Omega LVRD10 User guide

Page 1
Page 2
2
Page 3
INTRODUCTION SectionOne
The senor utilizes TDR (Time Domain Reflectometry) technology.  It is best described as low‐energy, high‐ frequencyelectromagneticimpulses,generatedbythesensor’scircuitrythatispropagatedalongtheprobeas itis immergedinthe liquidtobe measured.Impulses hitthesurface ofthemedia andpartof theimpulse energy is reflected back up the probe to the circuitry.  Level Measurementiscalculatedfromthetime differencebetweentheimpulsessent and theimpulses reflected.Thesensoranalyzestheleveloutputasa continuousmeasurement readingfromits analogoutput. TDR‐Sensorsarealso knownasGuided Radarsor GuidedWaveRadars(GWR).
NewFeatures
PrecisecontinuouslevelmeasurementinonedeviceCompletegalvanic insulationof deviceelectronicsfrom itsinputs/outputs and thetankpotential (no
problemswithelectrochemicalcorrosionprotection)
Highly robust measurement due to 3‐wire design, innovative signal analysis and disturbance signal
suppression
TableofContents
Introduction: .........................................................................................................................................................3
Specifications:..........................................................................................................................................4‐5
Dimensions:.................................................................................................................................................6
AboutthisManual:.....................................................................................................................................7
GettingStarted(SetupOverview):..........................................................................................................................8
PartNumbers:.............................................................................................................................................9
Probelength:.............................................................................................................................................10
MeasurementRange:...............................................................................................................................13
HeightofLiquidvs.VolumeofLiquid:......................................................................................................15
Installation(MountingConsiderations):...............................................................................................................16
Installationtips:...................................................................................................................................18‐21
Wiring(AnalogOutput):........................................................................................................................................22
CommonWiringtoDisplays,Controllers&PLCs:.....................................................................................24
Configuration:.......................................................................................................................................................25
USBFobinterface:....................................................................................................................................25
Sensorconfiguration:................................................................................................................................26
Tankshapeselection:................................................................................................................................27
DimensionalEntry:....................................................................................................................................27
Tanklevelconfiguration:..........................................................................................................................28
Writetounit:.............................................................................................................................................28
EmptySignalScan:................................................................................................................................................29
Appendix:..............................................................................................................................................................31
EchoCurve:...............................................................................................................................................31
Sensorconfiguration:...........................................................................................................................32‐34
Tankshapeselection:...........................................................................................................................34‐35
DimensionalEntry:...............................................................................................................................35‐36
TankLevelConfirmation:..........................................................................................................................37
Writetounit:.............................................................................................................................................38
CuttingtheProbe:................................................................................................................................39‐41
Troubleshooting:......................................................................................................................................42
Warranty/Disclaimer:...........................................................................................................................................43

3
Page 4
INTRODUCTION SectionOne
Electrical
Analogoutput: 4to20mA,3‐wire Totalloadresistance: <250Ω Lowerrangevalue: 4.0mA(span0%) Upperrangevalue: 20.0mA(span100%) Responsetime: 5s Supplyvoltage: 10to30VDC(reverse‐polarityprotected) Currentconsumption:<50mAat24VDC Start‐uptime: <6s Cableterminals: terminalblockforwires16to26AWG(solidorstranded) 
Measurement
Referencecondition:(dielectricconstant[εr]=80,watersurface,tank01m,DN200metalflange) Accuracy: ±3mm Repeatability: <2mm Resolution: <2mm Probetype:  Rod: 4mm  Cable: 4mm,type7x19  Coaxial: 21.3mm(0.843”)½”pipe Probelength StandardLengths  Rod: LVRD11: 9.84’ (3.0m)  LVRD11‐3FT: 3.0’ (0.91m)  LVRD11‐6FT: 6.0’ (1.82m)  Coaxial: LVRD12: 9.84’ (3.0m)  LVRD12‐3FT: 3.0’ (0.91m)  LVRD12‐6FT: 6.0’ (1.82m)  Cable: LVRD13: 18.0’ (5.5m) CustomProbe [canbeorderedin5mm(0.2”)incrementsfromthereferencepoint]  Rod: 2’to9.8’ (0.61to3.0m)  Cable: 3.3’to18’(1.0to5.5m)  Coaxial: 2’to9.8’ (0.61to3.0m) Probeloading  Rod: Maximumlateralload: 6Nm…(0.2kgat3m)  Cable: Maximumtensileload: 5kN  Coaxial: Maximumlateralload: 100Nm…(1.67kgat6m) Topdeadband: 100mm(4”) Bottomdeadband: 50mm(2”) 
ApplicationSpecifications
IntendedInstallation:  Rod: Metallictankorbelowgradeconcretebasin  Cable: Metallictankorbelowgradeconcretebasin  Coaxial: Non‐metallic,plastic,fiberglassormetallictankorbelowgradeconcretebasin Dielectric[εr] >1.8 Conductivity: norestrictions Density: norestrictions
4
Page 5
INTRODUCTION SectionOne
ApplicationSpecifications(continued)
Processtemperature   Rod: F:‐40°to302° C:‐40°to150°  Cable: F:‐40°to302° C:‐40°to150°  Coaxial: F:‐40°to266° C:‐40°to130° Ambienttemperature  Operation: F:‐13°to176° C:‐25°to80°C  Storage: F:‐40°to185° C:‐40°to85°C Applicationpressure: ‐14.5to250psi ‐1barto17.2bar Rateoflevelchange: 1”/s 
MechanicalSpecifications
Wettedmaterials:  Rod: 1.4404/316LSS,PEEK  Cable: 1.4404/316SS,PEEK  Coaxial: 1.4404/316LSS,PEEK Housingmaterials
Housingbodyandcover: AluminumalloyENAC‐AlSi9Cu3(DINEN1706),epoxyspray
coating(~70μm)otheralloysandcoatingsonrequest. covero‐ring: siliconerubber(ElastosilR750/50) screws;coverlockingscrew; 1.4301/304externalearthterminal screw: tinplatedstainlesssteel1.4301/304
Housingrating: IP66,NEMA4 Cableentries: Singlecableentry½”NPT Cordgrip: ½”NPT,FerriteBeadincluded Cordgripmat’l: Nylon CordgripCable  MinimumSize: 0.170”(4.3mm)  MaximumSize: 0.450”(11.4mm)  Processmount: ¾”NPT
Compliance: CE:EN61326‐1:2013&EN55011ClassAGroup1  CRN  RoHS 
 
