It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc.
accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected
applications.
Contents
1. MOUNTING INSTRUCTIONS
2. REPLACING FUSES
3. ASSEMBLY
4. SUPPLY VOLTAGE
5. MODES OF OPERATION
5.1 0-20 or 4-20mA output current selection
5.2 Switch Settings
6. PARALLEL CONTROL MODE
6.1 PLC Interface
6.2 The "E" (ENABLE) Terminal
7. SERIAL CONTROL MODE
7.1 RS232c / RS422 Select
7.2 RS422 Termination
7.3 Serial Control Switch Settings
7.4 Serial Communication Parameters
7.4.1 Baud Rate Select
7.4.2 ID Code
7.4.3 Command Formats
8. SELF TEST MODES
8.1 Self Test # 1
8.2 Self Test # 2
8.3 Self Test # 3
9. MULTIDROP CONFIGURATION
10. PUTTING THE UNIT INTO OPERATION
11. CALIBRATION
12. SPECIFICATIONS
1
1. MOUNTING INSTRUCTIONS
The DRA-DCC-8 is designed for standard DIN rail mounting.
Place the unit on the upper part of the mounting rail with the fastening tab facing
down. Using a suitable flat screwdriver loosen the tab slightly and attach the unit
to the rail. Once the tab is loosened, ensure that the unit is fastened securely in
place.
2. REPLACING FUSES
In order to replace a blown fuse, the unit has to be disassembled, as follows:
a. Take off both terminal strips by removing the four screws at the edges.
Note: This does not require disconnecting the cables connected to the strips.
b.
Remove the front panel using a suitable flat screwdriver. Press down gently on
the plastic springloaded tabs located in the slots either side of the unit.
c. Disconnect the flat connector which couples the LED circuit on the front panel.
d. Replace the blown fuse.
WARNING: Never install a fuse rated more than 800mA
3. ASSEMBLY
The DRA-DCC-8 unit includes
two printed circuit cards
designated as P.N 7041 and
P.N 7040. The two printed
circuit cards should occupy
the slots in the enclosure
according to fig 1.
Insert the two printed cards into their slots. Connect the flat cable between them.
Connect the front panel flat cable. The panel must be inserted into the grooves on
both sides of the case while pressing down until a distinct "click" is heard. Assembly
is completed by laying the terminal strips in place.
Figure 1
Note: The terminal strips are polarized and must not be placed backwards.
2
4. SUPPLY VOLTAGE
The DRA-DCC-8 is powered by a DC power supply at a range of 15-32Vdc. In order
to determine the minimum supply voltage, use the following equation:
Vmin = 8 + Rload(
where:
Vmin is the minimum required supply voltage.
Rload(
Ω) is the maximum output load including the leads resistance.
Ω) * 0.02
Note: If Vmin turns to be less than 15V, the minimum required voltage
should be 15 Vdc.
5. MODES OF OPERATION
The DRA-DCC-8 unit can be operated in several modes, determined by an internal
array of 8 DIP switches as follows:
4-20 or 0-20mA output current mode
Parallel control mode
Serial control mode
Self test mode
5.1 0-20 OR 4-20mA OUTPUT CURRENT MODE
Two current output spans are available: 4-20mA or 0-20mA selected by SW6.
The DRA-DCC-8 receives 12 bits of data which determine the output current value.
A channel data value of 4095 (FFF) is always interpreted as a 20mA output current.
A channel data value of 0 (000) will produce a 0mA output current when SW6
is OFF, or 4mA when ON.
