Omega OMG-ULTRACOMM2-PCI RS-232 User Manual

iDRN-ACV
AC VOLTAGE INPUT
General Description:
The iDRN Series of DIN rail-mountable signal conditioners are available for Thermocouple, RTD, Strain, Process, AC Voltage, AC Current and Pulse/Totalizer input types. The factory calibrated signal conditioners are ideal for all process and power monitoring applications, they feature 3-way isolation, high accuracy input, programmable outputs, and are excellent front end interfaces for programmable logic controllers or data acquisition systems. For maximum user configurability the signal conditioners allow complete input­output scaling via a RS-232 connection to any PC or PLC.
Software Description:
The signal conditioner configuration program is a MS DOS/Windows program (this manual is for the Windows version). It is designed especially for the iDRN Series Signal Conditioner. This program will run on any PC with Windows application and will start automatically.
Free Serial Communication software and ActiveX Controls
are on the CD-ROM enclosed with this shipment.
To download the latest software release
(or request a free CD-ROM) please go to:
www
.omega.com/software
What You need:
•Your choice of the signal conditioner
•IBM PC or compatible
•Windows software 3.1 or higher, or Windows 95/98
•RJ12 connector with telephone cable
•Adapter (DB9 or DB25 to RJ12)
Setting up your System
COMPUTER CONNECTION (DB9 or DB25)
RJ12 CONNECTOR with CABLE
ADAPTOR (DB9/25 to RJ12) #DB9-RJ12, #DB25-RJ12
COMPUTER POWER CONNECTION
RS-232 to RS-485 CONVERTER HALF-DUPLEX #CAT-285
SIGNAL CONDITIONER MODULE
Operation: Note: When connecting a voltage signal, extra care should be
taken to prevent electrical shock. Always turn the signal power off before making connections to the signal conditioner.
ALWAYS ENSURE THAT THE MAXIMUM VOLTAGE INPUT SIGNAL DOES NOT EXCEED
400 VOLTS AC.
PLEASE OBSERVE THE INPUT SIGNAL
CONNECTION SPECIFIED IN THE SECTION BELOW. THIS DEVICE MUST ONLY BE INSTALLED BY A PROFESSIONAL ELECTRICIAN.
Power Input and Analog Output Setup:
To connect the signal input proceed as follows:
1. Connect a DC power supply with an output voltage between 10 to 32 Volt DC to the signal conditioner (J1). Note: If power supply used has current limiting, it may not be able to power the signal conditioners if the available output voltage is around 10 Volt, since the peak current may reach 1 to 5 amp for a few milliseconds.
2. Determine the maximum voltage to be measured.
ANALOG OUTPUT LINEARITY:
0.1% of FS
ANALOG OUTPUT STEP RESPONSE TIME:
2 seconds to 99% of final value
INPUT POWER:
10 to 32 Volt DC
POWER CONSUMPTION:
2.4 watts (100 mA at 24 Vdc)
OPERATING AMBIENT:
-5 to +55 °C
STORAGE TEMPERATURE:
-40 to +85 °C
RELATIVE HUMIDITY:
90% at 40 °C non-condensing
DIMENSIONS:
Introduction:
The AC voltage input signal conditioners are high performance instruments that measure AC voltages in 4 ranges which are as follows: 400 mV, 4 Volt, 40 Volt and 400 Volt. Key features of the signal conditioners are built in active attenuator, scalable analog output and a simple RS232 interface for scaling analog output and range selection. The RS232 interface may also be used for digital transmission of input signal to a computer or a PLC. Additional features include three way isolation between DC power, signal input and analog output/RS232.
INPUT RANGES:
400 mV, 4V, 40 Volt, 400 Volt
FREQUENCY RANGE:
30 Hz to 1 KHz
INPUT IMPEDANCE:
2.1 Meg for all ranges.
ISOLATION:
Dielectric strength per 1 minute test based on EN 61010 for 50 Vdc or Vrms working voltage. Three way Isolation:
• Power to Signal Input: 1800V Peak
• Power to Analog Output/Communication: 1800V Peak
• Signal Input to Analog Output/Communication: 1400V
COMMON MODE REJECTION:
100 dB
INPUT OVER-VOLTAGE PROTECTION:
10% Above full scale continuously. 100% Above full scale for 10 seconds.
ANALOG TO DIGITAL TECHNIQUE:
Dual slope
READ RATE:
3 readings/second
ACCURACY AT 25 °C:
400 mV, 4V, 40V and 400V ranges 49 Hz to 500 Hz ±0.2% of FS 30 Hz to 1KHz ±0.2% of FS ±10 counts
TEMPERATURE STABILITY:
400 mV and 40 Volt range 150 ppm/°C typical
4V and 400 Volt range 100 ppm/°C typical
STEP RESPONSE FOR RS232 OUTPUT: 2 seconds to 99% of the final value (Filter time constant = 64)
RESPONSE TIME:
To verify the response time, check the carriage return <CR>, it will be sent at the end of the response. You can send another command after you receive the <CR>.
i.e. send: *X01
response: X01<DATA><CR>
WARM UP TO RATED ACCURACY:
30 minutes
ANALOG OUTPUT SIGNAL TYPE:
Voltage: 0-10 Volt, maximum current 10mA
Current: 0-20 mA or 4-20 mA, maximum compliance voltage 10 Volts (maximum loop resistance 500Ω)
START HERE
2
34
J4
J3
SIG HI
+
N/C N/C
SIG LO
J1
J2
15. If the program is not able to establish communication then an error message is displayed. This happens either when the wrong serial port is specified or when the cable is disconnected.
16. The procedure to disable Continuous Mode and change the iDRN to Command Mode is as follows:
Using HyperTerminal, or any serial communication program, type: Ctrl + S To change the device to Command Mode, type: ^AE To change the Bus Format Register, type: *W0814 To reset the device,type: *Z01 Cycle power to the unit.
