Omega VSHP, VSHP 040, VSHP 050, VSHP 060, VSHP 030 Installation And Operation Manual

...
OMEGA VSHP SERIES
Installation and Operation Manual (IOM)
VERTICAL STACKED
WATER SOURCE HEAT PUMPS
MODEL: VSHP
DEV. F
ISSUE DA TE: JULY 2019
3325A Orlando Dr. Mississauga, ON, L4V 1C5 T. 90 5.670 .2269 F. 905.670.3822 omega -heat pump. com omega@omega-heatpump.com
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
i www.omega-heatp ump.com
TABLE OF CONTENTS
1. General Information, Warnings and Disclaimer ................................................................................. 1
2. Cabinet Dimensions ............................................................................................................................. 2
3. General Unit Information ..................................................................................................................... 5
4. Inspection & Storage ........................................................................................................................... 5
Inspection of Unit...................................................................................................................... 5
Storage ...................................................................................................................................... 6
5. Cabinet & Riser Installation ................................................................................................................. 6
For Shipped Loose Riser Shut-Off Valves ................................................................................ 6
Cabinet Install ........................................................................................................................... 6
Riser Loop ................................................................................................................................. 7
Servicing .................................................................................................................... 7
Flushing & Cleaning .................................................................................................. 7
Riser System Loop Temperature ............................................................................................. 7
Cooling Season ......................................................................................................... 7
Heating Season ......................................................................................................... 7
Operating Limits ........................................................................................................ 8
6. Chassis Installation .............................................................................................................................. 8
Installation of Fittings and Hoses ............................................................................................ 8
Units with NPSM Riser and Chassis Fittings ........................................................... 8
Units with NPT Riser and Chassis Fittings ............................................................... 8
Chassis Install ........................................................................................................................... 8
7. Unit Start-Up ......................................................................................................................................... 9
Checklist ................................................................................................................................... 9
Initial Start-Up ........................................................................................................................... 9
8. Controls .............................................................................................................................................. 10
Microprocessor Controller ...................................................................................................... 10
DIP Switch Settings ................................................................................................. 10
Thermostat Cable ................................................................................................... 10
Automatic Fan Mode Operation ............................................................................. 10
Single/Manual Fan Mode Operation ..................................................................... 10
Fan Control with PSC Motors ................................................................................. 10
Fan Control with ECM ............................................................................................. 10
Whisper Mode (ECM Only) ...................................................................................... 10
Fan Control with ECM X13...................................................................................... 11
Sequence of Operation .......................................................................................................... 11
9. Troubleshooting ................................................................................................................................. 11
Test Mode ............................................................................................................................... 12
Web Based Access ................................................................................................................. 12
10. Maintenance Guide ......................................................................................................................... 14
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com i
LIST OF FIGURES & TABLES
FIGURES
Figure 1: Silver Series Cabinet Dimensions ..................................................................................................................... 2
Figure 2: Gold Series Cabinet Dimensions ....................................................................................................................... 3
Figure 3: VSHP Assembly View ......................................................................................................................................... 4
Figure 4: Silver and Gold Series Cabinets ...................................................................................................................... 17
Figure 5: Riser Handing Configurations.......................................................................................................................... 18
Figure 6: Riser Length Measurements ........................................................................................................................... 19
Figure 7: Riser Stub-Out Opening Detail (Side View) ...................................................................................................... 20
Figure 8: Riser Stub-Out Distance from Cabinet Wall .................................................................................................... 20
Figure 9: Hose Kit Details ............................................................................................................................................... 21
Figure 10: Standard “Knockout” Supply Openings ........................................................................................................ 22
Figure 11: Optional Fresh Outside Air Duct .................................................................................................................... 23
Figure 12: Top Supply Air Opening Configurations with Fresh Air Duct ......................................................................... 24
Figure 13: VSHP Acoustic Return Air Panel ................................................................................................................... 25
Figure 14: Acoustic Panel Cabinet Base Height Calculation ......................................................................................... 26
Figure 15: Acoustic R/A Panel Furring Drawing - Typ. 2x2 Framing .............................................................................. 27
Figure 16: Acoustic R/A Panel Furring Drawing - Typ. 2x4 Framing .............................................................................. 27
Figure 17: Acoustic R/A Panel Furring Drawing - Front & Side View ............................................................................. 28
Figure 18: Perimeter Panel Dimensional Drawing ......................................................................................................... 29
Figure 19: Perimeter Panel Cabinet Base Height Calculation ....................................................................................... 30
Figure 20: Perimeter R/A Panel Furring Drawing - Typ. 2x2 Framing ............................................................................ 31
Figure 21: Perimeter R/A Panel Furring Drawing - Typ. 2x4 Framing ............................................................................ 31
Figure 22: Perimeter R/A Panel Furring Drawing - Front & Side View ........................................................................... 32
Figure 23: VSHP Electrical Schematic- PSC Fan Motor.................................................................................................. 33
Figure 24: VSHP Electrical Schematic - ECM Fan .......................................................................................................... 34
Figure 25: Thermostat Wiring Detail............................................................................................................................... 35
TABLES
Table 1: VSHP Cabinet Dimensions (Silver & Gold Series) .............................................................................................. 2
Table 2: Unit Operation Limits .......................................................................................................................................... 8
Table 3: DIP Switch Settings ........................................................................................................................................... 10
Table 4: DIP 1 (ON) = Heat Pump Thermostat ............................................................................................................... 10
Table 5: DIP1 (OFF) = HEAT/COOL Thermostat .............................................................................................................. 10
Table 6: Replacement Filters .......................................................................................................................................... 14
Table 7: Troubleshooting Guide ...................................................................................................................................... 15
Table 8: Microprocessor LED Code Guide ...................................................................................................................... 16
Table 9: VSHP Cabinet Riser Dimensions ...................................................................................................................... 18
Table 10: Hose Kit Sizes ................................................................................................................................................. 21
Table 11: Supply Air Opening Sizes ................................................................................................................................ 23
Table 12: Supply Air Opening Sizes w/ Fresh Air Duct ................................................................................................... 25
Table 13: Acoustic Panel Sizes ....................................................................................................................................... 26
Table 14: Acoustic Panel Rough-In Dimensions............................................................................................................. 28
Table 15: Perimeter Panel Sizes .................................................................................................................................... 29
Table 16: Perimeter Panel Rough-In Dimensions .......................................................................................................... 32
Table 17: PSC Fan Data .................................................................................................................................................. 36
Table 18: ECM Fan Data ................................................................................................................................................. 37
VSHP UNIT START-UP SHEET ................................................................................................................................. 38
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
1 www.omega-heatpump.com
IMPORTANT
READ THE FOLLOWING MANUAL PRIOR TO INSTALLATION, OPERATION and SER-
VICING THIS UNIT.
1. GENERAL INFORMATION & WARNINGS
SAFETY SYMBOLS – Warnings, Cautions & Notices
There are three advisory symbols used in this document to alert the reader:
Warning: Indicates a potentially dangerous situation which could result in death or
serious injury.
Caution: Indicates a possible hazardous situation which can result in possible inju-
ries or damage to unit and/or environmental pollution, or to alert against practices
that are unsafe.
Note: Identifies important information to the technician to complete the installation
correctly.
Responsible Refrigerant Practices
All technicians who handle refrigerants must be certified in accordance with local codes for reclaiming, recovering, recycling and handling of refrigerants. Technicians must follow all
applicable local and federal laws.
Correct field wiring and grounding is required, failure to adhere and follow code could result in death of serious injury. ALL FIELD WIRING MUST BE PER- FORMED ONLY BY A QUALIFIED ELECTRICIAN. All wiring must be in accord-
ance of with the manufacturers specifications.
Wiring that is improperly installed and/or grounded could result in FIRE, ELECTRO­CUTION, and other serious hazards. Manufacturer is not responsible for damage/ equipment or site issues resulting from the improper connections of the unit or the
use of improper controls.
Personal Protective Equipment (PPE) is mandatory. Technicians installing or ser­vicing this unit must use all PPE including but not limited to: hard hats, safety glass-
es, cut resistant sleeves and gloves, electrical PPE, and fall protection.
Disclaimer
All units are certified and built in accordance to applicable government and industry stand­ards. Any customer modifications performed without the express written approval from the
manufacturer are strictly prohibited and will void all warranties expressed or implied.
Modifications to the unit may result in hazardous or unexpected operation of the unit. Modifications to the unit may result in a potentially hazardous situation result-
ing in equipment damage, property damage, injury or death.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 2
Notes:
Temporary riser supports provided (Contractor to
remove and install permanent riser clamps fastening risers to the building structure).
Return air opening is on the front of the unit. Unit includes hose kits and manual shut off valves. Optional risers are furnished with type L, M copper.
Available 3 inch deep swage connections on same size piping.
Contractor to provide couplings where the piping is not
swaged or for joining dissimilar piping sizes.
Use flexible duct connections to supply ducts and
registers.
