Omega DP6060 User Manual

Page 1
DP6060
Dual-Input Process Meter
Page 2
DP6060 Dual-Input Process Meter Instruction Manual
2
Page 3
DP6060 Dual-Input Process Meter Instruction Manual
3
W
ARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 37 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal three (3) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product. If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANT ABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUEST/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the
following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2012 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
Page 4
DP6060 Dual-Input Process Meter Instruction Manual
4
!
CAUTION: Read complete
instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
Warning!
This product is not recommended for life support applications or applications whe r e malfunc tionin g could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. OMEGA shall not be held liable for damages resulting from such improper use.
Page 5
DP6060 Dual-Input Process Meter Instruction Manual
5
Table of Contents
INTRODUCTION ------------------------------------------------------------ 8 ORDERING INFORMATION --------------------------------------------- 9 SPECIFICATIONS --------------------------------------------------------- 10
General ----------------------------------------------------------------------------- 10 Dual Process Input ------------------------------------------------------------- 12 Relays ------------------------------------------------------------------------------ 13 Isolated 4-20 mA Transmitter Output ------------------------------------ 14 Modbus® RTU Serial Communications --------------------------------- 15 DPA1044 Digital Input & Output Expansion Module ---------------- 15
COMPLIANCE INFORMATION ---------------------------------------- 16
Safety ------------------------------------------------------------------------------- 16 Electromagnetic Compatibility --------------------------------------------- 16
SAFETY INFORMATION ------------------------------------------------ 17 INSTALLATION ------------------------------------------------------------ 17
Unpacking ------------------------------------------------------------------------- 17 Panel Mounting Instructions ------------------------------------------------ 17
MOUNTING DIMENSIONS ---------------------------------------------- 19
Configuration for 12 or 24 VDC Power Option ------------------------ 20 Transmitter Supply Voltage Selection (P+, P-) ----------------------- 21 Connections ---------------------------------------------------------------------- 21
Connectors Labeling --------------------------------------------------------- 22 Power Connections ---------------------------------------------------------- 22 Signal Connections ---------------------------------------------------------- 23 Modbus RTU Serial Communications ----------------------------------- 24 Relay Connections ----------------------------------------------------------- 24 Switching Inductive Loads -------------------------------------------------- 25 F4 Digital Input Connections ----------------------------------------------- 26 4-20 mA Output Connections ---------------------------------------------- 26 Analog Output Transmitter Power Supply ------------------------------ 26 External Relays & Digital I/O Connections ----------------------------- 27 Interlock Relay Feature ----------------------------------------------------- 28
SETUP AND PROGRAMMING ---------------------------------------- 29
Front Panel Buttons and Status LED Indicators --------------------- 30 Display Functions & Messages -------------------------------------------- 31 Main Menu ------------------------------------------------------------------------ 35 Setting Numeric Values ------------------------------------------------------ 36 Setting Up the Meter (setup) ------------------------------------------------ 37
Page 6
DP6060 Dual-Input Process Meter Instruction Manual
6
Setting the Input Signal (Input) ------------------------------------------ 38
Setting the Decimal Point (dEc pt) -------------------------------------- 38 Programming the Meter (prog) ------------------------------------------- 39
Multi-Point Linearization (Linear) ------------------------------------ 40 Multi-Point Calibration & Scaling -------------------------------------- 40 DP6000-SOFT Software ------------------------------------------------ 40 Scaling the Meter without a Signal Source ------------------------- 40 Scaling the Meter for Channel A (SCal A) ------------------------- 41 Scaling the Meter for Channel B (SCal B) ------------------------- 41 Error Message (Error) -------------------------------------------------- 42 Calibrating the Meter with External Source ------------------------- 42 Calibrating the Meter for Channel A (CAL-A) ----------------------- 43
Calibrating the Meter for Channel B (CAL-B) ----------------------- 43 Setting the Display Parameter & Intensity (dsplay) ----------------- 44 Display Setup Menu --------------------------------------------------------- 45 Setting the Input Units or Custom Tags (units) ---------------------- 46
Setting the Relay Operation (relay) ------------------------------------- 47
Setting the Relay Assignment (asSign) -------------------------------- 48 Setting the Relay Action ---------------------------------------------------- 49 Programming Set and Reset Points ------------------------------------- 50 Setting Fail-Safe Operation ------------------------------------------------ 50 Programming Time Delay -------------------------------------------------- 50 Relay Action for Loss of 4-20 mA Input (Loop Break) --------------- 50
Relay and Alarm Operation Diagrams ----------------------------------- 51
High Alarm Operation (Set > Reset) ------------------------------------- 51 Low Alarm Operation (Set < Reset) -------------------------------------- 52 High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 53 Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 54 Pump Alternation Control Operation ------------------------------------- 55 Relay Sampling Operation ------------------------------------------------- 56 Signal Loss or Loop Break Relay Operation --------------------------- 57 Time Delay Operation ------------------------------------------------------- 58
Relay Operation Details ------------------------------------------------------ 59
Overview ------------------------------------------------------------------------ 59 Relays Auto Initialization ---------------------------------------------------- 59 Fail-Safe Operation ---------------------------------------------------------- 59 Front Panel LEDs ------------------------------------------------------------- 60 Latching and Non-Latching Relay Operation -------------------------- 60 Non-Latching Relay (Auto) ------------------------------------------------- 61 Non-Latching Relay (A-man) -------------------------------------------- 61 Latching Relay (LatcH) ----------------------------------------------------- 61 Latching Relay (Lt-Clr) ---------------------------------------------------- 62
Page 7
DP6060 Dual-Input Process Meter Instruction Manual
7
Acknowledging Relays ------------------------------------------------------ 62