5.2 SWITCH SETTINGS
Parallel Control Mode
MODE
0-20mA
4-20mA
S1S2S3S4S5S6S7
OFFOFFOFF OFF
OFFOFFON OFF
XXX
XXX
3
Serial Control Mode
BAUD RATE (BPS)
300
4800
9600
19200
SW5 MSB
S1S2S3S4S5S6S7
OFF OFF
OFF
OFFONON
UNIT ID CODE
ONON
Self Test Mode
MODE
SELF TEST#1
SELF TEST#2
SELF TEST#3
* according to para #5.2
S1S2S3S4S5S6S7
ONOFFXOFF
OFFONOFF
ONONOFF
6. PARALLEL CONTROL MODE
ON=4-20mA
OFF=0-20mA
X
X
X
ON
ON
ON
ON
*
*
MODE
PARALLEL MODE
* according to para #5.2
In the parallel control mode, the DRA-DCC-8 unit is controlled via a 15 bit bus.
Three Address bits (A0-A3) select the proper current output channel and 12 Data
bits (D0-D11) determine its value (A0 and D0 are MSB). The DRA-DCC-8
microprocessor continuously scans the input vector (Address + Data) terminals
and updates its memory tables upon recognizing a new vector. The unit is
asynchronous in nature. The data should be valid for at least 160 microseconds.
S1S2S3S4S5S6S7
OFF OFF*OFF
X
SINK
SOURCE
6.1 PLC INTERFACE
The PLC's output modules can be divided into
three popular types; TTL output module, 24Vdc
sink type and 24Vdc source type.
There is a jumper selector on printed circuit card
PN 7040 which selects between Sink/Source
input. (TTL output module should usualy be
considered as sink type). See figure 2.
4
Figure 2.
6.2 THE "E" (ENABLE) TERMINAL
For E="1" the unit is enabled, which means that all input vectors are received and
the output is updated. When E="0" the unit ignores any new input vector. The E
terminal is recommended to be used as a strobe for parallel data which has a long
setup time. In this case the following sequence is recommended: prior to applying
a new vector, the E terminal should be set to logical 0 (inhibit state), then the new
input vector should be imposed. Once the new data is set, the E terminal should
be pulsed.
The E terminal is also used for multidrop configuration. The 15 bit vectors are
applied to the units in parallel and the selection is carried out by controlling the
"E" inputs.
7. SERIAL CONTROL MODE
7.1 RS232c / RS422 SELECT
he DRA-DCC-8 is equipped with two serial
communication ports: The RS232c and the
RS422. A jumper switch at the right side of the
DIP switch array is used to select the required
communication type. See figure 3.
RS-422
7.2 RS422 TERMINATION
The SW8's ON state terminates the RS422 receiver terminals with a 100W load.
In a multidrop configuration, the last (most distant) DRA-DCC-8 unit should be
terminated in order to match the transmission lines.
Figure 3.
RS-232c
Note: Only one termination load per RS422 communication link is permissible.
7.3 SERIAL CONTROL SWITCH SETTINGS
S1S2S3S4S5S6S7
BAUD RATEID CODE*ON
* according to para #5.2
7.4 SERIAL COMMUNICATION PARAMETERS
The communication protocol is 8 bit ASCII, even parity, and one stop bit.
5
7.4.1 BAUD RATE SELECT
SW1 and SW2 select one out of four available baud rates.
SW1SW2
300 BPS
4800 BPS
9600 BPS
19200 BPS
OFF
OFF
ONOFF
OFFON
ONON
7.4.2 ID CODE
Up to eight DRA-DCC-8s can be connected in a multidrop configuration. Switches
SW3, SW4, and SW5 (MSB) set the ID code.
7.4.3 COMMAND FORMATS
Three types of command formats are available:
Without echo back
acknowledgment.
With echo back
The host computer sends a message and receives an acknowledgment stating
the DRA-DCC-8 ID number and the addressed channel number.
Status report
The host computer sends a massage and does not receives an
7.4.3.1. WITHOUT ECHO BACK FORMAT
[A] [ID CODE] [CHANNEL VALUE] [CR]
The character A begins the command block.
The second byte is the ID code (07). The third byte is the addressable channel
number (07). Up to four bytes of a channel's value can be in BCD mode (0-4095).
Leading zeroes can be omitted. The last byte is [CR] which must terminate the
command block.
