
mode. It basically defines the way the data is shown on a Remote Display. The
default value is 0000000F. This means that the value will be displayed up to 7
digits, followed by the unit of F, for a maximum of 8 characters. Any letters before
and/or after the number will be displayed accordingly. Keep in mind that the
displayed letters will take away from the available 8 characters.
Make sure that you have enough 0’s
to display the entire temperature
value. Any extra 0’s will be ignored.
If there is no temperature unit, then
the unit will be read from the "Input"
Remote End Char: The default value is 0D
(Hex representation of <CR>). This means that
the Meter sends <CR> after each temperature
reading. This will be done either in Continuous
or Command mode.
This is how the data will appear on the host
with 0D assigned:
menu of the Controller Setup.
T75F
T74F
Figure 4.24
Remote Display
54
Page 61
4.3.9.1 End Device Parameters (continued)
ACCESS CONTROL
ACCESS CONTROL
http://192.168.1.200
Address
Main Menu
Login Password 12345678
Admin Password
00000000
IP Address 192.168.1.200
Gateway Address
0.0.0.0
Subnet Mask
255.255.255.0
MAC Address 00:03:03:00:21:D9
Host Name wis21d9
Save Reset
Network Reset
If the end character for instance is 20 (Hex representation of space), the data will
then appear as: T75F T74F
If nothing is set for the "Remote End Char" field, the Meter will then forward the
data to the LAN with no characters followed.
Offset: If it’s determined that the readings are slightly off, the user can manually
assign numerical values to adjust the readings for temperature. The unit must be
in degree C.
Display: To enable or disable numerical display on the Meter’s Front Panel. By
default, the box is checked (enabled).
Alarm: To enable or disable alarms for that particular sensor. By default, the box
is checked (enabled).
Sensor 2
This is the field to modify the parameters for the ambient sensor.
Update: Saves changes.
Cancel: Ignores all the changes and goes back to the "End Device Setup" page.
Reset Device: Reset the End Device’s readings and status. Its data will be
cleared immediately.
4.3.10 Access Control
This section describes the "Access Control" page of the Wireless System Web
interface. This page allows the users to set up the network and security
parameters of the Wireless System.
At the initial entrance to the "Access Control" page you may be prompted for the
LOGIN Password (see Figure 4.6) prior to an ADMINISTRATOR Password.
Figure 4.25 Access Control
55
Page 62
4.3.10 Access Control (continued)
Login Password: This allows users to access and modify all of the Wireless
System Home Page menu items, except "Access Control", which requires an
Administrator password. The default Login password is 12345678. This password
can be up to 16 alpha-numeric case-sensitive characters. If there is no
Password assigned (blank box) the Wireless System will not require a password
to access and modify any of the menu items, except the "Access Control" page.
Admin (administrator) Password: This allows users to access and modify the
"Access Control" page. The default password is 00000000. This password can
be up to 16 alpha-numeric case-sensitive characters.
If there is no Administrator Password assigned (blank box) the Wireless System
will not require password to access and modify "Access Control" page.
Host Name: Name of the server (DNS) max 8 characters, default is "wis" and
the last 4 digits of the MAC address. Refer to Section 3.4, DNS.
MAC Address: This is also called Hardware address or Ethernet address,
which is assigned to the Meter at production. The MAC (Media Access Control)
address is the Meter’s unique hardware number and is not changeable.
IP Address: The IP (Internet Protocol) address is a 32-bit number that identifies
each sender or Meter of information that is sent in packets across the Ethernet
or the Internet. The Meter’s default IP address is 192.168.1.200. The Meter’s IP
address should be changed to fit user’s networking environment. Consult with
your IT department for obtaining an IP address.
The DHCP will be enabled in the Meter if its IP address is set to 0.0.0.0. The
DHCP can also be enabled by setting the 4 position DIP switch #3 to ON.
Gateway Address: A gateway is a network point that acts as an entrance to
another network. A gateway is often associated with a router, which knows where
to direct a given packet of data that arrives at the gateway. If the Meter is sending
packets to another network node that is not on the same network on which the
Meter is connected, a gateway address needs to be given to the Meter. The
gateway address should be the IP address of the router connected to the same
LAN to which the Meter is connected. The Meter default gateway address is
0.0.0.0. Consult with your IT department for obtaining a gateway address.
Subnet Mask: It’s a 32-bit number that is used to determine which part of the IP
address is the network portion and which part is the host portion. The Meter
default subnet mask is 255.255.255.0. Consult with your IT department for
obtaining a subnet mask.
Save: Saves any changes for above settings.
Reset: Pressing the Reset button will set all the fields back to their original values.
Network Reset: Reboots the embedded server. Note that all updated network
parameters take effect after reboot.
Changes made in the Access Control page can be saved permanently by
pressing the Save button and pressing the Network Reset button).
56
Login
Page 63
4.4 Telnet Setup
In the "Network Setup" page, under the Terminal Server section, set the TCP
Connections to 1 to 5 other than 0, and use a telnet emulation program to
connect to the Meter (using Port 2000). The command can be sent to query the
Meter and get a response back.