Pump Alternation Control Applications (Altern) --------------------- 63 Setting Up the Interlock Relay (Force On) Feature ------------------ 64
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 65 Reset Menu (reset) ------------------------------------------------------------ 66 Control Menu (Contrl) -------------------------------------------------------- 66 Setting Up the Password (pass) ------------------------------------------- 67
Protecting or Locking the Meter ------------------------------------------- 67 Making Changes to a Password Protected Meter -------------------- 68 Disabling Password Protection -------------------------------------------- 68
Advanced Features Menu ---------------------------------------------------- 69
Advanced Features Menu & Display Messages ---------------------- 70 Noise Filter (filter) -------------------------------------------------------- 73 Noise Filter Bypass (bypass) ---------------------------------------------- 73 Rounding Feature (round) ------------------------------------------------- 74 Modbus RTU Serial Communications (serial) ---------------------- 74 Select Menu (SElect) ------------------------------------------------------- 75 Signal Input Conditioning (Functn) -------------------------------------- 76 Multi-Point Linearization (Linear) ---------------------------------------- 77 Math Function (math) ----------------------------------------------------- 78 Math Constants (Const) ---------------------------------------------------- 79 Low-Flow Cutoff (CutofF) -------------------------------------------------- 79 Analog Output Programming (AoutPr) ---------------------------------- 79 Programmable Function Keys User Menu (user) -------------------- 81 Tare (tare A, tare B) ------------------------------------------------------ 83 Internal Calibration (ICAL) -------------------------------------------------- 83 Meter Copy Function (Copy) ----------------------------------------------- 85
METER OPERATION ----------------------------------------------------- 87
Front Panel Buttons Operation -------------------------------------------- 87 Function Keys Operation ---------------------------------------------------- 87 F4 Operation --------------------------------------------------------------------- 88 Maximum/Minimum Readings ---------------------------------------------- 88
TROUBLESHOOTING ---------------------------------------------------- 89
Diagnostics Menu (diag) ----------------------------------------------------- 89
Determining Software Version -------------------------------------------- 89
Reset Meter to Factory Defaults ------------------------------------------- 90
Factory Defaults & User Settings ----------------------------------------- 91
Alphabetical List of Display Functions & Messages --------------- 93 Troubleshooting Tips --------------------------------------------------------- 98
Page 8
DP6060 Dual-Input Process Meter Instruction Manual
8
Table of Figures
Figure 1. 1/8 DIN Panel Cutout Dimensions ..................................... 18
Figure 2. Panel Mounting Details ...................................................... 18
Figure 3. Meter Dimensions - Side View ........................................... 19
Figure 4. Meter Dimensions - Top View ............................................ 19
Figure 5. Jumper Configuration for 12/24 VDC Power .................... 20
Figure 6. Transmitter Supply Voltage Selection .............................. 21
Figure 7. Connector Labeling for Fully Loaded DP6060 ................. 22
Figure 8. Power Connections ............................................................ 22
Figure 9. Transmitters Powered by Internal Supply ........................ 23
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered .. 23
Figure 11. Voltage Input Connections .............................................. 24
Figure 12. Relay Connections ........................................................... 24
Figure 13. AC and DC Loads Protection ........................................... 25
Figure 14. Low Voltage DC Loads Protection .................................. 25
Figure 15. F4 Digital Input Connections ........................................... 26
Figure 16. 4-20 mA Output Connections .......................................... 26
Figure 17. Expansion Modules & DIN Rail Mounting Kit ................. 27
Figure 18. External Relays Module Connections ............................. 27
Figure 19. Digital I/O Module Connections ....................................... 28
Figure 20. Interlock Connections ...................................................... 28
Figure 21. Acknowledge Relays w/Function Key or Digital Input .. 62
INTRODUCTION
The DP6060 is a multipurpose, easy to use digital dual-input process meter ideal for level, flow rate, temperature transmitter, or pressure transmitter applications. It accepts current and voltage signals (e.g. 4-20 mA, 0-10 V). Various math functions may be applied to the inputs including addition, difference, absolute difference, average, weighted average, multiplication, division, minimum, maximum, draw, ratio, and concentration. This is in addition to the signal input conditioning functions (linear, square root, programmable exponent, or round horizontal tank calculations).
The displays, relays, and the analog output may be assigned to input channels A or B, or math result channel C.
Three of the front panel buttons can be custom-programmed for a specific operation.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to power the input transmitters or other devices. An additional isolated 24 VDC power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded DP6060 meter has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power supplies. The DP6060 capabilities may be enhanced by adding the following external expansion modules: four SPST relays –creating an eight-relay dual­input process meter, two digital I/O modules with four inputs and four outputs each, serial communication adapters for use with DP6000-SOFT or Modbus RTU, and a dual 4-20 mA expansion module.
Page 9
DP6060 Dual-Input Process Meter Instruction Manual
9
ORDERING INFORMATION
Standard Display Models
85-265 VAC Model
12/24 VDC Model
Options Installed
DP6060-6R0 DP6060-7R0 No options DP6060-6R2 DP6060-7R2 2 relays DP6060-6R3 DP6060-7R3 4-20 mA output DP6060-6R4 4 relays DP6060-6R5 2 relays & 4-20 mA output DP6060-6R7 4 relays & 4-20 mA output
Sunlight Readable Display Models
85-265 VAC Model
12/24 VDC Model
Options Installed
DP6060-6H0 DP6060-7H0 No options DP6060-6H2 DP6060-7H2 2 relays DP6060-6H3 DP6060-7H3 4-20 mA output
Accessories
Model Description
DPA1002 DIN rail mounting kit for two expansion modules DPA1004 4 SPST (Form A) relays DPA1044 4 digital inputs & 4 digital outputs (2 may be connected) DPA1200 Meter copy cable DPA1232 RS-232 serial adapter DPA1485 RS-485 serial adapter DPA7485-I RS-232 to RS-422/485 isolated converter DPA7485-N RS-232 to RS-422/485 non-isolated converter DPA8008 USB serial adapter DPA8232-N USB to RS-232 non-isolated converter DPA8485-I USB to RS-422/485 isolated converter DPA8485-N USB to RS-422/485 non-isolated converter
Page 10
DP6060 Dual-Input Process Meter Instruction Manual
10
SPECIFICATIONS
Except where noted all specifications apply to oper ation at +25°C.