2. CABINET DIMENSIONS
Table 1 VSHP Cabinet Dimensions (Silver & Gold Series)
Figure 1 Silver Series Dimensional Drawing
Model
Cabinet
Size
Dimensions (in)
"W" "D" "C"
VSHP 020
X
16 18.5 14 VSHP 030
VSHP 040 VSHP 050
Y 18 21.5 16
VSHP 060 VSHP 080
Z 22 25.5 20
VSHP 100 VSHP 120
(Drawing not to scale, dimensions are subject to change)
RIGHT SIDE VIEWFRONT VIEW
Total
Unit
Height
Base Height
Std.= 5"
3"
Cabinet
Height
Max.=120"
Std. = 79"
"W"
8"
29.5"
2.5"
"D"
48.75"
Power
Wiring
Entrance
7/8" OD
Low Voltage
Entrance
7/8" OD
High Voltage Cover
Low Voltage Cover
Discharge Supply Air Opening "Knockouts"
with 1-1/2" Duct Flange
Condensate Hose
Riser Stub-Out Opening "Knockouts"
Removable Service Cover Panel
"C"
45"
Neoprene Pad
4"
3"
Note:
Stub-Outs
Centered on
Back Riser
6"
6"
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
3 www.omega-heatpump.com
(Drawing not to scale, dimensions are subject to change)
Figure 2 Gold Series w/ Acoustic Plenum Dimensional Drawing
Notes:
Temporary riser supports provided (Contractor to remove and install permanent riser clamps fastening risers to the building
structure).
Return air opening is on the front of the unit. Unit includes hose kits and manual shut off valves.
Optional risers are furnished with type L, M copper. Available 3 inch deep swage connections on same size piping.
Contractor to provide couplings where the piping is not swaged or for joining dissimilar piping sizes. Use flexible duct connections to supply ducts and registers.
Power Wiring
Entrance
7/8" OD
3"
45"
8"
Total
Unit
Height
Cabinet
Height
Max. = 125"
Base Height
Std.= 5"
5"
"W"
*64.5"
2.5"
29.5"
"D"
48.75"
FRONT VIEW
RIGHT SIDE VIEW
Low Voltage
Entrance
7/8" OD
High Voltage Cover
Low Voltage Cover
Flexible 3" Canvas
Duct Connector
Discharge Supply Air Opening "Knockouts"
with 1-1/2" Duct Flange
Acoustic
Discharge Plenum
Condensate Hose
Riser Stub-Out Opening "Knockouts"
Removable Service Cover Panel
"C"
Neoprene Pad
3"
4"
6"
6"
Note:
Stub-Outs
Centered on
Back Riser
*Dimension varies with optional surface mount thermostat
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 4
.
.
.
.
.
Figure 3 VSHP Assembly View (Silver Series Cabinet)
1
1. Supply, return and condensate risers. Type M or Lcopper.
2. Field knockoutsupply air openings (Front/ Back/Side/Top) with 1-1/2” duct ange.
3. Electrical box with advanced microprocessor.
4. Removable direct drive blower motor assembly.
5. Heat pump chassis.
6. Chassis service cover panel.
7. 1” air lter.
8. Return air (R/A) panel available in acousc or perimeter (Acousc shown).
9. Standard stainless steel drain pan
2
3
4
5
6
7
8
9
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
5 www.omega-heatpump.com
3. GENERAL UNIT INFORMATION BLOWER & MOTOR
The unit comes with a blower and motor assembly that is mounted to a blower deck inside the unit cabinet, lo­cated above the chassis behind the electrical box. Re­moval of the blower/motor assembly is done through the
chassis compartment opening.
UNIT NAMEPLATES
The nameplate contains information about the unit in­cluding model and serial numbers, electrical data and refrigerant charge information. The cabinet nameplate is located on the surface of the cabinet and the chassis
nameplate is located on the chassis. Collecting the in-
formation on the nameplate will be useful when contact­ing your local customer service representative or when ordering parts. The compressor nameplate is located inside the chassis enclosure (requires removal of sheet
metal enclosure) on the compressor shell.
CONTROLS
The unit comes with a factory supplied transformer. See wiring diagram for field wiring a thermostat to the electri­cal box low voltage terminals. High voltage connection is made on the left side of the cabinet and low voltage con-
nections enter through the right side of the cabinet.
MICROPROCESSOR CONTROLLER
Unit comes with an advanced microprocessor controller
that monitors the entire function of the unit. The micro­processor board comes with an integral terminal strip for wiring thermostat cable.
REFRIGERANT CONNECTIONS
Low and high pressure side refrigeration service ports re located inside the compressor enclosure. Slide out chas-
sis and remove sheet metal enclosure to access fittings.
CABINET– SILVER SERIES
The standard Silver series cabinet is a fully factory as­sembled one piece cabinet. See Figure 1. Use flexible duct connections for connecting cabinet to supply ducts to prevent vibration and noise transmission into occu-
pant space.
CABINET– OPTIONAL GOLD SERIES
The optional Gold series cabinet comes in two sections for enhanced acoustic performance. See Figure 2. The upper section discharge plenum is lined with 1” thick insulation on all inside surfaces. Plenum is secured to cabinet with shipping brackets. Once discharge plenum is fastened to the underside of the concrete slab ship­ping brackets must be removed. See Figure 4 for com­parison of Silver and Gold series cabinets. Factory in-
stalled flexible connection joins the upper and lower sec­tions. Sand Dcleats are used to join upper and lower plenums to the metal portion of the flex connection. The
plenum comes with factory pre-punched knockouts on all sides.
RETURN AIR PANEL—ACOUSTIC & PERIMETER
The Acoustic Return Air Panel is insulated with 1/2” thick, acoustic insulation and removable without tools to allow access to the filter and (optional) service discon­nect switch. The panel is removed by swinging out and lifting it off the support pegs. The panel should be flush mounted to the drywall after the cabinet and riser instal­lation is complete. See Figures 14 to 17 for more de-
tailed information.
The Perimeter Return Air Panel door is mounted in the drywall opening and fastened to the wall studs. See Fig-
ures 18 to 21 for more detailed information.
Cabinet base height and maximum base­board height dimensions can be determined by referencing Figures 16 & 20. Use appro­priate Figure based on R/A Panel type or-
dered.
THERMOSTAT
Unit comes standard with a factory provided 24 inch
long, 6-wire thermostat cable whip pre-wired to the con­trol board terminal blocks.
4. INSPECTION & STORAGE INSPECTION OF UNIT
Prior to the installation of the unit perform the following
checks:
Visually inspect the packaging, cabinet and chassis
for signs of shipping damage prior to signing the bill of lading. Check that the units match the sales order by referring to the cabinet and chassis nameplate
information.
Inspect the riser ends for any sign of damage.
Verify breaker and power supply meet electrical
nameplate requirements of the unit.
Check that the nameplate of the units matches the
floor plan layout.
When construction is not complete including concrete core drilling, drywalling, plastering, painting or any work that would contaminate the storage space all necessary precautions are to be taken to prevent the cabinet and chassis from becoming contaminated. Particulate infil­tration (i.e. drywall dust) into cabinet and chassis coil could result in equipment damage. Fumes could result in premature corrosion (formicary corrosion) of the chas-
sis air-coil resulting in refrigeration system leaks.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 6
STORAGE
Both cabinet and chassis units are designed for indoor use only. Care must be taken to protect the unit from environmental damage. Store the chassis in an environ­ment with a temperature above (32oF). To prevent con­tamination the units should be stored indoors. For out-
door storage ensure:
Units should be placed in an area that will not be
exposed to moisture damage. Units should be placed on a dry surface and on a raised surface. Do
not stack units.
Cover the units with a waterproof tarp.
Failure to keep the units dry could result in the inte-
rior insulation becoming wet and cause the growth
of mold which is known to cause odors and serious
indoor air quality problems and health issues.
Chassis units must be stored in the upright position
to keep oil in the compressor.
Riser ends should be capped if being stored on site
to prevent contamination from foreign objects and
debris.
Wet insulation can cause the growth of mould. Any sign of mould growth in the interior insula­tion should be removed, cabinet interior disin-
fected with anti-microbial cleaner and re­placed prior to operating the unit.
Do not store cabinets on their side when chas-
sis units are inside. Chassis units should al­ways be stored and transported in the upright position otherwise damage to chassis may
occur.
The refrigeration system of these units con­tains POE oil. PVC/CPVC piping is prone to failure when in contact with POE oil. PVC/ CPVC piping should not be used for water supply and return with any heat pump prod
ucts as this may result in failure of the system
and serious property damage.
Do not rest or lean the unit on the risers. Do not use the risers or stub-outs to pick up the unit. Only des-
ignated lift points should be used when moving or
lifting cabinets. Do not drop the risers.
5. CABINET & RISER INSTALLATION
Risers are designed to have slight adjustments for riser system expansion and aligning the
stub-outs in the cabinet opening. When in-
stalling risers, do not let riser stubs bottom out
in the riser swage.
Risers are designed to allow for 1-1/2 inches of
movement due expansion and contraction. If the total calculated riser expansion exceeds ±1
-1/2 inches the field must provide expansion compensators.
Riser stub-outs should be located as centrally
as possible in the cabinet opening. Do not al-
low stub-outs to rest or contact the sheet metal opening.
Do not allow the risers to bottom out when
installing into the swage.
FOR SHIPPED LOOSE RISER SHUT-OFF VALVES
Visually inspect riser stub-outs and shut-off valves for debris or damage.
Follow industry standard soldering practices
when soldering shut-off valves to riser stub­outs.
Ensure riser stub-out surface is cleaned of any
residue, soot or oils. Failure to adequately clean soldering surfaces can result in water
leaks, property damage and physical injury.
