The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves
the right to alter specifications without notice.
The DP606A/DP612A Display Meter offers a flexible, easy to use 6 or 12 zone, 4 digit
temperature and process measurement solution in a rugged ¼ DIN Aluminum
housing. Selectable configuration eliminates the need for jumpers.
The DP606A supports 6 independent zones and the DP612A supports up to 12 zone
(3 wire RTD limited to 6 zones on all models). All zones are scanned at a 400ms rate.
The display shows the reading of each zone sequentially. High and low Alarms with
SPDT relay outputs are available for monitoring and alarm purposes.
The universal input supports 9 thermocouple types (J, K, T, E, R, S, B, C, and N), 2 or
3 wire RTDs (Pt 100, Ni 120, Cu 10), DC voltage (0-1 Vdc), or DC current (0 – 24 mA).
Independent alarms are available for each zone. Each alarm can be configured for
above (HI), below (LO) or HI/LO triggering. Alarms conditions will be indicated on
the display meter and may be used to activate either of the 2 SPDT relay outputs.
A user selectable RS232 or RS485 serial port interface is standard on all models and
uses the Modbus RTU protocol for configuration management and data transfer.
The universal AC power supply accepts 90–240 Vac. The isolated DC power option
accepts 9–36 Vdc.
A security password can be used to prevent front panel tampering of the
configuration.
1
Page 7
Installation and Operating Conditions
Section 2 - Installation and Operating Conditions
This Instrument is marked with the international Caution symbol. It is important to
read and follow the Setup Guide before installing or commissioning this device. The
Guide contains important information relating to safety and EMC.
The instrument is a device protected in accordance with UL 61010:2010 Electrical
Safety Requirements for Electrical Equipment for Measurement, Control and
Laboratory. The device has no power-on switch. Installations must include a switch
or circuit breaker that is compliant to IEC 947-1 and 947-3. It must be suitably
located to be easily reached and marked as the disconnecting device for the
equipment.
WARNING: Do NOT connect AC power to your device until you have completed
all input and output connections. This device is a panel mount device protected in
accordance with Class I of EN 61010 (115/230 AC power connections), Class III for
the DC power option (9-36Vdc). It must be installed by a trained electrician with
corresponding qualifications. Failure to follow all instructions and warnings may
result in injury.
Use Copper conductors only, minimum 20 AWG, UL Rated, for power and outputs.
Insulation must be rated for at least 85ºC and 600V.
2
This device is not designed for use in, and should not be used for, patient-connected
applications.
Safety:
EMC:
WARNING: Failure to follow all instructions and warnings is at your own risk and
may result in property damage, bodily injury and/or death. Omega Engineering
is not responsible for any damages or loss arising or resulting from any failure to
follow any and all instructions or observe any and all warnings.
• Do not exceed the voltage rating on the label located on the device housing.
• Always disconnect power before changing signal and power connections.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Whenever EMC is an issue use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• If EMC problems occur Install Ferrite Bead(s) on signal wires close to the
instrument.
CAUTION: Risk of electric shock. Disconnect all power sources before servicing.
2
Page 8
3
Pane l
Bezel
Cas eSlideSc re w
SideView
User
Acce ssible
BehindPanel
PanelCutout
92mm
92mm
Mounting Instructions
Section 3 - Mounting Instructions
Select a location for the monitor that is free from excessive shock, vibration, dirt,
moisture and oil. Mount the monitor into a 3 5/8” (92mm) square cutout. The
monitor as shipped is 1/4 DIN (92mm square), so it does not have to be removed
from its housing to be mounted. Remove the two screws that secure the mounting
slides. Remove the slides and insert the case into the cutout from the front side of
the panel. Reinstall the two slides and two screws. The length of the slides must be
reduced if the monitor is to be mounted in an extra thick panel.
Ensure that the unit is properly grounded to the panel which should be earth
grounded. Use the supplementary ground point indicated on the rear panel if a
good ground connection cannot be maintained from the mounting slides alone.
