Omega DPG1000ADA-15G, DPG1000ADA-30A, DPG1000ADA-60G, DPG1000ADA-30G, DPG1000ADA-100A Instruction Sheet

...
TM
Digital Pressure Gauges with Alarms
DPG1000ADA Series
INSTRUCTION
SHEET
M3362/0818
Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info
Ranges and Resolution
See table below. Resolution is fixed as indicated in table.
Dual Alarms, 4-20 mA Output Range
DPG1000ADA-30V100 DPG1000ADA-30INHGVAC DPG1000ADA-05G DPG1000ADA-15A DPG1000ADA-15G DPG1000ADA-30A DPG1000ADA-30G DPG1000ADA-60G DPG1000ADA-100A DPG1000ADA-100G DPG1000ADA-300G DPG1000ADA-500G DPG1000ADA-1KG DPG1000ADA-2KG DPG1000ADA-3KG DPG1000ADA-5KG
Alarm Setting
(All are field configurable)
–30.0 inHg to 100.0 psig
0.00-30.00 InHg Vac
0.00-5.000 psig
0.00-15.00 psia
0.00-15.00 psig
0.0-30.00 psia
0.0-30.00 psig
0.0-60.00 psig
0.0-100.0 psia
0.0-100.0 psig 0-300.0 psig 0-500.0 psig 0-1000 psig 0-2000 psig 0-3000 psig 0-5000 psig
Alarm Type
-1N (default if not specified) HI/LO Normal action
-2N
-3N
-1R
-2R
-3R
Numeric
display
Alarm1 Alarm 2
Select Test
Alarm 1
status
LED
ALARM 1
SEL
¼" NPT
HI/HI Normal action LO/LO Normal action HI/LO Reverse action HI/HI Reverse action LO/LO Reverse action
2
XXXXX
8
8
8
8
8
TEST
s
Alpha-
numeric
display
ALARM 2
Up
t
Down
Alarm 2
status
LED
0.75"
3.38" Standard
3.5" NEMA 4X
DPG1000-PS Optional Power Supply Kit
The optional power supply kit includes a UL and CSA listed 115 VAC (50/60 Hz) wall-mount power supply with U.S. style 2-prong plug.
Output is 12 VDC at 200 mA and is intended for gauges that accept DC power. The power supply’s two-conductor wire is approxi­mately 6 feet long and has plain wire ends.
Also included is a moisture resistant connector to allow easy hookup without having to strip wires. Use a pair of pliers to snap connector onto wires.
Accuracy
Accuracy includes linearity, hysteresis, repeatability ±0.25% of full scale ±1 least significant digit Sensor hysteresis: ±0.015% FS, included in accuracy Sensor repeatability: ±0.01% FS, included in accuracy
Display
Controls & Functions
SEL Select and display alarm trip points TEST Alarm acknowledge, or toggle alarms when in test mode
s Increase alarm setpoint when in setpoint adjust mode t Decrease alarm setpoint when in setpoint adjust mode
Multi-level pass code protection for set-up and calibration
Alarm Relay Outputs
Programmable dual form C (SPDT) relay contacts for HI/LO, HI/HI, LO/LO, normal or reverse acting with 1% deadband, or adjustable trip and reset points for each relay, manual or auto acknowledge.
1A/24VDC, 0.5A/115VAC, non-inductive 120 milliseconds typical response time
Calibration
Non-interactive, ±10% of range All pressure and absolute models: zero, midpoint, span All vacuum models: –span, –midpoint, zero Vacuum/pressure models: –span, zero, +midpoint, +span ±15 psi models: –span, –midpoint, zero, +midpoint, +span
2.88"
3 ft long, 22 AWG cables with stripped and tinned wire ends 2 conductor power 6 conductor alarms
Allow 1" wire clearance
Turn at hex
1.65"
DPG1000ADA
NC 1 C 1 NO 1
NC 2 C 2 NO 2
Alarm Contact Ratings
0.5A/115VAC, 1A/24VDC, non-inductive
WARNING: This product can expose you to chemicals including lead, nickel and chromium, which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
fitting only
BLACK
Power wires
8-24 VAC 50/60 Hz or
RED
6-conductor relay wires
BLACK NC Normally Closed
RED C Common
NO Normally Open
GREEN NC Normally Closed
BROWN C Common
BLUE NO Normally Open
9-32 VDC
SPDT
SPDT
Power
8 to 24 VAC 50/60 Hz or 9 to 32 VDC Gauge is on when power is on Designed for continuous operation.
