Omega TX83, TX84 User guide

Page 1
TX83 and TX84
Two-Wire Current Loop
Powered Indicators
TM
Shop online at
omega.com
For latest product manuals:
www.omegamanual.info
NORWALK, CT
MANCHESTER, UK
Page 2
Servicing North America:
U.S.A. Headquarters:
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
Omega Engineering, Inc. Toll-Free: 1-800-826-6342 (USA & Canada only) Customer Service: 1-800-622-2378 (USA & Canada only) Engineering Service: 1-800-872-9436 (USA & Canada only) Tel: (203) 359-1660 e-mail: [email protected]
Fax: (203) 359-7700
For Other Locations Visit omega.com/worldwide
Page 3
TABLE OF CONTENTS
TX83 AND TX84 TWO-WIRE CURRENT
LOOP INDICATORS
SECTION PAGE
SECTION 1 INTRODUCTION. . . . . . . . . . . . . . . . . . . 1
1.1 General Description . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SECTION 2 INSTALLATION 4
2.1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Signal Input Connections . . . . . . . . . . . . . . . . . . 11
2.3.1 TX83 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.2 TX84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4 Power Supply Requirements . . . . . . . . . . . . . . . 13
i
Page 4
TABLE OF CONTENTS (Cont’d)
SECTION PAGE
SECTION 1 CONFIGURATION PROCEDURES. . . 15
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 Field Set-Up Calculation Procedure . . . . . . . . . . 17
3.4 Alternate Field Set-Up Calculation Procedure . . . 18
3.5 Field Set-Up Procedure implementation . . . . . . . 20
3.6 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.6.1 Equipment Required . . . . . . . . . . . . . . . . . . . . . . 26
3.6.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
SECTION 4 SPECIFICATIONS . . . . . . . . . . . . . . . 29
ii
Page 5
SECTION 1 INTRODUCTION
1.1 GENERAL DESCRIPTION
The OMEGA
®
TX-83 and TX-84 are weather resistant digital indicators which accept 1-5 mA, 4-20 mA, or 10-50 mA process input signals. The digital display (±1999 active counts) can present the process variable in either percentage or directly in engineering units. The indicators are powered directly from the current loop with a volt drop of less than 2.5 volts, and a power consumption of 2. 5 mW at 1 mA.
The TX-83 and TX-84 are watertight to 5 PSIG, and have an ambient temperature specification of from
-40 to +85°C making them ideal for locations exposed to “wash-downs” or to the weather. Applications include the measurement of temperature, pressure, flow, PH, or for that matter, the measurement of any process variable for which a current loop transmitter is available.
1
Page 6
For indoor applications OMEGA offers 1/8 DIN size panel-mount Process Loop Indicators, including the TX-82A. TX82A Indicators, and others, are described in the “L” and “M” Section of the OMEGA Temperature Measurement Handbook.
The TX-83 and TX-84 feature in-field programmability. Coarse input ranges (1-5, 4-20, or 10-mA) are selected by internal shunts. Three decimal points and a dummy right-hand zero may also be selected with pin-forest shunts. Zero and span are fine-tuned with precision 25-turn potentiometers. Positive slope response can be changed to negative slope response (eg., +6000 to -18000) by simply changing two other internal shunts.
The TX-83 and TX-84 are electrically isolated from the case, and are immune to most sources of electrical noise encountered in process-control environments. In the event of input overrange currents, the TX-83 and TX-84 can tolerate 250 mA in the forward direction and 1000 mA reverse.
2
Page 7
Low mass and multi-point circuit board support give excellent vibration and shock resistance. Sturdy, die­cast construction, polyurethane paint, and full fluorosilicone gasketing ensure a virtually waterproof case. Circuit boards are conformally coated for added humidity protection.