Figure 1 - Side and Panel Cutout Views
3
Page 9
1
2
3
4
5
6
19
13
112
7
Section 4.1 - Rear Panel Diagram
Wiring Instructions
4
Figure 2 - DP606A/DP612A: Rear Panel Connections
ItemDescription
1Reset Pinhole
2Serial Connector
3Input 7 through 12
4Input 1 through 6
5Supplementary Ground Point
6Power and Alarm Connector
7Mounting Slide
Caution: Use only provided terminals. Torque all connections to 0.5-0.6Nm.
Table 1 - Rear Panel Connections
4
Page 10
4
NC
L
ALM1
NO C
(+)
N(-)
NC
ALM2
NO C
19
N
L
SW
Fuse
SW
+
-
Or
DCPOWEROPTION
90–240Vac
9–36Vdc
ACP O WER
Fuse
Wiring Instructions
Section 4.2 - Connecting Power
Pin No.CodeDescription
1N(-)Neutral Power / DC-Power supply
2ALM2 CAlarm Relay 2 Common
3ALM2 NOAlarm Relay 2 Normally Open
4ALM2 NCAlarm Relay 2 Normally Closed
5(+)DC + Power supply (9-36 VDC)
6LLine Power (90-240 VAC)
7ALM1 CAlarm Relay 1 Common
8ALM1 NOAlarm Relay 1 Normally Open
9ALM1 NCAlarm Relay 1 Normally Closed
Table 2 - 9-Pin Input Power/Relay Wiring Summary
Connect the main power connections to pins 4 and 9 (AC Power) or pins 5 (+) and 9
(-) (DC Power) of the 9pin power / output connector as shown in Figure 3.
Figure 3 - Main Power Connections
For the low-voltage power option, maintain the same degree of protection as the
standard high-voltage input power units (90–240 Vac) by using a Safety Agency
Approved DC source with the same Overvoltage Category and pollution degree as
the AC model.
The Safety European Standard EN61010-1 for measurement, control, and laboratory
equipment requires that fuses must be specified based on IEC127. This standard
specifies the letter code “T” for a Time-lag fuse.
5
Page 11
Section 4.3 - Connecting Alarms
NC
L
ALM1
NO C
(+)
N(-)
NC
ALM2
NO C
19
Fuse
Fuse
Lo ad
Load
The DP606A/DP612A Series includes SPDT mechanical relays with internal
snubbers on the normally open contact side. When powered and not in an alarm
state the relays are Energized and the NO contact is connected to the Relay
common contact. If an alarm condition occurs or if the unit loses power the relay is
deenergized and the NC contact is connected to the Relay common contact.
Wiring Instructions
4
Figure 4 - Relay Connections
WARNING: For the low-voltage power option, maintain the same degree of
protection as the standard high-voltage input power units (90–240 Vac) by using a
Safety Agency Approved DC or AC source with the same Overvoltage Category and
pollution degree as the standard AC unit (90–300 Vac).
The Safety European Standard EN61010-1 for measurement, control, and laboratory
equipment requires that fuses must be specified based on IEC127. This standard
specifies the letter code “T” for a Time-lag fuse.
6
Page 12
4
+-Z1+-Z2+-Z3+-Z4+-Z5+-
Z6
+-+-+-+-+-+-
Z7Z8Z9Z10Z11Z12
Wiring Instructions
Section 4.4 - Connecting Communications
Pin No.CodeDescription
1BRS485 B signal, RS232 TX (to remote device)
2ARS485 A signal, RS232 RX (from remote device)
3RTN signal for serial communications
Table 3 - Connecting Communications
Note: The RTN signal is isolated from the Signal RTN and the Power GND.
Section 4.5 - Connecting Inputs
Connect Input sensors to the terminals Marked Zone 1 though Zone 12 (Z1 – Z12) on
the rear panel. For the DP606A only Zones 1 through 6 are active and Terminals Z7
– Z12 are only used for 3 Wire RTDs. When connecting sensors follow the polarity
indicated on the rear panel. For Thermocouples the Negative wire is Red (NA) or
White (IEC 584-3). For Process Inputs the Negative terminal is ground.