When soldering shut-off valves to riser stub
outs, adequately protect cabinet, insulation and any other equipment from exposure to
flames and heat.
CABINET INSTALL
1. When cabinets are shipped with risers attached, place cabinets in a horizontal position on the floor (do not rest
cabinet on the risers).
2. If required, install any field or factory supplied riser
extensions to the unit mounted risers.
3. Raise the entire cabinet slowly upright while at the
same time lowering the risers through the floor cut-out
opening. Align the risers to the matching swaged section
of the riser on the floor below.
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
7 www.omega-heatpump.com
4.Swaged sections are approximately 3 inches deep.
Risers should be inserted at a depth of approximately 2 inches into the 3 inch deep swage. Confirm risers pene­trate at a minimum of 1 inch into the swage. Do not allow the riser tailpiece to bottom out fully into the 3 inch deep swage. This will allow for floor to floor variations, other­wise riser overlap may not be sufficient on upper floors.
See Figure 6.
5. Align and center riser positions in the pipe chase and
level cabinet as necessary.
6. Secure the cabinet to the floor. Cabinet base comes
with factory mounted neoprene pads.
7. Center the riser stub-outs in the cabinet openings to
allow for riser expansion and prevent contact with cabi-
net sheet metal. Prevent riser stub-outs from contacting sheet metal pass through otherwise damage to stub-
outs may occur, resulting in serious water damage. See
Figures 7 & 8.
8. Secure risers to building structure as per engineering design specifications. Do not allow the risers to be sup­ported by the cabinets. Field supplied riser compensa­tors are required if the temperature range of the system
exceeds the expansion and contraction limit.
9. Using industry accepted soldering and brazing stand-
ards and materials to solder or braze the riser joints.
10. Connect supply ducts and discharge grilles. See
Figure 11.
11. Optional Fresh Outside Air Duct details are shown in
Figures 12 & 13 when connecting to remote ERV.
RISER LOOP Servicing
To enable system flushing, servicing and balancing of supply and return risers the following field supplied com-
ponents are required: shut-off valves, drain tees and
drain valves, and flow measuring devices. Refer to the job site engineering design specifications and building
drawings for more detailed information. Flushing & Cleaning
Once the riser system is complete the riser system must
be flushed, cleaned and chemically treated. Do not con­nect chassis to the water circulating system when flush­ing is being conducted to prevent debris and fouling of the water side components of the chassis (i.e. auto bal-
ancing valve, auto shut-off valve, coaxial coil).
Do not flush and clean riser system with chas­sis units connected. Do not allow the flushing and cleansing solutions to flow in the chassis water coil. Damage to water components may
occur.
Supply and return pipes must be interconnected, at a
minimum in the top and bottom units of each riser, with factory supplied hoses to properly flush system and en­sure adequate elimination of foreign material and clean-
ing of riser system.
1. Use only clean water to fill water circulation system. Fill the water circulating system at the municipal water
makeup connection with all air vents opened.
2. After air vents have been sequentially closed and riser system is primed begin water circulation of the system to
purge remaining trapped air bubbles.
3. Shut off the circulating pump and open all the drains
and vents to completely drain the system.
4. The riser system should be cleaned after the initial flush and flushed a second time to adequately rinse the
riser system of cleaning solution.
Chassis installation is permitted once the riser system is thoroughly flushed, cleaned, and commissioned by the
riser treatment company and contractor.
RISER SYSTEM LOOP TEMPERATURE
Correct riser system loop temperature settings are im­portant for optimal unit operation. Temperatures outside of the recommended range will affect overall unit operat­ing performance (capacity and efficiency), long term
reliability and sound performance.
Cooling Season
In cooling mode recommended riser loop temperatures should be maintained between 85oF to 90oF. Higher riser loop temperatures reduce unit cooling capacity and effi­ciency and increase sound levels. Lower riser loop tem-
peratures will increase unit operating efficiency.
Operation of riser loop temperatures above 110oF EWT is not permitted, and sustained operation above 100oF will reduce cooling capacity and may increase unit sound levels and maintenance costs. If loop tempera­tures are close to permissible levels, riser loop can ex­perience water temperature spikes above recommended during peak demand loads. Refer to Table 2: Unit Oper-
ation Limits.
Heating Season
In heating mode riser loop temperatures must be main­tained within 55oF to 90oF for standard range operation. For Geothermal Range operation the system loop must contain an appropriate glycol mixture where system loop temperatures are low enough that could result in freez­ing of the water circuit. For low temperature operation units must come with factory Geothermal Range option. Do not operate riser system below 20oF EWT due to
reduced heating capacity and efficiency. See Table 2.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 8
Operating Limits
Table 2: Unit Operation Limits
Design limits can not be combined. Combin­ing maximum or minimum limits is not al­lowed. This could exceed the operation and
design limits of the unit.
For example: It is not allowed to combine maximum en­tering air temperature (EAT) limits with maximum enter-
ing fluid temperature (EFT) limits.
6. CHASSIS INSTALLATION
Do not apply plumbers putty, pipe dope or
sealing tape to NPSM fittings.
Always use a back-up wrench when tightening
hoses or fittings. Damage to copper pipes and solder joints could result in serious equipment
and property damage.
Check hoses and fittings for any visible dam-
age or debris.
INSTALLATION OF FITTINGS AND HOSES
Upon removal of service cover panel check cabinet inte­rior for construction debris and dust. Clean out all dust
and debris. Close riser shut-off valves and disconnect factory hoses
from riser supply or return shut off valves.
Units with NPSM Riser and Chassis Fittings
Connect the supplied hoses to the Male-NPSM riser shut-off valves. Do not apply pipe dope or pipe sealant to NPSM fittings. Always use a back-up wrench. Do not overtighten. See Figure 9: Hose Kit Details.
Units with NPT Riser and Chassis Fittings
Connect the supplied male-male (NPT/ NPSM) cou­plings to the Female-NPT supply and return riser shut-
off valves. Do not apply pipe dope to the NPSM fittings,
as these are JIC style fittings. Connect the supplied hoses to the riser shut-off valves.
Always use a back-up wrench. Do not overtighten.
CHASSIS INSTALL
1. Remove chassis packaging, leaving cardboard ship­ping cover on the air coil cover in place. Check chassis nameplate to verify chassis model matches cabinet
model for compatibility.
2. Align chassis with front of the cabinet and tilt chassis
so that the back aligns with the cabinet rails.
3. Slide chassis into cabinet partially. Check to ensure wiring harnesses are not being pinched. Adjust the chas­sis to ensure it is resting approximately centered in the
rails.
4. Connect the hoses by hand to the chassis supply and
return connections. Hand tighten, then using a back-up
wrench tighten fittings as necessary. Ensure that the hose supply and return connections are not reversed and matched to correct risers. Water IN and water OUT
is stamped on the chassis sheet metal enclosure.
5. If riser loop system has been commissioned and oper-
ational open the riser shut-off valves. Check for any signs of water leaks at all water connection points.
6. Connect the chassis electrical plugs to the quick con-
nect mating plugs in the cabinet electrical box.
7. Slide the chassis into the cabinet. Check to ensure wiring harnesses and hoses are not being pinched. Do
not push against the air coil surface.
8. Ensure hoses are not pressed against unit cabinet.
9. Remove cardboard shipping cover from the air coil.
10. Install the service cover panel and visually check foam gasket around service cover panel perimeter is not
damaged and providing an adequate seal.
11. Insert filter into service cover panel.
12. Install Return Air Panel into the closet drywall open-
ing if not already done and secure with screws.
Air Limits
Cooling Heating
DB WB DB
Std. Entering Air
Temperature (EAT)
75
o
F 63oF 68oF
Min. Entering Air
Temperature (EAT)
65
o
F 55oF 50oF
Max. Entering Air
Temperature (EAT)
85
o
F 71oF 80oF
Fluid Limits
Standard Range Geothermal Range Cooling Heating Cooli ng Heating
Std. Entering Fluid
Temperature (EFT)
85
o
F 70oF 85oF 60oF
Min. Entering Fluid
Temperature (EFT)
50
o
F 55oF 30oF 20oF
Max. Entering Fluid Temperature (EFT)
110
o
F 90oF 110oF 90oF
CFM Limits
Fluid GPM Limits
Min. CFM/
Ton
300
Min. GPM/
Ton
1.5
Design
CFM/Ton
400
Design
GPM/Ton
3
Max. CFM/
Ton
450
Max. GPM/
Ton
4
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
9 www.omega-heatpump.com
7. UNIT START-UP
Ensure the building loop system has been cleaned, flushed, chemically treated and commissioned by the water treatment company. Verify that the main system strainers or mechanical filtration system has been in­stalled and commissioned. The chassis should be at room temperature (68
o
F) prior to start up.
Once the installation of the cabinet and chassis units is
complete the riser shut-off valves can be opened. The
riser loop system should be filled and all trapped air
should be bled from the system prior to unit start-up.
Water flow failure will cause the unit to trip on the safety devices. Repeated water flow failures can cause equip-
ment damage.
CHECKLIST
Before energizing the unit ensure all steps are verified in
the following checklist:
___High voltage power supply is correct and in accord-
ance with unit nameplate ratings.
___Unit is electrically grounded and circuit protection is
the correct size.
___Low voltage control wiring is correct as per unit wir-
ing diagram.
___Riser loop system is clean, filled, and vented of any
air.