The TX-83 can be mounted in a control room on either American or European relay tracks with snaptrack adapters, mounted directly on a wall with a bulkhead adapter, or mounted in an explosion­proof enclosure for wiring compatibility with other equipment in hazardous environments. The TX-84 may be connected directly to a conduit with a “T” junction box. The TX-83 has barrier strip terminals and the TX-84 has a
1
⁄2" NPT conduit fitting with 12"
lead Wires.
3
Page 8
1.2 FEATURES
• 3
1
⁄2 Digit Display with Dummy Zero
• Powered Entirely by Signal Loop
• 1 to 5, 4 to 20, or 10 to 50 mA Ranges
• Scalable Zero and Offset for Engineering Units
• High Vibration and Shock Resistant with Cases of
Die-Cast Metal that are Waterproof to 35 kPa (5 psi)
SECTION 2 INSTALLATION
2.1 UNPACKING
Remove the Packing List and verify that all equipment has been received. If there are any questions about the shipment, please call OMEGA Customer Service Department at:
1-800-622-2378 or 203-359-1660.
We can also be reached at:
www.omega.com email: [email protected]
4
Page 9
Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take particular note of any evidence of rough handling in transit. Immediately report any damage to the shipping agent.
NOTE
The carrier will not honor any claims unless all shipping material is saved for their examination. After examining and removing contents, save packing material and carton in the event reshipment is necessary.
2.2 MOUNTING
The TX-83 and TX-84 are packaged in a small, rugged, die-cast, zinc-alloy case designed to fit 3" I.D. or larger housings, and requiring less than 2" of height. (Refer to Figure 2-1.)
5
Page 10
6
Figure 2-1. Outline Dimensions
Page 11
The TX-83 provides for surface, track, or explosion­proof housing mounting, and is connected with a three-terminal, #6 screw barrier strip. Tapped holes on the back of the TX-83 case provide for custom mounting to a flat surface; integral flanges on the back of the case provide for standard 8TK2 relay track mounting. For flat surface mounting, use #6 hardware For 8TK2 relay track mounting, simply push onto track.
The TX-83 also comes standard with an additional adapter plate for surface mount with two #8 front­entry screws through keyhole slots, or for push­mount Into TR2/2TK relay track.
The TX84 is equipped with a
1
⁄2" NPT conduit fitting. The fitting has two, 0.3 meter long, #18 stranded insulated wires passing through a neoprene moisture plug, for hook-up to junction boxes with standard wire nuts. The TX84-2 is the same as the TX84 with a
1
⁄2" male EMT conduit fitting.
Refer to Figures 2-3a and 2-3b for basic mounting configurations.
7
Page 12
8
Figure 2-2. Surface and TR2/2TK Relay Track Mounting, Model TX-83
Page 13
9
Figure 2-3a. Rear View: Standard Integral Mounting Plate (TX-83)
Page 14
10
Figure 2-3b. Basic Mounting Configurations
Page 15
2.3 SIGNAL INPUT CONNECTIONS
WARNING
Input currents in excess of protective limits can damage your TX-83/84 Current Loop Indicator.
2.3.1 TX-83
Figure 2-4 below shows a typical TX-83 installation and wiring when used with a two wire transmitter and power supply. Power supply requirements are covered in Section 2-4.
11
Page 16
12
Figure 2-4. TX-83 and Two-Wire Transmitter Wire
Page 17
2.3.2 TXB4
The TX84 comes equipped with a male
1
⁄2" NPT conduit fitting. The conduit fitting is plugged with a rubber stopper. Two 0.3 meter (12") long, 18 gage stranded Insulated wires are passed through the stopper. The black wire is the positive (+) signal input and the white wire is the negative (-) signal input. The unit can be hooked up using standard wire nuts. The TX84-2 is the some as the TX84 with a