For the RTD 3 wire option the common wires must be connected to the + terminals
of both the upper (Z1 – Z6) and lower (Z7 – Z12) input boards. The negative terminal
of Z7- Z12 remains unconnected. If a 2 wire RTD needs to be used in 3 Wire mode
use a jumper wire to connect the upper and lower terminals together. Refer to the
wiring diagram below.
Note that all negative input terminals share a common internal ground connection.
Ensure that all sensors share a common ground or are fully isolated.
When power is applied to the unit it will automatically enter the RUN mode,
sequentially scanning each active zone and activating alarms if required. The Main
display shows the measured value of the indicated zone. The unit will change to
each active zone in sequence the user determined rate.
While in the RUN mode the user may lock the display at the current zone, clear any
latched alarms, examine the current Alarm values or enter the PROGRAMMING
mode.
Figure 6 - Front Panel Diagram
8
Page 14
5
Series Navigation
Section 5.2 - Lock Zones
SymbolDescription
The display stops cycling thru each display. The currently selected
zone information will be continuously updated on the display. Note
that all active zones continue to be read and any alarm conditions
will activate the enabled alarm relays.
The Lock option is released and the value display will cycle thru all
active zones.
Section 5.3 - Clear Alarms
Any active, latched alarm is cleared.
Section 5.4 - Display Alarm Values
Displays the Alarm Value for the current zone and stops scanning.
The Main display shows the Alarm value. The Zone display shows
the zone.
Increments the Zone number and displays the next
Alarm Value.
Switches between HI and LO Alarm Values. The Function
display shows 3 when displaying Low values and 4 when
displaying High Values.
Return to Run Mode
Section 5.5 - Function Select Mode
Enter Function Select Mode from Run Mode
Section 5.6 - Reset Defaults
Hold all 3 buttons down for 5 seconds to reset unit to Factory
Defaults. The unit will reboot and return to Run Mode.
9
Page 15
Section 5.7 - Function Select Mode
While in function select mode 1 is displayed in the Function Display and the
selected function is displayed in the Main display.
The DP606A/DP612A monitor has several different Functions listed in the table
below.
FunctionDescription
0Return to Run Mode
1Function Select / Enter Password
2Set Active Zone
3Set Low Alarms
4Set High Alarms
5Set Modbus Address
6Set Scan Time
7Set Model Options
Series Navigation
5
8Password Enable and Disable
9Calibration
ASet Alarm 1 Options
BSet Alarm 2 Options
CSet Low Scale
DSet High Scale
FSet Serial Options
Table 4 - Function Codes
Navigate Function Select Mode using the button below.
Increments the Function Code displayed in the
Main display.
Enters the Function displayed in the Function
display.
If the Password option is enabled only Functions 0 and 1 will be available. Entering
the correct password in Function 1 will unlock the rest of the menu options. If the
Password is disabled Function 1 will not be available.
10
Page 16
5
ºC
ºF
mA
mV
FunctionZone
Series Navigation
Section 5.8 - Function 1 - Enter Password
A password may be enabled to prevent unintended changes to the unit. The
password is a 4 digit code and the default Password is 1011. The password can only
be changed using the serial port.
Use the buttons below to enter the password.
Increment the flashing digit of the Main display
Selects the next digit of the Main display, causing it to flash
Enters the Password
After entering the password the unit will return to function select mode. If the
password is correct all of the functions will be available. If the password was entered
incorrectly it must be re-entered by selecting Function 1 again.
Section 5.9 - Function 2 - Set Active Zones
The main display is blank when selecting active zones. The current zone being
edited is shown in the Zone Display. Active zones are displayed solid while disabled
zones are displayed flashing. By default all zones are active.
Disabled zones are skipped while scanning and do not generate alarms. Use the
buttons below to change the active zone.
Advance to the next zone.
Toggles the current zone between enabled (solid) or disabled
(flashing).
Stores the enabled / disabled state for all zones and returns to
Function Select mode
11
Page 17
Section 5.10 - Function 3 and 4 - Set Low and High Alarms
ºC
ºF
mA
mV
FunctionZone
The High and Low alarm values determine the readings that the Alarms will
activate at for each zone. The function selected is indicated in the function display.
