Omega iDRX-ACC, iDRX-ACV, iDRX-FP, iDRX-TC, iDRX-ST, iDRX-PR, iDRX-RTD User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
User’sGuide
®
®
Shop on line at
omega.com
e-mail: info@omega.com
For Latest Product Manuals
omegamanual.info
iDRX-ACC,iDRX-ACV,iDRX-FP,
iDRX-PR,iDRX-RTD,iDRX-ST,
iDRX-TC
CommunicationManualfor
iDRXSignalConditionerSeries
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the mark to
every
appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors
it contains, and reserves the right to alter specifications without notice.
WARN ING: These productsarenotdesignedforusein,andshouldnotbeusedfor,patientconnectedapplications.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as it contains important information relating to safety and EMC.
This device is marked with the international Caution symbol. It is important to read
this manual before installing or commissioning this device as it contains important
information relating to Safety and EMC (Electromagnetic Compatibility).
Unpacking & Inspection
Unpack the instrument and inspect for obvious shipping damage. Do not attempt to
operate the unit if damage is found.
For instruments with AC Voltage and AC Current inputs, observe the input signal
connections in the appropriate section of this manual. These instruments must only
be installed by professional electricians.
•Do not exceed voltage rating on the label located on the instrument housing.
•Always disconnect power before changing signal and power connections.
•Do not use this instrument on a work bench without its case for safety reasons.
•Do not operate this instrument in flammable or explosive atmospheres.
•Do not expose this instrument to rain or moisture.
•Unit mounting should allow for adequate ventilation to ensure instrument does
not exceed operating temperature rating.
•Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to
minimize electrical shock hazards.
SAFETY CONSIDERATIONS
EMC Considerations
•Whenever EMC is an issue, always use shielded cables.
•Never run signal and power wires in the same conduit.
•Use signal wire connections with twisted-pair cables.
•Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems
persist.
Failure to follow all instructions and warnings may result in injury!
ii
I. WHAT SIGNAL CONDITIONERS DO:
The iDRX Series Signal Conditioners are high performance devices used as a front end for PLC’s and
Data Acquisition systems to measure a variety of low level transducer signals with high precision and
accuracy. The iDRX Series Signal Conditioners interface directly to transducers and digitize the input
signal. The measured signal is then transmitted to a PLC or a computer using the RS485 Serial
Communication. Up to 32 units may be connected to the same serial RS485 bus, and each unit
may be addressed to transmit the signal being measured under program control, executed on a PLC
or a computer. The key features of the iDRX Series Signal Conditioners are the ease of set-up and
factory calibrated ranges. All range switching are done electronically by sending the appropriate
command; therefore, there is no need to remove or open the units when signal input levels are
changed. All set-up may be done by using the Set-up Software running on a computer or by user
supplied programs.
Communication with the UNIT will be performed via serial communication using RS485 standard (half
duplex). To use the RS485 communication for the Signal Conditioners you’ll need an available
Communication port in your computer and have access to a generic communication software program
1
(e.g.: Procomm
conditioner communication software program is also available as an option to speed the set-up. A
RS232 to RS485 converter box will also be required if your computer communications port is RS232.
1
Procomm is a registered trademark of Datastorm Technologies, Inc.
2
Windows is a registered trademark of Microsoft Corp.
3
HyperTerminal is a registered trademark of Microsoft Corp.
, Windows2HyperTerminal3, etc, see details below for information). A RS485 signal
Page 1
For Procomm:
Start the Procomm Program.
Press ALT + P (Select the appropriate communication parameters: Baud Rate, Parity, Data
Bits, Stop Bits.) The default settings may require modifications.
- Factory Default communication settings are as follows:
Baud Rate = 9600
Parity = Odd
Data Bits = 7
Stop Bits = 1
Press ALT + S (To save current communication settings)
Press ALT + O (To go to chat mode)
If the communication port selected is available and the communication parameters of both the
computer and the iDRX are matched, then a serial link may be established. To check the
communication any of the commands may be tried i.e. *01X01 would return the current
measured signal value.
For Hyper Terminal (Windows 95):
Start the Hyper Terminal Program from programs/accessories.
Click on the Properties from the File menu.
Under the Phone Number Menu choose:
Connect using “Direct to COM1 or COM2” whichever that’s available.
Click on Configure Button.
Choose:Baud rate, Data bits, Parity and Stop bits
According to iDRX’s settings.
Flow Control = None.
Click “OK” Button.
- Factory Default communication settings are as follows:
Baud Rate = 9600
Parity = Odd
Data Bits = 7
Stop Bits = 1
Under Settings Menu:
Click ASCII Setup Button.
Choose all options except “Force Incoming Data to 7 Bits ASCII”.
Click “OK” Button.
Page 2
Communication Parameter Settings:
Communication settings information are very critical during set-up, if any of the parameters are
changed, it should be recorded on the label for future reference. If the communication parameters
used by the computer does not match the communication parameter of the iDRX, then the
communication link may not be established. Hence it is important to record the communication
parameter on the label if different from default.