1
⁄2" male EMT conduit fitting.
2.4 POWER SUPPLY REQUIREMENTS
Please refer to Figure 2-4. Current loop powered transmitters and indicators normally operate well with both regulated and unregulated power supplies. The TX83 and TX84 will work well with both.
13
Page 18
The power supply required to power a current loop circuit is principally dictated by the power demand of the transmitter rather than the indicator. For our example, the typical OMEGA thermocouple transmitter voltage supply specification may read “12-60 Vdc”, with an implied 20 plus mA current draw per transmitter. To determine total power supply voltage needs, add to the 12 Vdc voltage (for the transmitter) the maximum voltage drop across the Digital indicator, in this case, 2.5 volts for the TX-83 or TX-84. This would give a power demand of
14.5 volts and 20 milliamps. (if you were working with a 50 milliamp loop, the 20 milliamps would become 50 milliamps).
For the case cited, a safe selection would be an 18 (plus) volt power supply capable of delivering 20 or more milliamps for each transmitter to be powered. The economical OMEGA PSU-24, 24 volt 100 mA unregulated power supply would be an excellent selection for powering up to 4 of the above.
14
Page 19
SECTION 3 CONFIGURATION PROCEDURES
3.1 GENERAL
The TX-83 and TX-84 are shipped from the factory with the standard configuration of 4 to 20 mA (displays 00.0 to 100.0). A custom configuration for other values of span and zero and/or changes in in the span slope, decimal point location, or dummy right-hand zero, may be made in the field by relocating internal shunt blocks, and adjusting the zero and span potentiometers (refer to paragraph
3.5). The following Field Set-Up Procedures (paragraphs 3.3 and 3.4) can be used to determine the necessary configuration.
3.2 GLOSSARY
The following terms appear throughout the Configuration Procedures:
15
Page 20
TERM DESCRIPTION
DP1 Decimal Point 1.999 DP2 Decimal Point 19.99 DP3 Decimal Point 199.9 DRHZ Dummy Right-Hand Zero
G Gain Expressed in Counts per mA
I1 Lowest Input Current in mA I2 Highest Input Current in mA
N1 Reading in Displayed Counts at Input
Current I1
N2 Readling In Displayed Counts at Input
Current I2
FIN Required Flange Number for Zero Range
Selection
RSS Reverse Span Slope
ZR1 Zero Range (- 2510 to -1420) ZR2 Zero Range (-1580 to -420) ZR3 Zero Range (-470 to + 850) ZR4 Zero Range (+ 760 to +2000)
16
Page 21
3.3 FIELD SET-UP CALCULATION PROCEDURE
1. Base all calculations on one of three ranges:
1 to 5 mA, 4 to 20 mA, or 10 to 50 mA.
2. Determine the lowest input current, I1, specified
by user. I1 = ______________ mA
3. Determine the highest input current, I2, specified
by user. I2 = ______________ mA
4. Determine the reading, N1, at input current 11,
specified by user. N1 = _____________ counts
5. Determine the reading, N2, at input current I2,
specified by user. N2 = _____________ counts
6. Calculate the gain (G1):
(N2 - N1)
G = ------------- = ____________ counts per mA
(I1 - I2)
7. Calculate the required range number:
RN = N1 - (I1 x G)
17
Page 22
NOTE
If G is greater than 500, it is out of the operating range for a standard unit.
8. Select the zero range (ZR) that includes the
required range number (RN) from the following ranges: ZR1 = -2610 to -1420 ZR2 = -1580 to -420 ZR3 = -470 to +850 ZR4 = +760 to +2000
9. Proceed to paragraph 3.5 Field Set-Up Procedure
Implementation.
3.4 ALTERNATE FIELD SET-UP CALCULATION PROCEDURE
1. (Line 1) Low Signal Input (mA) = _______________.
2. (Line 2) High Signal Input (mA) = ______________.