5
Page 6
INTRODUCTION SectionOne
Dimensions:
Rod Coaxial Cable 
  
6
Page 7
INTRODUCTION SectionOne
Aboutthis Manual:PLEASEREADTHEENTIREMANUALPRIORTOINSTALLINGORUSINGTHISPRODUCT.
This manualincludes informationon the LVRD10series Guided WaveRadarLevelTransmitterfromOmega Engineering®.  Please refer to the part number located on the switch label to verify the exact model configuration,whichyouhavepurchased.
User’s Responsibility for Safety:  Omega Engineering® manufactures a broad range of level sensing
technologies.Whileeachofthesesensorsisdesignedtooperatein awide varietyof applications,itis the user’sresponsibilitytoselectasensormodelthatisappropriatefortheapplication,installitproperly,perform tests of the installed system, and maintain all components.  The failure to do so could result in property damageorseriousinjury.
ProperInstallationandHandling:Onlyprofessionalstaffshouldinstalland/orrepairthisproduct.Never
overtightenthesensorwithinthefitting.Alwayscheckforleakspriortosystemstart‐up.
WiringandElectrical:Asupplyvoltageof10to30VDCisrequiredtopowertheLVRD10Series.Electrical
wiring of the transmitter should be performed in accordance with all applicable national, state, and local codes.
MaterialCompatibility:Theenclosureismadeofmetal.Makesurethatitischemicallycompatiblewith
theapplicationmedia.
Enclosure:Whilethesensorhousingisliquid‐resistanttheLVRD10Seriesisnotdesignedtobeoperational
whenfullyimmersed.Itshouldbemountedtoinsuretheenclosuredoesnotcomeintocontactwiththe applicationmediaundernormaloperationalconditions.Theprobeisdesignedforfullliquidcontact.
Handling Static‐SensitiveCircuits/Devices: When handlingthetransmitter, thetechnicianshould follow
these guidelines to reduce any possible electrostatic charge build‐up on the technician’s body and the electronicpart.
1. Alwaystouchaknowngoodgroundsourcebeforehandlingthepart. Thisshould be repeatedwhile handlingthe part andmorefrequently aftersittingdownfrom astandingposition, slidingacrossthe seatorwalkingadistance.
2. Avoidtouchingelectricalterminalsofthepartunlessmakingconnections.
3. DONOTopentheunitcoveruntilitistimetocalibrate.
MakeaFail‐SafeSystem: Designa fail‐safesystem thataccommodates thepossibility ofswitch and/or
powerfailure.OmegaEngineering®recommendstheuseofaredundantbackupsystemandalarminaddition totheprimarysystem.
Flammable,ExplosiveorHazardousApplications:TheLVRD10Seriessensorisnotcertifiedforapplication
inahazardouslocations.
7
Page 8
GETTINGSTARTED SectionTwo
SetupOverview
Belowhighlightstheinitialstepsinsettingupyoursensorforoperation.
1. CheckPartNumber(SectionTwo)
a. Confirmthatthesensor’spartnumbermatchestheorderedpartnumberandallcomponents
areprovidedwiththemodeldelivered.
2. MeasureProbe&Installation(SectionTwo)
a. Priortoinstallation,measurethelengthoftheprobe.Confirmthattheprobelengthmatches
theactualinstallationlocation. b. Iftheprobelengthistoolong,refertoCuttingtheProbeinSection8. c. Understand the location of the sensor’sMeasurement Range as wellas Minimum Fill‐Height
andMaximumFill‐Heightsettings.
3. Installthesensor(SectionThree)
a. Section3containsinformationonthelocationandmechanicalinstallationofthesensor.
4. Wirethesensor(SectionFour)
a. Section4containsinformationonelectricalwiringandpowerrequirementsforthesensor.
5. ConfigureSensorwithLVCN414‐SWSoftware(SectionFive)
a. Section5containsinformationonusingtheLVCN414‐SWconfigurationsoftware.
6. PerformanEmptyScan(SectionSix)
a. Section6containsinformationonhowtorunanemptyscan. b. Anemptyscanmaynotberequiredonasensorthathasacoaxialprobe.
      

8
Page 9
GETTINGSTARTED SectionTwo
Components:LVRD10Seriesisofferedin12differentmodels.Dependingonthemodelpurchased,youmayor
maynothavebeenshippedtheconfigurationcomponentshownbelow.
Part
Number
LVRD11‐B LVRD11 Yes LVRD11‐3FT‐B LVRD11‐3FT Yes LVRD11‐6FT‐B LVRD11‐6FT Yes LVRD11‐B LVRD11 Yes LVRD11‐3FT‐B LVRD11‐3FT Yes LVRD11‐6FT‐B LVRD11‐6FT Yes LVRD13‐B LVRD13 Yes
Maximum
Range
9.8’
(3m)
3.0’
(0.91m)
6.0’
(1.82m)
9.8’
(3m)
3.0’
(0.91m)
6.0’
(1.82m)
18.0’
(5.5m)
Probe
Style
Rod 316LSS ¾”NPT
Coaxial 316LSS ¾”NPT
Cable 316SS ¾”NPT
Probe
Mat’l
Thread
Coaxial style probe1 ‐ includes rod, threaded
½”pipeandspacers
Cablestyleprobe2‐includescounterweight
Fob
Included
No
No
No
No
No
No
No
Components
Housing,feed‐through,
rodstyleprobe
Housing,feed‐through,
coaxialstyleprobe
Housing,feed‐through,
cablestyleprobe
1
2
Manual
 
9
Page 10
GETTINGSTARTED SectionTwo
UnderstandingSensorHeight
ThisisacriticalsettingforLVRD10Series.SensorHeightdefinestheheightofthesensorabovethebottomof thetank.Theheightvaluemusttakeintoaccounttheshapeofthetankandanyrisers,fittings,structuresor extensions associated with the tank or the installation (see examplesbelow).Thereferencepointfor definitionoftheSensorHeightisalwaysthebottomofthemountingnut.
Simple
Tank
ConeBottomRaises
SensorHeight
DomeTopRaises
SensorHeight(SH)
MountingFixture
RaisesSensorHeight
SensorOffCenter
ChangesSH

Simple
Tank
SimpleOpen
TopTank
SensorExtendsinto
SumpLoweringSH

RiserRaises
SensorHeight
UnderstandingProbeLength
Thereferencepointfordefinitionoftheprobelength[Length]isalwaysthebottomofthethreads[bottomof thefeedthrough(seebelow)].Note:ThisisadifferentreferencelocationfromtheSensorHeight.Theprobe Lengthisanimportantmechanicaldimensionwhichisneededtomakesuretheprobephysicallyfitsintothe tankattheanticipatedmountinglocation.Probelengthhasaninfluenceontheactualmeasuringrangeofthe sensor,butitisadifferentaspectofthesensor.
Note:SensorHeightandProbeLengthhavedifferentreferencepointsformeasurement.

RodProbe (LVRD11Series)
CoaxialProbe (LVRD12Series)
CableProbe (LVRD13Series)
10
Page 11
GETTINGSTARTED SectionTwo
UnderstandingInstallLocationLength
Measurethespacebelowtheactualinstallationlocationforthesensor.Thisdistance(installlength)mustbe greaterthantheprobelength.Inmanytanks,theinstalllengthcorrespondstotheheightofthetank.With dometop,conebottomandhorizontaltanks,includetheaddedheightofthecurvedsurface.Besuretotake intoaccounttheheightoffittings,risers,tankflatsetc.whichmaybeaddedforinstallation.Alloftheabove canraisethebottomoftheprobehigherinthetankthanwhatwasoriginallyexpectedresultinginareduced lowestlevelofmeasurement(seeMeasurementRange).
TankwithFlatTop
&FlatBottom

DomeTopsandConeBottoms
ThelocationofanLVRD10Seriesinstalledalongthetopofadome top tank may have an effect on the installationofthesensor.Besuretomeasurefromtheactualpoint ofinstallation. Roundor conebottom tankswillreducetheinstallheightavailable,dependingoninstalllocation.Ifthisoccurs,eitherthesensorcan beraisedusingfittings(seeAddingaRisertoAvoidCuttingtheProbe)ortheprobe’slengthmaybereduced bycuttingtheprobe(seeCuttingtheProbeinSection7).
TankwithDomeTop
&FlatBottom
Horizontal
Tank
InstallHeight>
ProbeLength

11
InstallHeight<
ProbeLength
InstallHeight>
ProbeLength
Page 12
GETTINGSTARTED SectionTwo
AddingaRisertoAvoidCuttingtheProbe
Insomeconditions,arisermaybeaddedtoavoidcuttingtheprobe. 
RodandCableProbes
WiththeRodandCableversionsof theprobe,themaximumheightfor the riser is 12” (300mm).  The minimum diameter of the riser is 2”(50mm).Therisermustbe metallic in construction using the least number of fittings /connections.  Note:AnEmpty
SignalScanisarequirementso that the EchoWave® can eliminate the odd geometry created by the riser.
Leastnumberoffittings
ToomanyFittings
CoaxialProbes
Withthecoaxialprobe,thereisno maximumriserheightorminimum riserdiameter.Thisisbecausethe coaxial shield isolates the physical changes to the installation from thesensor’senergysignal.Inboth examples,theenergysignalcannot see any changes to the fitting/connections or from being installed in an extension that exceeds the maximum height for rodandcableprobes.

