INTRODUCTION / TABLE OF CONTENTS Step One
Offered in liquid and gas sensor types, the general purpose flow switch provides reliable low or no‐ flow
detection of relatively clean, non‐ coating media with one 1A relay output. Liquid examples in clued water and
acetic acid. Available in Polypropylene‐ PPS or PVDF, the short flow sensor is used in pipe or ducting from ½”
to 1‐ 1/2”, and the long flow sensor is used in 2” and up. The flow switch set point may be adjusted from 0.,04
to 3 fps in liquids or 1 to 90 fps in gases as a low‐ flow alarm. The flow sensor is best applied in applications
with relatively constanttemperatures.
New Features
Rugged Polypropylene ‐PPS or PVDF sensor for corrosive liquids and gasses.
Adjustable set point with LED for flow or no ‐flow status indication.
60VA relay selectable NO or NC via power supply wiring polarity
Solid State sensor is not damaged by over ‐ranging flow velocities.
Table of Contents
Specifications: ........................................................................................................................................................4
Make a Fail ‐Safe System: ...........................................................................................................................4
Dimensions: .........................................................................................................................................................5
Configurations: ...........................................................................................................................................5
Safety Precautions: ................................................................................................................................................6
Introduction: .........................................................................................................................................................7
Technology: ................................................................................................................................................7
Initializing Sequence for FST ‐200 Series: ...................................................................................................7
Set Points: ..................................................................................................................................................7
Installation: .........................................................................................................................................................8
Wiring: .........................................................................................................................................................9
Supply Voltage: ..........................................................................................................................................9
Signal Output: ............................................................................................................................................9
Wiring to an Omega Engineering Controller: .............................................................................................9
Wiring the Relay Output: ..........................................................................................................................10
Wiring as a P ‐Channel or N ‐Channel Output: ..........................................................................................11
Calibration: .......................................................................................................................................................12
Set Point: ..................................................................................................................................................12
Maintenance: .......................................................................................................................................................13
Cleaning Procedure: ..................................................................................................................................13
Testing the Sensor (FST ‐200 Series Only): ...............................................................................................13
Testing the Sensor (FST ‐300 Series Only): ...............................................................................................14
3
Page 4
SPECIFICATIONS Step Two
Set point range: FST ‐200: .04 to 3 fps (.012 to .91 mps)
FST ‐300: 1 to .90 fps (.3 to 27 mps)
Factory set point: FST ‐200: .2 fps (.06 mps)
FST ‐300: 10 fps (3 mps)
Repeatability: ±.5% of set point @ fixed temp.
Response time: 1‐ 10seconds
Set point adjust.: Potentiometer
LED indication: Flow Status
Viscosity range: 1‐ 200centipoise (FST‐ 200 series only)
Supply Voltage: 14‐ 36 VDC
Consumption: 70 mA maximum
Contact type: (1)SPST relay
Contact rating: 60 VA, 1A max
Contact output: Selectable NO/NC
Process temp.: F:32°to 140°
C: 0° to 60°
Electronics temp. F:‐ 40°to 140°
C:‐ 40° to 60°
Pressure: 150 psi(10 bar)@ 25°C., derated@ 1.667
psi (.113 bar) per °C. Above 25° C.
Sensor rating: NEMA 4X (IP65)
Sensor Material: FST ‐211/ ‐221/ ‐321/ ‐323: PP ‐PPS
FST ‐212/ ‐222/ ‐322/ ‐324: PVDF
Cable jacket mat.: FST ‐211/ ‐221/ ‐321/ ‐323: PP
FST ‐212/ ‐222/ ‐322/ ‐324: PFA
Cable type: 4‐ conductor, #22 AWG (shielded)
Cable length: 10’ (3m)
Process mount: 3/4" NPT(3/4”G/Rp)
Mount. Gasket: FKM (Gversion only)
Classification: General purpose
CE compliance: EN 61326 EMC
EN 61010 ‐ 1 safety
Make a Fail ‐ Safe System: Design a fail ‐ safe system that accommodates the possibility of switch and/or
power failure. OMEGA ENGINEERING recommends the use of redundant backup systems and alarms in
additionto the primary system. Addinga redundant alarm switch to the system is a cost effective means
to prevent costly run‐ dry issues.