Modbus Register Definition
Reg. # Read Function Write Function # of byte
1 Input Range Input Range 1 2 Input/Output Config. Input/Output Conf. 1 3 Decimal Point Decimal Point 1 4 Filter Time Constant Filter Time Constant 1 5 Reading/Output Scale Not supported 3 6 Reading/Output Offset Not supported 3 7 Comm. Parameters Comm. Parameters 1 8 Comm. Bus Format Comm. Bus Format 1
9 Comm. Data Format Comm. Data Format 1 A Comm. Device Addr. Comm. Device Addr. 1 B Comm. Recog. Char. Comm. Recog. Addr. 1 C Unit of measure Not supported 3 D Gate Time Gate Time 1 E Debounce Time Debounce Time 1
F Transmit Time Transmit Time 2
10 Main Value Hard Reset 3
11 Peak Value Reset Peak 1
12 Valley Value Reset Valley 1 13 Not Supported L.S. bytes Output Scale 2 14 Not Supported M.S. byte Output Scale 1 15 Not Supported M.S. bytes Output Offset 2 16 Not Supported L.S. byte Output Offset 1
Note:
1) Main, Peak, Valley value: 4 bytes will send from the unit a. Highest byte always 00h. b. 2nd Highest byte: (MSB is sign (1=negative, 0=positive),
next 3 bits are number of decimal points).
c. Low nibble of second byte, and lowest 2 bytes are the
value.
d. The decimal point register has to set to: 1, 2, 3, or 4.
2) Bus Format: Bit 5 1/0 = Modbus/Newport
3) Output Scale/Offset Write: Due to write single only, two write operation is needed to write scale/offset, and to make it effective it needs to follow with Hard Reset command.
4) To configure to Newport protocol, set bit 5 of Bus Format to low and follow with Hard Reset command.
3. Determine the appropriate input signal range, i.e. 400 mV, 4 Volt, 40 Volt or 400 Volt. Also ensure that the frequency of AC source is within the specified limits.
4. Ensure that if the selected range is different from the default then change the internal range by using the Setup Software and select the appropriate range.
5. Connect the signal input to screw terminal, and ensure that the screws are tight. Failure to do so may cause electrical shock should the wires become loose and come out of the screw terminal.
6. To verify that the set up is correct, you may connect a DVM to the analog output. Once connected, power the signal conditioner and apply a known voltage from an AC source to input. Measure and compare with expected values. To custom scale the analog output proceed to the next step.
7. To view/change the scaling that relates the analog output to signal input: connect the RS232 output of the signal conditioner to an available serial port of a computer. The cable and the DB9 or DB25 connectors are available as an option.
8. Turn on the computer, start Windows 3.0 or higher and run the Signal Conditioner Configuration Setup Program.
9. Start the configuration program, you need to indicate which serial port is to be used for serial communication by checking the appropriate check box on the opening menu. Note: It is not necessary to know the serial communication protocol. i.e. baud rate, parity, 7/8 data bit and stop bit; the program will determine this information automatically. However, it is good practice to mark the protocols used on the signal conditioner label if different from default.
10. Once the program starts it will automatically detect the signal conditioner configuration and will display a window of available options. To view the signal input click on the display on/off.
11. To change analog output scaling choose analog output scaling and enter the desired values.
12. Once the custom scaling is finished, ensure that Send Configuration is clicked, otherwise the changes will not take effect.
13. The input/output scaling may be fine tuned, while both
communication and analog output are active. In fact you may make a change to the analog output in the configuration program, and watch the DVM connected to analog output of the signal conditioner follow the new settings.
14. You may save or print a particular configuration by selecting the file menu. It’s always a good practice to both print and save the scaling of each signal conditioner.
56
iDRN-ACV
AC Voltage Signal Conditioner
M2533/0304
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895, 5,274,577/ Canada 2052599, 2052600/ Italy 1249456, 1250938/ France Brevet No. 91 12756/ Spain 2039150, 2048066/ UK Patent No. GB2 249 837, GB2 248 954/ Germany DE 41 34398 C2.
TRADEMARK NOTICE:
,
omega.com
®
are trademarks of OMEGA Engineering, Inc.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this device, as the guide contains important information relating to safety and EMC.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge. OMEGA'S WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use if its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUEST/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2004 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior written consent of OMEGA ENGINEERING, INC.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. P.O. number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. P.O. number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems relative to the product.
®
MADE
IN
USA
®
®
OMEGAnet® On-Line Service
www.omega.com
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
Canada: 976 Bergar Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA Customer Service: 1-800-622-2378 / 1-800-622-BEST Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
Mexico and TEL: (001)800-TC-OMEGA® FAX: (001) 203-359-7807 Latin American: En Espa
e-mail: espanol@omega.com
ñol: (001) 203-359-7803
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstelveen, The Netherlands TEL: +31 20 3472121 FAX: +31 20 6434643 Toll Free in Benelux: 0800 0993344 e-mail: sales@omegaeng.nl
Czech Republic: Frystatska 184, 733 01 Karviná TEL: +420 59 6311899 FAX: +420 59 6311114 e-mail: info@omegashop.cz
France: 11, rue Jacques Cartier, 78280 Guyancourt TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27 Toll Free in France: 0800 466 342
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany TEL: +49 7056 9398-0 FAX: +49 7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: info@omega.de
United Kingdom: One Omega Drive
ISO 9002 Certified River Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom TEL: +44 161 777 6611 FAX: +44 161 777 6622 Toll Free in England: 0800 488 488 e-mail: sales@omega.co.uk
e-mail: sales@omega.fr
Internet e-mail
info@omega.com
®
®
®
Loading...