Omega MLP2 User guide

Page 1
MLP2 SERIES
Installation & Operation Instructions
Website: workaci.com
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with the power applied. Do not allow live wires to touch the circuit board.
• An isolation transformer is recommended when powering the device with 24 VAC.
• Do not run the wiring in any conduit with line voltage.
• Failure to wire devices with the correct polarity when using a shared transformer may result in damage to any device powered by the shared transformer.
• Do not remove the cover. All user features are accessible from the outside of the unit.
88.9m88.9mmm
3.500i3.500inn
57.1m57.1mmm
2.250i2.250inn
106.3m106.3mmm
4.185i4.185inn
MEDIA
The MLP2 can be used to monitor the dierential pressure in any application that uses dry air or inert gas.
34.4m34.4mmm
1.354i1.354inn
MOUNTING INSTRUCTIONS
Using the two #8 x 3/4” self drilling mounting screws supplied by ACI, mount the unit vertically with the brass fittings pointing towards the ground. Attach the unit to the mounting surface using the two mounting openings located on the top and bottom flanges. This ensures that any condensation that may form in the tubing does not have an effect on the pressure sensor. If mounting the unit horizontally, a slight zero shift may occur and care must be taken to prevent moisture from building up in the sensor. For best results, all tubing lengths should be limited to a maximum length of 75 feet (23 meters).
DIN RAIL MOUNTING
The MLP2 oers two options for DIN Rail mounting: rear and side mount. The rear DIN rail mount is integrated into the enclosure. The side mount DIN adapter is included with the package. The side mount oers a much thinner prole for higher density panels. - See Figure 2 or Figure 3 (pg. 2)
To install the side mount DIN adapter, the front cover must be removed rst. The cover can be pried out with a at blade screw driver on the upper edge, or on the two side slots. The clip can then be slid into position. Once the clip is inserted, snap the front cover into place.
Page 1
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 12.0
I0000791
Page 2
WIRING INSTRUCTIONS
Shielded cable with 14 to 24AWG conductors is recommended. Use the Wiring Connections table below to determine the proper wiring for your application. Insert the wire into the depluggable terminal block sockets and tighten the screws. In some circumstances, it may be easier to remove the terminal blocks while connecting the wires. Refer to TABLE 1 (below).
All wiring must comply with local and National Electric Codes.
Note: When using a shielded cable, be sure to connect only (1) end of the shield to ground at the controller. Connecting both ends of the shield to ground may cause a ground loop. When removing the shield from the sensor end, make sure to properly trim the shield to prevent any chance of shorting.
OUTPUT SIGNAL SUPPLY VOLTAGE WIRE CONNECTIONS
0-5/10VDC AC/DC VIN GND OUT
4-20mA AC VIN GND OUT
4-20mA DC VIN ----- OUT
Page 2
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 12.0
I0000791
Page 3
PRESSURE CONNECTIONS
The recommended connection tubing is ¼” O.D. push-on tubing (1/8” – 3/16” I.D.). ACI recommends to keep the tubing runs as short as possible so as to not aect the response time.
ZERO ADJUSTMENT
Small positive or negative pressure osets can be removed using the Zero push button. Make sure that there is no pressure at the HI and LO pressure ttings. Additionally, a small piece of tubing can be connected between the HI and LO brass ttings to neutralize any external pressure eects. Press and hold the Zero button for 5 seconds. MLP2 will enter zero mode AFTER push button is released. The Zero
adjustment should only be performed with no pressure applied.
CALIBRATION
MLP2 utilizes a digital pot for Span calibration and is factory set. There is no Span potentiometer for adjustment. In the event you require Span calibration, the unit must be sent back to ACI.
The Oset can be adjusted using the Auto Zero function. Drift is a function of stress relaxation over time and this results in the oset shifting, and not the span. Periodically re-zeroing the device will eliminate the eect of drift.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 12.0
I0000791
Page 4
PRODUCT SPECIFICATIONS
4-20mA (250  Load): 16-36 VDC / 24VAC ± 10 %, 50/60 Hz
Supply Voltage:
Supply Current mA: [Power Consumption]
Output Signals:
Sensor Accuracy: ± 0.5 % FSO (Standard); ± 0.25 % FSO (Optional) Operating Temperature Range: 32 to 185 °F (0 to 85 °C) Compensated Temperature Range: 32 to 122 °F (0 to 50 °C) Humidity: 10 to 95 % RH, non-condensing Thermal Eects2: ± 0.056 % FSO/ºF (± 0.10 % FSO/ºC) Warm Up Time: 15 Minutes Response Time (T95): 4 Seconds Output Update Rate: 0.5 Second intervals Zero Function: Pushbutton Zero Function (Recommended after 15 minutes warm up)
Proof Pressure [Burst Pressure]:
Media Types: Dry air or inert non-conductive gases Din Rail Mounting: 35 mm (U.S. Patent No. 7,416,421)
Wiring Connections [Wire Size]:
Terminal Block Torque Rating: 4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm) Tubing Size Accepted: 0.250”(6.35mm) O.D. x 0.170”(4.318mm) I.D. | Push-On Flexible Poly Tubing Enclosure Material [Flame Rating]: Polycarbonate [UL 94 V-0]
WARRANTY
The ACI MLP2 sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
4-20mA (500  Load): 21-36 VDC / 24VAC ± 10 %, 50/60 Hz 0-5 VDC: 12-36 VDC / 24VAC ± 10 %, 50/60 Hz 0-10 VDC: 16-36 VDC / 24VAC ± 10 %, 50/60 Hz
4-20 mA Output: 23 mA minimum [0.83 VA] VDC Output Signals: 5 mA maximum [0.18 VA]
4-20 mA: 2-Wire Loop Powered (Output limited to 20.5 mA Max.) 4-20 mA: 3-Wire, VAC Powered (Output limited to 20.5 mA Max.) 0-5 VDC, 1-6 VDC, or 0-10 VDC: 3-Wire, VAC or VDC Powered
(Output limited to 5.25, 6.25, & 10.25 VDC)
Ranges < 1” wc (248.84 Pa): Proof: 270” wc (67.2 kPa) [Burst: 415” wc (103.3kPa)] Ranges > 1” wc (0.2488 kPa) to < 10” wc (2.488 kPa): Proof: 350” wc (87.12 kPa) [Burst: 550” wc (136.9kPa)] Ranges > 10” wc (2.488 kPa) to < 40” wc (9953.6 kPa): Proof: 562” wc (140 kPa) [Burst: 1004.7” wc (250 kPa)]
3 Position de-pluggable screw terminal block [14 AWG (1.628 mm²) to 24 AWG (0.5105 mm²)]
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with household waste. Do not burn.
Page 4
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562 Phone: 1-888-967-5224 | Website: workaci.com
Version: 12.0
I0000791
Loading...