4
Page 5
DIMENSIONS Step Three
Long Sensor (FST‐ 221/‐ 222/‐ 323/‐ 324)
Short Sensor (FST‐ 211/‐ 212/‐ 321/‐ 322)
Configurations (Liquid Flow Switches):
Part
Number
Length
Material
(body)
Material
(cable)
Thread
(insidex outside)
FST‐ 211‐ SPST Short (3”) PP‐ PPS Polypropylene ¾” NPTx ¾” NPT
FST‐ 212‐ SPST Short (3”) PVDF PFA ¾” NPTx ¾” NPT
FST‐ 221‐ SPST Long (4.5”) PP‐ PPS Polypropylene ¾” NPTx ¾” NPT
FST‐ 222‐ SPST Long (4.5”) PVDF PFA ¾” NPTx ¾” NPT
Configurations (Gas Flow Switches):
Part
Number
Length
Material
(body)
Material
(cable)
Thread
(insidex outside)
FST‐ 321‐ SPST Short (3”) PP‐ PPS Polypropylene ¾” NPTx ¾” NPT
FST‐ 322‐ SPST Short (3”) PVDF PFA ¾” NPTx ¾” NPT
FST‐ 323‐ SPST Long (4.5”) PP‐ PPS Polypropylene ¾” NPTx ¾” NPT
FST‐ 324‐ SPST Long (4.5”) PVDF PFA ¾” NPTx ¾” NPT
Note: The above products ship with a standard 10’ cable length. Adding “‐ 25” to the end of the part number
indicates that the product hasa 25’ cable length (ex. FST‐ 211‐ SPST‐ 25). Adding“‐ 50”to the end of the part
number indicates that the product hasa 50’ cable length (ex. FST‐ 321‐ SP
ST‐ 50).
5
Page 6
SAFETY PRECAUTIONS Step Four
About this Manual:PLEASE READ THE ENTIRE MANUAL PRIOR TO INSTALLING OR USING THIS PRODUCT.
This manual includes information on all models of Omega Engineering Thermal Dispersion Flow Switches: FST‐
200 and FST‐ 300 series.Please referto the part number located on the switch labelto verifythe exact model
which you have purchased.
User’s Responsibility for safety: Omega Engineering manufactures a wide range of flow switches and
technologies, while each of these sensors is designed to operate in a wide variety of applications; it is the
user’s responsibilityto selecta sensor model that is appropriate for the application, install it properly, perform
tests of the installed system, and maintain all components. The failure to do so could result in property
damage or serious injury.
Proper Installation and Handling: Because this is an eclectically operated device, only properly trained
staff should install and/or repair this product. Usea proper sealant with all installations. Note: Always install
the 3/4” FKM gasket with all versions of Flow switches with metric threads. The G threaded version will not
seal unless the gasket is properly installed. Never over tighten the sensor within the fitting, beyond a
maximum of 80 inch‐ pounds torque. Always check for leaks priorto system start‐ up.
Material Compatibility: The FST ‐ 200 and FST ‐ 300 series sensors are available in two different wetted
materials. Models FST‐ 211/‐ 221/‐ 321/‐ 323 are made of Polypropylene (PP) with PPS tips. Models FST‐ 212/‐
222/‐ 322/‐ 324 are made of Polyvinylidene Fluoride (PVDF). Make sure that the model you have selected is
compatible with the application liquid. To determine the chemical compatibility between the sensor and its
application liquids, referto an industry reference such as theCompass Corrosion.
Wiring and Electrical: The supply voltage used to power the sensor should never exceed a maximum of 36
volts DC. Electrical wiring of the sensor should be performed in accordance with all applicablenational, state,
and local codes.
Flammable, Explosive and Hazardous Applications: DO NOT USE THE FST‐ 200 or FST‐ 300 SERIES GENERAL
PURPOSE FLOW SWITCHES IN HAZAROUS LOCATIONS.
Warning
The rating fo r the relay is 60 VA, 1Amp max.
Omega Engineering’s Th e r m a l Dispersion flow switches are not recommendable for use with
electrically charged appl ication liqui ds. For most reliabl e operation, the liquid being measured may
need to be electrically grounded.
The sensing tip of the sensor must al ways be submersed in the liquid and never e x po se d to air.
The liquid temperature must remai n constant and not change throughout the proc ess.
6
Page 7
INTRODUCTION Step Five
Technology:The Thermal Dispersion flow switches measure liquid or gas temperatureto determine changes
in flow velocity. As fluid flows across the sensing tips, the temperature is reduced proportionately as a
function of the flow rate. Whena temperature or velocity shift reaches the user defined set point, the switch
changesstate indicating the appropriate flow condition (flow of no‐ flow).
OMEGAENGINEERING’s sophisticated electronics convert the temperature shift into a signal which indicates
whethera flow or no‐ flow condition occurs. Depending on how the sensor is wired, this signal may be wired
for normally open ornormally closed circuits.