Function 3 sets the low alarms and Function 4 sets the high alarms. The default Low
alarm is -900 and the default High alarm is 9000 for all zones.
The alarms for each zone are independent. The zone for the current alarm being
edited is shown in the zone display.
The current alarm value for the selected zone is shown in the main display. The left
most digit blinks indicating it can be edited. Use the buttons indicated below to edit
the alarm values.
Series Navigation
5
Increment the flashing digit of the VALUE display.
Selects the next digit of the VALUE display, causing it to flash.
Changes the decimal point.
Stores the current VALUE display as the alarm value for the
current zone and advances to the next zone.
Stores all values and returns to Function Select mode.
12
Page 18
ºC
ºF
mA
mV
FunctionZo ne
5
ºC
ºF
mA
mV
FunctionZo ne
Series Navigation
Section 5.11 - Function 5 - Set Modbus Address
The Modbus address is used for serial communications to determine which device
on a bus is being accessed. The current Modbus Address is shown in the Main
Display. The first digit flashes to indicate it can be edited. Use the buttons below to
edit the address.
By Default the Modbus address is 1 and any address from 1 to 247 can be used. The
unit will not allow an invalid address to be displayed. Trying to enter a number
greater than 247 will cause the display to roll back to a valid number.
Increment the flashing digit of the Main display.
Selects the next digit of the Main display, causing it to flash.
Stores the Device address and returns to the Function Select
mode.
Section 5.12 - Function 6 - Set Scan Time
The scan time is the time each zone is displayed on the front panel before advancing
to the next zone. By Default, the scan time is 3 seconds. The current scan time is
displayed in the Main Display and the zone display is blank. The left most digit
blinks indicating it can be edited. Use the buttons below to edit the scan time.
Increment the flashing digit of the VALUE display.
Selects the next digit of the VALUE display, causing it to flash.
Stores the current VALUE display as the SCAN time and returns
to the Function Select mode.
13
Page 19
Section 5.13 - Function 7 - Set Device Configuration
ºC
ºF
mA
mV
FunctionZone
Function 7 sets the device configuration including the Alarm Type, Units and input
type. The default setting for Function 7 is 2204 which represents Thermocouple
Type K inputs with High/Low Latching alarms in Degrees Celsius.
Each digit in the Main Display represents a different function. Refer to the table
below for the specific functions.
Please note: Digit 4 is dependent upon the “Input Type” selected under Digit 3. Ex: If “TC” is selected under “Input Type” under Digit 3, Digit
4 becomes one of the following “B, C, E, J, etc.” under “TC Type.”
Table 5 - Device Configuration
14
Page 20
5
Series Navigation
Section 5.13 - Function 7 - Set Device Configuration cont.
Digit 1 is the Alarm type. High alarms will deactivate the relay when the Zone
process value is Above the High Alarm Value defined in Function 4. Low alarms will
deactivate the relay when the Zone process value is below the Low alarm defined in
Function 3. High/Low will trigger on both alarms and Off will not trigger alarms at
all. If different operation is desired for Relay 1 and Relay 2 or if different alarm types
need to be used per zone these can be setup in Functions A and B by selecting
User controlled.
Digit 2 defines the Units displayed for TC and RTD inputs. It also selects between
Latching and Non-Latching alarms. Latching alarms will remain active until the
latch is cleared by the user regardless of the current input value. Non-latching
alarms will deactivate as soon as the input no longer meets the alarm conditions.
The Alarm Latch Type is overwritten by the User settings if user is selected for the
Alarm Type.
Digit 3 selects between the available input types. The input type cannot be changed
individually per zone. When selecting RTD 3 wire input only 6 zones will be active
on a 12 Zone unit.
Digit 4 is context sensitive and depends on Digit 3. If TC or RTD type input are
selected Digit 4 selects the type of sensor. If mV or mA type input are selected
Digit 4 represents the maximum number of decimal points that will be displayed.
If all decimal points cannot be displayed the display will be rounded to the nearest
displayable number. Temperature readings can only be displayed to the nearest
whole number.
