Omega FSW-6000, FSW-7000 User guide

Page 1
User’s Guide
Shop online at
omega.com
For latest product manuals:
www.omegamanual.info
SM
FSW-6000/FSW-7000 Series
Flow Switches
Page 2
Servicing North America:
U.S.A.: Omega Engineering, Inc.
Toll-Free: 1-800-826-6342 (USA & Canada only) Customer Service: 1-800-622-2378 (USA & Canada only) Engineering Service: 1-800-872-9436 (USA & Canada only) Tel: (203) 359-1660 Fax: (203) 359-7700 e-mail: [email protected]
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
Page 3
Contents
Introduction
Models&Dimensions .........................................5
WiringDiagram ..............................................6
FSWRelayStatusGuide ......................................8
Pre-Installation ..............................................9
Installation .................................................10
Calibration .................................................11
Handling ..................................................13
TechnicalSpecifications ......................................14
TroubleShooting ............................................16
.................................................4
www.omega.come-mail:[email protected]
03
Page 4
®
Introduction
FSW6000/7000
ThermalDispersionFlow SwitchMonitor
The
FSW series of thermal flow switches is designed to monitor flow status of liquids and
gases
and can also be usedto detect level.
Achain of 8LED's gives the user a visual indicationof the flow status of the switch. There are two red LEDs that indicatewhether or not the unit has detected flow, a yellow LED to indicate the set point (for increasing or decreasing flows) and 5 green LEDs that indicate the amount of flow beyond the set point of the unit. The FSW also includes a di-chromatic (red/green) LED which showsthe switch point statusof the unit.
The sensing element and connection of the FSW are made with 316 S.S. and can be coated when necessary .The enclosure is offered in either nylon oraluminum.
All models can be ordered with a great variety of threaded, flange, or sanitary process connections as wellas ECTFE or epoxycoating for aggressive mediums.
For ECTFE coating we recommend that the switches are made with flanged connections or a minimum of1” threaded connection.
Features
Simpletoinstall. Excellentlowflowsensitivity. Nomovingparts-maintenancefreereliabity. Canbecoatedforaggressivemediums. Maximumworkingpressureof1450PSI(100bar). Fastresponsetimeforfloworlevel(Adjustablefrom1-10seconds). Avaliableinthreaded,sanitaryandadjustableinsertionlengthconnections.
04
Page 5
MountingOptionsforFSW
ModelsandDimensions
NylonHousing
89mm
76mm
80mm
Aluminum Housing
89mm
126mm
ExtendedNecksforHigherTemperatures
UltraHightemp.neckw/ heatdissipatingrings
100mm
50mm
MT-Medium (upto120ºC) A
T-HighTemperature(upto150ºC)
Temperature
HT-UltraHightemperature(upto250ºC)
InsertionLength
FSWw/insertion
lengthof35mm
½” NPT
12mm
35mm
FSWw/insertion
lengthof50mm
1” NPT
12mm
50mm
Otherinsertionlengthsareavailableuponrequest
FSWw/insertion
lengthof75mm
3/4” NPT
75mm
12mm
AluminumHousing
130mm
130mm
FSWforUltraHightemperaturew/
minimuminsertionlengthof100mm
HTATMT
100mm
100mm
118mm
1” NPT
45mm
ProcessConnections
ThreadedConnections
½”
3/4”
”
1
1½”
NPT
1,75
BSP
www.omega.come-mail:[email protected]
Tri-ClampConnection FlangeConnections
1”
1½”
2”
2½”
TCConnection
RubberSeal
ProcessConnection
1”
1½”
2”
2½”
RF
FF
ANSI150# ANSI300#
05
Page 6
WiringDiagram