 
12
Page 13
GETTINGSTARTED SectionTwo
UnderstandingMeasurementRange
LVRD10Seriesleveltransmittershavesmall dead bandareasat boththetopandbottomoftheprobe.Itis duetothepresenceofunavoidablesignaldisturbancesatbothendsoftheprobe.Inthesedeadbandareas the measurementsare non‐linearor have reducedaccuracy. Therefore,itisnotrecommendedtoactually measurelevelwithinthosedeadbandareas.Theirlengthdependsontheprobetypeandthereflectivity(i.e. dielectricconstant)oftheliquidtobemeasured.
TheMeasurementRangeofLVRD10seriesextendsbetweenthetopand bottomdeadbandareas;thisistheareainwhichasensorwillhavethe specified measurement performance.  It is recommended that the maximumand minimumlevels to bemeasured inthetank areactually within theMeasurement Range ofthe sensor. The span betweenthe lower range value [4mA] and the upper range value [20mA] of the current output is proportionally equal from 0 to 100% of your continuouslevelmeasurementreading.Itisrecommendedthatthe span between these two range values stays within the Measurement Range.
The[TopDeadBand],closesttothethreads,issetto4”(100mm).This ismeasuredfromthebottomofthenutdowntotheprobe.Thisis consistent forall styles of probe. Note: the measurement location for
the Top Dead Band is different to the measurement location for the probelength.
The [BottomDead Band],closesttotheendoftheprobe,issetto2”
(50mm).Thisismeasuredfromtheendoftheprobeonrodandcoaxial probes.Forcableprobes,itismeasuredfromthetopofthecounter‐ weight.Thecounter‐weightmustbeincludedwiththedeadbandasthe sensor’sinactivearea.
 
13
Page 14
GETTINGSTARTED SectionTwo
UnderstandingMinimumFill‐Height(puttingitalltogether)
LVRD10SerieshasaMinimumFill‐Height(Min.Fill‐H),whichismeasured fromthebottomofthetanktothetopoftheBottomDeadBand.As shippedfromthefactory,Min.Fill‐Hiswherethe4mAcurrentislocated andisthelowestpointontheprobewherethesensorcandetectaliquid level.Anypoint belowthis positionwill stopat4mA. The Min.Fill‐His influenced by the Sensor Height (SH), Probe Length (P), Height of the Threads[0.65”(16.5mm)]andBottomDeadBand.
Min.Fill‐H=(SH)–[0.65”(16.5mm)]–(P)+(BottomDeadBand)
Withacableprobe,includetheheightofthecounter‐weight.SwitchoutputtovolumetricwillallowMin.Fill‐Htobesetto(0).Ifthe4‐20mAoutputisreversed(20mAatbottomand4mAat
top),thenthelevelwillmaxoutat20mAwhenthelevelfallsbelowtheMin.Fill‐H.
Note:Becauseofthebottomdeadband,theMinimumFill‐Heightcanneverbeattheendoftheprobe.
Note: The configuration ofthe sensor (Distanceor Volume) will affect the current output at Minimum Fill‐
Height.UponselectingDistance,thecurrentwillbesetto4mAatMinFill‐H.However,uponselectingvolume, the current at Min Fill‐H will be the calculated based upon 4mA being set at the bottom of the tank [see Distance(HeightofLiquid)vs.VolumeofLiquid].
UnderstandingMaximumFill‐Height
LVRD10 Serieshas a MaximumFill‐Height (Max. Fill‐H),which ismeasuredfrom thebottomofthetanktotheTopDeadBand.Asshippedfromthefactory,Max. Fill‐H definesthe 20mAcurrent depicting thehighest pointon the probewhere thesensor detectsliquid level.Anypointabovethisposition willstop at20mA. The Max. Fill‐H is influenced by the Sensor Height (SH), HeightoftheThreads [0.65”(16.5mm)]andTopDeadBand.
Max.Fill‐H=(SH)–[0.65”(16.5mm)]–(TopDeadBand)
TheMax.Fill‐Hmaybedecreasedtolowerthe20mAlocation,butit
cannotberaisedaboveitsoriginalsetting.
Ifthe4‐20mAoutputisreversed(20mAatbottomand4mAattop),then
thelevelwillmaxoutat4mAwhenthelevelrisesabovetheMax.Fill‐H.
Note:Becauseofthetopdeadband,theMaximumFill‐Heightcanneverbeatthebottomofthethreads.

14
Page 15
GETTINGSTARTED SectionTwo
Distance(HeightofLiquid)vs.VolumeofLiquid
Withthe LVCN414‐SWsoftware,the LVRD10seriescan beconfigured tooperateas adevicethat reads the distance(heightofliquid) or volumeof aliquid.  Thelocation ofthe emptycurrentwilladjustdependingon which configuration method is selected.  Note:The empty(4mA) location is placed at a different location baseduponselectingliquidheightorliquidvolume.
Distance(HeightofLiquid):WhentheLVRD10Seriesisconfiguredto readtheheightoftheliquid,thedefaultforthesensorEmptywillbeat the bottom of the measurement range (end of the probe minus the bottomdeadband).Thisiswhere4mAwillbeset.Thedefaultfor sensor Full will be at the top of the measurement range (Top Dead Band),where 20mA willbeset.  The20mAcanbe setbytheMaximum Fill‐Height.
Volume of Liquid:WhentheLVRD10seriesisconfiguredtoreadthe volumeofliquid,theoutputwilltrackthevolumeofthetankasthelevel increasesanddecreases.LikeDistance, theEmptyand Fullsettingswill defaulttothelowandhighendoftheMeasurementRange.The location of the 20 mA can be adjusted with the Maximum Fill‐Height settings.  However, the shape of the tank can influence the current output,dependinguponthetankbeinglinearornon‐linear(seebelow).
LinearTankExample
Note: In the above illustration, 10” of liquid will always be equal to 100 gallons of liquid (1” = 10 gallons).
Non‐LinearTankExample
Note: In the aboveillustration, 1”of liquiddoes not equal10gallons.The10”atthebottomrepresentsa rise of 62.8gallons.  As a changebetween 10” and 20”representsanincreaseof109.6gallons(i.e.172.4 gallons–62.8gallons).
 
15
Page 16
INSTALLATION SectionThree
LVRD10 series is mounted vertically into the tank via its connectionthread.Itisthen screweddirectlyintoastandardthreadedtankconnection,i.e.tankadapter,bushing,weld‐ insocket,oritcanbescrewedintoaflangewhichisconnectedtoatanknozzle.
Thesensorshouldnotbeweldeddirectlyintothetank.Neithershouldflangesbewelded ontothesensor.WeldingonthemetalpartsofLVRD10Serieswillcauseseriousdamageto thetransmitter.
DonotliftorhandletheLVRD10seriesbyitsprobe
probeconnection.LVRD10Seriesshouldbehandledbythehexagonorthelowersectionof thehousing.Donotscrewinthesensorbyitshousing.Itshouldbetightenedonlyviaits hexagon(wrenchsize32mm).
Theend userhas toensure propersealing ofthe sensorconnection; basedupon process conditions, i.e. temperature, pressure and resistance against the process liquid’s atmosphere.
ForNPTthreadconnections,pressure‐tightjointsrequireasealantdirectlyonthethreads.
Inthecasethatthesensorisdeliveredwithadetachedprobe(cableversiononly),attachtheprobeontothe smallthreadedstudbelowthehexagon.Makesuretoavoidcrossthreadingormisaligningthethreads.
MountingConsiderations
Theprobesshouldbeinstalledsothattheyarenotdirectlyimpactedbyliquidsflowingoutofthefillinginlet. They should neither touchnor swaytowards otherobjects insidethetankorthetank/nozzlewalls;e.g.by agitator or mixer swirls.  In applications with very strong fluid movements which can also cause excessive lateral force on the probe, it is recommended to anchor the probe.  The anchoring fixtures are end user supplied.
:thiswillcauseexcessivestressonthe