Increment the flashing digit of the VALUE display.
Selects the next digit of the VALUE display, causing it to flash.
Stores the current VALUE display as the Input Type advances
to the next zone. Note that this button will have no effect if the
VALUE display is selecting an invalid input type.
15
Page 21
Section 5.14 - Function 8 - Password Enable/Disable
ºC
ºF
mA
mV
FunctionZo ne
ºC
ºF
mA
mV
FunctionZone
Using Function 8, a user password may be enabled to protect the unit from
inadvertent changes. By Default the Password is disabled.
The default password is 1011. This can only be changed using the serial port.
Toggle the password from enabled (1) and disabled (0)
Stores the current VALUE display as the password enabled
state and returns to the Function Select mode.
Series Navigation
5
Section 5.15 - Function 9 - Calibration
The DP600A and DP612A are factory calibrated and do not require additional user
calibration under most circumstances. For 2 wire RTDs Function 9 may be used to
calibrate out lead wire resistance. This calibration is done independently for each
channel.
To perform lead wire calibration short the RTD that needs to be calibrated at the
end of the lead wire. Next select the Zone to be calibrated in the primary Display
using the increment button. Press the select button to perform the calibration. While
the unit is calibrating the Zone flashes to indicate it is busy. Once the calibration
is complete the Zone will stop flashing. If the lead wire resistance is more than 10
ohms the unit will display “FAIL” and the calibration value will be set to 0.
Scroll to next zone
Perform Calibration on current zone
Returns to Function Select mode
16
Page 22
ºC
ºF
mA
mV
FunctionZo ne
5
Series Navigation
Section 5.16 - Function A/B - Alarm Relay Function
When split operation is selected in Function 7, Alarm relay operation is customized
using functions A and B.
Function A Controls Alarm 1 and Function B controls Alarm 2. Each zone may be
assigned to one or more relays. By Default, Alarm 1 is assigned high / low alarms
for all zones and Alarm 2 is Disabled for all zones. The Current Zone being edited is
shown in the Zone Display. The current mode for that zone is displayed in the Main
Display.
Increment the flashing digit of the VALUE display
Selects the next digit of the VALUE display, causing it to flash
Moves to the next zone
Stores all values and returns to Function Select mode
Functions C and D set the scaling for the mA and mV input. Function C sets the
Low Scale and Function D sets the High Scale. The scaling factors for mA and mV
are separate so the values corresponding to the input type selected in Function 7 are
shown.
By default the scaling is set to display the measurement in mA/mV.
Scaling factors are applied independently for each zone. The current zone being
modified is displayed in the Zone Display. Enter the value to be displayed at 4mA or
0V in Function C and the value to be displayed at 20mA or 1V in function D. Values
between the two points are linearly interpolated.
Series Navigation
5
Increment the flashing digit
Selects the next digit, causing it to flash
Changes the decimal point
Stores the current scaling factor for the indicated zone
advances to the next zone.
Stores all values and returns to Function Select mode
Figure 7 - Process Input Scaling
18
Page 24
5
Series Navigation
Section 5.18 - Function F - Serial Configuration
Function F sets up the serial port of the device. The default serial settings are RS485,
115.2k baud no Parity.
Increment the flashing digit on the display
Selects the next digit of the VALUE display, causing it to flash.
Stores the current VALUE display as the Serial configuration and
returns to the Function Select mode. This button will have no effect if the current VALUE is does not match a valid configuration.
Digit 1Digit 2Digit 3Digit 4 (LSD)
Signaling TypeBaud RateParity
0RS485048000None0Reserved
1RS232196001Odd
2192002Even
338400
457600
5115200
Table 7 - Serial Port Configuration
19
Page 25
Section 6 - Serial Interface
The DP606A and DP612A uses the Modbus/RTU interface as described in MODBUS
APPLICATION PROTOCOL SPECIFICATION (V1.1b3).
The Modbus specification allows accessing to up 65535 internal ‘holding’ registers
using register READ, register WRITE and WRITE MULTIPLE commands. Each
Modbus holding register is defined as a 16 bit entity structured as BIG ENDIAN
values (most significant byte always presented first).