1.0 watt maximum power consumption
Weight
9.5 ounces (approx.), shipping wt. 1 pound (approx.)
Housing
Extruded aluminum case, epoxy powder coated, ABS/ polycar­bonate bezel, front and rear gaskets, polycarbonate label
Connection, Material, Media Compatibility
1/4” NPT male fitting, all wetted parts are 316L stainless steel
Overpressure, Burst, Vacuum
Ranges using 3000 psig sensor: 5000 psig overpressure Ranges using 5000 psig sensor: 7500 psig overpressure All others: 2 X pressure range
3000 psi, 5000 psi, and 4 digit ranges 112.5% full scale out­of-range display: 1– – – or I –.–.–.– Under-range display (non-vacuum sensors): –Err
4 X sensor burst pressure rating, or 10,000 psi, whichever is less Vacuum service: 15 psia, ±15 psig, 15 psig, 30 psia, 100 psig, 100 psia, 200 psig sensors
Environmental
Storage temperature: –40 to 203°F (–40 to 95°C) Operating temperature: –4 to 185°F (–20 to 85°C) Compensated temperature: 32 to 158°F (0 to 70°C)
Installation Precautions
4 Read these instructions before using the gauge. Configuration may
be easier before installation. Contact the factory for assistance.
4 These products do not contain user-serviceable parts. Contact
us for repairs, service, or refurbishment.
4 Gauges must be operated within specified ambient temperature
ranges.
4 Outdoor or wash down applications require a NEMA 4X
gauge or installation in a NEMA 4X housing.
4 Use a pressure or vacuum range appropriate for the application. 4 Use fittings appropriate for the pressure range of the gauge. 4 Due to the hardness of 316 stainless steel, it is recommended
that a thread sealant be used to ensure leak-free operation.
4 For contaminated media use an appropriate screen or filter to
keep debris out of gauge port.
4 Remove system pressures before removing or installing gauge. 4 Install or remove gauge using a wrench on the hex fitting only.
Do not attempt to turn gauge by forcing the housing.
4 Do not exceed relay current and voltage ratings. Use an appro-
priate contactor for larger loads. Inductive inrush currents may be up to 5x normal current and may require an RC snubber.
4 Good design practice dictates that positive displacement liquid
1
pumps include protection devices to prevent sensor damage from pressure spikes, acceleration head, and vacuum extremes.
Avoid permanent sensor damage! Do not apply vacuum to
2
non-vacuum gauges or hydraulic vacuum to any gauges.
Avoid permanent sensor damage! NEVER insert objects into
gauge port or blow out with compressed air.
Gauges are not for oxygen service. Accidental rupture of
sensor diaphragm may cause silicone oil inside sensor to react with oxygen.
NEVER connect the gauge wires directly to 115 VAC or per-
manent damage will result.
2
DPG1000ADA Series Digital Pressure Gauges With Alarms
Types of Gauges
Gauge reference models read zero with the gauge port open. Compound ranges read vacuum in inches of Mercury, pressure
in psig, and zero with the gauge port open. 1000 psi and higher sensors are a sealed-reference type. They
read zero with the gauge port open are internally referenced to
14.7 psi. They function like gauge reference sensors. Absolute reference gauges read zero at full vacuum and atmo-
spheric pressure with the gauge port open. Note that readings of atmospheric pressure vary continuously.
Gauge Wiring Diagram
DPG1000ADA
NC 1 C 1 NO 1
NC 2 C 2 NO 2
Alarm Contact Ratings
0.5A/115VAC, 1A/24VDC, non-inductive
BLACK
RED
BLACK NC Normally Closed
RED C Common
GREEN NC Normally Closed
BROWN C Common
BLUE NO Normally Open
Power wires
8-24 VAC 50/60 Hz or
9-32 VDC
6-conductor relay wires
NO Normally Open
SPDT
1
SPDT
2
Gauge Power Connections
The 2-conductor cable RED and BLACK leads is for the gauge power supply. Note the relay cable also has red and black wires. Do not connect power to them.