Table 4.1 List of ASCII / Telnet Commands (01 indicates End Device #1)
CommandDescriptionResponse
*SR01a\rReading from Sensor1 (process)66F
*SR01b\rReading from Sensor2 (ambient)68F
*SR01e\rReadings from Sensor166F
and Sensor268F
*SR01f\rSequence number (0-255)90
*SR01g\rSensor type230
*SR01h\rSignal strength (0-100%)49
*SR01i\rSuccess rate (0-100%)100
*SR01j\rBattery voltage (mV)2810
*SR01k\rDevice status (hex, msb on the left hand side)
12th bit: set to enable alarm control
8th bit: set to enable display
7th bit: set when Open detected1100
6th bit: set when Lost detected
*SR01l\rExpected sample rate in seconds 120
(also known as update time)
*SR01n\rNameConf Room
*SR01o\rReadings from Sensor1 in Celsius19
*SR01p\rReadings from Sensor2 in Celsius20
*SR00z\rDisplay all information
1 230 P66 F A68 F 90 49 100 2810 1100 120 Conf Room
2 230 P69 F A69 F 80 44 100 2810 1100 120 Engr Lab
6 230 P72 F A73 F 173 75 100 3110 1100 120 Server Room
7 230 P70 F A72 F 202 72 100 3450 1100 120 Clean Room
57
Page 64
4.5 HTTPget Program
The Httpget software is used to send a single HTTP or TCP request to the Meter.
In contrast, the telnet or Hyperterminal programs allow a continuous connection
with multiple requests to be sent to the Meter.
Generally HTTPget is used for simply programming an IP address to the Meter
or for quickly obtaining a reading from a End Device.
The Meter must be configured from the "Network Setup" page so that the "TCP
Connections" indicates any number between 1 and 5. Make sure that the Port
Field number indicates 2000.
Whenever Terminal Server service (using Port 2000 by default) is required, the #
of connections must be set to a value from 1 to 5. The Terminal Server mode is
the recommended mode for the most reliable connection when operating with
NEWPORT software or with other programs supporting TCP/IP communications.
The Port 2000 access can be used with NEWPORT software and may be
needed with some Meters when you need to view readings from the web page
while simultaneously collecting data through TCP/IP communications.
4.5.1 HTTPget using Port 2000
You can setup and read the information from the Meter by using the HTTPget
program. The following program can be used to read data from the embedded
server firmware by using TCP port 2000. The command string is sent to this TCP
port, then the response can be read back from the same socket.
The HTTPget.exe file is used to setup and read information from the Meter. This
file will be automatically installed when you install the MailNotifier software
available on our website and CD.
Notes on using HTTPget :
The Httpget.exe program is installed to the windows directory (usually c:\winnt or
c:\windows) when installing the Mail Notifier software.
1). Open up a command window (or have a DOS window)
a) Click on start menu
b) Click on "Run"
c) In the dialog box that appears, type "cmd" or "command" and click on
"OK" button.
d) A command window should now appear.
2). If you now type "httpget" and press the "enter", the program options should
be displayed.
3). Next run HTTPget with the options displayed below
httpget -r -S *SR00z 192.168.1.135:2000 -C1 -q
58
Page 65
where:
-r –S are parameters needed for the the command string
Command (See Table 4.1)
192.168.1.135 is an IP address
2000 is a socket port number
-C1 closes the TCP connection after 1 second
-q displays no error messages once the connection is closed
Figure 4.26 HTTPget Example of Polling End Device #2,6,7
Table 4.2 Connector/Transmitter Types
UWTC B Type TC221UWTC K Type TC230
UWTC C Type TC222UWTC N Type TC233
UWTC E Type TC224UWRTD235
UWIR228UWTC R Type TC237
UWTC J Type TC229UWTC S Type TC238
UWTC T Type TC239
4.5.2 HTTPget and ARP to Setup Device IP Address
Use the iConnect software, which may be downloaded from our website,
to do these IP changes whenever possible.
Use ARP first to assign the mac address to a static IP address in computer arp
table by this command:
arp –s 192.168.1.200 00-03-34-00-06-b6
Then use the following command to assign new IP to the device:
Httpget –r –S "00000000" 192.168.1.200:1
where:
"0000000" is admin. password. If the password is wrong, the unit will ignore the
new IP. If the new IP is taken, you will get the message "New IP is Assigned"
after the HTTPget command. The device will reset automatically.
"192.168.1.200" is an example of an IP address. It is replaced with IP address
suitable for your network
"00-03-34-00-06-b6" is replaced with your Meter’s MAC address.
59
Page 66
4.6 ARP Protocol
C:\>ping 192.168.1.96
Pinging 192.168.1.96 with 32 bytes of data:
Reply from 192.168.1.96=bytes=32 time=5ms TTL=32
Reply from 192.168.1.96=bytes=32 time=3ms TTL=32
Reply from 192.168.1.96=bytes=32 time=3ms TTL=32
Reply from 192.168.1.96=bytes=32 time=4ms TTL=32
C:\>arp -a 192.168.1.96
Interface: 192.168.1.118
Internet Address Physical AddresssType
192.168.1.9600-03-34-00-00-23dynamic
00-03-34-00-00-23
C:\>arp -d 192.168.1.96
C:\>arp -a 192.168.1.96
No ARP Entries Found
C:\>
ARP is the Internet layer protocol responsible for matching or obtaining the MAC
(hardware) address that corresponds to a particular IP address. The ARP
command allows the user to view the current contents of the ARP cache of the
local computer (residing on the same network). Microsoft includes the ARP.EXE
utility for viewing and modifying the ARP cache with its Windows products. The
following ARP commands can be used to view cache entries:
• arp –a
• arp –a
associated with one particular interface on a network with multiple adapters.