OMEGAENGINEERING’s Thermal Dispersion flow switches have no moving parts to clog or foul, making them
suitable for a verity of applications, including non‐ coating and non‐ scaling liquids. The FST‐ 200 series directly
measure mass flow and can operate over board range ofliquids from 0.4to 1.2 specific gravity and 1to 300
cp.
Initializing Sequence for FST‐ 200 ser
ies: When the flow switch is powered up while submersed, the FST‐ 200
series will immediately indicate flow before switching to its correct state. A time delay may be used to
eliminate the initialization sequence. Omega Engineering’s thermal dispersion relay controllers featurea0to
60 second ti
me delay for your convenience.
Set Points: The FST ‐ 200 series liquid flow switch set point is factory calibrated to 0.2 fps and the FST ‐ 300 gas
flow switch are setto 10 fps. To convert feet/secto GPM, please refer to the chart below.
FST‐ 200 Series
FlowRate vs. Velocity
(gpm vs. fps)
FST‐ 300 Series
FlowRate vs. Velocity
(scfm vs. fps)
7
Page 8
Installation Step Six
The FST‐ 200 series flow switch must always be in contact with
the liquid being measured. The FST‐ 300 series flow switch must
never be submersed in liquid.Both flow switches featurea 3/4”
NPT threads which will allow it to be used with various types of
fittings. Be sureto check the insertion depth of th
e flow switch in
thefitting after it is installed. See the diagramto the right for the
recommended insertion depth.
Thetwo tip of the sensor are to be perpendicular to the
flow (as seento the right). Never mount the tips with
one in fromt of the othe
r.
When using any type of fitting, the orientation as well as the
insertion depth of the flow switch in the pipe is critical. See the
diagramto the right for the recommendedorientation.
Warning
The flow switch tips have a thin plastic wall which may be damaged if dropped or installed improperly.
The FST ‐200 series flow switch is designed for use in liquid. For best results, avoid installing the FST ‐200
series where bubbles are present or where the tips of the switch may be out of theliquid.
TheFST‐ 300 series flow switch is designed for us in gas applications. For best results, avoid installing the
FST‐ 300 series where it may be submersed in liquid.
Always install the FKM gasket with all versions of the model FST‐ 212/‐ 222/‐ 322/‐ 324. The G threaded
version will not seal unless the gasket is properly installed.
The two temperature probes (tips) must always be perpendicular to the flow (see the flow at the same
time).
8
Page 9
WIRING Step Seven
Supply Voltage: The supply voltage to the Thermal Dispersion flow switch should never exceed a minimum
output of 14 VDC or maximum output of 36 VDC.
Required Cable Length: Determine the length of the cable required between the Thermal Dispersion flow
switch and its point of termination. Allow enough slack to ensure the easy installation, removal and/or
maintenance of the sensor. The cable length may be extended up to a maximum of 1000 ft, using a well‐
insulated 14to 20 gauge shielded four conductor cable.
Wire Stripping: Usinga 10 gauge wire stripper, carefully remove the outer layer of insulation from the last 1‐
1/4” of the sensor’s cable. Unwrap and discard the exposed foil shield from around the signal wires, leaving
the drain wire attached if desired. With a 20 gauge wire stripper, remove the last 1/4” of the colored
insulation from thesignal wires.
Signal Output (Relay Switching):
Allows the sensor to switch a small load on or off
Normally Open Wiring:
directly, using an internal relay rated below 60 VA.
The NO/NC status is set by the polarity of the voltage
feeding the red and black wires. The green wire is the
common for the relay and the white wire is the NO or
NC, depending on the polarity of red and black.
Wiring to an OmegaEngineering Controller:
LVCN‐ 131/‐ 141 Series Controller
FLCN‐ 100 Series Controller
9
Page 10
WIRING Step Seven
Wiring the Relay Output: The Flow switch relay output can be wired as a dry contact to a VDC or VAC power
source. The flow switch does require 14‐ 36 VDC power to operate the sensor and switch the relay. All
installations below identify a dry switch state as the normal position of the relay.
Switchinga Normally Open DC Load (Open during Flow, Closed during No‐ Flow):
The Red wire connects to Positive (+) of the power
supply and the Black wire connectsto Negative( ‐ ). The
LOAD can be attached to either the Green or White
wires. Completeth
e circuit by connecting the Green to
(+) VDC power or White to (‐) VDC power (see
illustrationto the right).
Switching a Normally Closed DC Load (Closed during Flow, Open during No ‐Flow):
The Black wire connects to positive (+) of the power
supply and the Red wire connectsto Negative(‐ ). Th
e
Load can be attached to either the Green or White
wires. Complete the circuit by connecting the Green
to (+) VDC power or White to (‐ ) VDC power (see
illustrationto the right).