Connect to 8-24 VAC, 50/60Hz or 9-32 VDC. The gauge will operate on either AC or DC power, either polarity. An unregu­lated power supply can be used. Note that 24 VAC transformers with small loads may operate at voltages over the 24 VAC limit. The supply voltage, when within the stated ranges, has negli­gible effect on the gauge calibration. Operation below 9 VDC or 8 VAC may cause erratic or erroneous readings or output.
When operating multiple gauges from the same power supply, refer to the mA rating in the specifications to ensure adequate power. Route the wires away from heat sources and moving equipment.
Power Up
The gauge is powered on whenever a supply voltage is applied. Warm-up time is negligible. The gauge may be left on at all times. All configuration information is stored in non-volatile memory.
When power is first applied, the gauge proceeds through a startup sequence. During the startup sequence, relays are de­energized and the status LEDs are off.
1. The firmware version number is displayed briefly
2. All active display segments are turned on for approx. 1 second.
3. The full scale pressure is indicated for approx. 1 second while the engineering units and FS (full scale) are indicated for 1/2 second on the character display.
4. The display is tested again for approximately 1 second.
The gauge then proceeds to the normal operating mode.
Alarm Contact Rating and Protection
The alarm contacts are rated at 1A/24VDC or 0.5A/115VAC. Using mechanical relay contacts above their rating, or with large inductive loads, will shorten their life. For inductive loads, RC snubbers or arc suppression devices are required to protect the contacts. For large loads a higher capacity contactor is required.
No internal fusing is included in the alarm contact circuits. The alarm outputs should be externally fused by the user in applica­tions where good design practice dictates.
Alarm Types
The factory default configuration is 1% fixed deadband mode, zero tare enabled, and no pass code required for test function.
Alarms may be configured to operate in fixed deadband mode or adjustable hysteresis mode.
In the fixed deadband mode, the alarm set/reset point deadband is factory set to 1% of full-scale. Each alarm may be configured as either HI or LO with a user adjustable alarm set point for each relay.
In the adjustable hysteresis mode, two independent set and reset trip points are user adjustable for each relay. The set or reset state at power up when between trip points is user configurable.
Gauge Configuration
From the normal operating mode, press and hold the TEST and s buttons.
Then press the SEL button. Release all buttons when the display indicates CFG.
Before the gauge enters the Configuration mode, the display initially indicates _ _ _ _ with the first underscore blinking, and CFGPC on the lower display.
Enter the pass code as described below.
Pass Code Entry
A pass code is required to configure the gauge. Additional levels of security may be enabled by defining separate pass codes for calibration, configuration, output test, and set point adjust modes. See Changing the User-Defined Pass Code at the end of this manual to change pass codes.
Functions in user configuration mode Restore original factory configuration Enable/disable zero tare function Choosing 1% deadband or adjustable hysteresis alarm mode Operation for blinking alarm LEDs Set point modes (high alarm/low alarm or state at power-up) Relay action mode (normal/reverse) Enable/disable pass code for output test and set point adjust
When the gauge requests a pass code, the display indicates
____ with the first underscore blinking, and either TSTPC, CFGPC, CALPC on the lower display. All three pass codes
are initially set to the factory default of 3510.
Note: During pass code entry the LEDs will be off and the gauge will not respond to changes in pressure. The relays will maintain their prior state. The gauge will automatically revert to the nor­mal operation if no buttons are ressed for approx.y 15 seconds.
Use the s and t buttons to set the left-most digit to 3.
Press and release the SEL button to index to the next position. The 3 will remain, and the second position will be blinking.
Use the s and t buttons to select 5.
Press and release the SEL button to index to the next position. 3 5 will remain, and the third position will be blinking.
Use the s and t buttons to select 1.
Press and release the SEL button to index to the next position. 3 5 1 will remain, and the fourth position will be blinking.
Use the s and t buttons to select 0.
Press and release the SEL button to proceed.
If an incorrect pass code was entered, the gauge will to exit to the normal operating mode. Upon successful pass code entry, follow the steps in the appropriate section of this manual.
Note: To exit a mode at any time, press and hold the SEL button until the display indicates – – – – .
Restore Factory Configuration
The upper display will be blank, and the lower display will display either USER_ or FCTRY.