• arp –g
• arp –N
• arp – s
manually add a permanent static entry to the ARP cache.
• arp –d
The following window shows examples of arp commands and responses.
• Your computer has an IP address of 192.168.1.118
• The destination computer has an IP address of 192.168.1.96
➞ Use this command to view all ARP cache entries.
plus IP address ➞ Use this command to view ARP cache entries
➞ Same as arp –a.
➞ Use this command to display ARP entries for specific network interface.
plus IP address plus Physical address ➞ Use this command to
plus IP address ➞ Use this command to manually delete a static entry.
Figure 4.27 ARP Commands and Responses
60
Page 67
4.7 iLog Software
This is an Excel application software that can log temperature from the Meter
over the local network (Ethernet) or the internet.
a) Download the iLog software from the website listed in this manual.
b) Install iLog software on a networked PC. This software is compatible with
Windows 95, 98, NT, 2000, and XP.
c)For complete information of how to use the iLog software, click on the HELP
button.
d) There is a list of Error Messages in Appendix E.
Figure 4.28 iLog Software Logging Data for End Device #2, 6, 7
The iLog application actually consists of several Excel files, though most
supported devices can be accessed by the main iLog program. The main
program is listed as "iLog", plus a version number, under the Start Menu
program links (those links available by clicking the Start button on the Windows
taskbar).
In the following table, the iLog File column shows how many sensors are logged
by the main iLog file. If more than 3 sensors are available, then the Alternate
column shows how many sensors the device can support. Devices with more
than 3 sensors will have their own Excel file. For these files, click on the model
device found in the Start Menu.
The "Auto" column shows number of columns per remote device that are
possibly displayed.
The Full column shows number of columns allocated per device for the "Full"
spreadsheet, which will be able to display all data for all active devices.
Networked ProductAutoFull
zSeries Receiver and Remotes1 to 4 column / device4 column / 32 device
wiSeries with zED Remotes1 to 2 column / device2 column / 32 device
UWTC REC-3 and Remotes1 or 2 column / device2 column / 32 device
wiSeries with UWTC Remotes1 to 2 column / device2 column / 32 device
The active wireless devices, when shown in the Excel application, will be shown
with the device number and the units returned.
For complete information of how to use the Mail Notifier software, click on the
Help menu of the main window.
The Mail Notifier software generates email notifications for alarm conditions.
Users can be notified automatically of alarm conditions monitored via internet
connections throughout the world. By use of the email forwarding of alarm
conditions, alarm conditions can be monitored on a network isolated from the
internet and forwarded to connections on the Internet.
The Mail Notifier utility operates under Windows 98, NT 4.0, 2000, and XP in
conjunction with existing email that supports the MAPI messaging interface. If
MS Outlook
4.8.1 Installation
The Mail Notifier must be loaded on a computer running MicrosoftTMWindows
(versions specified earlier) using an email program that provides MAPI access.
Network access must be available between this computer and the Meter.
Network access must also be available from this computer to the appropriate
email server and from the email server to the recipient’s email server.
TM
has been loaded, the MAPI support should be available.
Figure 4.29 Mail Notifier Main Window
63
Page 70
4.8.2 Program Options Setup and Configuration
Name/Profile
Password
Email AddressMS OutlookOutlook 2002
MAPI
Mail Server
Use Login
Box
Email Setup Content Startup GeneralSend To
HelpOKCancel
Options
Complete program setup requires:
•Entering a recipient for the email
•Specifying connection details to MAPI services.
Defining alarms for devices, and selecting how and when the email will be active.
•
Figure 4.30 Mail Notifier Profile Setup
Email Address Setup
The email addresses must be entered using individual addresses or alias. Select
"Options" from the "View" menu and enter the email addresses on the "Send To"
screen. This will be the list of email addresses to which alarm notifications will be sent.
Email Setup
The Mail Notifier is compatible with original MS Outlook
The Mail Notifier will attempt to automatically identify whether the Outlook is a
newer version. A red bar appears under the Mail Notifier splash window to
confirm that the detection of the 2002 or newer version is acceptable. With the
newer versions, no additional steps should be taken to enable the connection
between the Mail Notifier and the Email server.
MS Outlook tends to require that the users respond to a "login box" in
order for email access to be activated for Mail Notifier. Some other
email clients may allow for Mail Notifier to gain access without user
login, as may be desired for a system recovering from a power outage.
See the Help files for more information.
64
TM
and OutlookTM2002 to 2005.
Page 71
4.8.3 Device Setting and Configuration
The Meter and End Devices should first be configured and ready to use.
Make sure to have the following settings in the "Network" web page of the Meter
(Figure 4.20) .