3. (Line 3) Low Signal Input Reading (Counts) = ____________________.
18
Page 23
4. (Line 4) High Signal Input Reading (Counts) =
____________________.
5. (Line 5) Line 2 - Line I = ____________________.
6. (Line 6) Line 4 - Line 3 = ____________________.
7. (Line 7) Line 6 divided by Line 5 = _____________.
8. (Line 8) Line 7 x Line 1 = ____________________.
9. (Line 9) Line 3 - Line 8 = ____________________.
10.Select a zero range from one of the following,
where the number on Line 9 falls between the high and low numbers of that ZR range: ZR1 = -2510 to -1420 ZR2 = -1580 to -420 ZR3 = -470 to +850 ZR4 = +760 to +2000
11.Proceed to 3.5 Field Set-Up Procedure
Implementation.
19
Page 24
3.5 HELD SET-UP PROCEDURE IMPLEMENTATION
The TX-83 and TX-84 factory calibrated configuration displays 00.0 to 100.0 for an input of 4 to 20 mA. Internal shunt blocks are factory-installed in positions J, G, a, and L. A custom configuration for other values of span and zero and/or changes in the span slope, decimal point location, or dummy right­hand zero is accomplished by relocating internal shunt blocks as shown in Table 3-1 Configuration Chart. After the internal shunt blocks are changed, the Span and Zero potentiometers must be readjusted as described in paragraph 3.6.2 Calibration Procedure.
Six shunt blocks are provided with the TX-83 and TX-84 to accommodate in-field configuration changes. Unused or spare shunt blocks should be inserted in a vertical position on unused upper pins closest to the display board.
To access the shunt blocks, remove the four Phillips­head screws from the top of the TX-83 and TX-84 case, and lift the main unit from the case.
20
Page 25
Refer to Figures 3-1a and 3-1b for shunt block location and designations.
TABLE 3-1
CONFIGURATION CHART
CONFIGURATION SHUNT BLOCK
LOCATIONS REQUIRING SHUNT BLOCKS
1 to 5 mA None 4 to 20 mA J 10 to 50 mA A Normal Span Slope G and a Reverse Span Slope (RSS) F and Z Zero Range
-2510 to -1420 (ZR1) I
Zero Range
-1580 to -420 (ZR2) T
21
Page 26
TABLE 3-1 (Cont’d)
Zero Range
-470 to +850 (ZR3) None
CONFIGURATION SHUNT BLOCK
LOCATIONS REQUIRING SHUNT BLOCKS
Zero Range
+ 760 to +2000 (ZR4) c Dummy Right-Hand Zero (DRHZ) D Decimal Point 1.999 (DP1) W Decimal Point 19.99 (DP2) L Decimal Point 199.9 (DP3) V
22
Page 27
23
Figure 3-1a. Side View of TX-83/84 with Shunt Blocks Installed for
Standard Configuration (4 mA = 00.0 and 20 mA = 100.0). For Other
Application-Specific Configurations, Installed Shunt Blocks can
have Other Locations
Page 28
24
Figure 3-1b. Shunt Block Diagram
Page 29
To proceed with the Field Set-Up Procedure Implementation:
1. If the current range chosen in either paragraph 3.3
step 1, or paragraph 3.4 step 1 equals either 4 to 20 mA or 10 to 50 mA, install a shunt block as shown in Table 3-1. Pin forest designations are illustrated in Figure 3-1b.
2. If N1 (paragraph 3.3 step 4 or paragraph 3.4 step 3) is
more positive than N2 (paragraph 3.3 step 5 or paragraph 3.4 step 4), reverse the span slope (RSS) by installing two shunt blocks as shown in Table 3-1.
3. Select the zero range required (ZR1, ZR2, ZR3, ZR4),
and install a shunt block as shown in Table 3-1.
4. If a dummy right-hand zero (DRHZ) is required,
install a shunt block as shown in Table 3-1.
5 If a decimal point is required (DP1, DP2, DP3),
install a shunt block as shown in Table 3-1.
25
Page 30
3.6 CALIBRATION
3.61 Equipment Required
Precision mA power source or, 10 V power supply, 4
1
⁄2 digit DMM with mA range and 10 kilohm rheostat.
3.6.2 Calibration Procedure
1. Remove the four Phillips-head screws from the top
of the TX-83/84 case and lift main unit from case