Use the s or t buttons to select either USER_ or FCTRY. If USER_ is selected, the existing user configuration will be
retained and can be modified in the following steps. If FCTRY is selected, the existing user configuration will be
replaced with the factory configuration. It can be modified in the following steps.
When the desired setting is displayed, press and release the SEL button to move on to the next parameter.
Zero Tare Configuration
The upper display will be blank, and the lower display will indicate either ZTARE or NOZTR.
Use the s or t buttons to select either ZTARE or NOZTR If ZTARE is selected, the user will be able to manually zero
the gauge from the normal operating mode. If NOZTR is selected the user will be prevented from zeroing
the gauge from the normal operating mode. This is default set­ting for absolute reference ranges.
When the desired setting is displayed, press and release the SEL button to move on to the next parameter.
Alarm Type Selection
The lower display will either indicate DBAND or ADJ_H. If DBAND is selected, each relay will operate with 1% of full-
scale deadband between set and reset. If ADJ_H is selected, each output relay will have an adjust-
able set point and an adjustable reset point. Use the s or the t buttons to select either DBAND or
ADJ_H.
When to desired mode is displayed, press and release the SEL button to move on to the next parameter.
LED Alarm Annunciator Function Selection
This setting lerts the operator to an alarm conditionby blinking the LEDs. The choices are Automatically acknowledge: A_ACK Manually acknowledge: M_ACK No acknowledgement: NO_AN
Use the s or t buttons to cycle through the three choices. A_ACK: An alarm condition will be automatically acknowl-
edged when the alarm condition clears. When an alarm condi­tion occurs, the LED for that alarm will begin to blink red until it has been manually acknowledged by a pressing the TEST button, or until the alarm condition no longer exists. If an alarm is manually acknowledged, the LED will be steadily red while the alarm condition continues to exist. The LED will be steadily green whenever no alarm condition exists.
M_ACK: An alarm condition must be manually acknowledged. When an alarm condition occurs, the LED for that alarm will blink red if the alarm condition exists or blink green if the alarm condition no longer exists. The LED will continue to blink until it has been manually acknowledged by a pressing the TEST button. Once an alarm has been acknowledged, the LED will be steadily red while the alarm condition exists or green when the alarm no longer exists.
NO_AN: The LEDs will not blink. When an alarm condition occurs, the LED associated with that alarm will be steadily red if the alarm condition exists, or green if the alarm condition no longer exists. In addition, the LCD display for ALARM1 and ALARM2 will not be displayed during alarm conditions.
When the lower display indicates the desired annunciator action, press and release the SEL button to move on to the next parameter.
Fixed Deadband DBAND Alarm Setup
Alarm 1 Type in DBAND Mode
If ADJ_H was selected, skip to the Relay Power Up State Section.
Use the s or t buttons to select eitherSP1_L or SP1_H. If SP1_L is selected, Alarm 1 will be a LOW alarm.
Alarm 1 will be SET when the pressure falls below Setpoint 1.
Alarm 1 will be RESET when the pressure rises above Setpoint 1 plus the deadband. The fixed 1% deadband is .01 x the full scale range of the gauge.
If SP1_H is selected Alarm 1 will be a high alarm.
Alarm 1 will be SET when the pressure rises above Setpoint 1.
Alarm 1 will be RESET when the pressure falls below Setpoint 1 minus the deadband. The fixed 1% deadband is .01 x the full scale range of the gauge.
When the desired alarm type is displayed, press and release the
SEL button to move to Alarm 2. Alarm 2 Type in DBAND Mode
Use the s or t buttons to select eitherSP2_L or SP2_H. If SP2_L is selected, Alarm 2 will be a LOW alarm.
Alarm 2 will be SET when the pressure falls below Setpoint 1.
Alarm 2 will be RESET when the pressure rises above Setpoint 2 plus the deadband. The fixed 1% deadband is .01 x the full scale range of the gauge.
If SP2_H is selected Alarm 2 will be a high alarm.
Alarm 2 will be SET when the pressure rises above Setpoint 1.
Alarm 2 will be RESET when the pressure falls below Setpoint 2 minus the deadband. The fixed 1% deadband is .01 x the full scale range of the gauge.
When the desired alarm type is displayed, press and release the SEL button to move to the next parameter.
Loading...
+ 4 hidden pages