Number of Connections = 5
Port = 2000 (other values may be acceptable as long as Mail Notifier is setup
with the same Port number)
Then on the Mail Notifier Alarm Editor, set the BusAddress/DeviceID to match
the Device ID number for an End Device and set the Reading Cmd to a
Command String from the following table:
Table 4.4 Mail Notifier Commands
Desired Value to MonitorReading Command Actual Command
String String (see Note 2)
Temperature1 (Process)SR##a*SR05a\r
in scale configured at Meter
Temperature1 (Process)SR##o*SR05o\r
in Degree C
Temperature2 (Ambient at SR##b*SR05b\r
End Device sensor) in scale
configured at Meter
Temperature2 (Ambient at SR##p*SR05p\r
End Device sensor) in Degree C
Battery voltage (mV)SR##j*SR05j\r
Signal LevelSR##h*SR05h\r
Success RateSR##i*SR05i\r
1. The commands used in Mail Notifier are symbolic commands rather
than actual Meter commands described in Table 4.1.
2. The sample commands in the table above are shown for a sensor
with Device ID of 5 such that SR##a, for example, is sent as
*SR05a\r.
65
Page 72
4.8.3 Device Setting and Configuration (continued)
Alarm Editor
OK
Cancel
Help
Add
Del
Bus Address/Device ID
Socket Number
Description
Src ID
Reading Cmd
Server IP Address
3
2000
Dev1
zRdgA
192.168.1.200
Device Info (1 of 2)
Alarm Type
Alarm High
Alarm Low
Alarm High
73
0
Info Message
Email Interval
Monitor Interval
0.05
Alarm Hold Time 0.0
0.5
hrs.
min.
min.
Alarm Configuration
Only Monitor Access
to iServer device
5
SR##a
Figure 4.31 Mail Notifier Device Setting
66
Page 73
Part 5
ENVIRONMENT / OPERATING CONDITIONS
The End Device and Meter are designed to be fixed mounted and operated in a
clean and dry environment. Care should be taken to prevent the components of
your wireless system from being exposed to moisture, toxic chemicals, extreme
cold or hot temperature that are outside the specification listed in this manual.
The following is a list of basic good practice you should apply when operating
this Wireless System.
1. Do not operate the wireless meter in flammable or explosive
environments.
2. Do not use the wireless meter in medical, nuclear or other critical
application where failure can cause damage or harm.
3. Always operate the wireless meter within the recommended
environmental limits specified in the manual.
4. Do not operate the wireless meter with a battery or AC adapter other than
what’s supplied or specified in this manual or on the battery compartment
label.
5. Keep each wireless meter at least 8 inches (20 cm) from other radio
transmitters, antennas, and people.
6. The FCC approval for this meter specifies the specific antenna supplied
with this meter.
5.1 General Deployment Guidelines
1. Position Meter in a central location. When multiple End Devices are in
operation, position your Meter in a central space if possible in equal
distance to each End Device.
2. Test your system before permanent mounting. Try to move the devices to
different location around and mounting angles to determine what
installation achieves the best signal strength before permanently
mounting the End Device.
3. Move your system components higher off the floor and away from exterior
walls. The closer the End Device and Meter are, the greater the
interference and lose of signal strength will be.
4. Maintain a line-of-sight between antennas and keep Fresnel zone free of
obstruction. See Figure 5.2.
5. Maintain a constant ambient temperature environment. Exposing your
system components to extreme cold or hot temperatures, or sudden
changes in ambient conditions will have an effect on the performance of
your system.
6. As a general rule in buildings, head height or above is preferred. On the
other hand, an End Device which stays close to the floor may have its
range reduced by 50% to 90%.
67
Page 74
7. Where possible, try to ensure an uninterrupted line-of-sight between
Meter/
Receiver
CONTROL ROOM
MANUFACTURING
AREA
MANUFACTURING
AREA
End Devices
OFFICEOFFICE
STORAGE ROOM
UWTC
UWIR
-NB9
UWRTD
UWTC
nodes. Avoid obscuring objects (e.g. metal pillars, posts, sign) near the
antenna. A close object obscures a wider range of solid angle.
8. It is important to understand that the environment may change over time
due to new equipment or machinery being installed, building construction,
etc. If new obstacles exist between the End Device and Meter, antenna
angle may need to be re-adjusted and/or the unit has to be relocated.
9. An IEEE 802.15.4 wireless network will not work under water. Wet
condition (e.g. in heavy rainfall) may exhibit some degradation. In most
cases, water droplets on or close to the antenna are more serious than
the rain itself. Humidity can affect radio performance as well.
10. Reduced performance scenario:
a. A large building may have few obstructions between nodes but large
amount of metallic paneling that cause reflections.
b. A small domestic installation may have numerous brick walls between
nodes in individual rooms.
c. An office building may have metalized dry-wall partitions together with
mezzanine ceilings.
Data is sent through radio signal at 2.4 GHz. Radio signals are
electromagnetic waves, hence the signal becomes weaker the further it
travels.
While radio waves can penetrate some solid materials like a wall, they
can diminish more than when a direct line-of-sight between the
transmitting and receiving antenna exist.
Therefore, it is generally a good idea to place Meter at the center while
End Devices are located about the same distance away from it. If
possible, keeping clearance around the line of site will improve
performance as well.
Figure 5.1 Operation in Buildings
68
Page 75
5.2 With Line-of-Sight
When installing the Meter it is important to position your device in such a way to
optimize the antenna location within what’s known as the "Fresnel Zone".
