Omega SMLA, SMLA-1, SMLA-2 User guide

Page 1
Specications
Inputs:
Voltage Input: Range: 10mV to 200V Impedance: >100Kohms Overvoltage: 400V, max Current Input: Range: 1mA to 100mA Impedance: 20ohms, typical Overcurrent: 200mA, max Overvoltage: 60VDC Common Mode (Input to Ground): 1000VDC, max LED Indications: Input Range (Green)
  >100%input:8Hzash   <0%input:4Hzash
Setpoint (Red) Tripped: Solid red Safe: Off Limit Differential (Deadband): >50mV/5mA: 0.25% to 50% of span <50mV/5mA: 1% to 50% of span
Response Time:
Dynamic Deadband: Relay status will change when proper
setpoint/process condition exists uninterrupted for 100msec.
 NormalMode(analogltering):
<250msec, (10-90%)
OMEGA ENGINEERING, INC., warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase.
omega.com info@omega.
Servicing North America:
U.S.A.:
Omega Engineering, Inc., One Omega Drive, P.O. Box 4047, Stamford, CT 06907-0047 USA Toll-Free: 1-800-826-6342 (USA & Canada only) Customer Service: 1-800-622-2378 (USA & Canada only) Engineering Service: 1-800-872-9436 (USA & Canada only) Tel: (203) 359-1660 Fax: (203) 359-7700 e-mail: info @omega.com
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
com
OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product. If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA.
1. Purchase order number which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords customer s the latest technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © COPYRIGHT 2015 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, translated, or reduced to any electronic medium-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
Setpoint:
Effectivity: Setpoints are adjustable over 100% of
the selected input span. Repeatability (constant temp): >50mV/5mA: 0.1% of full scale <50mV/5mA: 0.2% of full scale
Stability:
Line Voltage: ±0.01%/%, max. Temperature: ±0.05% of full scale/°C, max.
Common Mode Rejection:
DC to 60Hz: 120dB
Isolation:
1000VDC between contacts, input & power
ESD Susceptibility:
Meets IEC 801-2, Level 2 (4KV) Humidity: Operating: 15 to 95% (@45°C) Soak: 90% for 24 hours (@65°C) Temperature Range: Operating: 0 to 60°C (32 to 140°F) Storage: -15 to 70°C (5 to 158°F)
Power:
Consumption: 2W typical, 5W max. Standard: Selectable 120/ 240VAC (±10%, 50-
60Hz)
Optional: 9 to 30VDC, Inverter-Isolated
Pin Connections
1 AC Power (Hot) 2 No Connection 3 AC Power (Neu) 4 Input (+) 5 Input (-) 6 (A) N.O. 7 (A) C 8 (A) N.C. 9 (B) N.O. 10 (B) C 11 (B) N.C.
WARRANTY/DISCLAIMER
RETURN REQUESTS/INQUIRIES
FOR NON-WARRANTY RETURNS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA.
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product and
3. Repair instructions and/or specific problems relative to the product.
Relay Contacts:
SMSL-1: DPDT (2 Form C) SMSL-2: 1 SPDT (1 Form C) per setpoint Current Rating (resistive) 120VAC: 5A; 240VAC: 2A; 28VDC: 5A Material: Silver-Cadmium Oxide Electrical Life: 105 operations at rated load Note: External relay contact protection is
required for use with inductive loads. See relay protection section (Fig 2 & 3).
Mechanical Life: 107 operations
Latch Reset Time:
5 seconds
Weight:
AP1080: 0.46lbs; AP1090: 0.62lbs Agency Approvals: UL recognized per standard UL508,
(File No. E99775)
Key:
N.O. = Normally Open C = Common N.C. = Normally Closed DC Power: Pin 1 = (+) Pin 3 = (-)
*
Contacts are in the “normal” state
when the relay is de-energized.
SMLA Series
DC Input, Field Configurable Limit Alarms
INSTRUCTION
SHEET
Shop online at omega.comSM e-mail: [email protected] For latest product manuals: www.omegamanual.info
 FieldCongurableInputRangesforDCVoltage
and Current
Exclusive “Dynamic Deadband” Prevents
False Trips
Description
Models SMLA-1 single setpoint and SMLA-2 dual setpoint limit
alarmsofferexible,wide-rangingDCinputcapability.Voltage
spans from 10mV to 200 volts and current spans from 1mA to
100mAcanbeeldcongured.Bipolarinputsarealsoaccepted. Both models offer congurable latching, failsafe and HI/LO
operation. The SMLA-1 and SMLA-2 also include 0.25%-50% adjustable deadbands and selectable 120/240VAC input power.
Diagnostic LED
Models SMLA-1 and SMLA-2 are equipped with a dual function diagnostic LED. The green center LED indicates line power and input signal status. Active line power is indicated by an illuminated LED. If the center LED is off, check line power and the wiring connection. If the input signal is above 100% full
scale,theLEDwillashatapproximately8Hz.Below0%,the ashrateisapproximately4Hz.
Output Selection
The single setpoint SMLA-1 and the dual setpoint SMLA-2 provide the following relay outputs:
SMLA-1 Single Trip (DPDT, 5A) SMLA-2 Single/Dual Trip (2 SPDT, 5A)
Setpoints are top accessed multi-turn potentiometers or option "P" provides top mounted ten-turn dials.