2. Select the desired shunt block configuration and
install the push-on shunt blocks in locations indicated in Table 3-1. (Refer to paragraph 3.5.)
NOTE
Store unused shunt blocks in a vertical position, on unused upper pins closest to the Display Board.
26
Page 31
3. Pull off two sealing plugs that cover the Span (S)
and Zero (Z) potentiometer screw heads on the front of the TX-83/84.
4. Set up the TX-83/84 as shown in Figure 3-2.
5. Calibrate the unit as follows:
A. Alternately apply input currents I1 and I2, and
adjust Span pot (S) until span reading equals N2
- N1 counts.
B. Apply input current I1, and adjust the Zero pot
(Z) until a reading equal to N1 is displayed.
6. Remove the TX-83/84 from the calibration set-up.
7. Replace the two sealing plugs over the Span and
Zero potentiometer screw heads.
8. Apply new labels onto the bottom end side of the
TX-83/84, stating the new values of I1, I2, N1, and N2.
9. Re-install the TX-83/84 main unit into its case.
27
Page 32
28
Figure 3-2. Calibration Set-Up
Page 33
SECTION 4 SPECIFICATIONS
INPUT
CURRENT: 1-5 mA, 4-20 mA. or 10-50
mA, field selectable by internal shunt
VOLTAGE DROP: 2.5 V max forward; up to 50
MA
PROTECTION: 250 mA forward; 10DO mA
reverse at 2.5 V
INPUT RESISTANCE: 50 ohms, 1-5 mA range;
12.5 ohms, 4-20 mA range; 5 ohms, 10-50 mA range
29
Page 34
ZERO RANGE: -2510 to +2000 counts; field-
selectable by internal shunts in four overlapping coarse ranges, with a 25-turn potentiometer for continuous adjustment within the following selected ranges: -2510 to
-1420; -1580 to -420; -470 to +850; and +760 to +2000
SPAN RANGE: 0 to 2000 counts,
continuously adjustable with 25-turn potentiometer
NORMAL MODE 46 dB min. a 50/60 Hz REJECTION:
COMMON MODE 120 dB typical, DC to 60 Hz REJECTION:
COMMON MODE 700 V peak from DC to 60 Hz VOLTAGE: (meter to case)
30
Page 35
RFI SUSCEPTIBILITY: Less than ± 0.5% of span at
a distance of one meter from a 2-watt, hand-held transceiver (approximately equivalent to 10 V/m field strength) at frequencies of 27 MHz or 440 MHz
NOTE
Proper lead dress and shielding required.
ACCURACY AT 25°C: Max error: ±0.l% of span ±1
count; Zero Tempco: ±0.1 count/°C typ., ±0.2 count/°C max.; Span Tempco: ±0.005% of span/°C typ., ±0.015% if span/°C max.
DISPLAY TYPE: 7 segment LCD, 8.9 mm
(0.35") high; jumper selectable decimal point
31
Page 36
OVERRANGE: Three least-significant active
digits blank
ANALOG-TO-DIGITAL CONVERSION
TECHNIQUE: Dual-slope, average-value
with autozero, correction
POLARITY: Determined automatically at
the end of signal integration period
SIGNAL 100 ms typ. INTEGRATION PERIOD:
READING RATE: 2.5/sec
ENVIRONMENTAL
TEMPERATURE: -40 to +85°C
HUMIDITY: To 95% at 40°C
32
Page 37
VIBRATION: 1.52 mm (.06") double
amplitude, 10-W Hz cycled
SHOCK: 55 g, half-sine, 9-13 msec
duration
WATER Watertight to a proof RESISTANCE: pressure of 35 kPa (5 psi)
MECHANICAL
WEIGHT: 400 g (14 oz)
DIAMETER: 74 mm (2.9")
HEIGHT (INCL. 48 mm (1.9") BARRIER):
ELECTRICAL TX-83: three-position CONNECTIONS: terminal barrier strip with
#6 screw wire clamps TX-84:
1
⁄2" NPT male conduit fitting with two 0.3 meter long (12") #18 stranded wires
33
Page 38
34
Upper P. C. Board Component Layout
Page 39
35
Lower P. C. Board Component Layout
Page 40
36
Block diagrams are on the following pages for
TX83 and TX 84 with FM and CSA Approvals for
use in hazardous area with the appropriate
approved intrinsic safety barrier.
Page 41
Block Diagram of TX83 - FM Approval
37
Page 42
NOTES
1. APPARATUS WHICH IS UNSPECIFIED EXCEPT THAT IT MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN EXCESS OF 250V RMS OR 250VDC.
2. THE FOLLOWING OUTPUT PARAMETERS APPLY;