 
16
Page 17
INSTALLATION SectionThree
MountingConsiderations(continued)
Therodandcable probesare suitablefor avery widerange ofapplications in liquids.However,thesignalhasawiderdetectionradiusaroundtherod/cable. Therefore,itismoreresponsive formeasurementsignaldisturbancesthatare overcome by a few Mounting Considerations (see below) as well as simple configurationadjustmentstothesensor.Inmostcasesitisenoughtoactivate and utilize the powerful LVRD10 series empty signal scan feature.Itworks mostefficiently onstationaryinterference targets liketalland narrownozzles orclose‐byobjects.
In case a non‐stationary interference target is close to the rod probe, like slowly rotating agitator blades causing problems with the measurement,itis recommendedtousethecoaxialprobe.Inanycase,therodandcableprobes shouldnevergetindirectcontactwiththetank/nozzlewallorotherobjectsinthe tank.
 nozzlediameter >2”(50mm) >2”(50mm) +
Rod Cable Coaxial
(1)
nozzleheight <12”(300mm) <12”(300mm) +
clearancetotankwallorotherinternalobjects >4”(100mm) >4”(100mm)
+
clearancebetweenprobeendandtankbottom >0.1”(2mm) >0.1”(2mm) +
diameterofbypasschamber/stillingwell >1”(25mm) >1”(25mm) +
(2)
metallictankorbelowgradeconcretebasin + + +
Non‐metallicorplastictank NR NR + + =recommended
(1)
+
 =enoughdiametertofitinthecoaxialtube(0.843”/21.3mm)
(2)
+
 =enoughdiametertofitinthecoaxialtube(0.843”/21.3mm)withallocatedroomaroundthe
probeforliquidflowthroughthebypasschamber/stillingwell
NR =NotRecommended
TherodprobeisalsotherecommendedprobetypeformountingtheLVRD10seriesintobypasschambersor stillingwells.Inthiscase,plasticcenteringspacersareneededtopreventtheprobefromcontactingthewall.
The cable probe is recommended for installations in tall tanks where limited installation headroom is available.Itsperformancecharacteristicsandmountingconsiderationsaresimilartotherodprobe.
Thecoaxialprobedoesnothaverestrictionsregardingmountingposition,tankconnection,proximitytothetank walland other objects inside thetank. The coaxialprobe isrecommendedfor installingLVRD10 seriesinto a non‐metallictankoropenpit

17
Page 18
INSTALLATION SectionThree
InstallationTips
TallandNarrowRisers
Rod and Cable probescan beinstalled intall and narrowrisers underthefollowingcriteria:
NozzleDiametermustbe>2”(50mm),NozzleHeightmustbe<12”(300mm),Risermustbemetallic,Anemptysignalscanisrequiredafterinstallation.
Coaxialprobesarenotaffectedbytallandnarrowrisers.
DifficultTankorRiserGeometries
RodandCableprobesmustfollowthecriteriabelow:
Tall and Narrow Risers criteria must be
followed,
Nozzlediameterremainsthesamediameter,NozzleDiameterdoesnotdecrease,NozzleDiametermaygetlarger,butaempty
signalscanisrequired.
Coaxialprobesarenotaffectedbytheshapeofthe tankorthegeometryofthenozzleastheaboveisnot applicable.
ClosetoSideWallorInternalObstructions
RodandCableprobesmustfollowthecriteriabelow:
>4”(100mm)fromthesidewall,>4”(100mm)fromanyobjectsorobstructionswithinthe
tank,
Aemptysignalscanmayberequiredafterinstallation.
Coaxialprobesarenotaffectedbythedistancefromtheside wallorfromotherobjects/obstructionswithinthetank.
MovingProbe
RodandCableprobesmustfollowthecriteriabelow:
Avoid applications where the movement of the tank will cause the
probetoswingortouchobjectsandobstructionsinthetankortheside
wallofthetank.
Avoidapplicationswherethetankistruck/vehiclemounted.
Coaxialprobesarenotaffectedbythemovementofliquidwithina stationary tank.
 

18
Page 19
INSTALLATION SectionThree
InstallationTips(continued)
LiquidSpray
RodandCableprobesmustavoidanyliquidthatspraysorpours ontotheprobe.
Coaxialprobes arenot affectedbyliquid sprayingon parts that are above the liquid surface.  However, avoid installing probe whereliquidwillpourontotheprobe.
Non‐Stationaryobjects
RodandCableprobesfollowthecriteriabelow:
>4”(100mm)fromanyobjectsorobstructionswithinthe
tank,
Anemptysignalscanmayberequiredafterinstallation,Non‐stationaryobjectsmust notbemovingwhen empty
signalscanispreformed.
Coaxial probes are not affected by the movement of non‐ stationaryobjects,suchasmixerbladesorpumpliftingchains.
Note:All probes(rod, cableandcoaxial) canbe affectedbyany liquidvortexcreatedbyamixer.
Measurementreadingsattheverytoporbottomofthetank
Rod and Cable probes do not have the outer tube and must adheretoallmountingrequirements,specifically:
>4”(100mm)fromanyobjectsorobstructionswithinthe
tank,includingthebottomofthetank,
Criteriafordifficulttankorrisergeometriesmustbe
followed. Coaxialprobescaneasilybemechanicallymountedtoensurethe measurementofliquiduptoafulloremptytank.Becausethe coaxial is encased within the outer tube, the sensor is self‐ containedsootherobjectsorobstructionsarenotanissue.This makesraisingorloweringthesensorsimpleandstraightforth.
  
19
Page 20
INSTALLATION SectionThree
InstallationTips(continued)
Non‐metallictanks
Unlike coaxial, rod and cable probes have no containment mechanism.Thisenergymustbecontainedbythetankwall, requiring that all rod and cable probe sensors be installed in metallictanksorwithinbelowgradeconcretesumps.
Coaxial probes can be installed in any type of tank, including non‐metallic tanks.  This is because the outer tube acts as an insulatorpreventing thesensor’s energyemanating beyondthe probe.
StillingWells/BypassChambers
Installations within a stilling well or a bypass chamber are recommendedwitharodprobe.Ametallicpipeisrequired.Acoaxial probe can be used in a stilling well or bypass chamber if required. Note:Neveruseacableprobewithinastillingwellorbypasschamber.
Makesurethattheprobedoesnotcomeinto contactwiththe
innerwallofthestillingwellorbypasschamber
o Non‐metallicspacersmayberequiredtokeeptheprobe
withinthecenterofthestillingwellorbypasschamber
Make sure the liquid is able to freely fill, empty and that no
residueremainswithinthestillingwellorbypasschamber.
AllothermountingcriteriamustbeobservedAemptysignalscanmayberequiredafterinstallation
Limitedheadroom
Wheninstallinginatankwherethereislimitedspaceabovethetopof the tank, the cable probe is the recommended solution.  The cable probedesignallowsfortheprobetobeinstalledthroughasmallspace abovethetank.
Therodandcoaxialprobes may beinstalled aslong as theprobes are notdamagedorbentandaslongasthesensorisnotheldbytheprobe (sensormustbeheldbythehead).
Allothermountingcriteriamustbeobserved.
 