___Chassis unit high and low pressure caps are firmly
secure and in place. ___Chassis matches the cabinet model number.
___Protective cardboard air coil cover is removed and
unit service cover panel and filter are in place.
___There is a proper seal between chassis service cov-
er panel and unit cabinet. ___Riser shut-off valves are in the OPEN position.
___Riser loop system has been vented for any air intro-
duced during chassis installation.
___Riser loop water is circulating through all units and at
design conditions.
___Unit condensate drain hose is securely attached to
drain pan and condensate riser. ___Indoor unit blower spins freely. ___All ductwork is complete. ___Clean filters are installed.
___All cutting, sanding, drywalling, patching work is
complete.
___Unit blower spins freely. ___Thermostat is in the OFF position.
INITIAL UNIT START-UP
1. Close disconnect switch.
2. Set thermostat to a high setting (above current room
temperature), set system to COOL with fan on AU-
TO. The compressor should not run.
3. Lower the thermostat temperature setting until the
fan and compressor energize. Verify the following
results:
Leaving water temperature (LWT) in the heat ex-
changer water coil is warmer than the entering wa­ter temperature (EWT) by approximately 9oF—12
o
F.
Blower is running smoothly.
Compressor and blower amps are within nameplate
data.
Suction line is cool and no frosting is forming in the
refrigeration circuit.
4. Set thermostat to the OFF position. Unit compressor and fan should stop running.
5. Allow the system to equalize for approximately 5 minutes.
6. Set thermostat to the lowest setting and switch to the HEAT position.
7. Adjust thermostat temperature higher until the fan
and compressor energize. The following should
occur:
Warm air will flow from the supply register.
Leaving water temperature (LWT) in the heat ex-
changer water coil is cooler than the entering water temperature (EWT) by approximately 5oF—9
o
F.
Blower and compressor operation is smooth and no
frost development is visible in the refrigeration cir-
cuit.
8. Set the thermostat to the desired temperature.
9. Check for any water leaks at the hose connections.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 10
8. CONTROLS
MICROPROCESSOR CONTROLLER DIP Switch Settings
Controller DIP switch contains 6 switches for setting up thermostat, Fan, and system settings. Microprocessor DIP settings are factory set. Make changes if warranted
by site conditions. Below are the 6 settings: Table 3: DIP Switch Settings
Heat Pump Thermostat
Set DIP #1 to the ONposition for Heat Pump Thermo­stat. Refer to the following table for connecting thermo-
stat to unit terminal blocks: Table 4: Heat Pump Thermostat Connections
Heat/Cool Thermostat
Set DIP #1 set to the OFFposition for conventional HEAT/COOL Thermostat. Refer to the following wiring table for connecting HEAT/COOL thermostats to unit
terminal blocks: Table 5: Heat/Cool Thermostat Connections
Thermostat Cable
Unit comes with a 24 inch long standard 6-wire thermo-
stat cable. This cable is factory wired to TB1 and TB2 terminal blocks on the controller board. Wire other end
of pigtails to thermostat. A minimum 4-wire thermostat
cable is required for single speed thermostats. A field
supplied 7-wire thermostat cable is required if 3-speed fan control is required from a 3-speed thermostat. See Figure 24: Thermostat Wiring Detail.
Multi Fan Speed Thermostat
If connecting thermostats with 3 speed control at the thermostat, DIP switch #6 (FanMode) should be set to
the ONposition. This will ignore the position of the unit
mounted fan speed selector switch. Fan speed will be controlled by thermostat. Connect thermostat fan speed control wiring to the G1,G2, and G3 terminals as shown below. Fan speed is determined by the G1,G2, and G3
signals from the thermostat: G1 Signal = LOW fan speed enabled. G2 Signal = MEDIUM fan speed enabled. G3 Signal = HIGH fan speed enabled.
Single Speed Thermostat
If connecting thermostats with single speed control at the thermostat set DIP switch #6 to the OFFposition,
In this mode thermostat can be connected to any of the
G1,G2, and G3 terminals and a Run Fanrequest from thermostat will energize the fan to a speed determined
by the position of the unit mounted 3-speed fan selector switch:
L = LOW fan speed M = MEDIUM fan speed HI = HIGH fan speed
Fan Control with PSC Motors
Fan speed for units with PSC motors is set using each of
the built-in motor speeds and are selected by either set-
ting the fan speed using the unit mounted fan speed
selector switch or a thermostat with 3-speed fan control
capability. See electrical schematic in Figure 22.
Fan Control with EC Motors (ECM)
Low voltage PULSE WIDTH MODULATED (PWM) sig­nal is utilized to control motor speed between 0 and 100% of full speed. The controller has been pro­grammed to use 3 preprogrammed speeds for Low, Me-
dium and High. See electrical schematic in Figure 23.
Whisper Mode (ECM Only)
Whisper mode runs fan a pre-determined low fan speed
for continuous air circulation. Field wire R1 and G1 with
DIP DESCRIPTION OFF ON
1 Tstat Type Heat/Cool Tstat HeatPump Tstat
2 HP Type Hybrid HP Std Heat Pump
3 FlowType Variable Flow Constant Flow
4 Coax Valve Coax Valve NO Coax Valve NC
HeatCoil Valve NO Heat Coil Valve NC
RV Energized to Heat RV Energized to Cool
6 FanMode Fan Auto Fan Manual
NO = Normally Open and NC = Normall Closed
5
Reversing Valve
(RV)/ HeatCoil
DIP 1 (ON) = HeatPump Thermostat
TERMINAL
BLOCK
WIRE DESCRIPTION
TB1 #4 R 24VAC – Line (R)
TB1 #3 G1 Fan Speed 1 - Low Speed
TB1 #2 G2 Fan Speed 2 - Medium Speed
TB1 #1 G3 Fan Speed 3 - High Speed
TB2 #3 Y Call for Compressor
TB2 #2 O/B Call for Reversing Valve
TB2 #1 C Common
DIP 1 (OFF) = HEAT/COOL Thermostat
TERMINAL
BLOCK
WIRE DESCRIPTION
TB1-4 R 24VAC – Line – (R)
TB1-3 G1 Fan Speed 1 - Low Speed
TB1-2 G2 Fan Speed 2 - Medium Speed
TB1-3 G3 Fan Speed 3 - High Speed
TB2-3 Y Call for Cooling
TB2-2 O/B Call for Heating
TB2-1 C Common
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
11 www.omega-heatp ump.com
a jumper wire to enable this feature. See Figure 24:Thermostat Wiring Detail for wiring instructions.
Fan Control with ECM X13 Motors
Omega utilizes the X13 ECM motor for larger sized Heat
Pumps. The X13 ECM motor is a multi-voltage motor,
with 5 low voltage speed taps, utilizing 208VAC for pri-
mary power and 24VAC for speed selection.
SEQUENCE OF OPERATION Call for Heating and Cooling
Demand call for Heating or Cooling are initiated at the
thermostat.
If a HEAT PUMP Thermostat type is used, with DIP #1
set to ON”, control signal form thermostat to terminal
block sets the following:
YTerminal Closed = call for compressor. O/BTerminal Open = Reversing Valve De-Energized
(call for HEATING).
O/BTerminal Closed = Reversing Valve Energized
(call for COOLING)
If a 1HEAT/1COOL Thermostat type is used, then DIP #1 should be set to OFF. Control signal form thermostat
to terminal block sets the following:
YTerminal Closed = call for COOLING. O/BTerminal Closed = call for HEATING.
Note: If both Yand Oare closed, a call for HEATING
is assumed. When a compressor request is made, the auto shut-off
control valve (COAX Flow valve) will open. The com­pressor contactor will then be energized so long as none
of the following fault conditions are present:
High-Pressure Alarm
Low-Pressure Alarm
Condensate Over Flow Alarm (Optional)
Compressor Anti-Short Cycle 7 min. timer has not
expired
Entering Water Temperature is greater than 115
o
F
Leaving Water Temperature greater than 127
o
F
When call for compressor request is terminated, the
auto shut-off control valve (COAX Flow Valve) and the blower fan will remain open for an additional 3 minutes.
Low-Pressure Bypass
During a call for compressor, the low-pressure switch is
bypassed for the first 2 minutes of compressor operation
to prevent nuisance low-pressure start-ups.
Timers and Interlocks
Microprocessor board utilizes a number of timers and
interlocks in the control sequence of the unit.
Anti-Short Cycle Timer
The compressor anti-short cycle timer of 7 minutes
starts every time a call for compressor is terminated to
prevent compressor over cycling.
Fan-On Timer
The Fan-On timer of 3 minutes starts anytime there is a call for fan request.
Fan-Off Timer
The Fan-Off timer of 3 minutes starts anytime a call for
compressor is terminated to ensure fan runs for a period
of 3 minutes after the compressor turns off.
Valve Open Timer
The valve open timer of 1 minutes starts anytime a fan and compressor request are made to develop flow in the
water coil.
Valve Closed Timer
The valve closed timer of 1 minutes starts anytime a call for compressor is terminated to allow for flushing of the
water coil.
Random Wait Time on Unit Power Up
Microprocessor controller uses a random wait time dur-
ing unit start up between 1-30 seconds.
9. TROUBLESHOOTING
Refer to the Table 6: Troubleshooting Guide for identify­ing common issues and possible resolutions. The micro­processor control board has a number of LED lights for simple identification of common alarms and faults. Refer
to Table 7.