General
DISPLAY Upper display: 0.60" (15 mm) high, red LEDs
Lower display: 0.46" (12 mm) high, red LEDs 6 digits each (-99999 to 999999), with lead zero blanking
DISPLAY INTENSITY
Eight user selectable intensity levels
DISPLAY UPDATE RATE
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
DISPLAY ASSIGNMENT
The
Upper and Lower displays may be assigned to
process values for Channels A (Ch-A), B (Ch-B), or C (Ch­C), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel & units, show channel gross value (no tare) or toggle net (tare) and gross values, show relay set points, max & min values, or Modbus input. The lower display may also be set to show engineering units or be off, with no display.
PROGRAMMING METHODS
Four front panel buttons, digital inputs, PC and DP6000-SOFT software, Modbus registers, or cloning using Copy function.
NOISE FILTER Programmable from 2 to 199 (0 will disable filter) FILTER BYPASS Programmable from 0.1 to 99.9% of calibrated span RECALIBRATION All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN DISPLAY
Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
PASSWORD
Three programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs.
NON-VOLATILE MEMORY
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
POWER OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or jumper selectable 12/24 VDC  10%, 15 W max
Page 11
DP6060 Dual-Input Process Meter Instruction Manual
11
FUSE Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse
ISOLATED TRANSMITTER POWER SUPPLY
Terminals P+ & P-: 24 VDC  10%. 12/24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal jumper J4). 85-265 VAC models rated @ 200 mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
NORMAL MODE REJECTION
Greater than 60 dB at 50/60 Hz
ISOLATION 4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
OVERVOLTAGE CATEGORY
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
ENVIRONMENTAL Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial communication adapters.
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: black MOUNTING 1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket assemblies are provided.
TIGHTENING TORQUE
Screw terminal connectors: 5 lb-in (0.56 Nm)
OVERALL DIMENSIONS
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
WEIGHT 9.5 oz (269 g) WARRANTY 3 years parts & labor
Page 12
DP6060 Dual-Input Process Meter Instruction Manual
12
Dual Process Input
TWO INPUTS Two inputs, each separately field selectable:
0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
CHANNELS Channel A, Channel B, Channel C (Math channel) PROGRAMMA-
BLE CONSTANTS
Constant P (Adder): -99999 to 999999, default: 0.000 Constant F (Factor): 0.00001 to 999999, default: 1.000
MATH FUNCTIONS
Name Function Setting Addition (A+B+P)*F Sunm
Difference (A-B+P)*F diF Absolute diff. ((Abs(A-B))+P)*F diFAbS Average (((A+B)/2)+P)*F AvG Multiplication ((A*B)+P)*F nmulti Divide ((A/B)+P)*F divide Max of A or B ((AB-Hi)+P)*F Hi-Ab Min of A or B ((AB-Lo)+P)*F Lo-Ab Draw ((A/B)-1)*F drAuw Weighted avg. ((B-A)*F)+A uw avg Ratio (A/B)*F ratio Concentration (A/(A+B))*F Concen Note: The F constant can be any value from 0.00001 to
999999. If the value is less than 1, it will have the same effect as a divider. For example, the average could also be derived by using (A+B)*F, where F = 0.500.
SEQUENCE OF OPERATIONS FOR INPUT PROGRAMMING
1. Select Input for A and B
2. Set up the engineering units for A, B, and C
3. Set up decimal point for A, B, and C
4. Program A & B
5. Set up the displays for A, B, or C
6. Select the transfer function for A & B (e.g. Linear)
7. Select Math function for Channel C
8. Program constants for Factor (F) and Adder (P).
9. Program cutoff values for A and B
ACCURACY ±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range: 10-100% of calibrated span
TEMPERATURE DRIFT
0.005% of calibrated span/C max from 0 to 65C ambient,
0.01% of calibrated span/C max from -40 to 0C ambient
SIGNAL INPUT CONDITIONING
Linear, square root, programmable exponent, or round horizontal tank volume calculation
MULTI-POINT LINEARIZATION
2 to 32 points for channel A and B
PROGRAMMA- 1.0001 to 2.9999
Page 13
DP6060 Dual-Input Process Meter Instruction Manual
13
BLE EXPONENT LOW-FLOW
CUTOFF
0-999999 (0 disables cutoff function)
DECIMAL POINT Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
CALIBRATION RANGE
Input Range
Minimum Span
Input 1 & Input 2 4-20 mA 0.15 mA 10 V
0.10 V
An error message will appear if the input 1 and input 2 signals are too close together.
INPUT IMPEDANCE
Voltage ranges: greater than 500 k Current ranges: 50 - 100
(depending on resettable fuse impedance)
INPUT OVERLOAD
Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
F4 DIGITAL INPUT CONTACTS
3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 DIGITAL INPUT LOGIC LEVELS
Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads
NOISE SUPPRESSION
Noise suppression is recommended for each relay contact switching inductive loads; see page 25 for details.
DEADBAND 0-100% of span, user programmable HIGH OR LOW
ALARM
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
RELAY OPERATION
Automatic (non-latching) Latching (requires manual acknowledge) Sampling (based on time) Pump alternation control (2 to 8 relays) Off (disable unused relays and enable Interlock feature) Manual on/off control mode
Page 14
DP6060 Dual-Input Process Meter Instruction Manual
14
RELAY RESET User selectable via front panel buttons or digital inputs
1. Automatic reset only (non-latching), when the input
passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
TIME DELAY 0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
FAIL-SAFE OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO INITIALIZATION
When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT SOURCE
Process channel A, B, or C, max or min for channel A, B, or highest or lowest max or min of A and B, set points 1-8, Modbus input, or manual control mode
SCALING RANGE 1.000 to 23.000 mA for any display range CALIBRATION Factory calibrated: 4.000 to 20.000 = 4-20 mA output ANALOG OUT
PROGRAMMING
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
ACCURACY ± 0.1% of span ± 0.004 mA TEMPERATURE
DRIFT
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
ISOLATED TRANSMITTER POWER SUPPLY
Terminals I+ & R: 24 VDC 10%. May be used to power the 4-20 mA output or other devices.Refer to Figure 7 on page 22 and Figure 16 on page 26.