20
Page 21
INSTALLATION SectionThree
InstallationTips(continued)
TallTanks
Therodandcoaxialprobeshaveamaximuminsertionlength of
9.8’(3m).Formetalorconcretetanksthataretaller/deeper,the cableprobecanbeusedforlengthsupto18.0’(5.5m).
The maximum length is based from the bottom of the
threads.
o Note: the coaxial probe consists of a rod probe
with a metal outer tube installed around the originalrod.Thebottomofthemountingthreads areusedasthereferencepointformeasurement.
SideMountBrackets(LMV‐30Series)
Rodand Cable probescanbe installedwiththe side mountbracketunder the followingcriteria:
The side wall or any object / obstructions do not come within 4”
(100mm)fromtheprobe
Anymovementof theliquid willnotcausethe probetoswinginto the
sidewalloranyobject/obstruction
ThetankmustbemetallicorabelowgradeconcretebasinAnemptysignalscanmayberequiredafterinstallationAmetalplateof6”indiametermayberequiredifthereisnorooftothe
tank/basin
Coaxialprobesarenotaffectedbythesidemountbracket.
ProbeTooLong Forinformationoncuttingtheprobe,seeCuttingtheProbewithintheAppendix,Section7.  
21
Page 22
WIRING SectionFour
AnalogOutput(4‐20mA):TheanalogoutputoftheLVRD10Seriesisasourced4‐20mAcontrolcircuit.The
typicalwaytousethisfeatureistoconnectapositivesupplytothe(+)inputterminal,anegativesupplytothe (‐)inputterminalandtoconnectthecurrentoutputoutofthe420(+)terminal.Thedevicethatacceptsthe4‐ 20mAcurrentsignalmustreferencethesamenegativesupplylistedabove(seediagrambelow).
SampleWiringDiagram
Diagram will change based upon the sensor’s configuration, use LVCN414‐SW software to view appropriatewiringdiagram.
ThecablingshouldbeshieldedandtwistedtominimizeEMIinterference.Itsshieldshouldbeconnectedateither endandneverconnectedatbothends.Typically18to24gaugewireisusedinthisapplication.
GeneralNotesforelectricalconnections,usageandsafety:
Where personal safetyor significant property damagecan occurdue to a spill, theinstallation must
havearedundantbackupsafetysysteminstalled.
Wiringshouldalwaysbecompletedbyalicensedelectrician.
Protectthesensorfromexcessiveelectricalspikesbyisolatingthepower,wheneverpossible.
Supplyvoltageshouldneverexceed30VDC.
Makesurethatthepowersupplydoesnothaveacurrentmorethan2Aorthatthereis2Aratedfuse
intheelectricalcircuitthatenergizesthedevice.
Thesensormaterialsmustbechemicallycompatiblewiththeliquidstobemeasured.
Designafail‐safesystemforpossiblesensorand/orpowerfailure.
Neverusethesensorinenvironmentsclassifiedashazardous.
22
Page 23
WIRING SectionFour
WireConnections
Thehousinghassinglecableentryandcanbeattachedtoscrewplugs,cordgripsorconduitwiththe½”NPT thread.  Note:  the customer must confirm the suitability of those connectors for the specific application requirementsandcabling;andreplace themwhen necessary. IP66‐ratedscrew plugsand cordgrips haveto beproperlymountedandtightenedaround cableof suitabletypeanddiameterto ensure theIP66 rating of thehousing.
Note:Aliquid‐tightcordgripandferritebeadareincludedwiththe sensor(seeSpecificationSectionforcordgripdata).
Note: Always include the ferrite bed when using the cord grip or whenusingnon‐metallicconduit.
Note:Alwaysshieldthesignalwireperinstructionsonthewiringdiagram.
ConduitConnection CableGland(LiquidTight)w/Washer
FerriteBead
Liquid‐TightCordgrip
AvoidCondensationintheConduit
You can give your instrument additional protection against moisture penetration byleadingtheconduitconnectionorcable downward in front of the cable entry. Condensationin theconduit will thusnot enterthesensorenclosure.

23
Page 24
WIRING SectionFour
CommonWiringtoDisplay,Controllers&PLC’s(continued)
GenericLoop
PoweredDisplay
DataPoint™LVCN‐51Series
LevelController
JWBmode
GenericPLC
 
Note:LVCN‐51shippedfromfactorywithjumperinJWAmode.JumpermustbeswitchedtoJWBmodefor operationwiththeLVRD10Series.
Note:4‐20mAsignalwirerequiresshielding(powersupplywiresmayusethesameshieldingasthesignal wire).Shieldwirecanbeconnectedateitherend.Neverconnectshieldwireatbothends.
Note:LVRD10Seriesisa3‐wiresensorandshouldneverbetreatedasa2‐wirelooppowereddevice.Follow theillustrationsaboveforwiringtothemostcommondevices.
  
24
Page 25
CONFIGURATION SectionFive
LVRD10SeriesisconfiguredthroughafreePCsoftwareprogram(LVCN414‐SW,version6.5 orgreater).  The software is a free download from Omega Engineering®’s website.  You must download and install the softwarepriortopluggingintheUSB®Fob.
Pleasegotohttp://www.omega.com/ftp.
ClickonFlow,Level,pH,Environmental,andPressureSectionandpressonProducts.
Selecttheinstaller–LVCN414InstallerVerXpXX.zip.
o Thiswilldownloadtheinstallerontoyourcomputer. o Oncecompleted,runtheinstaller.
LVCN414‐SWSoftwareSystemRequirements
Windows®2000,XP,Vista,7,8
32or64‐bitsystem
1USB®2.0port
10mBharddrivespace
256mBRAM
Internetconnection
USB®FobInterface:LVRD10SeriescommunicateswiththeLVCN414‐SWsoftwarethroughaUSB®interface calledaFob. Before pluggingyourFobinto yourcomputer’sUSB®port, besurethatyou have installedthe softwareontoyourcomputer.
Connect the red, green, white and black terminals on the Fob to the corresponding terminals within the LVRD10Series.TightenthescrewsontheterminalsandplugyourFobintotheUSB®portofyourcomputer.
WiringisidenticalforallseriesofLVRD10Series
The maximumcable distance betweenthe computer andLVRD10 Seriesis15’.Thisonlyapplieswhen
configuringtheLVRD10Series.
Once LVRD10 Series is configured and prior to installation, disconnect all wires from the center two
terminalstopreventashortoftheconfigurationcircuit
Note:WhenusingtheFob,donotaddVDCpower.TheFob,whenconnectedtothecomputer,willprovide
therequiredpowertotheLVRD10Series.
25
Page 26
CONFIGURATION SectionFive
With LVRD10 Series connected to your computer, open the LVCN414‐SW software by clicking on the software’sicon.FollowstepsAtoDtoconfigurethetransmitter.Click“Help”inthelowerrighthandcorner andopenthehelpmenu for additionalinstructions onthe software.Ifyouneedadditionalassistanceusing theLVCN414‐SWsoftware,pleasecontactanOmegaEngineering®applicationengineer.
ConfiguringLVRD10SerieswiththeLVCN414‐SWSoftware
A. SensorConfiguration
1. ConfiguresLoopFail‐Safe,OutputatEmpty,StartupCondition&DielectricRangeforthesensor.
2. AlsoconfirmProbeType(Rod,CoaxialorCable)inthepulldownmenu.
B. DimensionalEntry
1. DistanceMode(default) i. Basicinformationforoperation(SensorHeight,ProbeLength&MaximumFill‐Height).
2. VolumetricMode i. Definesthe shape ofthe tankaswell as thedimensionalinformation forthe tankwith
respecttothesensor’slocationonthetank.
C. TankLevelConfirmation
1. Confirmthevaluesareaccuratefortheapplication.
D. WritetoUnit
1. Uploadsconfigurationintothesensor.
2. Accesstoacustomerwiringdiagramspecifictotherelayconfiguration.
A.SensorConfiguration:

26
Page 27
CONFIGURATION SectionFive
B.DimensionalEntry:
1.DistanceMode (default):Outputof sensorisbasedon thedistance(heightof liquid)inthetank.
Anychangeinliquidlevelwill reflect linearlyto the currentoutput.  Note: Mostapplicationswill fall intothiscategory.ThethreesettingsyoumustenterforDistance Mode are Sensor Height, Probe LengthandMaximumFill‐Height.Allthreesettingscanbeenteredonthemainconfigurationscreen.
2.Volumetric Mode: Allowstheendusertoswitchfromthe standarddistanceoutput toanoutput based upon the volumetric shape of the tank.  In Volumetric Mode, the shape of the tank is first selectedfollowedbytheentryof dimensional information for thetankwithrespecttothesensor’s locationonthetank.
Enter theoperational dimensionsfor the sensorand tank withinthedefinedapplication.Allofthe showndimensionsarerequiredandwilladjustdependingontankshapewhethertheoperationisfor volumeordistance.PressApplywheninformationiscompleted.

Note:While in Volumetric Mode, the sensor may be switched between Distance and Volumetric outputs (under Sensor Output Units).  When Distance is selectedtheunitsareinches,cm,feetor meters.  When Volume is selected, the units are Gallons or Liters.Thetypeofconfiguration output (Volumetricor Distance) and themeasured units may bechanged under Sensor Output Units.
 
27
Page 28
CONFIGURATION SectionFive
D. Tank Level Confirmation:  Verify the Height Units, Sensor Height, Probe Length, Maximum Fill‐Height,
Minimum Fill‐Height, Capacity as well as the Max./Min. Volume and Max./Min. Current.  All values were calculatedinthepreviousDimensionalEntrywindow.Toadjustthesesettings,clickonVolumetricModes.

E.WritetoUnit–Thisoperationuploadsconfigurationintothesensor.Otherfeaturesinthesectioninclude providingacustomwiringdiagramspecifictothesignaloutputandsavingtheconfigurationfiletoyourhard drive.
VolumetricSensorOutput
TheVolumetricModebuttonwill be highlighted in Blue when a volumeoutputisselected.
  