Switchinga Normally Open AC Load (Open during Flow, Closed during No‐ Flow):
The Red wire connects to Positive (+) of the DC power
supply and the Black wire connects to Negative(‐ ). The
LOAD can be attached to the Green wire andthe Hot of
the VAC power. Connect the white to the Neutral of
the VAC power (see illustration to the right). Low
voltage VAC is less than 36 VAC.
Switchinga Normally Closed AC Load (Closed during Flow, Open during No‐ Flow):
The Black wire connects to Positive (+) of the DC
power supply and the Red wire connects to Negative
(‐ ). The LOAD can be att
achedto the Green wire and
the Hot of the VAC power. Connect the White to the
Neutral of the VAC power (see illustration to the
right). Low voltage VAC is less than 36 VAC.
For all Sensor Wiring diagrams above:
Sensor Power: Red and Black Wires(36 VDC Max.)
Rela
y Rating: Green and White Wires (60VA, 1A Max.)
10
Page 11
WIRING Step Seven
Wiring asaP‐ Channel orN‐ Channel output:The Flow switch can be substituted for either a P ‐ Channel (PNP,
Sourcing) output orN‐ Channel (NPN, sinking) output.
Normally Open DC Load asaP‐ Channel Output (Open during Flow, Closed during No‐ Flow):
To wire as a NO P‐ Channel o
utput follow the
directions below. The Red Wire connects to Positive
(+) of the power supply and the Black wire connects
to Negative (‐ ). The Green wire is jumping to the Red
wire while the White wire is connected to the LOAD.
Jumper the LOAD backto the Negative(‐)to complete
the circui
t.
Normally Closed DC Load as a P ‐ Channel Output (Closed during Flow, Open during No ‐Flow):
To wire as a NC P‐ Channel output, follow the
directions below. The Black wire connects to Positive
(+) of the power supply and the Red wire connects to
Negative (‐ ). The Green wire is jumping to the Black
wire while the White wire is connected to the LOAD.
Jumper the LOAD backto the Negative(‐)to complete
the circuit.
Normally Open DC Load asaN‐ Channel Output (Open during Flow, Closed during No‐ Flow):
To wire as a NO N‐ Channel output, follow the
directions below. The Red wire connects to Positive
(+) of the power supply and the Black wire connects
to Negative ( ‐ ). The white wire is jumping to the Black
wire while the Green wire is connectedto the LOAD.
Jumper the LOAD back to the Positive (+)to complete
the circuit.
Normally Closed DC Load asaN‐ Channel Output (Closed during Flow, Open during No‐ Flow):
To wire as a NC N‐ Channel output, follow the
directions below. The Black wire connects to Positive
(+) of the directions below. The Black Wire connects
to Negative (‐ ). The white wire is ju
mping to the Red
wire while the White wire is connected to the LOAD.
Jumper the LOAD back to Positive (+)to complete the
circuit.
For all Sensor Wiring diagrams above:
Sensor Power: Red and Black Wires(36 VDC Ma
x.)
Relay Rating: Green and White Wires (60VA, 1A Max.)
11
Page 12
CALIBRATION Step Eight
Set Point:If the preset factory calibration is not adequate for your application, follow the calibration steps
listed below.
Note: The switch’s internal LED will be on when the switch detects no‐ flow and will off when the switch
detects flow, regardless of the polarity of the Red and Black wires. Reversing the Red and Black wires will
reversethe polarity of the relay switch, but not the internal LED.
1. Install the fitting and flow switch as described in the Installation section of this manual. Turn the flow
switch and controller power on and adjust the flow rate to the application setting. If the medium to be
sensed is likely to be subject to any temperature variation, the flow switch should be set as the highest
normal temperature likelyto be encountered.
2. Locate the potentiometer knob at the top of the flow switch. The red LED is visible through the
potentiometer. The adj
ustment isa single turn 270° potentiometer. The initial response time of the flow
switch after adjustment is 1 to 10 seconds. Adjust the potentiometer in slow increments and wait for the
response.
a. LED is ON‐ If the LED is on, slowly adjust the potentiometer counter‐ clockwise, witha small flat head
screwdriveruntil the LED turn off.
b. LED is OFF‐
If the LED is off, slowly adjust the potentiometer clockwise. with a small flat head
screwdriveruntil the light turns on.
3. Adjustthe potentiometer back and forth where the LED is switching, eventually settling for where the LED
is OFF (this is the low flowstate for the switch).
a. If the flow is increased, the LED will remain OFF indicatinga flow condition
b. If the flow is decrease, the LED will turn ON indicatinga no‐ flow condition.