Modbus is structured using a MASTER-SLAVE topology, in which there is one
MASTER device and up to 247 slave devices. All transactions are initiated by the
MASTER device. The DP606A and DP612A acts as a slave device, with a device
address in the range 1 to 247.
Modbus slave devices are individually accessed using a one byte SLAVE address.
The MASTER device initiates a transaction by sending a request packet to a specific
slave. The SLAVE device processes the transaction and returns either response
packet indicating success or failure.
Address 0 is reserved as a ‘broadcast’ address, in which all slave devices will accept
and process the transaction but will not send a response.
Serial Interface
6
Section 6.1 - Modbus Functions
The DP606A and DP612A Modbus interface supports the following Modbus
FUNCTION requests.
Function CodeMnemonicDescription
0x03Read Holding RegisterReads one or more consecutive 16 bit
holding registers
0x06Write Single RegisterWrites a specific 16 bit holding register
0x07Read Exception statusReads structured status information
0x08Reserved
0x10Write Multiple RegistersWrite one or more consecutive 16 bit
holding registers
0x0bGet Comm eventsRead communication event counters
Table 8 - Modbus Functions
20
Page 26
6
Serial Interface
Section 6.2 - Data Formats
Modbus holding registers are represented as 16 bit entities. The following encoding
is used for extended data items. Note that ‘byte 0’ will be the first byte received/
transmitted.
For data types that can be represented in 16 bits (Boolean, byte, char, int16 and
uint16) a single register is used.
For data types that require 32 bits two consecutive registers are used. The lower
number register will represent the most significant data. The 2nd register represents
the leas significant data.
Section 6.3 - Multiple Register Reads
When reading a dual register entity the lower order register should be used as the
requested ‘holding register’, with a request for a minimum of 2 registers. Internally
the entire entity is read and data is then built into a response packet.
The access can be split into 2 consecutive single register reads. When the lower
(base) register is accessed the entire 32 bit entity is read and the two most
significant bytes are returned. The following single register read must specify the
next consecutive register address. The two least significant bytes of the internally
buffered data used in the response.
Attempts to access the two least significant bytes without first reading the two most
significant bytes will result in an error response.
21
Page 27
Section 6.4 - Multiple Register Writes
When writing a dual register entity the lower order register should be used as the
requested ‘holding register’, with a request for minimum of 2 registers. The write
data is internally buffered and transferred to the database entry as a 32-bit value.
The access can be split into 2 consecutive single register writes. When the lower
(base) register is written the 16-bit entity is internally buffered BUT NO DATA
TRANSFER IS MADE TO THE DATABASE. The following single register write
must specify the next consecutive register address. The two least significant bytes
of the write request are combined with the previous write data and the entire 32-bit
entity is written to the database.
Attempts to write the two least significant bytes without first writing the two most
significant bytes will result in an error response.
Series Interface
6
Data
Types
Number of
Registers
0123
Byte
Description
Boolean1LSBN/AZero= OFF, non-zero = ON
Byte,
Char
Int16,
uint16
Int32,
uint32
float2Sign+E xpMantisa
1LSBN/AEntity contained in LSB of
register, Byte 0 ignored.
1MSB
0
LSB
1
N/A
2 3
Entity contained in MSB/LSB of
register. (dual register data)
2MSBB-1B-2LSBRequires 2 consecutive
registers, MSB transferred first
MSB
B-1Mantisa
LSB
IEEE formatted value contained in 2 consecutive registers
Table 9 - Multiple Register Writes
Section 6.5 - Request Packet Sizes
Multiple consecutive registers may be accessed in a single transaction.
The DP606A and DP612A Modbus interface imposes a maximum of 72 bytes for the
total transaction. Allowing for the required framing, addressing and CRC results
in the following data size restrictions using the READ and WRITE MULTIPLE
functions.
FormatProtocol OverheadMaximum Read dataMaximum Write data
RTU824 Registers24 Registers
Table 10 - Packet Sizes
22
Page 28
7
Modbus Register Assignments
Section 7 - DP606A and DP612A Modbus Register Assignments
All accesses to the DP606A and DP612A database information is made thru the
following Modbus registers.