FSW6000- ACPowered
Bargraph(B1)
®
NylonHousing
M12ConnectorOptional
StandardConnectionw/
2metersofCable
FSW7000-DCPowered
Adjust
Adjust
CentralLED(L1)
(Red/Green)
Adjust(P1)
Red
Black
Green(NC)
Blue(common)
White(NO)
Greenand
Yellow
orsolid Yellow
Bargraph(B1)
CentralLED(L1)
(Red/Green)
Power Supply
Ground
1
2
Connector
12mm
Contacts
M12ConnectorOptional
1
2
NOorNC
contact
1
-PowerSupply 2­3-NOContact 4-NCContact 5-
NOorNC
contact
2
3
5
4
2000mm
PowerSupply
Common
2
3
5
4
1
_
1
+
06
_
+
Adjust(P1)
1
-PowerSupply(+)
2- (-)
PowerSupply 3-Ground 4-NOContact
Connector
12mm
2000mm
1
-PowerSupply(+)
2- (-)
PowerSupply 3-NOContact 4-NCContact 5-
Common
5-Common 6-
NCContact
Page 7
FSW6000/7000with Aluminum-Housing
(P1)-SetPointPotentiometer Adjust
WiringDiagram
(B1)-8LED´s
(L1)-CentralLED-Green:Withflow
Small
1
-PowerSupply(+)
2- (-)
PowerSupply 3-Ground 4-NOContact 5-Common 6-
NCContact
Bargraph
Aluminum
:RedLED
YellowLED GreenLED
Red:Noflow
(
)
(
)
Large Aluminum
(
-PowerSupply(+)
1
PowerSupply
2- ( 3-Ground 4-NOContact 5-Common 6-
NCContact 7-NOContact 8-Common 9-NCContact
)
(
)
-)
1 2 3 4 5 6
_
+
100%0
Flow
1 234
+
-
5 6
7 9
Adjust
8
CentralLED(L1)
Red/Green
1SPDT
Adjust(P1)
Bargraph(B1)
Bargraph(B1)
2SPDT
CentralLED(L1)
Red/Green
Adjust(P1)
www.omega.come-mail:[email protected]
07
Page 8
FSWRelayStatusGuide
®
Application
FSH
Application
FSL
Condition
Normal
Alarm
Condition
Normal
LEDStatus
RED
GREEN
LEDStatus
GREEN
SetPoint
OFF
ON
SetPoint
ON
FSWSPDT
Status
NO(4)
C(5)
NO(4)
C(5)
FSWSPDT
Status
NO(4)
NC(6)
NC(6)
NC(6)
08
Alarm
RED
OFF
NO(4)
C(5)
NC(6)
C(5)
Page 9
Pre-Installation
®
Pre-Installation Checks:
1)
Its recommended that the flow switch is installed with bent where the flow enters and 5x times the diameter of the pipe where the flow exits, enabling it to havean accurate reading (Fig.1).
Verify that the installation point isn’t near any connections, valves, elbows or anything similar, this can cause errors in the reading of the probe due to turbulencein the pipe.
2) It isimportant that theflow switch isnot installed at the highest point in the pipe run or in a location where there is the risk of air accumulating in the pipe. Keep in mind that the ideal mounting location is where the pipe is always full. This will ensure that the switch is always immersed in the flow. (Fig. 2 correct, fig. 3 incorrect)
3) In pipes that have pressure pumps or retention valves, we recommend that the probe be installed before the pump due to the fact that it will have less turbulence. (Fig.4)
a distance of ½ a meter of the pipe
Fig.1
Fig.2
Fig.3
Fig.4
1/2m
5xØ
4) Confirm that the wire connections are correct and that the available power supply is compatible with the FSWunit.
5) Verify that the operating pressure and temperature of the process corresponds to the operating p arameters of the FSW unit.
More recommendations and handling instructions can be foundon page 14.
www.omega.come-mail:[email protected]
Pump
09
Page 10
Installation
Installation:
The FSW may be installed in a pipe using a “T”connection (see the pipe (see fig. 2). The site might need to adapt the installation so that it conforms with the following recommendations.
The FSW is not affected by its fixed position so it may be installed at any angle around the pipe. However we recommendthat when thepipe is in a horizontal position theFSW should beinstalled on the side, as long as the tip of the probe sits within the middle ofthe pipe (See Fig. 2).