28
Page 29
EMPTYSIGNALSCAN SectionSix
EmptySignalScan
The empty signal Scan is a powerful disturbance signal suppression feature of LVRD10 Series.  The sensor scans its entire probe length for any disturbance/interference signals within the application that could potentially be misinterpreted as level readings by memorizing and suppressing them during operation. Therefore,theLVRD10seriesonlyrecognizestheactuallevelsignalscausedbytheliquidbeingmeasured.
Theemptysignalscanisintendedfortherod&cableprobe,sinceitssignalhasawiderdetection radiusaroundtheprobemakingitmoreresponsiveformeasurementsignaldisturbances.
Theemptysignal scanworks mostefficientlyonstationaryinterference targetslike talland narrowrisersor close‐byobjects/obstructions. To enablean emptysignal scan,theLVRD10serieshastobemountedinits finalposition.Thetankhastobecompletelyempty.Thiswill ensurea reliableidentification ofthe actual disturbancesignals only.Incasetherearenon‐stationaryinterferencetargetsclosetotherodprobe(slowly rotatingagitatorbladesorstreamsofliquidfillingintothetank),itisrecommendedtousethecoaxialprobe.
ActivateEmptySignalScan
WhenLVRD10Seriesisshipped,thisfeatureisdeactivated.Toinitiatea emptysignalscan,usethefollowinginstructions:
1. Make sure theLVRD10 series is installedin its final installation position.
2. Makesuretheliquidisatitslowestlevel(empty).
a. Performing an empty signal scan when the tank is not
empty will create an incorrect scan.  It can affect the sensorsperformanceespeciallyatliquidlevelsbelowthe emptysignalscantanklevel.
3. PressandholdtheSCANbuttonfor6seconds.
a. The LED will begin to flash Orange indicating theempty
signalscanhasbegun,releasethebutton. b. Uponcompletionoftheemptyscan,asolidgreenLEDwillreturn c. Iftheemptyscanisnotsuccessful.TheLEDwillflashred
EraseEmptySignalScan
Ifthereisaneedtoeraseorturnofftheemptysignalscan,performthefollowing:Firstremovepowertothe LVRD10 Series. Next,hold down theSCAN button while applying powerto the sensor. When the LVRD10 seriesacquiresasignal(LEDwillflashGreen),thedisturbancesignalscanwillbeerased.
Noothersettingorfunctionswillbeaffectedwhenthisstepispreformed.Theemptysignalscancannotberetrievedonceerased.Anewdisturbancesignalscanmustbepreformedforthisfunctiontooperateagain.
TheemptysignalscancanalsobeerasedusingtheLVCN414‐SWsoftware.Pleaserefertotheinstructionsin theAppendix.
 
29
Page 30
EMPTYSIGNALSCAN SectionSix
ViewingtheEmptySignalScan
TheEmptySignalScancanbeviewedwiththeLVCN414‐SWsoftware(version6.5andgreater).Note:Always consultaOmegaEngineering®representativeforreviewingofthesignaldata.Toview,followthe directions
below:
1. Activateanemptysignalscan(seeinstructionsinEmptySignalScan,Section6).
2. ConnectLVRD10SeriestoLVCN414‐SWsoftwareviaFob
3. ClickonDiagnosticsTabonthemainscreen
4. IntheSelectSignalDatapulldown,selectEmptyScan.
5. Theemptysignalscanwillbedisplayedinthewindow.
EraseEmptySignalScanwithLVCN414‐SWSoftware
Ifthereisaneedtoeraseorturnofftheemptysignalscan,performthefollowing:
1. Disconnectthesensorfromtheapplicationwiring.
2. ConnectLVRD10SeriestoLVCN414‐SWsoftwareviaFob.
3. ClickonDiagnosticsTabonthemainscreen.
4. ClickonEraseEmptySignalScan.

30
Page 31
APPENDIX SectionSeven
EchoCurve
Thisfunctiondisplays theprimary echoreturn(s)thatthe sensoris seeinggraphicallyas well asthelocation and amplitude of the return(s).  It can be used to confirm the correct level reading by the sensor or to troubleshootanyfalsesignals.Thereisatwostepprocessinvolving the creating and viewing of an echo curve.Note:AlwaysconsultaOmegaEngineering®representativeforreviewingofthesignaldata.
#1‐CreateanEchoCurve
Tocreateanechocurve,usethefollowinginstructions:
1. Make sure the LVRD10 series is installed within the actual application.
a. Echo curve will not provide any useful information when
placedoutsideoftheapplication.
2. Press and hold the SCAN button for 1 second (LED will turn off), thenrelease.
3. Echocurveiscompleted.
a. Toview,youmustconnectthesensortotheLVCN414‐SW
software.
Note: LVRD10series canstore upto atotal ofthree emptysignal scans and/orecho curve. Example:If an emptysignalscanisactive,LVRD10Serieswillonlystoretwoechocurves.Ifanemptysignalscanisnotactive, threeechocurvescanbestores.Echocurvesfollowafirstinfirstoutlogic.
#2‐ViewingtheEchoCurve
The echo curve(s)scan can be viewed with theLVCN414‐SW software (version 6.5 and greater). To view, followthedirectionsbelow:
1. Create an echo curve (see instructionsabove).
2. ConnectLVRD10Seriestothe LVCN414‐SWsoftwareviaFob
3. ClickonDiagnosticsTabon themainscreen
4. In the Select Signal Data pull down,selectEchoCurve.
5. The echo curve will be displayedinthewindow.
 

31
Page 32
APPENDIX SectionSeven
A.SensorConfiguration
LoopFail‐Safe
Thisfeatureallowsyoutoselectthefail‐safecurrentoutputifthesensor looses echo confidence (LOST). When the sensor regains echo confidence, the output current will revert back to the current level condition.
Hold Last Value‐Theoutput will remain in the samestate as
the lastconfident echo detected. Example: If the output was
6.7mA justprior tothe lost signal, the sensor willcontinue to output6.7mAuntilechoconfidenceisregained.
Empty ‐ The output will revert to the current value for an
emptycondition.When4mAatBottomisselected,thesensor will output 4 mA during a fail‐safe condition.  If 20 mA at Bottomis selected,the sensorwilloutput 20mAduring afail‐ safecondition.
Full ‐ The output will revert to the current value for a full
condition.  When4 mA at Bottom is selected, the sensor will output20mAduringafail‐safecondition.  If20mAatBottom is selected, the sensor will output 4 mA during a fail‐safe condition.
Overfill(21mA)‐Thesensorwilloutput21mAduringafail‐safe
condition.
Overfill(22mA)‐Thesensorwilloutput22mAduringafail‐safe
condition.
OutputatEmpty
Thisfeatureallowsyoutoselecttheorientationofthe4to20mAoutput (4to20mAor20to4mA).Choosewhichoutputsettingbestfits the application.Typical applicationsaresetwith 4mAatBottom.Factory default is 4mA at bottom and 20mA at top.  When connecting your
sensortoadisplay,youmustaccountforyouroutputorientationsetting.
4mA at Bottom‐The output current will be 4mA when the
sensormeasuresanemptytankand20mAwhenthesensor measuresafulltank. 
20mA at Bottom‐Theoutput currentwill be20mA whenthe
sensormeasuresanemptytankand4mAwhenthesensor measuresafulltank.
Note:Rightclickonanyitemtoopenthehelpmenu.
Note:Toresettheconfigurationtable,presstheClearScreenbutton
 