The Fresnel Zone can be thought of as a football-shaped invisible tunnel
between two locations that provides a path for RF signals between the End
Device and the Meter.
Figure 5.2 Fresnel Zone
In order to achieve maximum range, the football-shaped path in which radio
waves travel must be free of obstructions. Obstacles in the path (especially
metal) will decrease the communication range between the End Device and
Meter.
Also, if the antennas are mounted just barely off the ground or below the ceiling,
over half of the Fresnel zone ends up being obstructed resulting in significant
reduction in range.
Below is the calculated radius of the football-shaped tunnel for different distance
range:
Distance (feet)Radius (feet)
1003.2
2004.5
3005.5
It is recommended that within the tunnel of the above radius, at least 60% of
space is free of obstruction.
Since signal reaches destination directly in a line-of-sight situation, it is important
to adjust the antenna properly to achieve maximum performance. Antenna for
the Meter and End Device should be perpendicular to the plane where the Meter
and End Device is located.
69
Page 76
5.3 Without Line-of-Sight
When line-of-sight is not possible, signal penetrates and is reflected by different
objects to reach the destination. Therefore, it is important to learn about how
these materials would affect signal propagation.
Depending on the thickness, moisture content and angle of incidence, a wall
may allow between 1% and 25% of the radio power to pass through.
Metal panel or metalized glass window will not allow much radio power to pass
through. Signal will be reflected if the panel is a mirror.
Some radio power may propagate through small holes in the panel or around
metal edges through the process of diffraction.
Material TypePossible Signal
Reduction
Wood, Plaster, Sheetrock, Fiberglass
Uncoated Glass w/out Metal0 to 10%
Brick, Pressboard5 to 35%
Reinforced Concrete10 to 90%
Metal Walls, Metal Doors, Elevators, Metal Piping,
Metal Stair Cases, Metal Mesh, Metal Screening90 to 100%
Figure 5.3 Materials in Buildings
In a non-line-of-sight situation at 2.45 GHz, it is possible to move the receive
antenna only 1 to 1 1/2" (3 to 4 cm) and see signal strength varies from
6 dB to -20 dB due to multiple signal reflection path. Therefore, there should be
about 20 dB path loss margin to take signal fading into account.
5.4 Casing and Closure Around the Antenna
See Section 2.1.4.2 and Figure 2.5.
70
Page 77
PART 6
SPECIFICATIONS
ON/OFF CONTROL OUTPUT 1 & 2
Relay: 250 Vac or 30 Vdc @ 3 A (Resistive Load), SPDT
Solid State Relay (SSR): 20 to 265 Vac @ 0.05 to 0.5 A (Resistive Load);
continuous
DC Pulse: Non-Isolated; 10 Vdc @ 20 mA
Analog Output (Output 1 only)Non-Isolated, 0 to 10 Vdc or 0 to 20 mA, 500 Ω
max
Operation:Direct (cool), reverse (heat); deadband; single
sensing input
ConfigurationOutput 1 and 2 can be configured as Alarm 1
and 2, respectively. Analog Output for Output 1
can be configured as retransmission.
ALARM 1 & 2 (PROGRAMMABLE)
Type:SPDT Relay, SSR, and DC Pulse
Operation: High/low, above/below, band, latch/unlatch,
normally open/normally closed and
process/deviation; front panel configurations;
single/multiple sensing input(s)
ANALOG RETRANSMISSION OUTPUT (PROGRAMMABLE)
Type:Non-Isolated, Retransmission 0 to 10 Vdc or
0 to 20 mA, 500 Ω max (Output 1 only).
Operation: Single sensing input; accuracy is +
when following conditions are satisfied:
1) Input is not scaled below 1% of Input FS.
2) Analog Output is not scaled below 3% of
Output FS.
INSULATION
Power to Output:2300 Vac per 1 min. test
1500 Vac per 1 min. test
(Low Voltage/Power Option)
Power to Relays/SSR Outputs:
Relays/SSR to Relay/SSR Outputs: 2300 Vac per 1 min. test
GENERAL
Display:4-digit, 9-segment LED, 10.2mm (0.40
Digital Filter: Programmable
2300 Vac per 1 min. test
21mm (0.83
programmable colors
") red, green and amber
1% of FS
") and
71
Page 78
GENERAL
Connection: Screw terminals
Line Voltage/Power:90 to 240 Vac +/-10%, 50 to 400 Hz*;
110 to 375 Vdc, equivalent voltage; 5 W
* No CE compliance above 60 Hz
Low Voltage/Power Option:
20 to 36 Vdc or 24 Vac
**
+/-10%
; 4 W
External power source must meet Safety Agency
Approvals.
** Units can be powered safely with 24 Vac power
but, no Certification for CE are claimed.
External Fuse Required:
Time-Lag, IEC 127-3 recognized:100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Time-Delay, UL 248-14 listed:100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions:0 to 50°C (32 to 122°F), 90% RH non-condensing
Protection:NEMA-1/Type 1 front bezel
Dimensions:48H x 96W x 127mm D (1.89 x 3.78 x 5")
Panel Cutout:45H x 92mm W (1.772 x 3.622")
Weight:353 g (0.78 lb)
Software:The software packages available for the
Temperature Wireless System products are
iConnect (configuration software for the Ethernet
interface), iLog (Excel-based software for
automatic data logging), and Mail Notifier (email
alarm notification software).