All models rated @ 40 mA max.
EXTERNAL LOOP POWER SUPPLY
35 VDC maximum
OUTPUT LOOP RESISTANCE
Power supply Minimum Maximum
24 VDC
10 700
35 VDC (external)
100 1200
Page 15
DP6060 Dual-Input Process Meter Instruction Manual
15
Modbus® RTU Serial Communications
SLAVE ID 1 – 247 (Meter address) BAUD RATE 300 – 19,200 bps TRANSMIT
TIME DELAY
Programmable between 0 and 199 ms
DATA 8 bit (1 start bit, 1 or 2 stop bits) PARITY Even, Odd, or None with 1 or 2 stop bits BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 second
TURN AROUND DELAY
Less than 2 ms (fixed)
Note: Refer to the Modbus Register Tables located at www.omega.com for details.
DPA1044 Digital Input & Output Expansion Module
CHANNELS 4 digital inputs & 4 digital outputs per module SYSTEM Up to 2 modules for a total of 8 inputs & 8 outputs DIGITAL INPUT
LOGIC HIGH
3 to 5 VDC
DIGITAL INPUT LOGIC LOW
0 to 1.25 VDC
DIGITAL OUTPUT LOGIC HIGH
3.1 to 3.3 VDC
DIGITAL OUTPUT LOGIC LOW
0 to 0.4 VDC
SOURCE CURRENT
10 mA maximum output current
SINK CURRENT
1.5 mA minimum input current
+5 V TERMINAL
To be used as pull-up for digital inputs only. Connect normally open contacts across +5 V & DI 1-4.
Page 16
DP6060 Dual-Input Process Meter Instruction Manual
16
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED USA & Canada
UL 508 Industrial Control Equipment
UL FILE NUMBER E356479 FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided LOW VOLTAGE
DIRECTIVE
EN 61010-1:2001 Safety requirements for measurement, control, and laboratory use
Electromagnetic Compatibility
EMISSIONS
EN 55022:2006/A1:2007 Class A ITE emissions requirements
Radiated Emissions
Class A
AC Mains Conducted Emissions
Class A
IMMUNITY
EN 61326-1:2006 Measurement, control, and laboratory equipment
EN 61000-6-2:2005 EMC heavy industrial generic immunity standard
RFI - Amplitude Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast Transients
±2kV AC mains, ±1kV other
Electrostatic Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency Magnetic Field
3 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods 70%V for 25 periods
Voltage Interruptions
<5%V for 250 periods
Page 17
DP6060 Dual-Input Process Meter Instruction Manual
17
Note:
Testing was conducted on DP6060 meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.omega.com
SAFETY INFORMATION
!
CAUTION: Read complete
instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
WARNING! Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
INSTALLATION
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications.
Instructions are provided for setting up a 12/24 VDC powered meter to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 20.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Figure 1 below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Page 18
DP6060 Dual-Input Process Meter Instruction Manual
18
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable Connectors
Figure 2. Panel Mounting Details
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A
: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Page 19
DP6060 Dual-Input Process Meter Instruction Manual
19
MOUNTING DIMENSIONS
Figure 3. Meter Dimensions - Side View
N
O
N
C
N
C
C
N
O
C
N
O
N
C
N
C
C
N
O
C
+
-
R
Figure 4. Meter Dimensions - Top View
Page 20
DP6060 Dual-Input Process Meter Instruction Manual
20
Configuration for 12 or 24 VDC Power Option
Warning!
Do not exceed voltage rating of the selected configuration.
Meters equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power connector, for 12 V as shown below.
MAIN BOARD
24 VDC 12 VDC POWER
J9
12 V
24 V
J9 CONFIGURATION
Factory Default
M-LINK
+ _
Figure 5. Jumper Configuration for 12/24 VDC Power
Page 21
DP6060 Dual-Input Process Meter Instruction Manual
21
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation voltage as shown.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
!
Caution!
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
Page 22
DP6060 Dual-Input Process Meter Instruction Manual
22
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with requested configuration.
Warning!
Do not connect any equipment other than Omega’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Figure 7. Connector Labeling for Fully Loaded DP6060
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 7. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-
Figure 8. Power Connections
Page 23
DP6060 Dual-Input Process Meter Instruction Manual
23
Signal Connections
Signal connections are made to a nine-terminal connector labeled SIGNAL on Figure 7. The COM (common) terminals are the return for the 4-20 mA and the 10 V input signals. The two COM terminals connect to the same common return, and are not isolated.
Current and Voltage Connections
The following figures show examples of current and voltage connections. There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
Figure 9. Transmitters Powered by Internal Supply
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condition, and automatically resets itself when the fault condition is removed.
Page 24
DP6060 Dual-Input Process Meter Instruction Manual
24
Figure 11. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 7. For interfacing to the DP6060, use the DPA1232 for RS-232, the DPA1485 for RS-485, or the DPA8008 for USB. The same port is used for interfacing with all expansion modules
(e.g. external relays, digital I/O).
Use the DPA1200 meter copy cable for meter-to-meter interfacing for
cloning purposes (i.e. copying settings from one meter to other meters).
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 7. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
CNONO NC NC C
RELAY4 RELAY3
4365 21
CNONO NC NC C
RELAY2 RELAY1
4365 21
Figure 12. Relay Connections
Page 25
DP6060 Dual-Input Process Meter Instruction Manual
25
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
C
R
C
R
Figure 13. AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load. Experiment for best results.
Figure 14. Low Voltage DC Loads Protection
Note:
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
Page 26
DP6060 Dual-Input Process Meter Instruction Manual
26
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected with a normally open closure across F4 and COM, or with an active low signal applied to F4.