32
Page 33
APPENDIX SectionSeven
A.SensorConfiguration
StartupCondition
Thisfeatureallowsyoutoselectthestartupcurrentwhenpowerisfirst applied to the sensor.  The sensor will consume the selected power whileit isacquiringthe liquidlevel. Whenthecorrect levelhasbeen identified,theoutput willadjustto the leveloutput. Usethisfeature toavoidfalsealarmswiththecontrollerwhenpowerisfirstappliedto thesensor.
Empty ‐The currentoutput willrevert tothe selectedcurrent
valueforanemptycondition.
o 4 mAat Bottom ‐ The sensor will output4 mAwhile the
sensorpowersup.
o 20mAatBottom‐Thesensorwilloutput20mAwhilethe
sensorpowersup.
Mid Tank (12 mA) – The sensor will output 12 mA while the
sensorpowersup.
Full‐Theoutputwillreverttotheselectedcurrentvalueforafull
condition.
o 4 mA at Bottom‐Thesensorwilloutput20mAwhile
poweringup.
o 20 mA at Bottom‐Thesensorwilloutput4mAwhilethe
sensorpowersup.
Overfill(22mA)‐Thesensorwilloutput22mAwhilethesensor
powersup.
ProbeType
Thisfeatureallowsyoutoselectthetypeofprobeattachedtothe feed‐through.Itiscriticaltoselectthecorrecttypeofprobe.
Rod ‐ Recommended for installations in liquids, in bypass
chambersand stillingwells(when combinedtogether withthe rodemulateacoaxialprobe).
Cable‐ Recommendedforinstallations intall tanksandwhere
limitedheadroomisavailable.
Coaxial‐Recommended fortheuse withcleanliquids only. It
cannotbeusedwithviscous,crystallizing,adhesive,coating, or stickyliquids; fibrousliquids, sludge, slurry,pulp orany liquids containingsolidparticles.
Note:Onlychangetheprobetypewhentheprobehasbeenphysicallychanged.Neverchangethissettingto improvesensorperformance.ThiswillonlycauseissuewiththeoperationofLVRD10Series.
Note:Rightclickonanyitemtoopenthehelpmenu.
Note:Toresettheconfigurationtable,presstheClearScreenbutton

33
Page 34
APPENDIX SectionSeven
A.SensorConfiguration
DielectricRange
Thisfeatureallowsyoutoselectthedielectricrange,whichsets the amplitudethresholdwithinthesensor.
Waterbasedmedia(water,H2SO4,HCl)
o 40to100 o 20to39.9 o 10to19.9
Varyingdielectrics(Alcohols,EthylAcetate,CasterOil)
o 9to9.9 o 8to8.9
TypicalHydrocarbons(DieselFuel,MineralOil,Solvents)
Note:  It is very important to select the correct range for the dielectric value of the liquid.  Choosing an incorrectrangewillaffecttheperformanceofthesensor.
Note:Rightclickonanyitemtoopenthehelpmenu.
Note:Toresettheconfigurationtable,presstheClearScreenbutton.
B.TankShapeSelection
The sensor may be configured in volumetric units (Gallons or Liters) or Distance (Height of Liquid) units (inches, cm, feet or meters).  LVCN414‐SW softwarewilldefaultinDistance(Heightof Liquid)withunitsofInches.Tochangethe units or to change from Distance to Volume, press the Volumetric Mode button located near the center of the window.
o 7to7.9 o 6to6.9
o 2to2.9
o 5to5.9 o 4to4.9 o 3to3.9
Note:  The Volumetric Mode button will be highlightedin Bluewhen avolume outputis selected.
 

34
Page 35
APPENDIX SectionSeven
ShapeSelectionWindow:Thiswindowwillshowsthedifferenttankshapeoptionsavailable.
VerticalCylinder
VerticalCylinderwithConeBottom
HorizontalCylinderwithEndcaps
HorizontalCylinderwithSphericalEnds
Spherical
Rectangular
Strapping Table– Usethisfeatureformanualentry
ofmeasuredtankdistancesandvolumes.
Select any of the above tank shapes and press OK to confirm.
C.DimensionalEntry–VerticalCylinderExample: Choosethe Sensor OutputUnits as Distanceor Volume. AfterchoosingtheSensorOutputUnits,selecttheunitsofmeasurementinthepulldowntotheleft.
UnitsofMeasurement
Distance Volume
Inches
Cm
Feet
Meters
Gallons
Liters
Distance–SensorOutputUnits(VerticalCylinderExample):
Enterthedimensionsof thetank. Youmust enterdatainallfieldsshown.
SensorHeight:Distancefromthebottomof thetanktothetopofthethreads.
Max.Fill Height: Distancefromthe bottom ofthetanktotheoperationalfulllevelof liquid (20mA).  This setting defines the locationoffullcurrentoutputand isthe top ofthesensor’smeasurementrange.
Min.FillHeight:Distancefromthebottomof the tank to the operational empty level of
liquid(4mA).Thissettingdefinesthelocation ofemptycurrentoutputandisthebottomofthesensor’smeasurementrange.
ProbeLength:Distanceoftheprobefromthebottomofthethreads(feedthrough)totheendoftheprobe. 
35
Page 36
APPENDIX SectionSeven
Volume–SensorOutputUnits(VerticalCylinderExample):
Enterthedimensionsof thetank. Youmust enterdatainallfieldsshown.
SensorHeight:Distancefromthebottomof thetanktothetopofthethreads.
Max.Fill Height: Distancefromthe bottom ofthetanktotheoperationalfulllevelof liquid (20mA).  This setting defines the locationoffullcurrentoutputand isthe top ofthesensor’smeasurementrange.
Min.FillHeight:Distancefromthebottomof the tank to the operational empty level of liquid(4mA).Thissettingdefinesthelocation ofemptycurrentoutputandisthebottomofthesensor’smeasurementrange.
TankHeight:Distancefromthebottomofthetanktothetopofthestraightsidewall.
Diameter:Distanceoftheinsidetankdiameter.
ProbeLength:Distanceoftheprobefromthebottomofthefeedthroughtotheendoftheprobe.
Volume–TankCapacity(VerticalCylinderExample):  After entering the dimensions, press the Capacity
buttonto show the CalculatedCapacity of the tank.  If the CalculatedCapacity isslightly differentthan the expected capacity, click on the Adjust Capacity box and enter the expected capacity of the tank.  If the AdjustedCapacityismorethan10%oftheCalculatedCapacity,recheck the dimensionsinformationentered above.

Whenalldimensionsareentered,presstheApplybuttontoreturntothepreviousConfigurationwindow.
Apply–TransfersthedimensionstotheoriginalConfigurationwindow.
Tanks–ReturnstothepreviousShapeSelectionwindow.
Cancel–ReturnstotheConfigurationwindowwithoutsavinganyinformation.
Help–JumpstotheHelpmenu.

36
Page 37
APPENDIX SectionSeven
D.TankLevelConfirmation:ThissectionoftheLVCN414‐SWsoftwareiswhereyouconfirmthevaluessetin
thepreviousstep.ThevalueswereenteredundertheDimensionalentrywindow.Toeditthesesettings,you mustgobacktotheDimensionalentrywindowviatheVolumetricModebutton.
HeightUnits:Unitsselectedforconfiguration.Whenusedasadevicetomeasuretheheightofliquid,
theoptions areinches, cm, feetor m.When usedas adeviceto measurethe volumeofliquid, the optionsaregallonsorliters.
SensorHeight:Distancefromthebottomofthetanktothebottomofthetopofthethreads.Max.Fill‐Height:Distancefromthebottomofthetanktotheoperationalfulllevel ofliquid(20mA).
Thissettingdefinesthelocationoffullcurrentoutputandisthetopofthesensor’smeasurement range.
Min.Fill‐Height:Distancefromthebottomofthetanktotheoperationalemptylevelofliquid(4mA).
This value defines the location of empty current output and is the bottom of the sensor’s measurementrange.
ProbeLength:Totallengthoftheprobefromthebottomoftheprobetothebottomofthethreads
(feedthrough).
o Cableversiononly:Theheightofthecounter‐weightisincludedinthismeasurement.
Capacity:Thetotalvolumeofthetank.Onlyshownwhengallonsorlitersareselected.MaximumCurrent: Displayed valueof thelargest operationalcurrent of the sensor’s measurement
range.Typically20mAwhenOutput@Emptyissetto4mA.
MaximumVolume: Displayedvalue ofthe largestoperationalvolume ofthe sensor’smeasurement
range.ThisisthecalculatedvolumeofliquidattheMax.Fill‐Height.Thisfeatureisonlyshownwhen thesensorisselectedtomeasurethevolumeofliquidinthetank.
MinimumCurrent:Displayedvalueofthesmallestoperationalcurrentofthesensor’smeasurement
range.ThisvalueisdependentonthelocationoftheMin.Fill‐Height.
MinimumVolume:Displayedvalueofthesmallestoperationalvolumeofthesensor’smeasurement
range.ThisisthecalculatedvolumeofliquidattheMin.Fill‐Height.Thisfeatureisonlyshownwhen thesensorisselectedtomeasurethevolumeofliquidinthetank.
Note:Byextendingtheempty(4mA)tothebottomofthetank,the4‐20mAoutputwilltrackthevolumeofthetank. Thisallowsanylocaldisplaytoreadtheactualvolumeofliquidwithouttheneedforanyuniqueconfiguration.This featureisveryusefulwithanynon‐lineartankssuchashorizontal,sphericalor
HeightUnits
   