INTERFACE SPECIFICATIONS
Ethernet:Standards Compliance IEEE 802.3 10Base-T
(RJ45)
Supported Protocols:TCP, UDP, ARP, ICMP, DHCP, DNS, HTTP, and
Telnet
LED Indicators:Network Activity, Network Link, Diagnostics,
Receive & Power
Management:Device configuration and monitoring through
embedded Web Server
Embedded Web Server:Serves WEB pages (Java™ Applets) containing
real-time data and live updated charts within
definable time intervals.
Radio Power Output:100 mW (20 dBm), 10 mW (10 dBm)
Limitations on Equivalent Isotropic Radiated Power (EIRP) levels in the
European Community and other countries applies. An improper combination of
power level can result in an EIRP above the allowed amount per regulations.
See Appendix F.
Data Rate:Bit rate 250 Kp/s; Symbol rate 62.5 Symbol/s; Chip rate 2000
kchip/s
Modulation:Orthogonal Quaternary Phase Shift Keying (O-QPSK)
Meter/Receiver Sensitivity:-100 dBm
Range:The range depends on the specific Connector/Transmitter
used. Refer to the UWTC Manual for more specifications.
The range assume a Line-of-Sight (LOS) between the Meter/Receiver and
Connector/Transmitter without obstructions or interference at which the
diagnostic signal strength web interface registers approximately 25%.
Antenna Frequency:2400 to 2500 Mhz
Impedance:50 ohm
Connector:Reverse Polarity SMA Plug
SAFETY & REGULATORY COMPLIANCE
Safety:EN 61010-1:2001
Safety requirements article 3.1.a of the R&TTE
EMC:EN 301 489-1 V1.6.1:2005-09
Electromagnetic compatibility article 3.1.b of the R&TTE
EN 301 489-17 V1.2.1:2002-08
Electromagnetic compatibility article 3.1.b of the R&TTE
EN 55022:2006 + A1:2007, Class A, (CISPR 22 +A1:2005)
Radio:EN 300 328 V1.7.1:2006-10 Spectrum article 3(2) of the R&TTE
FCC:Part 15C, Class DTS Intentional radiator tested for 15.205, 15.209,
15.247(d), 15.215(c), 15.247(a)(2), 15.247(b), 15.247(e).
See Appendix F.
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
CE:The product herewith complies with the essential requirements and other
relevant provisions of the R&TTE Directive 1999/5/EC, the EMC
Directive 2004/108/EC, and the Low Voltage Directive 2006/95/EC, and
carries the CE-marking accordingly.
The following CE Mark is affixed to this equipment.
See Appendix F. The CE declaration is available at the website listed
on the cover page of this manual.
73
Page 80
PART 7
FACTORY PRESET VALUES
To set the Wireless and Ethernet settings back to Factory Default do the
following to the DIP switches (see Figure 2.11).
To set the Ethernet board
1) Put the 4 position DIP switch #2 to ON position (it does not matter if the
Meter is On or Off).
2) Power-cycle the Meter and wait about 10 seconds until the Meter fully boots
up.
3) Put the DIP switch #2 back to OFF position (it does not matter if the Meter is
powered On or Off, just make sure that the DIP switch is set to OFF,
otherwise, everytime the unit is power-cycled the factory settings will take
over.
To set the Wireless board
1) Put the 8 position DIP switch #1 to ON position (it does not matter if the
Meter is On or Off).
2) Power-cycle the Meter and wait about 10 seconds until the Meter fully boots
up.
3) Put the DIP switch #1 back to OFF position (it does not matter if the Meter is
powered On or Off, just make sure that the DIP switch is set to OFF,
otherwise, everytime the unit is power-cycled the factory settings will take
over.
The defaults that will change are noted by a "W" or "E" in the Table
below. The defaults for the Meter/Controller "C" are set by the individual
Setup menus.
to Factory Default settings:
to Factory Default settings:
C = Meter/Controller Board
W = Wireless or Coordinator Board
E = Ethernet or iServer Board
Table 7.1 Factory Preset Values
CONTROLLER SETUP
Input
Control End Device ID1W
Filter4C
Temperature UnitFC
74
Page 81
Table 7.1 Factory Preset Values (continued)
Setpoints & On/Off Control
Auto Setpoint Deviation DisabledC
Setpoint 10C
Setpoint 2 100C
Permanent Store
IDNameUpdate Network Units Remote Format End Char Display Alarm
1 ABCDEFGH120
2 ABCDEFGH120
3 ABCDEFGH120
4 ABCDEFGH120
5 ABCDEFGH120
6 ABCDEFGH120
7 ABCDEFGH120
8 ABCDEFGH120
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
F0
000000F0D
F0000000F0D
END DEVICE PARAMETERS
End Device # (1 - 8)
Device NameABCDEFGHE
Update120 secsW
Sensor 1
Remote Display Format0000000FE
Remote End Char(Hex) 0x 0DE
Offset (xxxx)0W
Display
Al
arm
W
W
Sensor 2
Remote Display Format0000000FE
Remote End Char(Hex) 0x 0DE
Offset (xxxx)0W
77
Page 84
APPENDIX AGLOSSARY
User of this manual should be familiar with following definitions:
ARP (Address Resolution Protocol) is a protocol for mapping an Internet Protocol
address (IP address) to a physical machine address that is recognized in the local
network. For example, the IP address in use today is an address that is 32-bits long.