Figure 15. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
RI- I+
132
RELAY1
321
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
RI- I+
MA OUT
132
RELAY1
321
24 V
MA OUT
Figure 16. 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
Page 27
DP6060 Dual-Input Process Meter Instruction Manual
27
External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules DPA1004 & DPA1044 are connected to the meter using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the
DPA1044 must be removed on the second digital I/O module in order for the system to recognize it as module #2.
Warning!
Do not connect or disconnect the expansion modules with the power on! More detailed instructions are provided with each optional expansion module.
Figure 17. Expansion Modules & DIN Rail Mounting Kit
12
RLY5 RLY6 RLY7 RLY8
345678
NO C NO C NO C NO C
Figure 18. External Relays Module Connections
Page 28
DP6060 Dual-Input Process Meter Instruction Manual
28
123456
+5 I1 I2 I3 I4 O1
78
O2 O3
910
O4 G
DI 1-4 DO 1-4
5 VDC GND
Figure 19. Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page
64). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O contact). See below.
Figure 20. Interlock Connections
Page 29
DP6060 Dual-Input Process Meter Instruction Manual
29
SETUP AND PROGRAMMING
The meter is factory calibrated prior to shipment to read in milliamps and volts, depending on the input selection. The calibration equipment is certified to NIST standards.
Overview
There are no jumpers to set for the meter input selection. Setup and programming is done through the front panel buttons. After power and input signal connections have been completed and verified, apply power to the meter.
Page 30
DP6060 Dual-Input Process Meter Instruction Manual
30
Front Panel Buttons and Status LED Indicators
Button Symbol
Description LED Status
Menu
1-8 Alarm 1-8 indicator
Right arrow/F1
1-8 M
Flashing: Relay in manual control mode
Up arrow/F2
A B C
Channel displayed Flashing: Tare
Enter/F3
1-4
Flashing: Relay interlock switch open
Notes: F4 is a digital input. Alarms 5-8
are enabled when relay expansion module installed.
Note: LEDs for relays in manual mode
flash with the “M” LED every 10 seconds.
Press the Menu button to enter or exit the Programming Mode at
any time.
Press the Right arrow button to move to the next digit during digit or
decimal point programming.
Press or hold the Up arrow button to scroll through the menus,
decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.  Press and hold the Menu button for three seconds to access the
advanced features of the meter.
Page 31
DP6060 Dual-Input Process Meter Instruction Manual
31
Display Functions & Messages
The following table shows the main menu functions and messages in the order they appear in the menu.
Display Parameter Action/Setting Description
setup
Setup
Enter Setup menu
Input
Input
Enter Input selection menu
Ch-A*
Input
Set input type for channel A (*or B)
mA
4-20 mA
Set meter for 4-20 mA input
volt
0-10 VDC
Set meter for 10 VDC input
units
Unit
Select the display units/tags
Ch-A*
Unit
Set unit or tag for channel A (*or B or C)
Dec pt
Decimal point
Set decimal point
Ch-A*
Decimal point
Set decimal point for channel A (*or B or C)
prog
Program
Enter the Program menu
InCAL
Input Calibration
Enter the Input Calibration menu
Ch-A*
Input A
Set input type for channel A (*or B)
SCAL A
Scale A
Enter the Scale menu for channel A
SCAl B
Scale B
Enter the Scale menu for channel B
Cal A
Calibrate A
Enter the Calibration menu for channel A
Cal B
Calibrate B
Enter the Calibration menu for channel B
Inp 1
Input 1
Calibrate input 1 signal or program input 1 value
Dis 1
Display 1
Program display 1 value
Inp 2
Input 2
Calibrate input 2 signal or program input 2 value (up to 32 points)
Dis 2
Display 2
Program display 2 value (up to 32 points)
Error
Error
Error, calibration not successful, check signal or programmed value
dsplay
Display
Enter the Display menu
big
Upper display
Assign the upper display parameter
Page 32
DP6060 Dual-Input Process Meter Instruction Manual
32
Display Parameter Action/Setting Description
Little
Lower display
Assign the lower display parameter
D Ch-A
Display Ch-A
Assign display to channel A
D Ch-B
Display Ch-B
Assign display to channel B
D Ch-C
Display Ch-C
Assign display to channel C (math)
D Ab
Display AB
Alternate display of channel A & B
D AC
Display AC
Alternate display of channel A & C
D BC
Display BC
Alternate display of channel B & C
D AbC
Display ABC
Alternate display of channel A, B, & C
D set1*
Display Set 1*
Displays relay 1(*through 8) set point.