Max.Fill‐H
 
Min.Fill‐H
Capacity
tankswithconebottoms.
SensorHeight
ProbeLength
Max.Volume
Max.Current
Min.Current
Min.Volume
37
Page 38
APPENDIX SectionSeven
E. Write to Unit ‐ After you have entered
configurations, selected and configured the Tank Shape and entered the Tank Values, click “Write to Unit”andloadtheconfigurationintothememoryof the sensor.  Whencompleted, thisconfiguration will remaininsidethesensormemoryandwillnotchange unless the sensor is connected to the LVCN414‐SW softwareandanewconfigurationiswrittentothe
WritetoUnit
Wiringdiagram       
sensor.  Loss of power will not change or lose the configurationwithinsensormemory.
SaveConfigFile
Next,usethefilemanagementfeaturestosaveyourconfigurationbyclicking“SaveConfigFile”andprintyour wiringdiagrambyclicking“WiringDiagram.”
“SaveConfig File”will savethis configuration asa textfile whichcan be loadedback intothe LVCN414‐SW softwarebypressingthe“OpenConfigFile”button.Itisgoodpracticetosavetheconfigurationfileforeach different configuration with a unique name for easy identification.  If using multiple sensors in identical applications,thenuseofasingleconfigurationfileisrecommended.
“WiringDiagram”willdisplayaPDFfileshowingtheuniquewiringforthespecificconfigurationcreatedinthe LVCN414‐SWsoftware.ThePDFcanbeprintedoremailed.Itisgoodpracticetosavethewiringdiagramasa backup.

38
Page 39
APPENDIX SectionSeven
CuttingtheProbe
Ifthelengthoftheprobeistoolong(touchesbottomoftank,preventsthesensorfrombeingthreadedinto thetankorashorterlengthisrequiredfortheapplication),theprobecanbecuttolengthinthefield.Note:
Themostimportantrequirementforcuttingtheprobeistoprotectthehousingfrombeingdropped,banging intootherobjectsorswingingfreely.Followtheinstructionsfortheappropriateprobestyle.
 Rod(LVRD11Series)
Placetheprobeonasturdysurface.Measureandmarkthelocationforthecut.
Securetherodtopreventitfrommovingduringcutting.
o Besuretosecurethehousingtopreventitfrommovingwhentheprobeiscut.
Useasawwithabladedesignedtocut316LSStocuttheprobe.
o Examplesincludehacksaw,diamondwheelrotarytool,etc. o Oncetheprobeiscut,trim/filethefreshcut.
Installtheprobepermountinginstructions.
 Coaxial(LVRD12Series)
Placetheprobeonasturdysurface.Measureandmarkthelocationforthecutonthecoaxialshield.
UnthreadthecoaxialshieldfromtheGWRsensor.
 

39
Page 40
APPENDIX SectionSeven
Measureandmarkthelocationforthecutontheexposedrod.
o Usethecoaxialshieldasaguidetoconfirmbothcutsareatthesamelength.
Cuttingtherod
o Securetherodtopreventitfrommovingduringcutting.
Besuretosecurethehousingtopreventitfrommovingwhentheprobeiscut.
o Useasawwithabladedesignedtocut316LSStocuttheprobe.
Examplesincludehacksaw,diamondwheelrotarytool,etc.Oncetheprobeiscut,trim/filethefreshcut.
o Attachaspacertotheendofprobe.
Offsetthespacerapprox.1/8”(3mm)fromtheendoftheprobe.Makesuretheremainingspacersarenofurtherthan39.4”(1m)apart.Secureretainingringsoneachsideofthespacer.
Cuttingthecoaxialshield
o Securethecoaxialshieldtopreventitfrommovingduringcutting. o Useapipecutterwithabladedesignedtocut316LSStocutthecoaxialshield.
Ahacksawcanbeusedtocutthecoaxialshieldifthepipecutteristoodifficult.Usetheinitialcutofthepipecutterasascorelineforthehacksaw.Oncethecoaxialshieldiscut,trim/filethefreshcut.
Slidethecoaxialshieldovertherodmakingsurenottomovethespacers.ThreadthecoaxialshieldtotheGWRsensor.
Installtheprobepermountinginstructions.
  
40
Page 41
APPENDIX SectionSeven
Cable(LVRD13Series)
Placetheprobeonasturdysurface.Measurethelocationforthecutonthecable.Wrapthecablewithelectricaltapealongtheareaofthecut.
o Thiswillpreventthecablefromfrayingwhilebeingcut.
Markthelocationofthecutontheelectricaltape.Loosenthe(¼–20,⅛Hex)setscrewsinthecounterweightandremovefromthecable.
Securethecabletopreventitfrommovingduringcutting.
o Besuretosecurethehousingtopreventitfrommovingwhentheprobeiscut.
Usingawirecutterorarotarytool,cutthecable.
o Oncetheprobeiscut,removethetapekeepingthecableintact.
Insertthefreshlycutcableintothecounterweightandtightenthe(¼–20,⅛Hex)setscrews.
Installtheprobepermountinginstructions.

41
Page 42
APPENDIX SectionSeven
FactorySettings:
 FromBottom
(Lowestpointofprobe)
ProbeStyle Sensor 4mA 20mA 4mA 20mA
Rod
(LVRD11Series)
Coaxial
(LVRD12Series)
Cable*
(LVRD13Series)
LVRD11
Series
LVRD11‐3FT
Series
LVRD11‐6FT
Series
LVRD12
Series
LVRD12‐3FT
Series
LVRD12‐6FT
Series
LVRD13Series
2.0”
(50.8mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
7.9”
(200.7mm)
114.8”
(2915mm)
32”
(812.8mm)
68”
(1727.2mm)
114.8”
(2915mm)
32”
(812.8mm)
68”
(1727.2mm)
219.1”
(5566mm)
(BottomofMountingNut)
(2966mm)
(862.6mm)
(1778.0mm)
(2966mm)
(862.6mm)
(1778.0mm)
(5145mm)
116.8”
34”
70”
116.8”
34”
70”
216.2”
FromTop
3.4”
(85.1mm)
3.4”
(85.1mm)
3.4”
(85.1mm)
3.4”
(85.1mm)
3.4”
(85.1mm)
3.4”
(85.1mm)
3.4”
(85.1mm)
Cable‐includescounter‐weight
Note:CableversionsoftheLVRD13seriesmustaccountforthecounterweightattachedtotheendofthe
probe.
Note:WhenclickingontheFactoryConfig.Buttonintheconfigurationsoftware,thiswillreturnthesensorto itsbasedfactoryconfigurationwhichisforthefulllengthsensor(i.e.LVRD11,LVRD12orLVRD13)andnotany oftheshorterlengthconfigurations(i.e.LVRD‐11‐3FT,LVRD‐12‐6FT,etc.).
Troubleshooting:
PROBLEM SOLUTION
NoLED
LEDflashesRed
Sensorislockedonalevel
abovethetruelevel.

Sensor is not receiving power (10 to 30 VDC).  Check wiring to the sensoraswellasthepowersupply. Sensorcannotacquireavalidlevelreading.Makesurethesensor is installed properly within the application and the probe is touching liquid. Sensorislikelyacquiringafalseechofromsomeinterferenceclose to theprobe.RunninganEmptySignalScanshouldaddressthisissue.
42
Page 43
43
Page 44
44
Loading...