Resetting Communication Parameters to Factory Defaults
To restore the communication parameters to the factory default settings, two test points must be
shorted together. There are two ways of shorting these test points together, both are detailed below
and shown in the following figure.
Version A-- Test point TP6 must be shorted, by a wire, to test point TP17.
or
Version B-- Newer units have a jumper position S1-A for connecting these two test points together.
Factory Default Settings for Communication:
Baud Rate = 9600
Data Bit = 7
Parity = Odd
Stop Bits = 1
Recognition Character = *
Address = 01
Page 3
Open the Signal Conditioner Unit
Disconnect all signal input and outputs before attempting this procedure.
Instructions
1) To open the Signal Conditioner Unit—Remove Side Covers from Unit by removing 4 screws, using
a Phillips head screwdriver.
2) Short TP6 & TP17 together, either by wire or
, if available, jumper S1-A.
3) After shorting TP6 to TP17, apply power to the unit.
4) The Front Panel Power Indicator (LED) will NOT
turn on.
5) After power has been applied to the unit for about 3 seconds, remove jumper S1-A or open the TP6
& TP17 connection without turning off the power.
Opening Unit
Solder wire from
TP6 to TP17 on
solder side of board.
Version A Testpoint/Jumper LocationsVersion B
Install Jumper onto
S1-A on component
side of board.
6) The communication parameters now have been restored to the default settings temporarily in
RAM memory. (If power is removed from the unit, the RAM memory will be lost and the
communication parameters will be lost.)
Page 4
7)To read the default communication parameters, type the following command using
HyperTerminal or some other terminal communication program.
^AE01
8)The unit will respond with the following ASCII characters depending on the model of iDRX
unit.
PR/FP/STTC/RTD/ACV/ACC
2A011C0D2A01140D
9)The ASCII response is decoded below:
2A = Recognition Character = *
01 = Unit Address = 01
1C = Command Mode, Multipoint Address, Echo ON, Checksum OFF, Line Feed OFF
0D = 9600 Baud, Odd Parity, 7 Data Bits, 1 Stop Bit
10)To permanently write the above default communication parameters to EEPROM send the
following sequence of commands:
*01W0B2AUnit Response = 01W0B
*01W0A01Unit Response = 01W0A
*01W081CUnit Response = 01W08
*01W070DUnit Response = 01W07
*01Z01Unit Response = 01Z01 LED on iDRX unit will blink
11)The default communication parameters are now permanently stored in the unit’s EEPROM
and will not be lost upon power removal.
12)Use the iDRX Set-up Program to establish communication with the unit.
13)This procedure will not affect calibration. It only resets the communication parameters to the
factory default settings.
Page 5
IV. COMMANDS FOR ACCESSING EEPROM:
NO.command letter indexmeaning# of bytes
1.R,W01Input range or function1
2.R,W02Input/output Configuration1
3.R,W03Decimal point1
4.R,W04Filter time constant1
5.R,W05Reading Scale3
6.R,W06Reading Offset3
7.R,W07Communication parameters1
8.R,W08Communication bus format1
9.R,W09Communication Data format1
10.R,W0ACommunication device address1
11.R,W0BCommunication recog. char.1
12.R,W0CUnit of measure3
13.R,W0DGate time1
14.R,W0EDebounce time1
15.R,W0FTransmit time2
16.R,W12Reading Scale (iDRX-PR)3
17.R,W13Reading Offset (iDRX-PR)3
NOTE:
1. Data (Number of hex digits) = 2 * number of bytes
2. command letter
meaning
RRead from EEPROM
W Write to EEPROM
3."W" commands should be followed by "Z01" command for new values to take
effect.
A. COMMAND FORMAT (TRANSMITTING):
*[nn]Cxx[data][hh]<cr>
Note:
Data is required if Command Letter is “W”
B.RESPONSE FORMAT (RECEIVING):
A.Correct response :
1.If unit is in echo mode
[nn]Cxx[data][hh]<cr>
*echo mode = unit will send back the command.
* (see "BUS FORMAT") :
Page 6
2. If unit is not in echo mode :
i.For the commands which require the data to be transmitted by the iDRX Signal
Conditioner, data is sent in the following formats:
data[hh]<cr>
ii. For the commands which do not require the data:
NO RESPONSE
B.Error response:
NOTE :
1. If unit is in echo mode
:
[nn]?ee<cr>
2. If unit is not in echo mode
:
?ee<cr>
[ ]:Means will be used wherever applicable.
*:Is the security recognition character(default is “*”).
nn:Is the unit's address in hexadecimal(default is 01).
Address may be from 01 to FF.
C:Is the command letter ( must be capital ).
W:For writing to the EEPROM (requires data)
R:For reading from the EEPROM (doesn’t require data)
xx:Command index is a hexadecimal number from 01 to FF.
data:Is one, two, or three bytes (2,4,6 characters respectively). It will be in
hexadecimal format except when command "X" is executed in which case it
is in decimal format.
hh:Is checksum characters
( Required if Checksum option is on. See “BUS FORMAT”).
The checksum is one byte (two characters) that is the simple hexadecimal
addition of all the previous bytes, ignoring any overflow.
Page 7
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.