In an Ethernet local area network, however, addresses for attached devices are 48-bits
long. (The physical machine address is also known as a Media Access Control or MAC
address.) A table, usually called the ARP cache, is used to maintain a correlation between
each MAC address and its corresponding IP address. ARP provides the protocol rules for
making this correlation and providing address conversion in both directions.
Ethernet is a network protocol defined by the IEEE 802.3 standard. Ethernet-based
networks use MAC Address rather then IP Address to exchange data between computers.
By using ARP and adding TCP/IP support, Ethernet devices may be connected as part of
the Internet. An Ethernet LAN typically uses coaxial cable or special grades of twisted pair
wires. The most commonly installed Ethernet systems are called 10BASE-T and provide
transmission speeds up to 10 Mbps. Devices are connected to the cable and compete for
access using a Carrier Sense Multiple Access with Collision Detection (CSMA/CD)
protocol.
IP (Internet Protocol) is the method or protocol by which data is sent from one computer
to another on the Internet.
IP address (Internet Protocol address) is a 32-bit number that identifies each sender or
receiver of information that is sent in packets across the Internet.
IP Netmask is a 32-bit pattern of bits used to determine which part of the IP address is the
network portion and which part is the host portion.
MAC (Media Access Control) Address is your computer's unique hardware number.
When you're connected to the Internet from your computer, a correspondence table relates
your IP address to your computer's physical (MAC) address on the LAN.
Ping is a utility that tests the network connectivity. It is used to determine if the host is
capable of exchanging information with another host.
Port number/Socket number is a way to identify a specific process to which an Internet
or other network message is to be forwarded when it arrives at a server. It is a predefined
address that serves as a route from the application to the Transport layer or from the
Transport layer to the application of the TCP/IP system.
Sockets are a method for communication between a client program and a server program
in a network and defined as "the endpoint in a connection." Information transferred across
the Internet primarily occurs between sockets.
TCP/IP (Transmission Control Protocol/Internet Protocol) is the basic communication
language or protocol of the Internet. When you are set up with direct access to the
Internet, your computer is provided with a copy of the TCP/IP program just as every other
computer that you may send messages to or get information from also has a copy of
TCP/IP. TCP/IP often is used as a general term to indicate generic access to the Internet.
UDP/IP (User Datagram Protocol/Internet Protocol) is the TCP/IP standard protocol that
allows an application program on one machine to send a datagram to an application
program on another. The UDP can be either in Broadcast or Directed form. The Broadcast
UDP transmits data to every node on the same network. The Directed UDP transmits data
to one node only.
78
Page 85
Appendix BIP Address
An IP address is a unique 32-bit address assigned to a computer and includes:
• A network ID number identifying a network.
• A host ID number identifying a computer on the network.
All IP addresses have been divided into three smaller groups (classes) A, B and C
• Class A addresses have 8-bits of network ID and 24-bits of host ID. They can support
a large number of hosts, approximately 2 = 16,777,216 computers per network.
The IP addresses range in binary from 00000001.xxxxxxxx.xxxxxxxx.xxxxxxxx
to 01111111.xxxxxxxx.xxxxxxxx.xxxxxxxx
The IP addresses range in decimal from 1.x.x.x to 127.x.x.x
Class A network ID’s support a very large number of hosts.
• Class B addresses have 16-bits of network ID and 16-bits of host ID. They can
support approximately 216= 65,536 computers per network.
The IP addresses range in binary from 10000000 00000000.xxxxxxxx.xxxxxxxx
to 10111111 11111111.xxxxxxxx.xxxxxxxx
The IP addresses range in decimal from 128.0.x.x TO 191.255.xxx.xxx
Class B network ID’s support a medium number of hosts.
• Class C addresses have 24-bits of network ID and 8-bits of host ID. They can support
approximately 28= 256 computers per network.
The IP addresses range in binary from 11000000.00000000.00000000.xxxxxxxx
to 11011111.11111111.11111111.xxxxxxxx
The IP addresses range in decimal from 192.0.0.xxx to 223.255.255.xxx
Class C network ID’s support a small number of hosts.
The rest of the addresses are divided into two classes, D and E.
Class D networks are not assigned to the host. They are used for multicasting.
The address range from 224.x.x.x to 239.x.x.x
Class E networks are experimental or reserved addresses.
The address range from 240.x.x.x to 247.x.x.x
79
Page 86
Appendix CIP Netmask
IP Netmask or Subnet Mask is a 32-bit pattern of ones and zeros used to determine
network portion of an IP address from the host portion of the IP address. Subnet mask is
a network ID that is created by borrowing bits from host portion of IP address and using
them as part of a network ID. The table below shows a default subnet mask for address
Classes A, B, and C. Each bit that is set to "1" in the subnet mask corresponds to the bit
in the IP address that is to be used as the network ID. Each bit that is set to "0" in the
subnet mask corresponds to a bit in the IP address that is to be used as the host ID.