7.4.3.2. WITH ECHO BACK FORMATS
[C] [ID CODE] [CHANNEL VALUE] [CR]
This format differs only in the opening character. After every command block
transfer, the DRA-DCC-8 echoes back the following:
6
[C] [ID CODE CHANNEL] [LF] [CR]
Note: If the value is omitted it will be treated as zero. Separators such as
blanks or commas are not allowed.
Example:
Channel 4 in DRA-DCC-8 no. 7 has to receive the value of 981. Echo back is required
The command format is:
[C] [7] [4] [981] [CR]
The echo back will be: C 7 4
Note: The channel numbers on the DRA-DCC-8 front panel are designated
from 1 to 8, in binary they are designated from 0 to 7.
Note: When applying the echo back mode, it is advisable to wait for the
echo back before transmitting a new command.
7.4.3.3 STATUS REPORT FORMAT
[S] [ID CODE] [CR]
The addressed DRA-DCC-8 unit will respond with the values stored in its eight
channels. The response will start with S, ID code, following with eight channel
values separated with commas and [LF] [CR] as terminators.
Example:
DRA-DCC-8 unit number 3 has the following stored data: ch1: 300, ch2: 1270,
ch3: 0, ch4: 4087, ch5: 2099, ch6: 764, ch7: 3078, ch8: 550. The response from
the device will be:
S3,300,1270,0,4087,2099,764,3078,550 [LF] [CR].
Note: Wait until the status report has terminated before transmitting new
commands.
8. SELF TEST MODES
The DRA-DCC-8 is provided with three test modes.
MODE
SELF TEST#1
SELF TEST#2
SELF TEST#3
* according to para #5.2
S1S2S3S4S5S6S7
ONOFFXOFF
OFFONOFF
ONONOFF
X
X
X
*
*
7
8.1 SELF TEST #1 (Communication Ports T est)
In order to test the serial communication ports, this test mode converts the unit to
a transponder for ASCII characters. Any transmitted character will be echoed to
the host terminal. The host parameters should be set to:
In this test mode, the DRA-DCC-8 unit ignores the address field. All the outputs
are set according to the data field only.
8.3 SELF TEST #3 (Saw Tooth)
In this test mode, only one output channel (according to the address setting) will
produce a saw tooth wave form in which the whole value range is used.
9. MULTIDROP CONFIGURATION
Up to eight DRA-DCC-8 units can be installed in a multidrop configuration using
the RS422 communication port.
The controller's RS-422 transmitter is connected to the units' receivers while the
controller's RS-422 receiver is connected to the units' transmitters.
As the communication cable might be several thousand feet long, it is necessary
to terminate the end of the line with its characteristic impedance in order to avoid
reflections in the transmission line causing data distortion. SW8 in its ON state
terminates the Rx inputs with a 100Ω load.
10. PUTTING THE UNIT INTO OPERATION
The DRA-DCC-8 is supplied with a set configuration for parallel control mode.
The DIP switch setting is:
MODE
PARALLEL 4-20mA
The communication port selector (see para #7.1) is set to RS232C.
The unit should be set up according to the required configuration.
Before applying voltage to the unit see para #4 for power supply consideration.
8
S1S2S3S4S5S6S7
ONOFFOFFOFFOFFOFF OFF
The channel LEDs are connected in series with the output current so that they will
light only as an indication of a closed current loop.
Note: After every power on, the unit is reset and the initialized
default output currents are according to the SW6 setting
(see para #5.2).
In the parallel control mode, internal pull-up resistors on each of the input terminals
keep them in logical 1 state. The unit will recognize input voltage up to 0.5V as
logical 0 and voltages from 4V to 60V as logical 1.
11. DRA-DCC-8 CALIBRATION
Generally there is no need to calibrate the DRA-DCC-8 unit. However if calibration
is required, the following steps should be carried out: Two potentiometer trimmers,
one for "Zero" and the other for "Span" are located on printed card 7040. The
trimmer close to the card edge is the "Zero". Use the following switch setup for
switching all the outputs between 4 and 20mA
MODE
ALL CH. = 4mA
ALL CH. = 20mA
Note: Set the unit to sink mode (fig.2).