D Hi-A
Display Hi A
Display high value of channel A
D Lo-A
Display Lo A
Display low value of channel A
D HL-A
Display Hi/Low A
Alternate between high/low value of channel A
D Hi-B
Display Hi B
Display high value of channel B
D Lo-B
Display Lo B
Display low value of channel B
D HL-B
Display Hi/Low B
Alternate between high/low value of channel B
D Hi-C
Display Hi C
Display high value of channel C
D Lo-C
Display Lo C
Display low value of channel C
D HL-C
Display Hi/Low C
Alternate between high/low value of channel C
D a-u
Display A and units/tags
Alternate display of channel A and the unit/tag
D B-u
Display B and units/tags
Alternate display of channel B and the unit/tag
D C-u
Display B and units/tags
Alternate display of channel C and the unit/tag
A Gros
Display A gross
Display input channel A gross (no tare)
A nt-G
Display A net and gross
Alternate display of channel A net (tare) and gross (no tare)
B Gros
Display B gross
Display input channel B gross (no tare)
Page 33
DP6060 Dual-Input Process Meter Instruction Manual
33
Display Parameter Action/Setting Description
B nt-G
Display B net and gross
Alternate display of channel B net (tare) and gross (no tare)
m bus
Display Modbus
Display Modbus input register
d-Inty
Display intensity
Set display intensity level from 1 to 8
RELaY
Relay
Enter the Relay menu
Assign
Assignment
Assign relays to channels or Modbus
Asign1
Assign 1
Relay 1 assignment
Ch-A*
Channel A*
Assign relay to channel A (*or B or C)
m bus
Modbus
Assign relay to Modbus register
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-nman
Auto-manual
Set relay for auto or manual reset any time
LatCH
Latching
Set relay for latching operation
Lt-CLr
Latching­cleared
Set relay for latching operation with manual reset only after alarm condition has cleared
Altern
Alternate
Set relay for pump alternation control
SAmpl
Sample
Set relay for sample time trigger control
Off
Off
Turn relay off
FaiLSF
Fail-safe
Enter Fail-safe menu
FLS 1
Fail-safe 1
Set relay 1-8 fail-safe operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe operation
DeLAY
Delay
Enter relay Time Delay menu
DLY 1
Delay 1
Enter relay 1 time delay setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay setup
Page 34
DP6060 Dual-Input Process Meter Instruction Manual
34
Display Parameter Action/Setting Description
break
Loop break
Set relay condition if loop break detected
ignore
Ignore
Ignore loop break condition (Processed as a low signal condition)
On
On
Relay goes to alarm condition when loop break detected
Off
Off
Relay goes to non-alarm condition when loop break detected
Aout
Analog output
Enter the Analog output scaling menu
AOut 1*
Aout Channel
Analog Output source channel (*1-3)
Dis 1
Display 1
Program display 1 value
Out 1
Output 1
Program output 1 value (e.g. 4.000 mA)
Dis 2
Display 2
Program display 2 value
Out 2
Output 2
Program output 2 value (e.g. 20.000 mA)
reset
Reset
Press Enter to access the Reset menu
Rst Hi
Reset high
Press Enter to reset max display
Rst Lo
Reset low
Press Enter to reset min display
Rst HL
Reset high & low
Press Enter to reset max & min displays
Rst tr
Reset tare
Press Enter to reset (cancel) tare
Contrl
Control
Enter Control menu
Auto
Automatic
Press Enter to set meter for automatic operation
mAn
Manual
Press Enter to manually control relays or analog output operation
pass
Password
Enter the Password menu
Pass 1*
Password 1*
Set or enter Password 1 (*through 3)
unloc
Unlocked
Program password to lock meter
locd
Locked
Enter password to unlock meter
999999
-99999
Flashing
Over/under range condition
Page 35
DP6060 Dual-Input Process Meter Instruction Manual
35
Main Menu
The main menu consists of the most commonly used functions: Reset,
Control, Setup
, and Password.
Press Menu button to enter Programming Mode then press the Up
arrow button to scroll main menu.
Press Menu, at any time, to exit and return to Run Mode. Changes
made to settings prior to pressing Enter are not saved.
Changes to the settings are saved to memory only after pressing
Enter.
The display moves to the next menu every time a setting is
accepted by pressing Enter.
Page 36
DP6060 Dual-Input Process Meter Instruction Manual
36
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit value.
The digit being changed is displayed brighter than the rest. Press and hold up arrow to auto-increment the display value. Press the Enter button, at any time, to accept a setting or Menu button
to exit without saving changes.
004.000
004
.
000
00 5
.
000
dis 1 dis 1 dis 1
Next
Setting
Select
Next Digit
Increment
Digital
Value
Accept Setting
Page 37
DP6060 Dual-Input Process Meter Instruction Manual
37
Setting Up the Meter (setup)
The Setup menu is used to select:
1. Input signal the meter will accept for channel A and channel B
2. Units for A, B, and C
3. Decimal point position for A, B, and C
4. Program the meter using the Scale or Calibrate functions
5. Display parameter and intensity
6. Relay assignment and operation
7. 4-20 mA analog output scaling
Press the Menu button to exit at any time.
Page 38
DP6060 Dual-Input Process Meter Instruction Manual
38
Setting the Input Signal (Input)
Enter the Input menu to set up the meter to display current (mA) or
voltage (
volt) inputs for channel A and channel B.
The current input is capable of accepting any signal from 0 to 20 mA. Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC. Select voltage input to accept 0-5, 1-5, 0-10, or
10 VDC signals.
Channel C is the Math Function calculation, which is set up in the Advanced Features menu.
Setting the Decimal Point (dEc pt)
The decimal point may be set with up to five decimal places or with no decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right until no decimal point is displayed, and then it moves to the leftmost position.
There are three decimal points to set up for three channels: Ch-A, Ch-B, and Ch-C.
After the decimal points are set up, the meter moves to the
Program
menu.
Page 39
DP6060 Dual-Input Process Meter Instruction Manual
39
Programming the Meter (prog)
It is very important to read the following information, before proceeding
to program the meter:
The meter is factory calibrated prior to shipment to read in
milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards.
Use the Scale menu to scale the process input (e.g. 4-20 mA). A
calibrated signal source is not needed to scale the meter.
Use the Calibrate menu to apply a signal from a calibrator or a
flowmeter.
The
Program menu contains the Scale and the Calibrate menus for
channels A & B. The process inputs may be calibrated or scaled to any display value
within the range of the meter.
Note: The Scale and Calibrate functions are exclusive of each other. The meter uses the last function programmed. Only one of these methods can be employed at a time. The Scale and Calibrate functions can use up to 32 points (default is 2). The number of points should be set in the Advanced Menu under the menu selection pri or to scaling and calibration of the meter, see page 77 for details.
Page 40
DP6060 Dual-Input Process Meter Instruction Manual
40
Multi-Point Linearization (Linear)
The process inputs may be calibrated or scaled to any display value within the range of the meter.
Additional parameters, not needed for most applications, are programmed in the
Advanced Features menu; see Multi-Point
Linearization
, page 77.
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The number of points for multi-point calibration/scaling is set up in the
Advanced Features menu. Up to 32 linearization points may be
selected. See page 77 for details.