When the pipeis in a verticalposition, the FSW
should be installedonly when the waterflow is upward (See Fig.3).
fig. 1) or inserted directly into
Fig.1
FlowSwitchwith “T” connection
Fig.2
Fig.3
®
Care should betaken when installing the FSWthat the probe extends to the center of the pipe away from the internal wall andis fully immersed into the flow ( Fig. 4 and 5 incorrect, Fig.1 and 2 are correct).
In pipes with smaller diameters use an adaptor to enlarge the diameter of the pipe so that the sensor can be properly installed (See Fig. 6). If the installation is not correct the FSW’s performance may be affected.
10
Fig.4
Incorrect
Fig.5
Fig.6
Page 11
Calibration
T
o Start:
1 - Removethe enclosure lid (Note:the screws are self-retaining) 2
Start the power supply and wait 5 minutes until the FSW is active and has reached a
­stable point withinthe medium.
3 - Letthe regular or desiredflow reach its point of normal operation.
Calibration for Flow/ No Flow:
1 - Setthe flow rate atthe normal range of operation. 2 - Turn the potentiometer counter-clockwise until thecentral LED turns red. 3 - With the central LED red, turn the potentiometer clockwise until the central LED
changes to ablinking green state.
4 - Continue to turn the potentiometer clockwise until all green LEDs in the bar graph are
on.
5 - In order to be sure that the adjustment is not at a critical state give the potentiometer
an additional quarterturn clockwise.
Set Point Adjustment:
The flow switch can beadjusted to indicate either increasing flow, or decreasing flow at a specific set pointwithin 3cm/s to 3m/s. It is important to determine the specific set point at which the flow switch should activate or de-activate.
Adjust
SetPoint
0%
BARGRAPH-LightsON
BARGRAPH-LightsON
100%
www.omega.come-mail:[email protected]
0%
SetPoint
Adjust
100%
BARGRAPH-LightsOFF
BARGRAPH-LightsOFF
11
Page 12
Calibration
T
o Activate The Switch OnIncreasing Flow:
1 - Set the flowrate to the desired set point and allow it to stabilize for 2minutes. 2 - Turn the potentiometer counter-clockwise until thecentral LED turns red. 3 - Turn the potentiometer clockwise until thecentral LED changes toa blinking green. 4 - Continue to turn the potentiometer clockwise until the first 2 green LEDs in the bar
graph turn on.
In this mode the FSW will activated on or above the set point. If there is a decrease of flow, the FSW will de-activate. When the flow rate reaches the set point, the FSW will activate.
To De-Activate The Switch On Decreasing Flow:
1 - Set the flowrate to the desired set point and allow it to stabilize for 2minutes. 2 - Turn the potentiometer clockwise until thecentral LED is blinkinggreen. 3 - Turn the potentiometer counter-clockwise until thecentral LED turns red. 4 - Continue to turn the potentiometer counter-clockwise until the 2 red LEDs in the bar
graph are off.
In this mode the FSW will de-activate on or below the set point. If there is an increase of flow the FSW will activate. When the flow rate reaches the set point, the FSW will de­activate.
Detecting level:
1 - Fill the tank until the probe of the FSW is fully submerged. Turn the potentiometer
counter-clockwise until the central LED turns red. With the central LED red, turn the potentiometer clockwise untilthe central LED changesto a blinking green.
2 - Continueto turn potentiometer clockwiseuntil all green LEDs in the bar graph turn on. 3 - In order to be sure that the adjustment is not at a critical state give the potentiometer
an additional quarterturn clockwise.
12
Page 13
Handling
Sealthethreadwith Teflontapebefore installation(Fig.1).
Donotturnorhandlebythehousing(Fig.2).
Usethecorrecttoolduringinstallation(Fig.3)
The FSW should not be dropped or suffer any impact or fall that could damage the electronics or the thermal tipsof the probe (Fig.4 and 5).
