Omega HHM250 User guide

Page 1
omega.com
For latest product manuals:
omegamanual.info
User’s Guide
HHM250
AC Clamp Meter
Shop online at
Page 2
Servicing North America:
U.S.A.: Omega Engineering, Inc. One Omega Drive, P. O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047 USA
Toll-Free: 1-800-826-6342 Tel: (203) 359-1660 FAX: (203) 359-7700 e-mail: [email protected]
Canada: 976 Bergar
Laval (Quebec), Canada H7L 5A1 Toll-Free: 1-800-826-6342 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: [email protected]
For immediate technical or application assistance:
U.S.A. and Canada: Sales Service: 1-800-826-6342/1-800-TC-OMEGA
®
Customer Service: 1-800-622-2378/1-800-622-BEST
®
Engineering Service: 1-800-872-9436/1-800-USA-WHEN
®
Mexico: En Espan˜ol: 001 (203) 359-7803 FAX: (001) 203-359-7807
Servicing Europe:
Benelux: Managed by the United Kingdom Office
Toll-Free: 0800 099 3344 TEL: +31 20 347 21 21 FAX: +31 20 643 46 43 e-mail: [email protected]
Czech Republic: Frystatska 184
733 01 Karviná, Czech Republic Toll-Free: 0800-1-66342 TEL: +420-59-6311899 FAX: +420-59-6311114 e-mail: [email protected]
France: Managed by the United Kingdom Office
Toll-Free: 0800 466 342 TEL: +33 (0) 161 37 29 00 FAX: +33 (0) 130 57 54 27 e-mail: [email protected]
Germany/Austria: Daimlerstrasse 26
D-75392 Deckenpfronn, Germany Toll-Free: 0 800 6397678 TEL: +49 (0) 7059 9398-0 FAX: +49 (0) 7056 9398-29 e-mail: [email protected]
United Kingdom: OMEGA Engineering Ltd.
ISO 9001 Certified One Omega Drive, River Bend Technology Centre, Northbank
Irlam, Manchester M44 5BD England Toll-Free: 0800-488-488 TEL: +44 (0)161 777-6611 FAX: +44 (0)161 777-6622 e-mail: [email protected]
OMEGAnet®Online Service Internet e-mail
It is the policy of OMEGA Engineering, Inc.to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, human applications.
Page 3
TABLE OF CONTENTS
1.
SAFETY INFORMATION....................................................... 1
2.
GENERAL SPECIFICATION................................................. 1
3.
ELECTRICAL SPECIFICATION........................................... 2
3-1
DIRECT VOLTAGE..................................................................... 2
3-2
ALTERNATING VOLTAGE ........................................................... 2
3-3
ALTERNATING CURRENT ........................................................... 2
3-4
RESISTANCE(Ω)....................................................................... 3
3-5
CONTINUITY( )...................................................................... 3
3-6
FREQUENCY HZ ....................................................................... 3
4.
DESCRIPTION OF THE INSTRUMENT ............................. 4
4-1
DESCRIPTION OF THE DISPLAY ................................................... 4
4-2
DESCRIPTION OF FRONT AND REAR ............................................ 5
5.
BUTTON INSTRUCTION....................................................... 6
5-1
HOLD FUNCTION .................................................................... 6
5-2
INRUSH FUNCTION ................................................................ 6
5-3
BACKLIGHT FUNCTION .......................................................... 6
6.
MEASURING INSTRUCTION............................................... 6
6-1
AC VOLTAGE MEASUREMENT.................................................... 6
6-2
DC VOLTAGE MEASUREMENT ................................................... 7
6-3
AC CURRENT MEASUREMENT ................................................... 7
6-4
RESISTANCE MEASUREMENT..................................................... 8
6-5
CONTINUITY MEASUREMENT ..................................................... 8
6-6
MEASUREMENT OF THE VOLTAGE FREQUENCY........................... 9
6-7
MEASUREMENT OF THE CURRENT FREQUENCY .......................... 9
7.
BATTERY CHANGING .......................................................... 9
8.
MAINTENANCE..................................................................... 10
Page 4
Clamp Meter
1. SAFETY INFORMATION
Do not operate the tester if the body of meter or the test lead look broken. Check the main function dial and make sure it is at the correct position before each measurement. Do not perform resistance and continuity test on a live power system. Do not apply voltage between the test terminals and test terminal to ground that exceed the maximum limit record in this manual. Keep the fingers after the protection ring when measuring through the test lead. Chang the battery when the data.
Environmental Conditions
Operation Temperature: 0°C to 40°C(32°F to 104°F); < 70 % RH Storage Temperature: -10°C to 60°C(14°F to 140°F); < 80 % RH
Explanation Symbols
Attention refer to operation Instructions.
Dangerous voltage may be present at terminals.
This instrument has double insulation.
Approvals:
EN61010 600V CAT III
symbol appears to avoid incorrect
2. GENERAL SPECIFICATION
Digital Display:
4 digital liquid crystal(LCD), Maximum reading 6600.