Operation
TheeldcongurableSMLA-1andSMLA-2limitalarmsetpoints canbeconguredforHI,LO,latchingorfailsafetripoperation.
Non-latching HI and LO setpoints have respective HI and LO deadbands. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above
theLOdeadband(seegure 1).  To resetalatchedsetpoint
the signal must be in the safe region and the line power turned off for at least 5 seconds. For proper deadband operation, a HI setpoint must always be set above a LO setpoint.
M5484/0715
Provides Relay Contact Closures
at a Preset DC Input Level
Setpoints Programmable HI or LO Selectable Failsafe/Latching Operation Selectable 120/240VAC Input Power
(9 to 30 VDC Available)
In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In the failsafe mode, the relays go to the tripped condition when the power fails.
Dynamic Deadband
The input must remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This effectively results in a “dynamic deadband” - based on time - in addition to the normal deadband.
Options
U Urethane coating of internal circuitry for protection from corrosive atmospheres.
P Top Mounted, Ten-Turn Dial(s) for setpoint adjustment.
C620 Factory calibration to input range, setpoints and output relays. Not available with option P.
Conguration
The factory presets models SMLA-1 and SMLA-2 as follows:
SMLA-1 SMLA-2 Input 0-20mA 0-20mA Output Single, DPDT Dual, SPDT Trip HI A: HI, B: LO Latching No No Failsafe Yes No Deadband 0.25% A/B: 0.25% Power 120VAC 120VAC
For other I/O ranges, remove the four base screws and case
toaccessthecongurationswitches.
Replace the cover before applying power.
Refer to Figure 5 for switch locations.
Page 2
b) Setpoint B (SMLA-2 only): Type (HI/LO); Units (mA, mV, V); Deadband (%)
c) Latching (ON/OFF)
d) Failsafe (ON/OFF)
Notethatifadeadbandentryisnotspecied,thedefaultentry
will be used.
Figure 1: Limit alarm operation and effect of deadband.
Input
1. Position input jumper “W2” for Current or Voltage inputs.
I
V
Current
I
V
Voltage
2. Set position 1 of the Mode Selector for Unipolar or Bipolar operation. Unipolar is the default.
ON
>
1
BP
2 3
4
Unipolar
5
ON
>
BP
2 345
1
Bipolar
6
6
Note: A bipolar span selection will double any span from Table 1 (e.g., 10V unipolar span = ±10V bipolar span)
3.Using Table1,congurepositions1 through4oftheInput
Range Selector for the desired maximum setpoint input. Round desired maximum input values to the next highest range (e.g., 0-120V = 200V range).
Output
ConguretheModeSelectorfortherequiredfunction.SeeFigure6.
Power
ConguretheACjumpersforeither120or240VACoperation.
See Figure 4.
Relay Protection and EMI Suppression
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 & 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly-rated MOV across the load in parallel with a
seriesRCsnubber. Use a 0.01 to 0.1mF pulse lm capacitor (foil polypropylene recommended) of sufcient voltage, and
a 47ohm, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
Table 1: SMLA-1 and SMLA-2
Input Ranges
Figure 2: DC Inductive Loads
Figure 5: SMLA-2 Factory Calibration 0-20mA, Dual HI/
Figure 3: AC Inductive Loads
Figure 6: Mode Selection Dual Trip/A: HI, B: LO, Non-
LO, Non-Latching, Non-Failsafe.
Mounting
All modules feature plug-in installation. Models SMLA-1 and SMLA-2 use an 11-pin base, either molded socket (SKT-SM-11P) or DIN rail socket (SKT-DR-11P).
Dimensions
Dimensions are in millimeters (inches)
Figure 4: 120/240 VAC Selection
ON = Closed
1
Unipolar
BipolarOnOff
"A" Hi Trip
"A" Low TripOnOff
"B" Hi Trip
"B" Low TripOnOff
3
2
*
45
6
*
Single Trip (A)
Dual Trip TripOnOff
Non-Failsafe
FailsafeOnOff
Latching
Non-LatchingOnOff
Latching, Non-Failsafe *SMLA-2 only.
Calibration
Note:Tomaximizethermalstability,nalcalibrationshouldbe
performed in the operating installation, allowing approximately 1-2 hours for warmup and thermal equilibrium of the system.
Setpoint: Set deadband at its minimum (factory default - 20 turns Counter Clockwise) before adjusting the setpoint. With the
speciedtripvoltageorcurrentinputapplied,adjustsetpointuntil
the relay trips. For HI trip calibration, start with the setpoint above the desired trip. For LO trip calibration, start below the desired trip.
Deadband: Set deadband to its minimum (factory default - fully CCW). Set setpoint to desired trip. Adjust voltage/current input until relay trips. Readjust deadband to 50% (20 turns CW). Set voltage/current input to desired deadband position. Slowly adjust deadband until relay untrips.
Note that Custom Calibration (option C620) is available from the factory (settings MUSTbewithinspecications):
a) Setpoint A: Type (HI/LO); Units (mA, mV, V); Deadband (%)
*Note:UseJumper(W2)tocongureeithervoltageorcurrentinput.
All unipolar input ranges are zero based.
Mark III
SKT-SM-11P (Track/Surface)
SKT-DR-11P (DIN Rail)
Loading...