TEST MODE
A Test mode feature can be enabled in order to perform diagnostic testing of the unit. Test mode will bypass all
unit timer delays for 10 minutes.
To enable test mode jumper DI1pins on the micropro­cessor board. The unit will operate in test mode. Re­move jumper from DI1 if not already done so to get out of test mode. Failure to remove DI1 jumper will disable important safety controls such as High and Low Pres-
sure switches.
Failure to remove DI1 jumper will disable criti­cal safety controls and may cause equipment
or property damage if left disabled.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 12
Unit status and diagnostics temperature readings can be easily accessed using the Web based tool as described
in the following Web Based Access section.
WEB BASED ACCESS
The Omega controller hosts a webpage configuration and troubleshooting aid. There are two ways to connect:
using a mini-wireless router or directly to a laptop. Wire-
less router is the preferred method for fewer configura-
tion steps.
Wireless Router Method
1. To connect to the controller you will need the follow­ing: Ethernet cables, Laptop, and wireless router (e.g.
TP Link TL-WR802N, shown below).
2. Remove electrical box access panel and connect ethernet cable directly into surface mounted ethernet port (RJ45) on controller board and to wireless router
port.
3. Open up your internet browser (i.e. Explorer, Google Chrome) and type in the following address
192.168.0.99.
Direct to Laptop Method
1. To connect to the controller you will need the follow-
ing: Ethernet cable & Laptop.
2. Remove electrical box access panel and connect ethernet cable directly into surface mounted ethernet
port (RJ45) on controller board.
3. On laptop access Network and Sharing Center though the Network & Internet Settingsicon located in
the bottom right taskbar.
4. In the Network & Sharing Center click on Ethernet” /
Local Area Connectionas indicated below.
5. Local Area Connection Status will open, click on Properties, then click on Internet Protocol Version 4
(TCP/IPv4)”, and click on Properties for IPv4.
6. With Internet Protocol Version 4 (TCP/IPv4) window open click on Use the Following IP Addressand change the IP address to 192.168.0.100 and Subnet mask to 255.255.255.0, as show below. Then click
OK”.
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
13 www.omega-heatp ump.com
7. Open up your internet browser (i.e. Explorer, Google Chrome) and type in the following address
192.168.0.99.
8. The following home page will load for the controller software. Below is a screen shot of the interface (version
5.4 software is shown).
9. An event log feature called Log Dump allows for re-
cording unit operation information during faults or at start
-up as a troubleshooting aid. For example in the figure
below the first line item indicates Yterminal was ener­gized (Y=1) when the Cooling (CLG=1) and tripped on
Low Pressure fault (LP=0).
Captured unit controller details include: Y’ ,’O/B’, ‘CPR =compressor, RV’= reversing valve, HTG’ = heating, CLG’ = cooling, LP = low pressure, HP’ = high pres-
sure, Fan, Condensate, LPALM = low-pressure alarm, HPALM = high-pressure alarm.
. The following home page will load for the controller software. Below is a screen shot of the interface (version
5.4 software is shown).
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 14
10. MAINTENANCE GUIDE
Proper unit maintenance will result in optimal unit performance and prevent potentially costly repairs or property damage. Turn unit disconnect switch to off and turn unit off at circuit breaker/
fuse panel before starting maintenance procedure.
Do not operate unit without filters or during any temporary construction that could clog the air filter
or air coil.
Do not use any cleaning solutions that contain acids
on the air-refrigerant coil or any refrigerant compo-
nents.
30 DAY MAINTENANCE
1. Visually inspect filter monthly for dirt and clogging. Re- place as required with a quality filter.
2. Vacuum dust from unit air grilles and surrounding coil area with soft bristle brush attachment as required.
3. Filters with a rating higher than MERV 11 may reduce
airflow and increase fan power consumption and unit cool-
ing or heating performance.
4. Every month visually inspect unit for any signs of water
leaks, or water damage around floor or surrounding dry-
wall.
3 MONTH MAINTENANCE
1. Inspect condensate drain every 3 months for signs of
stagnant water, microbial growth, and mineral buildup. Clean drain pan with an appropriate cleaning solution as required to prevent condensate hose blockages and mi-
crobial growth.
2. Check valves and hoses for signs of leaks, cracking or deterioration.
6 MONTH MAINTENANCE
1. Check condensate flow to ensure adequate drainage and test for signs of impending blockages.
2. Check that condensate alarm is operating correctly. Alarm
trips whenever water level rises above sensor threshold
and locks unit operation.
3. Visually inspect the air coil for signs of dirt accumulation. Use a mild detergent or coil-cleaning agent. DO NOT use
any cleaning solutions that contain an acid, including ace­tic acid (vinegar). Damage to the air coil may occur result-
ing in possible refrigerant leaks.
ANNUAL MAINTENANCE
1. Perform an annual maintenance inspection of the fan and
blower motor assembly. All units come with permanently lubricated fan motors. DO NOT oil or lubricate fan motors.
Clean up any dirt or debris that may have accumulated.
2. Visually inspect the electrical box annually for signs of
component damage due to overheating or poor electrical
contact.
3. Completely clean the interior of the cabinet. Vacuum any dust or debris.
REPLACEMENT FILTERS
Disposable 1-inch thick replacement filters, sizes listed below and can be obtained from any HVAC parts supplier.
Pleated filters rated between MERV 8 to MERV 11 are prefera­ble as they will provide optimal filtration. Higher rated filters (MERV 12, 13+) may reduce airflow and affect unit heating and cooling performance. Verify that the unit can produce the de-
sired airflow before installing high efficiency filters.
Table 6: Filter Sizes
VSHP 020
VSHP 030
VSHP 040 VSHP 050 VSHP 060 VSHP 080 VSHP 100 VSHP 120
Y
16 x 25 x 1
Z
20 x 25 x 1
Model
Cabinet
Size
X
14 x 25 x 1
Replacement Filter
Size (in)
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
15 www.omega-heatp ump.com
Table 7: Troubleshooting Guide
Problem Mode Possible Cause(s) Correction Method
No response to any thermostat
setting
Heating/Cooling Main power off
Check unit disconnect switch/ circuit breaker/ fuses
Heating/Cooling Defective control transformer
Confirm thermostat is wired correctly before replacing
Heating/Cooling Broken or loose connection
Check for loose thermostat connections. Repair and/or tighten as required.
Heating/Cooling Defective thermostat
Check and replace
Unit short cycles Heating/Cooling Thermostat improperly located
Relocate thermostat away from supply registers
Only blower runs,
but not compres-
sor
Heating/Cooling Defective compressor overload
Check and replace if required (if external)
Heating/Cooling Defective compressor contactor
Check and replace if required
Heating/Cooling Supply voltage too low
Correct incoming supply voltage setting at Transformer
Heating/Cooling Defective compressor capacitor
Check and replace if required
Heating/Cooling Defective compressor windings
Check and replace if required
Heating/Cooling Limit switches open
Check for faulty pressure switches. Switches are normally closed. Replace if switches are open when unit is shutdown.
Heating/Cooling
Clogged Drain Pan / Condensate hose /
Faulty Sensor
Condensate switch detects overflow condition in drain pan, check for obstruction. If no
water, check switch, replace if required.
Insufficient
capacity
Heating/Cooling Dirty filter
Check and replace
Heating/Cooling Blower RPM too low
Set to blower to higher fan speed
Heating/Cooling
Loss of conditioned air due to ductwork
leaks
Check for duct leaks and repair
Heating/Cooling Low on refrigerant charge
Possible leak in system. Check for leaks at piping joints and coil. Repair if possible, and recharge to unit nameplate charge rating.
Heating/Cooling Defective reversing valve
Check and replace
Heating/Cooling Thermostat improperly located
Relocate thermostat
Heating/Cooling Inadequate water flow
Increase GPM
Cooling Entering Water Temperature too hot
Adjust EWT Loop temperature lower
Heating/Cooling Entering Water Temperature too cold
Adjust EWT Loop temperature higher
High Pressure
Fault
Cooling Inadequate GPM
If auto shut-off valve is installed, check that control valve actuator opens during call for Heating. Set valve to manual mode and remove power connections from actuator and re
-test. If manual mode re-test confirms proper water flow, actuator is likely faulty.
Cooling W ater too hot
Reduce water loop temperature
Heating Inadequate air flow
Check blower. Typical airflow should be 400 cfm/Ton across air coil. Check for dirty or obstructed air coil.
Heating Dirty filter
Clean/replace
Heating/Cooling Overcharged with refrigerant
Decrease charge/Confirm charge matches nameplate.
Heating/Cooling Defective pressure switch
Check or replace
Low Pressure
Fault
Heating/Cooling Undercharged
Possible leak in system. Check for leaks at piping joints and coil. Repair if possible, and recharge to unit nameplate charge rating.
Cooling
Faulty thermal expansion valve (TXV)
operation
Flooding of refrigerant caused by the TX valve not opening/closing correctly. Check TX valve bulb has not come loose.
Cooling Inadequate air flow
Check blower. Typical airflow should be 400 cfm/Ton across air coil. Check for dirty or obstructed air coil
Cooling Dirty filter
Check and replace
Heating Inadequate GPM
Check GPM to unit. If auto-flow reg. valve installed check GPM matches rating of auto­flow reg. valve.