4. Verifythat the new calibration is correct by lowering the system flow rate below the set point and check to
see that the red LED turns on. Then increase the flow rate above the set point and verify thatthe red LED
turns off accordingly.
FST‐ 200 Series Flow Switch
(Liquid Only)
Potentiometer
Location
FST‐ 300 Flow Switch
(Gas Only)
12
Page 13
MAINTENANCE Step Nine
General:The Flow switch requires no periodic maintenance exceptto clean off any deposits or scaling from
the sensor tip as necessary. It is the responsibility of the user to determine the appropriate maintenance
schedule, based on the specific characteristics of the application liquids.
Cleaning Procedure:
1. Power: Make sure that all power to the sensor, controller and/or power supply is completely
disconnected.
2. Sensor Removal: Make sure that the flow is off and the pressure is down prior to removing the Flow
switch.Carefully, remove the sensor from the installation. Replace the sensor with a 3/4” NPT plug to
insure that the liquid doe
s not leak out during this procedure. Do not re‐ install the Flow switch if the
threads are damaged.
3. Cleaning the sensor: Use a soft bristle brush and mild detergent, carefully wash the Thermal Dispersion
flow switch. Do not use harsh abrasives such as steel wool or sandpaper, which mig
ht damage the surface
sensor. Do not use incompatible solvents which may damage the surface sensor. Do not use incompatible
solvents which may damage the sensor’s PP/Ryton or PVDF plastic body.
4. Sensor Installation: Follow the appropriate steps of installation as outlined in the installation section of
this manual.
Testing the Sensor (FST‐ 200 Series Only):
1. Immersing the switch:Place the switch ina cup of water. Make sure the tips are submersed in the water.
2. Power: Turn on power to the swit ch with Red to (+) and Black to (‐ ). You can reverse the polarity if
desired.
3. No ‐ Flow/Flow Test: With the switch setting still in the cup, wait until the Red LED turns ON (no ‐ flow
condition).
a. Swirl the switch in the cup and waituntil the Red LED turn OFF (flow condition).
b. Stop swirling the sensor and let it rest in the cup waiting for the Red LEDto turn ON again (no‐ flow
condition).
c. Repeatthe above two steps.
4. Relay Test: Connecta multimeter (setto read Ohms) to the White and Green Wires. Perform the above
No‐ Flow/Flow test with the multimeter connect to observe the actuation of the relay.
a. With Red to (+) and Black to (‐ ), the multimeter will read a small resistance during no‐ flow (closed
relay) and OL duringa flow condition (open relay).
b. Reverse Polarity [Red to (‐) and Black to (+)] to see the multimeter read OL during a no‐ flow state
(open relay) anda small resistance duringa flow condition (closed relay).
The No‐ Flow/Flow test determines if the switch is capable ofsensing the changes between no‐ flow and flow.
The Relay test determines the ability of the relayto switch betweena no‐ flow and flow condition. This is the
basic test to determine functionality of the sensor.
13
Page 14
MAINTENANCE Step Nine
Testing the Sensor (FST‐ 300 Series Only):
1. Creating a No‐ Flow Test Point: The purpose of this step is to create a no ‐flow state for the sensor to be
tested against. Since this is a low flow switch, even a buildings HVAC system can create a flow that the
sensor can read.
a. Place the switch on a table and place an empty cup over the sensing tips.
b. The cup will act like a shield to protect the sensor from air flow.
2. Power: Turn on power to the swit ch with Red to (+) and Black to (‐ ). You can reverse the polarity if
desired.
3. No ‐ Flow/Flow Test: With the switch setting still under the cup, wait until the Red LED turns ON (no ‐ flow
condition).
a. Remove the cup and move the sensor in air and observe when the Red LED turn OFF (flow
condition).
b. Place the sensor on the table and place the cup over the sensor and let it rest waiting for the
Red LEDto turn ON again (no‐ flow condition).
c. Repeatthe above two steps.
4. Relay Test: Connecta multimeter (setto read Ohms) to the White and Green Wires. Perform the above
No‐ Flow/Flow test with the multimeter connect to observe the actuation of the relay.
a. With Red to (+) and Black to (‐ ), the multimeter will read a small resistance during no‐ flow
(closed relay) and OL duringa flow condition (open relay).
b. Reverse Polarity [Red to (‐) and Black to (+)] to see the multimeter read OL during a no‐ flow
state (open relay) and a small resistance during a flow condition (closed relay).
The No‐ Flow/Flow test determines if the switch is capable ofsensing the changes between no‐ flow and flow.
The Relay test determines the ability of the relayto switch betweena no‐ flow and flow condition. This is the
basic test to determine functionality of the sensor.
14