Step 1:
Select one channel (for example ch.#1) for the initial tuning. Set the DIPswitch array
to "all 4mA".
Apply supply voltage to the unit. The initial state of all the output currents is 4 mA.
Use SW2 to switch all the outputs between 4 and 20mA. Iteratively set the "Zero"
and the "Span" trimmers for 4.00mA and 20.00mA.
S1S2S3S4S5S6S7
XX
ONOFFON OFF
XXX
ONOFFOFFOFFX
Step 2:
Monitor all the 8 channels in 4mA state, and calibrate the Zero trimmer so that
their average readings is 4.000mA.
Then repeat for 20mA state, and calibrate the Span trimmer so that their average
readings is 20.000mA. This procedure should be repeated until calibration is
satisfactory.
9
12. SPECIFICATIONS
INPUTS:
PARALLEL INPUTS
LOGIC LEVELS:
DATA HOLD TIME:
MAXIMUM PARALLEL INPUT RATE:
SERIAL COMMUNICATION
BAUD RATES:
PARITY:
STOP BIT:
STATUS REPORT:
MULTIDROP CAPABILITY:
OUTPUTS:
OUTPUT CURRENT SPAN:
OUTPUT CURRENT SETTLING TIME:
POWER SUPPLY:
CURRENT CONSUMPTION:
MAXIMUM LOOP RESISTANCE:
ACCURACY:
RESOLUTION:
INDICATORS:
AMBIENT TEMPERATURE
Operation:
Storage:
RELATIVE HUMIDITY:
HOUSING
Box:
Terminals:
MOUNTING:
FUSE:
WEIGHT:
DIMENSIONS:
Parallel & Serial control inputs
3 - Output current loop address
12 - Output current value (Data)
1- Enable (E)
0<"0"<0.5V, 4 <"1"< 60V
160 microsecond
6000 updates per second
RS232c full duplex
RS422 full duplex
300, 4800, 9600, 19200 BPS
Even
One
Reports as interrogated
Up to eight units
8 continues current loops
0-20mA or 4-20mA (user selected)
4.2 ms max. for 99% of step
15-32 Vdc (regulated)
85mA max.
According to Rmax(K
±
0.1% of span typical, ±0.2% of span max.
0.025% of span typical,0.05% of span max.
Yellow Power On LED
8 Red output channel LEDs
-10 to 60 oC (14 to 140 oF)
-25 to +85 oC (-13 to 185 oF)
5 to 95%, non condensing
Plastic Polycarbonate
According to IP 50 DIN 40050
Standard DIN rail
630mA fast blow (5x20mm)
0.7Kg (1.5 lb.)
73.2H x 200W x 121mmD (2.88"x7.88"x4.76")
Ω
)= (Vsupply -6)/20
According to IP 20 DIN 40050
10
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship
for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month
grace period to the normal one (1) year product warranty to cover handling and shipping time. This
ensures that OMEGA’s customers receive maximum coverage on each product. If the unit should malfunction,
it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized
Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is
found to be defective it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects
resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing,
operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if
the unit shows evidence of having been tampered with or shows evidence of being damaged as a result
of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse
or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including
but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes
liability for any damages that result from the use of its products in accordance
with information provided by OMEGA, either verbal or written. OMEGA warrants
only that the parts manufactured by it will be as specified and free of defects.
OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND
WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIM ITATION
OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the
total liability of OMEGA with respect to this order, whether based on contract,
warranty, negligence, indemnification, strict liability or otherwise, shall not exceed
the purchase price of the component upon which liability is based. In no event
shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth
in our basic WARRANTY / DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and
hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED
RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE contacting
OMEGA:
1. P.O. number under which the product was
PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.