Address ClassMask Binary Value Mask Decimal Value
or Dotted Notation
Class A255.0.0.0
Class B255.255.0.0
Class C255.255.255.0
11111111
11111111
11111111
00000000
11111111
11111111
00000000
00000000
11111111
00000000
00000000
00000000
If your network requires more network ID’s, you can extend the default subnet mask to
include additional bits from the host ID. This allows for additional network ID’s within the
network. The table below shows some examples of subnet masks and bits moved from
the hosts ID to create a new subnet.
To determine the number of valid hosts ID’s remaining after subnetting, use the following
equation: 2n– 2, where n is the number of octet digits left after the subnet mask.
ASCII Dec Hex Ctrl KeyDefinitionASCII Dec Hex Ctrl KeyDefinition
CharEquiv.CharEquiv.
NUL0000Crtl @Null CharacterDC11711Crtl QData Control 1
- XON
SOH0101Crtl AStart ofDC21812Crtl RData Control 2
Header
STX0202Crtl BStart of TextDC31913Crtl SData Control 3
- XOFF
ETX0303Crtl CEnd of TextDC42014Crtl TData Control 4
EOT0404Crtl DEnd ofNAK2115Crtl UNegative
TransmissionAcknowledge
ENQ0505Crtl EInquirySYN2216Crtl VSynchronous
Idle
ACK0606Crtl FAcknowledgeETB2317Crtl WEnd of Trans
Block
BEL0707Crtl GBellCAN2418Crtl XCancel
BS0808Crtl HBack SpaceEM2519Crtl Y End of Medium
HT0909Crtl IHorizontalSUB261ACrtl ZSubstitute
Tabulation
LF100ACrtl JLine FeedESC271BCrtl [Escape
VT110BCrtl KVerticalFS281CCrtl \File Separator
Tabulation
FF120CCrtl LForm FeedGS291DCrtl ]Group
Separator
CR130DCrtl MCarriageRS301ECrtl |Record
ReturnSeparator
SO140ECrtl NShift OutUS311FCrtl_Unit Separator
SI150FCrtl OShift InSP3220Space
DLE1610Crtl PData Link
Escape
82
Page 89
Appendix EiLog Error Messages
Error # DescriptionNote
-8003User stopped logging readings.
-10005 Failed to find the Meter.Ethernet cable is disconnected,
iServer is powered off, connections
across the firewall require longer
“connection to socket time out”
setting.
-10006 Windows socket was closed.
-10007 Windows socket error.Wrong IP or wrong Port number
was used.
-10008 The Meter failed to respond to a request.Wrong IP or wrong Port number
was used.
-10011 Response came empty.No data was sent.
-10012 Device responded with Possibly the iLog is configured for
"Serial Time Out" string.wrong product model.
-10014 Terminal Server Mode when the Port is 1000. Try Port 2000 in iLog configuration.
-15100 Error on obtaining the temperature reading.Possibly the iLog is configured for
wrong product model.
Appendix FWarnings and Regulatory Information
In order to comply with FCC radio frequencies (RF) exposure limits, dipole antennas
should be located at a minimum 7.9" (200mm) or more from the body of all persons.
This device complies with part 15 rules. Operation is subject to the following two conditions:
1) this device may not cause harmful interference, and
2) this device must accept any interference received, including interference that may cause
undesired operation.
This equipment has been tested and found to comply with the limits of a Class B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
residential environment. This equipment generates, uses, and radiates radio frequency
energy, and if not installed and used in accordance with the instructions, may cause harmful
interference. However, there is no guarantee that interference will not occur. If this equipment
does cause interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to correct the interference by one of the
following measures:
• Reorient or relocate the receiving antenna.
• Increase separation between the equipment and receiver.
• Connect the equipment to an outlet on a circuit different from which the receiver is
connected.
• Consult dealer or an experienced radio/TV technician.
83
Page 90
Appendix F Warnings and Regulatory Information (continued)
The following alert sign indicates that there are restrictions on usage of the
equipment in regards to power limitations on Equivalent Isotropic Radiated Power
(EIRP) levels in the European Community.
The following are user restrictions:
• Wideband Data Transmission Systems on the band 2400 – 2483.5 MHz in Europe is
limited to a Maximum of 10 mW (10 dBm) for Direct Sequence Spread Spectrum (DSSS).
See Annex 3 of ERC/REC 70-03, decision ERC/DEC/ (01)07.
• Combinations of power levels and antennas resulting in a radiated power level above
10 mW - EIRP for Direct Sequence Spectrum (DSSS) devices are considered as not
compliant, and are not allowed for use within the European Community and other
countries that have adopted the European R&TTE directive 1995/5/EC or the CEPT
recommendation ERC/REC 70-03 or both.
• The users in Europe are instructed to change the default 20 dBm level to 10 dBm via the
Web Interface of the Meter/Receiver.
The default 20 dBm must be changed to 10 dBm to comply with power level
regulations. The 0.5 dBm variation depends on the internal DC power used (3V,
3.3V, 3.7V max) of the different models.
84
Page 91
WARRANTY/ DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year
from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty
period for one (1) additional year if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found
to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which
wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the
parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”
under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on
humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on
humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage
whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR
number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
2. Model and serial number of the product under warranty,
and
3. Repair instructions and/or specific problems relative to
the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.