Heating Inadequate GPM
If auto shut-off valve is installed, check that control valve actuator opens during call for Heating. Set valve to manual mode and remove power connections from actuator and re
-test. If manual mode re-test confirms proper water flow, actuator is likely faulty.
Heating Inadequate GPM
Inadequate water flow from riser loop system. Units are nominally rated for 3GPM/Ton. Check water flow from riser system and confirm capability to provide required GPM to unit.
Water Loop
Discharge Temp
Alarm
Cooling
Inadequate GPM/Too High Riser Loop
Temperature
Leaving water temperature from water coil exceeds acceptable operating temperature (127oF). Check for clogged or faulty water components, or too low GPM riser supply or too high entering water temperature.
Water Loop
Supply Temp
Alarm
Heating/Cooling Too High Riser Loop Temperature
Entering water temperature to water coil exceeds acceptable operating temperature (115
o
F). Lower riser water loop temperature.
Condensate
Overflow Alarm
Cooling Clogged Drain Pan / Condensate hose
Condensate switch detects overflow condition in cabinet drain pan. Check for plugged, obstructed or pinched condensate hose.
Refrigerant
Suction Alarm
Heating/Cooling Suction Temperature sensor defective.
Check that sensor is not open or closed. Check for resistance, if reading Zero of Infinity replace sensor.
Heating/Cooling Suction Temperature below threshold
Suction temperature is below 50oF in cooling and 70oF in heating. Refer to possible causes under "Low Pressure Fault".
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 16
Table 8: Microprocessor LED Code Guide
LED Description LED Code Alarm Description
HP High Pressure
Red = Solid High pressure alarm. Hard Lock-Out. 3 Trips
Red = Blinking High pressure alarm. Soft Lock-Out
LP Low Pressure
Red = Solid Low pressure alarm. Hard Lock-Out. 3 Trips
Red = Blinking Low pressure alarm. Soft Lock-Out
WLDT
Water Loop Dis-
charge Temp
Red = Solid Water loop discharge temperature too hot. Non-latching alarm
Red = Blinking Sensor open/missing or close/shorted. Latching alarm, replace sensor
CO
Condensate Over-
flow
Red = Solid Condensate overflow alarm. Hard Lock-Out. 2 Trips
Red = Blinking Condensate overflow alarm. Soft Lock-Out
RST
Refrigerant Suction
Temp
Red = Blinking Sensor open/missing or close/shorted. Latching alarm, repair/replace part
WLST
Water Loop Supply
Temp
Red = Solid Water loop supply temperature too hot. Non-Latching fault
Red = Blinking Sensor open/missing or close/shorted. Latching fault
STA PCB Status Green = Blinking PCB is operational
CLG Cooling Green = Solid Cooling call from thermostat input
HTG Heating Green = Solid Heating call from thermostat input
Note: LED table applicable to version 5.4 software only.
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
17 www.omega-heatp ump.com
Ceiling
Acoustic
Top Discharge
Plenum
Neoprene Isolation Pads
Fastened to Ceiling Slab with Brackets
(by others)
Flexible Connection
Bottom Fan Cabinet
Silver Series Gold Series
Figure 4 Silver and Gold Series Cabinets
Silver series is the Omega standard product built as free standing design. The optional Gold series cabinet includes a factory built-in canvas flex duct collar between the base chassis/blower section and upper discharge plenum. The Gold series upper plenum and base cabinet are secured with shipping brackets to be removed in the field. The upper discharge plenum is field mounted to the ceiling structure creating a non-rigid, acoustically isolated connec­tion between the discharge plenum and the cabinet compressor and blower base section.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 18
Right Hand Riser (RH-SR)
Back (BK-SR)
Left Hand (LH-SR)
Right Hand (RH-RS)
Back (BK-RS)
16.0
(Typ.)
6.0
(Typ.)
6.0
(Typ.)
S
R
c
S
R
Chassis
6.0
(TYP.)
3.0 (TYP.)
3.0 (TYP.)
S
R
c
R
S
Chassis
K
3.0 3.0
D
W
S
R
c
S
R
Chassis
FRONT Return
Air
FRONT Return
Air
FRONT Return
Air
S
R
c
S
R
Chassis
S
R
c
R
S
Chassis
S
R
c
S
R
Chassis
FRONT Return
Air
FRONT Return
Air
FRONT Return
Air
Left Hand (LH-RS)
Legend:
S = Supply Riser
C = Condensate Riser
R = Return Riser
Figure 5 Riser Handing Configurations (Top View)
Table 9 VSHP Cabinet Riser Dimensions
Notes:
As viewed from top, risers can be order in either SR configuration (supply, condensate, return) or RS (return, condensate, supply). Risers can be ordered from factory with 3 inch deep swage. Contractor to provide riser transition pieces when joining dissimilar riser sizes. All handing's determined by facing front of the unit (return air opening)
020 030 040 050 060 080 100 120
Cabinet Size
W (in)
D (in)
K (in)
Model
VSHP
568
161822
18.5
21.5
25.5
XYZ
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
19 www.omega-heatp ump.com
Figure 6 Riser Length Reference Measurements
Notes:
Risers are positioned relative to cabinet using a standard “Top” Datum reference (optional “Base” Datum). Top Datum Offset
indicates where the top of riser will be located relative to top of cabinet. A Base Datum indicates where bottom of riser will be located relative to base of cabinet.
Upon request Omega will provide 3 inch deep swage on risers of same pipe size (optional for all risers) for connection to units on the
floor below.
Risers should insert 2 inches into the 3 inch deep swage connection (minimum 1 inch insertion is required) Riser Length = Floor Clearance Height + Slab Thickness + 2 inch (overlap) (Rounded up to 120” or 144”). Omega supplies two standard riser lengths, 120” (10’) and 144” (12’), to be field cut on-site.
Omega does not supply extension tailpieces or transition riser pieces for joining dissimilar piping sizes. Items are field provided.
Risers available in Type L and Type M/DWV copper. Condensate riser comes standard with 3/8 inch thick closed cell insulation to prevent condensation. Optional insulation on supply and return risers is available.
Cabinet
Height
5"
Floor
Clearance
Height
Slab
Thickness
2"
Overlap with
Connected Pipe
3"
Extended From
Unit Top (Std.)
3"
Swage
End
Slab Thickness
+
Desired Overlap
Slab
Unit Top
(Datum)
Custom vertical
riser offset
positions taken from
above Unit Top
(Optional) Offset
taken from
Unit Bottom
Unit Bottom
(Datum)
Slab
Bottom
Datum
Top
Datum
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 20
Figure 8 Riser Stub Distance from Cabinet Wall
RIGHT SIDE VIEW
29.5"
2.5" Condensate
Connection
Riser Stub-Out Opening
4"
3"
Note:
Stub-Outs
Centered on
Back Riser
6"
6"
Base Height
Figure 7 Riser Stub-Out Opening Detail (Side View)
(Note: Back/Rear Risers are centered to the cabinet)
Return Air
Return Air
Center riser stub-outs in cabinet riser openings. Do not let stub­outs rest on or contact sheet metal cabinet, otherwise can result in water leaks and property damage.
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
21 www.omega-heatp ump.com
Riser
Shut-off Valve w/ MNPSM Male Thread
Flexible Hose
w/ FNPSM Female Thread
Chassis Connection
w/ MNPSM Male Thread
Figure 9 Hose Kit Details
Table 10 Hose Kit Sizes
Model
Hose Kit
Size (in)
Length
(in)
VSHP 020 1/2 24
VSHP 030 1/2 24
VSHP 040 1/2 24 VSHP 050 1/2 24 VSHP 060 1/2 24 VSHP 080 3/4 30 VSHP 100 3/4 30 VSHP 120 3/4 30
Hose kits are supplied with each unit. Hose kit configurations vary by unit size as shown.
Right Side Riser Installation shown
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 22
Notes:
Unit comes standard with field “knockout” style discharge openings on all sides. Discharge flanges are 1-1/2 inches. Line of Site Baffles (LOSB) are available where two or more horizontal discharge (Front, Left, Right and/or Back) openings are
specified.
All handing's determined by facing return air opening
Table 11 Supply Air Opening Sizes
Return Air
W
W
H
H
TOS = Top Offset
3" Std
1.5" Min.
TOS
F
(Front)
L
(Left)
T
(Top)
B
(Back)
R
(Right)
TOS
020 030 040 050 060 080 100 120
Horizontal
14 x 8 14 x 8 14 x 10 16 x 12 16 x 12 18 x 14 18 x 16 18 x 16
Top
12 x 12 12 x 12 12 x 12 14 x 12 14 x 12 14 x 14 16 x 14 16 x 16
Model
VSHP Supply Discharge Opening (W X H) inches
Units comes with standard “Knockout” style discharge openings on top and all sides for field configuration. This allows for custom dis­charge configurations based on site requirements.
Figure 10 Standard “Knockout” Style Openings
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
23 www.omega-heatp ump.com
Optional built-in Fresh Air Duct is suited for applications where the Energy Recovery Ventilator (ERV) unit is remote mounted. The factory installed fresh air intake accepts fresh air connection from a remote mounted ERV.
Figure 11 Optional Fresh Outside Air Duct
Note: Handing is referenced
by facing the unit return air
opening (front).