DP6000-SOFT Software
The meter can also be programmed using the PC-based DP6000-SOFT software available for free download at www.omega.com.
Data logging for one meter at the time is available with DP6000-SOFT software. More advanced data acquisition may be accomplished by using any Modbus RTU compliant software.
In order to program the meter using a computer, the meter must be connected using a USB, RS-232, or RS-485 serial adapter, see ORDERING INFORMATION on page 9 for details.
Scaling the Meter without a Signal Source
The process inputs (4-20 mA, 10 VDC) can be scaled to display the process variables in engineering units.
A signal source is not needed to scale the meter; simply program the inputs and corresponding display values.
Page 41
DP6060 Dual-Input Process Meter Instruction Manual
41
Scaling the Meter for Channel A (SCal A)
Scaling the Meter for Channel B (SCal B)
For instructions on how to program
numeric values see
Setting Numeric
Values
, page 36.
Page 42
DP6060 Dual-Input Process Meter Instruction Manual
42
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 2 during calibration or scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is connected backwards.
2. Wrong signal selection in
Setup menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter.
Input Range Input 1 & Input 2 Span
4-20 mA 0.15 mA
10 VDC
0.10 VDC
Calibrating the Meter with External Source
To scale the meter without a signal source refer to
Scaling the Meter without a Signal
Source
, page 40.
Warm up the meter for at least 15 minutes before performing calibration to ensure specified accuracy.
The meter can be calibrated to display the process variable in engineering units by applying the appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to calibrate the meter.
Page 43
DP6060 Dual-Input Process Meter Instruction Manual
43
Calibrating the Meter for Channel A (CAL-A)
Calibrating the Meter for Channel B (CAL-B)
Page 44
DP6060 Dual-Input Process Meter Instruction Manual
44
Setting the Display Parameter & Inte nsity (dsplay)
The Upper display (Big) can be programmed to display:
1. Process value Ch-A
2. Process value Ch-B
3. Process value Ch-C
4. Toggle between Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C,
and Ch-A, Ch-B, & Ch-C
5. Relay set points
6. Max & min values for each channel
7. Toggle between Channel & units
8. Channel gross value (no tare) or toggle net (tare) and gross
values
9. Modbus input
The Lower display (
Little) can be programmed to display:
1. Process value Ch-A
2. Process value Ch-B
3. Process value Ch-C
4. Toggle between Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C,
and Ch-A, Ch-B, & Ch-C
5. Relay set points
6. Max & min values for each channel
7. Toggle between Channel & units
8. Channel gross value (no tare) or toggle net (tare) and gross
values
9. Modbus input
10. Off (no display)
11. Engineering units or custom legends
Display Intensity: The meter has eight display intensity levels to give
the best performance under various lighting conditions. Select intensity 8 for outdoor applications. The default intensity setting is 8.
Page 45
DP6060 Dual-Input Process Meter Instruction Manual
45
Display Setup Menu
After setting up the input and display, press the Menu button to exit programming and skip the rest of the setup menu.
The displays can be set up to read channels A, B, or C, toggle between A & B, B & C, A & C, A & B & C, toggle between channels A, B, or C & units, the max/min of any of the channels, including the math channel (C), set points, gross (without tare) or net (with tare) & gross values of channel A or B, or the Modbus input. In addition to the parameters available on the Upper display, the Lower display can display Engineering units or it could be turned off.
Page 46
DP6060 Dual-Input Process Meter Instruction Manual
46
Setting the Input Units or Custom Tags (units)
Enter the input unit or custom tag that will be displayed if alternating rate, total, or grand total and units is selected in the
units menu, or d
unit
is selected as the lower display parameter. See the flow chart on page 45 to access the display menu to show the unit or tag on the lower display. The engineering units or custom legends can be set using the following 7-segment character set:
Display Character
Display Character
0
0
k
K
1
1
l
L
2
2
m
m
3
3
n
n
4
4
O
O
5
5
o
o
6
6
p
P
7
7
q
q
8
8
r
r
9
9
s
S
A
A
t
t
b
b
u
u
C
C
v
V
c
c
uw
w
d
d
x
X
e
E
y
Y
f
F
z
Z
g
G
-
-
9
g
/
/
H
H
[
]
h
h
]
[
I
I
=
=
I
i
!
Degree(<)
j
J
Space
Notes: Degree symbol represented by (<) if programming with DP6000­SOFT. The letters “m” and “w” use two 7-segment LEDs each; when selected the characters to th e right are shi fted one position .
Press and hold up arrow to auto-scroll the characters in the display.
Page 47
DP6060 Dual-Input Process Meter Instruction Manual
47
Setting the Relay Operation (relay)
This menu is used to set up the assignment and operation of the relays.
!
Caution!
During setup, the relays do not follow the input and they will remain in the state found prior to entering the Relay menu.
1. Relay assignment a. Channel A b. Channel B c. Channel C (Math channel) d. Modbus
2. Relay action a. Automatic reset only (non-latching) b. Automatic + manual reset at any time (non-latching) c. Latching (manual reset only) d. Latching with Clear (manual reset only after alarm
condition has cleared) e. Pump alternation control (automatic reset only) f. Sampling (the relay is activated for a user-specified time) g. Off (relay state controlled by Interlock feature)
3. Set point
4. Reset point
5. Fail-safe operation a. On (enabled) b. Off (disabled)
6. Time delay a. On delay (0-999.9 seconds) b. Off delay (0-999.9 seconds)
7. Relay action for loss (break) of 4-20 mA input (ignore, on, off)
Page 48
DP6060 Dual-Input Process Meter Instruction Manual
48
Setting the Relay Assignment (asSign)
Page 49
DP6060 Dual-Input Process Meter Instruction Manual
49
Setting the Relay Action
Operation of the relays is programmed in the Action menu. The relays
may be set up for any of the following modes of operation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Pump alternation control (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.