Data types:
R – single 16 bit register (may be Boolean, byte, char, int16 or uint16 data)
L – dual (32 bit) register (may be int32 or uint32 data)
F – IEEE Floating point value
B – Byte Array
All data is transferred using Big Endian formatting, where the most significant byte
is transmitted first.
Section 7.1 - System Registers
IndexMnemonicTypeAccessDescription
0x000040000Layout VersionRRHardware layout version
0x000140001Device DescriptionRRDevice description
0x000240002FW Version Major MinorRRFirst two octets of Firmware Version
0x000340003FW Version Minor FixRRLast two octets of Firmware Version
0x000440004HW VersionRRHardware version
0x000540005Max ZonesRRMax zones supported by device
0x000640006Temperature ScaleRRWSelect Fahrenheit or Celsius degree
0TYPE_BThermocouple B type
1TYPE_CThermocouple C type
2TYPE_EThermocouple E type
3TYPE_JThermocouple J type
4TYPE_KThermocouple K type
5TYPE_RThermocouple R type
6TYPE_SThermocouple S type
7TYPE_TThermocouple T type
8TYPE_NThermocouple N type
Section 7.10 - Sensor Status
Thermocouple Type
0VALIDSensor is normal
1OUT_OF_RANGE_LOWSensor Reading is below valid range
2OUT_OF_RANGE_HIGHSensor Reading is above valid range
3SHORT_CIRCUITSensor is short circuit
4OPEN_CIRCUITSensor is open circuit
Section 7.11 - System State
0PROGRAM_MODEAlarms are disabled
1RUN_MODEAlarms are enabled.
Sensor Status
System State
27
Page 33
Modbus Register Assignments
Section 7.12 - Process Unit
Process Unit
0DEGREE_CProcess unit is Celsius
1DEGREE_FProcess unit is Fahrenheit
Section 7.13 - Alarm Type
Alarm Type
0ALARM_HIGHAlarm activated when PV > Alarm High SP
1ALARM_LOWAlarm activated when PV < Alarm Low SP
2HI_LOW_ALARMAlarm activated when Alarm Low SP < PV < Alarm
High SP
3ALARM_OFFAlarm is disabled.
7
4ALARM_SPLIT_A_BAlarm 1 activates Alarm relay A, alarm 2 activates
Alarm relay B
Section 7.14 - Alarm Status
Alarm Status
0ALARM_NONENo alarm condition is triggered
1ALARM_HIGHAlarm high condition is triggered
2ALARM_LOWAlarm low condition is triggered
3ALARM_HIGH_LOWAlarm high low condition is triggered
Section 7.15 - Setting Toggle
Toggle
0DISABLESetting is disabled.
1ENABLESetting is enabled.
28
Page 34
8
Display Meters User’s Guide
Section 8 - Specifications
Display4-digit, 7-segment LED; red, 21 mm (0.83)
Dimensions95 x 95 x 135mm
Panel Cutout¼ DIN 92 x 92mm
Environmental Conditions-20 to +70°C (-4 to +158°F), 90% RH non-condensing
External Fuse RequiredTime-Delay, UL 248-14* listed:
(Operating)
-40 to +85°C (-40 to +185°F), 90% RH non-condensing
(Storage)
Pollution Degree 2
Altitude of up to 2000 meters
Indoor use
• 25 mA/250 V
• 300 mA/250 V (Low-Voltage Option)
Time-Lag, IEC 127-3 recognized:
• 25 mA/250 V
• 300 mA/250 V (Low-Voltage Option)
Line Voltage/Power120/240 Vac, 50/60Hz, 3W Max
Low-Voltage/Power OptionExternal power source must meet Safety Agency Ap-
ProtectionNEMA-1/Type 1 front bezel
Weight725 g
CommunicationsSelectable RS232 / RS485
* For UL installations
Section 8.1 - Alarm Relays
AC Power Option2x SPDT, 240Vac, 5A Load
DC Power Option2x SPDT, 36Vdc, 3A Load
provals.