Vmax=12.5V, Imax=250mA, Ci=8.6µF, Li=0mH
3. THE INTERCONNECTING CABLE MAY BE A TWIN PAIR, OR A PAIR CONTAINED IN A TYPE A OR TYPE B MULTICORE CABLE (AS DEFINED IN EN50 039 CLAUSE 5.3) PROVIDED THAT THE PEAK VOLTAGE OF ANY CIRCUIT CONTAINED WITHIN THE MULTICORE DOES NOT EXCEED 60 VOLTS.
4. THE CAPACITANCE OR INDUCTANCE OR INDUCTANCE TO
RESISTANCE (4R) RATIO OF THE INTERCONNECTING CABLE MUST NOT EXCEED THE VALUES SPECIFIED FOR THE BARRIER IN USE.
5. THE ELECTRICAL CIRCUIT IN THE HAZARDOUS AREA MUST BE CAPABLE OF WITHSTANDING WITHOUT BREAKDOWN AN AC TEST VOLTAGE OF 500V RMS TO EARTH OR FRAME FOR ONE MINUTE.
38
Page 43
Block Diagram of TX83 - CSA Approval
39
Page 44
NOTES
1. APPARATUS WHICH IS UNSPECIFIED EXCEPT THAT IT MUST
NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN EXCESS OF 250V RMS OR 250VDC.
2. ANY SHUNT ZENER DIODE SAFETY BARRIER CERTIFIED BY
CSA RATED 28V AT 300Ω.
3. THE INTERCONNECTING CABLE MAY BE A TWIN PAIR, OR A
PAIR CONTAINED IN TYPE A OR TYPE B MULTICORE CABLE (AS DEFINED IN EN50 O39 CLAUSE 5.3) PROVIDED THAT THE PEAK VOLTAGE OF ANY CIRCUIT CONTAINED WITHIN THE MULTICORE DOES NOT EXCEED 60 VOLTS.
4. THE CAPACITANCE OR INDUCTANCE TO RESISTANCE (4R)
RATIO OF THE INTERCONNECTING CABLE MUST NOT EXCEED THE VALUES SPECIFIED FOR THE BARRIER IN USE.
5. THE ELECTRICAL CIRCUIT IN THE HAZARDOUS AREA MUST
BE CAPABLE OF WITHSTANDING WITHOUT BREAKDOWN AN AC TEST VOLTAGE OF 500V RMS TO EARTH OR FRAME FOR ONE MINUTE.
40
6
REVERSING CONNECTIONS WILL NOT DAMAGE UNIT.
Page 45
Block Diagram of TX84 - FM Approval
41
Page 46
NOTES
1. APPARATUS WHICH IS UNSPECIFIED EXCEPT THAT IT MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN EXCESS OF 250V RMS OR 250VDC.
2. THE FOLLOWING OUTPUT PARAMETERS APPLY; Vmax=12.5V, Imax=250mA, Ci=8.6µF, Li=0mH
3. THE INTERCONNECTING CABLE MAY BE A TWIN PAIR, OR A PAIR CONTAINED IN A TYPE A OR TYPE B MULTICORE CABLE (AS DEFINED IN EN50 039 CLAUSE 5.3) PROVIDED THAT THE PEAK VOLTAGE OF ANY CIRCUIT CONTAINED WITHIN THE MULTICORE DOES NOT EXCEED 60 VOLTS.
4. THE CAPACITANCE OR INDUCTANCE TO RESISTANCE (4R) RATIO OF THE INTERCONNECTING CABLE MUST NOT EXCEED THE VALUES SPECIFIED FOR THE BARRIER IN USE.
5. THE ELECTRICAL CIRCUIT IN THE HAZARDOUS AREA MUST BE CAPABLE OF WITHSTANDING WITHOUT BREAKDOWN AN AC TEST VOLTAGE OF 500V RMS TO EARTH OR FRAME FOR ONE MINUTE.
42
Page 47
Block Diagram of TX84 - CSA Approval
43
Page 48
NOTES
1. APPARATUS WHICH IS UNSPECIFIED EXCEPT THAT IT MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN EXCESS OF 250V RMS OR 250VDC.
2. ANY SHUNT ZENER DIODE SAFETY BARRIER CERTIFIED BY CSA RATED 28V AT 300Ω.
3. THE INTERCONNECTING CABLE MAY BE A TWIN PAIR, OR A PAIR CONTAINED IN A TYPE A OR TYPE B MULTICORE CABLE (AS DEFINED IN EN50 O39 CLAUSE 5.3) PROVIDED THAT THE PEAK VOLTAGE OF ANY CIRCUIT CONTAINED WITHIN THE MULTICORE DOES NOT EXCEED 60 VOLTS.
4. THE CAPACITANCE OR INDUCTANCE TO RESISTANCE (4R) RATIO OF THE INTERCONNECTING CABLE MUST NOT EXCEED THE VALUES SPECIFIED FOR THE BARRIER IN USE.
5. THE ELECTRICAL CIRCUIT IN THE HAZARDOUS AREA MUST BE CAPABLE OF WITHSTANDING WITHOUT BREAKDOWN AN AC TEST VOLTAGE OF 500V RMS TO EARTH OR FRAME FOR ONE MINUTE.
44
REVERSING CONNECTIONS WILL NOT DAMAGE UNIT
6
Page 49
NOTES:
45
Page 50
NOTES:
46
Page 51
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1.
Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2003 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
WARRANTY / DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 25 months from date of purchase. OMEGA’s Warranty adds an additional one (1) month grace period to the normal two (2) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
Page 52
TEMPERATURE

Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies

Wire: Thermocouple, RTD & Thermistor

Calibrators & Ice Point References

Recorders, Controllers & Process Monitors

Infrared Pyrometers
PRESSURE, STRAIN AND FORCE

Transducers & Strain Gages

Load Cells & Pressure Gages

Displacement Transducers

Instrumentation & Accessories
FLOW/LEVEL

Rotameters, Gas Mass Flowmeters & Flow Computers

Air Velocity Indicators

Turbine/Paddlewheel Systems

Totalizers & Batch Controllers
pH/CONDUCTIVITY

pH Electrodes, Testers & Accessories

Benchtop/Laboratory Meters

Controllers, Calibrators, Simulators & Pumps

Industrial pH & Conductivity Equipment
DATA ACQUISITION

Data Acquisition & Engineering Software

Communications-Based Acquisition Systems

Plug-in Cards for Apple, IBM & Compatibles

Datalogging Systems

Recorders, Printers & Plotters
HEATERS

Heating Cable

Cartridge & Strip Heaters

Immersion & Band Heaters

Flexible Heaters

Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL

Metering & Control Instrumentation

Refractometers

Pumps & Tubing

Air, Soil & Water Monitors

Industrial Water & Wastewater Treatment

pH, Conductivity & Dissolved Oxygen Instruments
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at www.omega.com
M0586/0918
Loading...