Polarity:
When a negative signal is applied, the
Low Battery Indication:
When the battery is under the proper operation range, on the LCD display.
Sample Rate:
3 times/sec for digital data.
signal appears.
will appear
1
Page 5
Clamp Meter
Power Source:
1.5V size AAA battery X 2 Typical battery Life: 50 hours (without buzzer, backlight function)
Auto Power Off:
If there is no key or dial operation for 15 minutes, the meter will power itself off to save battery consumption. This function can be disabled by
press and hold the “
” button then power the unit on.
Over Load:
When the signal larger than the maximum will be show
.
Maximum jaw opening:
∅ 25 mm
Dimensions:
210 x 62 x 36 mm
Weight:
273g (with battery)
Accessories:
Carrying case, Batteries, Test Lead & Instruction Manual.
3. ELECTRICAL SPECIFICATION
Accuracy is to within ± [% of the reading + number of counts (cts)] in the reference conditions indicated in the appendix.
3-1 Direct Voltage
Range Resolution Accuracy
600 V 0.1 V
Input impedance: 1 MΩ
3-2 Alternating Voltage
Range Resolution Accuracy
600 V 0.1 V
Input impedance: 1 MΩ
3-3 Alternating Current
Range Resolution Accuracy
66 A 0.01 A
660 A 0.1 A
1% ± 2dgts
1.2% ± 5dgts
1.9% ± 5dgts
2
Page 6
3-4 Resistance (Ω)
Range Resolution Accuracy
660 Ω 0,1 Ω
1% ± 2dgts
3-5 Continuity
Range Resolution Accuracy
Ohm function Buzzer<30
3-6 Frequency Hz
Input impedance: 100 kΩ
For current:
Range Resolution Accuracy Sensitivity 660Hz 0.1 Hz
6.6KHz 0.001KHz 30KHz 0.01KHz
0.2% ±1 dgt
For voltage:
Range Resolution Accuracy Sensitivity 660Hz 0.1 Hz
6.6KHz
66KHz
100KHz
0.001KHz
0.01KHz
0.1KHz
0.2% ±1 dgt
Clamp Meter
Ω
3 Arms
5 Vrms
3
Page 7
Clamp Meter
4. DESCRIPTION OF THE INSTRUMENT
4-1 Description Of The Display
Auto power off indication
Polarity indication
Low battery indication
Alternative source indication
Direct source indication
Current measurement indication
Voltage measurement indication
Data hold indication
INRUSH Current Indication
Continuity test indication
Measurement unit
Resistance measurement indication
Frequency measurement indication
4
Page 8
4-2 Description Of Front And Rear
1
Clamp Meter
2
4
5
7
I
3
6
10
98
61010600
1.5VX2
1
Current Sensing Clamp
○
2
Clamp opening handle
○
○3 Function select dial
4
Inrush button
○
5
Backlight button
○
6
Data hold button
○
7
LCD display
○
8
COM input terminal
○
9
Positive input termina
○
10
Battery cabinet
○
5
Page 9
Clamp Meter
5. BUTTON INSTRUCTION
5-1 HOLD Function
It i
s possible to freeze the value displayed by pressing on the
OLD" button. To deactivate this function, press the "HOLD"
"H button a s
5-2 INRUSH F
In ACA range, pre INRU SH mode . Then LCD display “ - - - - until the motor starts
econd time.
unction
ss INRUSH button will force meter to enter
” up and is detected (10A above). The detection will be done only one tim e and the out put reading w ill be held. When done, p ress IN
RUSH button could enter INRUSH mode again. To exit INRUSH
mode, pres
s INRUSH button more than one second. Enter INRUSH mode in automatic ACA range will force the range be locked in higher one.
-3 BAC
KLIGHT Function
5
“
If yo
u press on the
function.(The b
ll light for 1 minutes)
it wi
u press on the
If yo
acklight is blue light. When you turn on this function,
“
utton, i
”
b
t will turn on the backlight
button again, the function will be turned
”
off.
6. MEASURING INSTRUCTION
6-1 AC Voltage Measurement:
Swi
tch the main function selector
range.
to Connect r
ed test lead to “ + terminal and black one to the “ C
OM terminal.
” Measure the voltage by touching the test lead tips to the test circuit where the value of voltage is needed. Read the result from the LCD
anel.
p
”
ICATI
I
600V
6
Page 10
Clamp Meter
6-2 DC Voltage Measurement:
Swi
tch the main function selector
to
range.
Connect r
ed test lead to “ + ”
terminal and black one to the
”
OM terminal.
“ C Measure the voltage by touching the test lead tips to the test circuit where the value of voltage is needed.