9–36 Vdc, 3W Max
Modbus RTU
5A External Fuse Required
3A External Fuse Required
29
Page 35
Section 8 - Input Accuracy
Measurement Ranges and Accuracies based on
Input TypeDescriptionRange
Process
Type T/CJ Iron-Constantan
Type T/C
Type T/CCopper-Constantan
Type T/C
Type T/CPt/13%Rh-Pt
Type T/CPt/10%Rh-Pt
Type T/C30%Rh-Pt/6%Rh-Pt
Operating Temperature
Process Voltage0 to 1000 mV± 1 mV± 1 mV± 1 mV
Process Current0 to 24.00 mA± 10 µA± 10 µA± 10 µA
-150 to 0°C± 1.0°C± 2.0°C± 6.0°C
0 to 1200°C±1.0°C± 1.0°C± 2.0°C
CHROMEGA™ ALOMEGA™
-150 to 0°C± 1.0°C± 2.0°C± 5.0°C
0 to -1372°C± 1.0°C± 1.0°C± 2.0°C
-150 to 0°C± 1.0°C± 2.0°C± 7.0°C
0 to 400°C± 1.0°C± 1.0°C± 2.0°C
CHROMEGA™
-Constantan
-150 to 0°C± 1.0°C± 2.0°C± 5.0°C
0 to 1000°C± 1.0°C± 1.0°C± 2.0°C
-50 to 0°C± 1.0°C± 2.0°C± 6.0°C
0 to 1788°C± 1.0°C± 1.0°C± 2.0°C
-50 to 0°C± 1.0°C± 2.0°C± 5.0°C
0 to 1768°C± 1.0°C± 1.0°C± 2.0°C
150 to 700°C± 1.0°C± 2.0°C± 3.0°C
700 to 1820°C± 1.0°C± 1.0°C± 1.0°C
Display Meters User’s Guide
8
Operating Temperature
Accuracy (25°C)Accuracy (0 to 50°C)Accuracy (-20 to 70°C)
Type T/C5%Re-W/26%Re-W0 to 2320°C± 1.0°C± 1.0°C± 3.0°C
Type T/CNicrosil-Nisil
-150 to 0°C± 1.0°C± 2.0°C± 5.0°C
0 to 1300°C± 1.0°C± 1.0°C± 2.0°C
Pt, 0.00385, 100 Ω-200 to 850°C± 1.0°C± 1.0°C± 1.0°C
2/3 Wire
2
⁄3 Wire
2
⁄3 Wire
Cu, 0.00427, 10 Ω-200 to 260°C± 1.0°C± 1.0°C± 1.0°C
Ni, 0.00672, 120 Ω-80 to 260ºC± 1.0ºC± 1.0ºC± 1.0ºC
Table 16 - Input Accuracy
* Absolute Maximum 3.3V (Process Voltage) or 30mA (Process Current).
30
Page 36
9
Approvals information
This product conforms to the EMC: 2014/30/EU (EMC Directive).
Electrical Safety:
This product conforms to the LVD: 2014/35/EU (Low Voltage Directive)
UL / CSA
UL 61010-1 / CSA C22.2 NO. 61010-1-12
Safety Requirements for Electrical Equipment for Measurement, Control, and
Laboratory Use
UL 61010-2-201 / CSA C22.2 NO. 61010-2-201:14
Standard for Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use. Part 2-201: Particular requirements for control
equipment
UL File Number: E209855
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
In conformity with Directive 2012/19/EU-WEEE, this marking shown on the product or its
literature, indicates that it should not be disposed of, with other household wastes at the
end of its working life. To prevent possible harm to the environment or human health from
uncontrolled waste disposal, please separate this product from other types of wastes
and recycle it responsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or
their local government office, for details of where and how they can return this item for
environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the
purchase contract. This product should not be mixed with other commercial wastes for
disposal
31
Page 37
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 25 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal two (2) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for
any damages that result from the use of its products in accordance with information provided
by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE contacting
OMEGA:
1. Purchase Order number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have
the following information available BEFORE
contacting OMEGA:
1. Purchase Order number to cover the COST
of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.