OA - Fresh Outside Air Intake
The introduction of cold conditioned outside air from a remote energy recovery ventilation device into the heat pump cabinet can result in potential freezing and bursting of mechanical components. All necessary precautions should be taken to temper Outside Air sufficiently above freezing point before entering the unit.
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 24
Top discharge for VSHP cabinet with fresh air duct is available in two orientations: Horizontal and Vertical. With in each orienta-
tion, Omega offers (4) different configuration option for fresh air duct location. Customer to advise required configuration.
Table 12 Supply Air Opening Sizes w/ Fresh Air Duct
Figure 12 Top Supply Air Opening Configurations with Fresh Air Duct
HFL - Horiz.
Front Left Duct
HFR - Horiz.
Front Right Duct
3" Typ.
3" Typ.
"A"
"B"
"HORIZONTAL"
DISCHARGE
"VERTICAL"
DISCHARGE
HBL - Horiz.
Back Left Duct
HBR - Horiz.
Back Right Duct
"A"
"B"
3" Typ.
3" Typ.
3" Typ.
3" Typ.
3" Typ.
3" Typ.
2" Typ.
2" Typ.
2" Typ.
2" Typ.
VBL - Vert.
Back Left Duct
VBR - Vert.
Back Right Duct
VFL - Vert.
Front Left Duct
VFR - Vert. Front
Right Duct
"W"
"D"
RETURN AIR RETURN AIR RETURN AIR RETURN AIR
"W" "D" "Horizontal" "Vertical"
VSHP 020
12 x 10 8 x 14
VSHP 030
12 x 10 8 x 14
VSHP 040
12 x 10 8 x 14
VSHP 050
14 x 12 10 x 16
VSHP 060
14 x 12 10 x 16
VSHP 080
14 x 14 14 x 14
VSHP 100
16 x 14 14 x 18
VSHP 120
16 x 16 14 x 18
Top Supply Opening w/ Fresh Air
Duct (A x B) inches
Y
Z
Model
Cabinet
Size
X
Dimensions (in)
22
16
18.5
21.5
25.5 18
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
25 www.omega-heatp ump.com
Note: Apply acousc Insulaon to the internal surface of closet for enhanced sound aenuaon.
Table 13 Acoustic Panel Sizes
Figure 13 VHSP Acoustic Return Air Panel
"D"
"C"
"A"
2"
Mounting Holes x4
A B C D
VSHP 020
VSHP 030
VSHP 040 VSHP 050 VSHP 060 VSHP 080 VSHP 100 VSHP 120
21 1/4
X5415 1/4
23 5/8 56 1/2
19 5/8
56 1/2
Y5417 1/4
Z
54
Cabinet
Size
Model
Acoustic RA Panel Dimensions (inches)
56 1/2
17 5/8
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 26
Figure 14 Acoustic Panel Cabinet Base Height Diagram
Acoustic Panel Cabinet Base Height Calculation
BH = Baseboard Height + Finish Floor Height* G = Gap (min 0.5”) between baseboard and panel. B = Cabinet Base Height
(Min 5", increases in 1" increments)
B = BH + G - 1.5”
Note: *Include flooring thickness, underlayment, and any concrete leveling as part of calculation.
Example:
If using a 5" baseboard, with 1” Finished Flooring
height, and 0.5" gap:
B = (5” + 1”) + (0.5”) - 1.5”
B = 5" Therefore a 5” Cabinet Base is required.
G
BH
B
Flooring
Cabinet Base
Concrete Slab
Baseboard
Acoustic
Return Air
Panel
1.25"
Example: Baseboard to Base Height Table
Baseboard Height* Cabinet Base Height
Up to 5" 5" >5" to 6" 6" >6" to 7" 7" >7" to 8" 8"
*Includes 1" Total Flooring *Using gap G= 0.5" (from top of baseboard to return panel flange)
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
27 www.omega-heatp ump.com
Notes:
The framing should be installed for a min. 1/8” and max. 1” clearance between unit RA flange and RA panel sleeve.  Return air panel should be centered in front of the unit return air opening.  With rear/side risers, allow for min. 6” typical clearance at the rear/side of the units.  Insulate the drywall enclosure with plenum rated acoustical insulation for additional sound attenuation.
Figure 15 Acoustic Panel Furring DetailTyp. 2x2 Framing Plan View
0.625"
Min. 2"
Front of Cabinet to
Front Drywall
Typ. 1/2" Drywall
Nom. 2x2 Studs Shown (1-1/2" x 1-1/2")
Removable
Acoustic RA Grille
1/2" Unit RA Flange
Screws x 4
Rough-In Width
Acoustic
RA Panel Frame
Unit Cabinet to Back Wall:
No Risers = Min. 1/2"
W/ Risers = Min. 6" Typ.
"S"
Unit RA Flange to RA Panel (Min. = 1/8"; Max.= 1")
Unit Cabinet to Left/Right Wall:
W/ Nom. 2"x2" Studs = Min. 1-1/2"
Seal RA Perimeter w/
Foam Gasket Tape / Foil Tape
VSHP CABINET
Use Foam Gasket Tape
Figure 16 Acoustic Panel Typ. 2x4 Framing Plan View
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 28
Figure 17 Acoustic Panel Furring DrawingFront & Side View
B = Cabinet Base Height (Min 5", increases in 1" increments) C = Flange Height Above Floor (B + 1.25”) D = Rough-In Height Above Floor ( B + 2.5")
Table 14 Acoustic Panel Rough-In Dimensions
Y
X
W D "X" "Y"
VSHP 020
VSHP 030
VSHP 040 VSHP 050 VSHP 060 VSHP 080 VSHP 100 VSHP 120
15 3/4 17 3/4
21 3/4
Rough-In (in)
54 1/2
Cabinet Dimensions (in)
Model
Cabinet
Size
X1618 1/2
Y1821 1/2
54 1/2
Z2225 1/2
54 1/2
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
29 www.omega-heatp ump.com
Figure 18 Perimeter Panel Dimensional Drawing
Table 15 Perimeter Panel Sizes
"D"
"C"
"A"
2"
"B"
A B C D
VSHP 020
VSHP 030
VSHP 040 VSHP 050 VSHP 060 VSHP 080 VSHP 100 VSHP 120
Model
Cabinet
Size
Perimeter RA Panel Dimensions (inches)
X
58 1/4
19 1/8
60 3/4
21 5/8
Y
58 1/4
21 1/8
60 3/4
23 5/8
Z
58 1/4
25 1/8
60 3/4
27 5/8
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 30
Perimeter Panel Cabinet Base Height Calculation
BH = Baseboard Height + Finish Floor Height* G = Gap (min 0.5”) B = Cabinet Base Height
(Min 5", increases in 1" increments)
B = BH + G + 0.5”
Note: *Include flooring thickness, underlayment, and any concrete leveling as part of calculation.
Example:
If using a 5" baseboard, with 1” Finished Flooring height,
and 0.5" gap:
B = (5” + 1”) + (0.5”) + 0.5” B = 7"
Therefore a 7” Cabinet Base is required.
G
BH
B
0.5"
Flooring
Cabinet Base
Concrete Slab
Baseboard
Perimeter
Return Air
Panel
Example: Baseboard to Base Height Table
Baseboard Height* Cabinet Base Height
Up to 3" 5" >3" to 4" 6" >4" to 5" 7" >5" to 6" 8"
*Includes 1" Total Flooring *Using gap G= 0.5" (from top of baseboard to return panel flange)
Figure 19 Perimeter Panel Cabinet Base Height Diagram
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
31 www.omega-heatp ump.com
Figure 20 Perimeter Panel Furring DetailTyp. 2x2 Framing Plan View
Notes:
The framing should be installed for a min. 1/8” and max. 1” clearance between unit RA flange and RA panel sleeve.  Return air panel should be centered in front of the unit return air opening.  With rear/side risers, allow for min. 6” typical clearance at the rear/side of the units.
Seal RA perimeter with foam gasket tape or foil tape.
Insulate the drywall enclosure with plenum rated acoustical insulation for additional sound attenuation.
2"
Min. 2"
Front of Cabinet to
Front Drywall
Typ. 1/2" Drywall
Nom. 2x2 Studs Shown (1-1/2" x 1-1/2")
1/2" Unit RA
Flange
Screws x 6
Rough-In Width
Perimeter
RA Panel Frame
Unit Cabinet to Back Wall:
No Risers = Min. 1/2"
W/ Risers = Min. 6" Typ.
"S"
Unit RA Flange to RA Panel (Min. = 1/8"; Max.= 1")
Unit Cabinet to Left/Right Wall: W/ Nom. 2"x2" Studs = Min. 3"
Seal RA Flange Perimeter w/
Foam Gasket Tape
VSHP CABINET
Use Foam Gasket Tape
Figure 21 Perimeter Panel Typ. 2x4 Framing Plan View
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 32
Figure 22 Perimeter Panel Furring Drawing– Front & Side View
B = Cabinet Base Height (Min 5", increases in 1" increments) C = Flange Height Above Floor (B - 0.5”) D = Rough-In Height Above Floor ( B + 0.625")
Table 16 Perimeter Panel Rough-In Dimensions
Y
X
W D "X" "Y"
VSHP 020
VSHP 030
VSHP 040 VSHP 050 VSHP 060 VSHP 080 VSHP 100 VSHP 120
Rough-In (in)
Cabinet Dimensions (in)
Model
Cabinet
Size
Z2225 1/2
58 3/4
18 1/2
Y1821 1/2
58 3/4
58 3/4
X1619 1/2
21 1/2
25 1/2
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
33 www.omega-heatp ump.com
Figure 23 VHSP Electrical SchematicPSC Fan Motor
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 34
Figure 24 VHSP Electrical SchematicECM Fan
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
35 www.omega-heatp ump.com
Note: Factory supplied 6-wire 24 inch thermostat cable coiled up in low-voltage compartment of electrical box for field wiring to
thermostat. Single speed thermostat thermostats require minimum 5-wire low voltage control wire harness.