I
CATII 600V
Read the result from the LCD
anel.
p
AC Current Measurement:
6-3
tch the main function selector to
Swi
range. Open the clamp by pressing the jaw-opening handle and insert the cable to be measured into the jaw. Close the clamp and get the reading from the LCD panel.
ote:
N
efore t
his measurement, disconnect the test lead with the meter
B
r safety.
fo In some occasion that the reading is hard to read, push the HOLD
nd read the result later.
utton a
b
CORRECT
C
A
6
T
0
I
0
I I
V
INCORRECT
I
ICATI
600V
7
Page 11
Clamp Meter
6-4 Resistance Measurement
Swi
tch the main function to Connect r and b Connect t points wh is n
ed test lead to “ + ” terminal
lack one to the “COM” terminal.
ip of the test leads to the
ere the value of the resistance
eeded.
range.
Read the result from the LCD panel.
ote:
N
hen taking resistance readings from a
W circuit sys cut o
tem, make sure the power is
ff and all capacitors need to be
discharged.
-5 Contin
6
uity Test With Buzzer:
Swi
tch the main function to Connect r “ COM ”
Connect t
ed test lead to
termi
nal.
ip of the test leads to the points where the conduction
range.
terminal and black one to the
“ + ”
condition needed.
he resistance is under 30Ω, the beeper will sound continuously.
f t
I
Beepe
Short circuit Open circuit
8
Page 12
Clamp Meter
6-6 Measurement Of The Voltage Frequency
Swi
tch the main function to Connect r and b Pla ce the p robes in cont act w ith the poi nts wher e fre quency i s to be measured. Read the result on the LCD panel.
Measurement Of The Current Frequency
6-7
Swi Open the clamp by pressing the trigger. Encircle the conductor and close the j Read the result on the LCD panel.
ed test lead to “ + ” terminal
lack one to the “ COM ” terminal.
tch the main function to
correctly by releasing the trigger.
aws
range.
range.
7. BATTERY CHANGING
When the battery voltage drops below proper operation range the symbol will appear on the LCD display and the battery needs to be
hanged.
c
efore changing the battery, switch t he mai n d ial to “ OFF ” and
B disconnect t Open t Replace t Close t
est leads.
he back cover by a screwdriver.
he old batteries with two new 1.5V (AAA Size) battery.
he back cover and fasten the screw.
9
Page 13
Clamp Meter
8. MAINTENANCE
WARNING!
Before opening the meter, disconnect both test lead and never use
e meter before the cover is closed.
th
CAUTION!
T
o avoid contamination or static damage, do not touch the circuit
bo
ard without proper static protection.
8-
1 REMARK:
If the meter is not going to be used for a long time, take out the
battery and do not store the meter in high temperature or high humidity environment.
When taking current measurement, keep the cable at the center of
the clamp to get more a ccurate test result.
Repairs or servicing not covered in this manual should be performed
only by qualified personal.
8-
2 CLEANING:
Periodicall so
y wipe the case with a dry cloth. Do not use abrasives or
lvents on these instruments.
10
Page 14
Clamp Meter
NOTES:
11
Page 15
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibra­tion; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of pur­chaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY
RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which
the product was PURCHASED,
2. Model and serial number of the product
under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the
COST of the repair,
2. Model and serial number of the
product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2008 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
Page 16
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
SM
TEMPERATURE
䡺⻬
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
䡺⻬
Wire: Thermocouple, RTD & Thermistor
䡺⻬
Calibrators & Ice Point References
䡺⻬
Recorders, Controllers & Process Monitors
䡺⻬
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
䡺⻬
Transducers & Strain Gages
䡺⻬
Load Cells & Pressure Gages
䡺⻬
Displacement Transducers
䡺⻬
Instrumentation & Accessories
FLOW/LEVEL
䡺⻬
Rotameters, Gas Mass Flowmeters & Flow Computers
䡺⻬
Air Velocity Indicators
䡺⻬
Turbine/Paddlewheel Systems
䡺⻬
Totalizers & Batch Controllers
pH/CONDUCTIVITY
䡺⻬
pH Electrodes, Testers & Accessories
䡺⻬
Benchtop/Laboratory Meters
䡺⻬
Controllers, Calibrators, Simulators & Pumps
䡺⻬
Industrial pH & Conductivity Equipment
DATA ACQUISITION
䡺⻬
Data Acquisition & Engineering Software
䡺⻬
Communications-Based Acquisition Systems
䡺⻬
Plug-in Cards for Apple, IBM & Compatibles
䡺⻬
Datalogging Systems
䡺⻬
Recorders, Printers & Plotters
HEATERS
䡺⻬
Heating Cable
䡺⻬
Cartridge & Strip Heaters
䡺⻬
Immersion & Band Heaters
䡺⻬
Flexible Heaters
䡺⻬
Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
䡺⻬
Metering & Control Instrumentation
䡺⻬
Refractometers
䡺⻬
Pumps & Tubing
䡺⻬
Air, Soil & Water Monitors
䡺⻬
Industrial Water & Wastewater Treatment
䡺⻬
pH, Conductivity & Dissolved Oxygen Instruments
M4655/1108
Loading...