Periodic visual inspection of the FSW is required to check for corrosion or deposit build-up. If deposits are found, clean the sensor to ensure optimum performance.
Care should be taken when handling and installing probes
with coated rods to avoid scratching them. Scratching the coating could interfere with the probe performance.
When cleaning the rod use a soft brush or any other similar object.
Fig.1
Fig.2
Fig.3
Fig.4
www.omega.come-mail:[email protected]
Fig.5
13
Page 14
TechnicalSpecifications
®
FSW6000
Adjust
NylonHousing
Application
OperatingV
oltage
CurrentConsumption
Output
SetPointRange
Accuracy
Repeatability
Response Time
Gradient Temperature
FlowRateIndication
1 2 3 4 5 6
_
+
Adjust
1 234
+
100%0
Flow
5 6
8
7 9
-
AluminumHousingAluminumHousing
Flowforliquidsandgaslevelforliquidsonly
85-240Vac(50/60hz)or125Vdc
+/-100mA
Relay(SPDT)5A -250VacforNylonandSmall AluminumHousing
(2SPDT Large AluminumHousing)
Liquid:3cm/sto3m/s-Gas:5cm/sto5m/s
+/-10%
+/-1%setpoint
1to10s
15ºC/min
Redled-flowisbelowsetpoint
Yellowled-flowisatsetpoint
Greenled-flowisabovesetpoint
EnclosureMaterial
ElectricalConnection
ProcessConnection
WettedMaterial
Operating Temperature
MaxPressure
ClassProtection
14
Glassfillednylon(option- Aluminum)
Cableglandw/2000mmcable,M12connectoror½” NPT
½” to11/2” BSP orNPT,adjustable,sanitaryorflangedconnections
316StainlessSteel
14to176ºF(-10to80ºC)sanitaryoptionto248ºF(120ºC)
1450PSI(100Bar)/4500PSI(300Bar)uponrequest
IP 65
Page 15
FSW7000
TechnicalSpecifications
Adjust
_
+
NylonHousing
Application
OperatingV
oltage
CurrentConsumption
Output
SetPointRange
Accuracy
Repeatability
Response Time
Gradient Temperature
FlowRateIndication
1 2 3 4 5 6
_
+
Adjust
Flowforliquidsandgaslevelforliquidsonly
Relay(SPDT)5A
Liquid:3cm/sto3m/s-Gas:5cm/sto5m/s
100%0
Flow
5 6
8
1 234
7 9
+
-
AluminumHousingAluminumHousing
24Vdc(+/-10%)
+/-100mA
-250VacforNylonandSmall AluminumHousing
(2SPDT Large AluminumHousing)
+/-10%
+/-1%setpoint
1to10s
15ºC/min
Redled-flowisbelowsetpoint
Yellowled-flowisatsetpoint
Greenled-flowisabovesetpoint
EnclosureMaterial
ElectricalConnection
ProcessConnection
Cablegland-1/2” NPT conduitentryorM12connector
½” to11/2” BSP orNPT,adjustable,sanitaryorflangedconnections
WettedMaterial
Operating Temperature
MaxPressure
14to176ºF(-10to80ºC)sanitaryoptionto248ºF(120ºC)
1450PSI(100Bar)/4500PSI(300Bar)uponrequest
ClassProtection
www.omega.come-mail:[email protected]
Glassfillednylon(option- Aluminum)
316StainlessSteel
IP 65
15
Page 16
TroubleShooting
®
Fault
Relaydoesnot
changestate.
Flowswitch
turnsonor
of
fsuddenly
Relayremains
closed
Cause
LEDoff,nopower
LEDdoesn’tchangecolor
Radiofrequency
interference
Sensorispotentialy
defective
Solution
Checkpowersupply
Check theinstallation
(insertion length)
Verify thecalibration
Usearmoredcable
andshieldedhousing
ContactOmegaoryour
localrepresentativefor
furtherinstruction
16
Page 17
Page 18
M-3993/1014
Loading...