G1
G2RG3
Y
O/B
C
Power Cable
Entrance
Low Voltage Control Wire Entrance
G1
G2RG3
Y
O/B C
Notch For Optional Front Low Voltage Control Wire Entrance
Optional ECM Fan w/ Whisper Mode Jumper R1 & G1
Standard Fan Mode w/ Factory 6-wire Control Harness
Factory supplied 6-
wire thermostat cable shown. Field supplied
7-wire required for 3-
speed fan thermo-
stats
Figure 25 Thermostat Wiring Detail
Heat Pump Thermostat Connection Detail: R = 24VAC G1 = Fan Speed 1 G2 = Fan Speed 2 G3 = Fan Speed 3 Y = Compressor On O/B = Reversing Valve C = Common
On Heat/Cool Thermostats: Y = Cooling O/B = Heating
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 36
Note: All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).
Airflow ratings include resistance of dry coil, Return Air panel and clean MERV10 air filters.
Contact customer service for external static pressure requirements exceeding 0.5” w.g.
Model
Min.
SCFM
Rated SCFM
Speed
External Static Pressure (in w.g.)
0 0.1 0.2 0.3 0.4 0.5 0.6
SCFM SCFM SCFM SCFM SCFM SCFM SCFM
020 150 200
LOW 285 230 210 195 160 - ­MED 320 270 250 225 200 160 -
HIGH 430 355 340 315 280 240 185
030
210 350
LOW 275 235 220 - - - ­MED 310 275 250 230 - - -
HIGH 405 370 350 315 280 235 -
040 270 460
LOW 340 300 275 - - - ­MED 410 370 350 338 315 - -
HIGH 600 550 520 500 380 310 -
050 370 530
LOW 560 510 475 450 - - ­MED 645 585 550 505 460 415 -
HIGH 765 715 670 630 585 530 455
060 410 630
LOW 560 510 475 450 - - ­MED 645 585 550 505 460 415 -
HIGH 765 715 670 630 585 530 455
080 270 820
LOW 785 735 700 655 615 570 ­MED 855 790 750 710 670 615 -
HIGH 895 840 790 745 710 645 600
100 640 1010
LOW 895 855 790 745 670 - ­MED 1045 970 925 855 785 710 -
HIGH 1155 1075 1010 935 845 775 670
120 740 1200
LOW 1155 1080 1015 950 875 790 ­MED 1170 1095 1025 970 890 800 -
HIGH 1225 1150 1080 1000 935 850 760
Table 17 PSC Fan Data
OMEGA | WATER SOURCE HEAT PUMPS O MEGA -VSHP .F-IOM- 1907
37 www.omega-heatp ump.com
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6
SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM
WHISPER*
MODE
N/A
N/A N/A 210 195 180 160 145 130 115 100 75 55 - - -
LOW
250 240 225 210 200 185 150 - - - - - -
MED
- - 255 240 225 215 200 190 175 165 150 - -
MED
- - 255 240 225 215 200 190 175 165 150 - -
HIGH
- - - - 260 240 230 220 210 195 185 175 165
WHISPER*
MODE
N/A
N/A N/A 225 210 195 175 160 145 130 115 100 85 70 - -
LOW
315 305 295 285 275 265 250 240 225 - - - -
MED
350 340 335 325 315 305 295 285 275 265 255 245 235
MED
350 340 335 325 315 305 295 285 275 265 255 245 235
HIGH
- - 365 355 350 340 330 320 310 305 295 285 275
WHISPER*
MODE
N/A
N/A N/A 250 230 225 205 180 160 145 125 110 90 75 - -
LOW
410 400 390 380 370 365 350 340 330 325 310 300 -
MED
460 450 445 440 430 425 415 405 395 385 375 365 355
MED
460 450 445 440 430 425 415 405 395 385 375 365 355
HIGH
- - - - 470 465 455 445 435 430 420 410 400
WHISPER*
MODE
N/A
N/A N/A 450 430 410 390 370 350 320 300 270 250 220 - -
LOW
520 510 490 470 450 430 410 390 375 - - - -
MED
- - 550 540 520 505 485 470 450 430 410 390 375
MED
- - 550 540 520 505 485 470 450 430 410 390 375
HIGH
- - - - - - 555 540 525 510 490 475 460
WHISPER*
MODE
N/A
N/A N/A 450 430 410 390 370 350 320 300 270 250 220 - -
LOW
580 565 550 540 520 505 485 470 450 - - - -
MED
640 620 610 595 580 565 555 540 525 510 490 475 460
MED
640 620 610 595 580 565 555 540 525 510 490 475 460
HIGH
- - 675 670 655 650 640 620 610 595 580 565 550
WHISPER*
MODE
N/A
N/A N/A 620 580 560 520 480 440 410 380 340 300 260 - -
LOW
800 760 740 720 695 660 640 620 - - - - -
MED
880 860 840 820 800 780 750 720 700 670 650 625 600
MED
880 860 840 820 800 780 750 720 700 670 650 625 600
HIGH
- - - - 895 880 860 820 805 795 780 770 760
WHISPER*
MODE
N/A
N/A N/A 620 580 560 520 480 440 410 380 340 300 260 - -
LOW
960 940 920 890 860 840 820 800 775 750 - - -
MED
1080 1060 1040 1010 990 970 950 930 900 880 860 840 820
MED
1080 1060 1040 1010 990 970 950 930 900 880 860 840 820
HIGH
- - - - 1110 1090 1070 1060 1040 1020 990 980 960
WHISPER*
MODE
N/A
N/A N/A 620 580 560 520 480 440 410 380 340 300 260 - -
LOW
1120 1100 1090 1070 1050 1025 1010 990 970 940 920 - -
MED
1230 1200 1185 1170 1150 1130 1110 1095 1080 1055 1040 1020 1000
MED
1230 1200 1185 1170 1150 1130 1110 1095 1080 1055 1040 1020 1000
HIGH
1320 1290 1275 1260 1240 1225 1205 1190 1175 1160 1140 1120 1100
100
LOW ESP
750
1010
HIGH ESP
120
LOW ESP
900
1200
HIGH ESP
060
LOW ESP
450
630
HIGH ESP
080
LOW ESP
600
820
HIGH ESP
040
LOW ESP
300
460
HIGH ESP
050
LOW ESP
375
530
HIGH ESP
020
LOW ESP
150
200
HIGH ESP
030
LOW ESP
220
350
HIGH ESP
External Static Pressure (in w.g.)
Model
EC Motor
Speed
External
Static
Pressure
Option
Min.
SCFM
Rated SCFM
Note: All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt). Airflow ratings include resistance of dry coil, Return Air panel and clean MERV10 air filters.
*Whisper mode during Fan On / Compressor Off mode for air circulation. Requires filed jumper of Rand G1on terminal strip. See
Figure 24 for wiring information.
Table 18 ECM Fan Data
OMEGA-VSHP.F-I OM-1907
www.omega-heatpump.com 38
Omega has a policy of continuous product improvement and reserves the right to change design and specifications without notice.
VSHP UNIT START-UP SHEET
INSTALLATION INFORMATION Job Name____________________________ City______________________Province/State_______________Postal/ZIP Code___________ OMEGA Unit Model #____________________________________________________________ OMEGA Unit Serial #____________________________________________________________ Unit Tag#__________________________ Technician___________________________Company_________________________________
Heating
Riser Fluid Loop Temperature: Entering Water Temperature (EWT):______F Leaving Water Temperature (LWT): ______F
T = EWT - LWT = _________oF
Water Flow Rate (GPM):______
(units with optional balancing valve see nameplate for
GPM rating)
Air Temperature (Measure the difference in temperature across air coil) for measuring
sensible capacity: T = LAT - EAT Sensible Capacity (Btuh) = T x CFM x 1.08
Entering Air Temperature (EAT):______F Leaving Air Temperature (LAT): ______F
T = _________
o
F
Sensible Capacity (Btuh) = _________
Fan Speed Used: Low Med High
Compressor Amp: ________ Fan Amp: ________ Run Time For Test: ________
Cooling
Riser Fluid Loop Temperature: Entering Water Temperature (EWT):______F Leaving Water Temperature (LWT): ______F
T = LWT - EWT = _________oF
Water Flow Rate (GPM):______
(units with optional balancing valve see nameplate for
GPM rating)
Air Temperature (Measure the difference in temperature across air coil) for measuring
sensible capacity: T = EAT - LAT Sensible Capacity (Btuh) = T x CFM x 1.08
Entering Air Temperature (EAT):______F Leaving Air Temperature (LAT): ______F
T = _________
o
F
Sensible Capacity (Btuh) = _________
Fan Speed Used: Low Med High
Compressor Amp: ________ Fan Amp: ________ Run Time For Test: ________
Loading...