The Omega Engineering OMG-COMM8-A provides the PC with eight
RS-232 asynchronous ports. The OMG-COMM8-A allows for connection
to any device utilizing the RS-232 electrical interface, such as modems,
data-entry terminals, and plotters.
What’s Included
The OMG-COMM8-A is shipped with the following items. If any of these
items are missing or damaged, contact the supplier.
• OMG-COMM8-A Serial I/O Adapter
• “Octopus” Cable providing 8 DB-25 connectors.
• 3.5″ Serial Utility Diskette
• User Manual
Factory Default Settings
The OMG-COMM8-A factory default settings are as follows:
Port #Base AddressIRQ
Port 12802/9
Port 22883
Port 32904
Port 42985
Port 52A02/9
Port 62A83
Port 72B04
Port 82B85
Omega Engineering OMG-COMM8-APage 1
Introduction
To install the OMG-COMM8-A using factory default settings, refer to the
Installation section of this manual.
For your reference, record installed OMG-COMM8-A settings below:
Port #Base AddressIRQ
Port 1
Port 2
Port 3
Port 4
Port 5
Port 6
Port 7
Port 8
The following table shows which port is connected to which connector and
the corresponding address in the Factory Default setting.
The OMG-COMM8-A contains several jumper straps that must be set for
proper operation.
Address Selection
The OMG-COMM8-A occupies 64 I/O locations and can be addressed
two different ways. If header E1 is set to the “Switch” position the OMG-COMM8-A occupies 64 consecutive I/O locations and the DIP-switch is
used to set the base address for these locations. The starting address for
these 64 I/O locations must be on a 64-byte boundary i.e.: Hex 200, 240,
280, or 2C0. Be careful when selecting the base address as some selections
conflict with existing PC ports. The following table shows several
examples that usually do not cause a conflict.
Note: Some of these selections may not be valid for your system, due to
port contention. If in doubt, call Sealevel Technical Support
(864) 843-4343 for assistance. These addressing restrictions are
simplified when using the “PAL” option.
Note: If Xenix is the operating system and COM1 is not installed, use base
address 500 Hex and IRQ 4 (Xenix COM1:). If COM1: is installed,
then select 580 Hex as a base address and IRQ 3 (Xenix COM2:).
Omega Engineering OMG-COMM8-APage 3
Card Setup
The following illustration shows the correlation between the DIP-switch
setting and the address bits used to determine the base address. In the
example below, address 280 (Factory Default) is selected as a base.
A12A6
ON
OFF
1 2 3 4 5 6 7
Figure 2 - DIP-switch Illustration
Note: Setting the switch “On” or “Closed” corresponds to a “0” in the
address, while leaving it “Off” or “Open” corresponds to a “1”.
Refer to Appendix A for common address contentions.
“PAL” Addressing
If header E11 is set to the “PAL” position, the board can be addressed at
many customized locations. Using the “PAL” option will allow you to
obtain COM1: - COM4: addresses, XENIX COM: addresses, or any other
standard or nonstandard address configuration. Using the “PAL” feature is
a very cost-effective means of solving complex addressing problems. For
more information on implementing the “PAL” option, please contact
Omega Engineering Technical Support.
Omega Engineering OMG-COMM8-APage 4
Card Setup
IRQ Selection
The OMG-COMM8-A has an interrupt selection jumper that corresponds
to each port that may have to be set prior to use. The software you are
using with the board will determine which interrupts, if any are to be used.
The DOS serial port interface software does not use interrupts, while
interrupt buffer programs do. DOS does not require the interrupt to be set,
while most Multi - User Operating Systems will. Consult the particular
manual for the software that you are using to determine the proper setting.
To set the interrupt for a particular port, first select the header for the port
desired. Headers E1-E8 correspond to Ports 1-8. Next select an IRQ by
placing one of the jumpers on the header location that corresponds to the
IRQ number that you wish to use. Below is an example of a selected IRQ.
234567 10 11 12 15
Figure 3 - Headers E1 to E8 (IRQ15 selected)
Omega Engineering OMG-COMM8-APage 5
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.