Page 50
DP6060 Dual-Input Process Meter Instruction Manual
50
Programming Set and Reset Points
High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point. The deadband is determined by the difference between set and reset points. Minimum deadband is one display count. If the set and reset points are programmed with the same value, the relay will reset one count below the set point.
Note: Changes are not saved until the reset point has been accepted.
Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is energized when the process variable is within safe limits and the relay coil is de-energized when the alarm condition exists. The fail-safe operation is set independently for each relay. Select
on to enable or select off to
disable fail-safe operation.
Programming Time Delay
The On and Off time delays may be programmed for each relay
between 0 and 999.9 seconds. The relays will transfer only after the condition has been maintained for the corresponding time delay.
The
On time delay is associated with the set point.
The
Off time delay is associated with the reset point.
Relay Action for Loss of 4-20 mA Input (Loop Break)
The loop break feature is associated with the 4-20 mA input. Each relay may be programmed to go to one of the following conditions when the meter detects the loss of the input signal (i.e. < 0.005 mA):
1. Turn
On (Go to alarm condition)
2. Turn
Off (Go to non-alarm condition)
3. Ignore (Processed as a low signal condition)
Note: This is not a true loop break condition; if the signal drops below
0.005 mA, it is interpreted as a “loop break” condition.
Page 51
DP6060 Dual-Input Process Meter Instruction Manual
51
Relay and Alarm Operation Diagrams
The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To detect a new alarm condition, the signal must go below the set point, and then go above it.
Page 52
DP6060 Dual-Input Process Meter Instruction Manual
52
Low Alarm Operation (Set < Reset)
Reset
Set
Input
Relay
LED
energized
de-energized
on
off
Relay
LED
Automatic or Manual (non-latching)
ACK
pressed
Relay
LED
Manual (latching)
ACK
pressed
Relay
LED
ACK
pressed
Automatic (non-latching)
Manual only after passing above Reset (latching with clear)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back "on", signal must go above set point, and then go below it.
Page 53
DP6060 Dual-Input Process Meter Instruction Manual
53
High Alarm with Fail-Safe Operation (Set > Reset)
Relay
LED
Input
Automatic (non-latching)
energized
de-energized
off
on
Relay
LED
Automatic or Manual (non-latching)
ACK
pressed
Relay
LED
Manual (latching)
ACK
pressed
Relay
LED
Manual only after passing below Reset (latching with clear)
ACK
pressed
Set
Reset
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
Page 54
DP6060 Dual-Input Process Meter Instruction Manual
54
Low Alarm with Fail-Safe Operation (Set < Reset)
Reset
Set
Input
Relay
LED
Automatic (non-latching)
de-energized
energized
on
off
Relay
LED
Automatic or Manual (non-latching)
ACK
pressed
Relay
LED
Manual (latching)
ACK
pressed
Relay
LED
Manual only after passing above Reset (latching with clear)
ACK
pressed
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
Page 55
DP6060 Dual-Input Process Meter Instruction Manual
55
Pump Alternation Control Operation
Pump 1
Relay1 Set
Relay2 Reset
Relay2 Set
Relay1 Set
Relay2 Set
Input
de-energized energized
Relay1 Set
Relay2 Set
Relay1 &
Relay2 Reset
LEDs indicate the relay status
Input
Input
Relay1 Reset
Relay2 Reset
Relay1 Reset
Pump 2
Pump 1
Pump 2
Pump 1
Pump 2
de-energized energized
de-energized energized
Page 56
DP6060 Dual-Input Process Meter Instruction Manual
56
Relay Sampling Operation
Set
Reset
Relay
LED
Input
Sample
Tim e
Sample
Tim e
Sample
Tim e
When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.
Page 57
DP6060 Dual-Input Process Meter Instruction Manual
57
Signal Loss or Loop Break Relay Operation
The following graph shows the loop break relay operation for a high alarm relay.
Relay
LED
Input
Loop Break = Ignore
de-energized energized
off on
Relay
LED
Loop Break = Off
Relay
LED
Loop Break = On
Set
Reset
When the meter detects a break in the 4-20 mA loop, the relay will go to one of the following selected actions:
1. Turn
On (Go to alarm condition)
2. Turn
Off (Go to non-alarm condition)
3. Ignore (Processed as a low signal condition)
Page 58
DP6060 Dual-Input Process Meter Instruction Manual
58
Time Delay Operation
The following graphs show the operation of the time delay function.
Set
Reset
Relay
LED
*
Input
On Time Delay
<Tdelay <Tdelay >=Tdelay
Set
Reset
Relay
Input
Off Time Delay
<Tdelay <Tdelay >=Tdelay
LED
*
When the signal crosses the set point, the
On time delay timer starts
and the relay trips when the time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the
On time delay timer resets and the relay does not change state. The
same principle applies to the
Off time delay.
Note: IfAutomatic or Manual (A-mAn)” reset mode is selected, the
LED follows the reset point and not the relay state when the relay is acknowledged.
Page 59
DP6060 Dual-Input Process Meter Instruction Manual
59
Relay Operation Details
Overview
The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with alarm and control functions. These capabilities include front panel alarm status LEDs as well as either 2 or 4 optional internal relays and/or 4 external relays expansion module. Typical applications include high or low temperature, level, pressure or flow alarms, control applications such as simple on/off pump control, and pump alternation control for up to 8 pumps. There are four basic ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps
Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm relays will reflect the state of the input to the meter. The following table indicates how the alarm LEDs and relays will react on power-up based on the set and reset points:
Alarm # HI or LO
Alarm
Set
Point
Reset
Point
Power-Up
Reading
Relay &
LED
1 HI 1000 500 499 Off 2 LO 700 900 499 On 3 LO 250 400 499 Off 4 HI 450 200 499 On
Fail-Safe Operation
The following table indicates how the relays behave based on the fail­safe selection for each relay:
Fail-Safe Selection
Non-Alarm State Alarm State Power Failure
NO NC NO NC
Off Open Closed Closed Open Relays go to
non-alarm state
On Closed Open Open Closed Relays go to
alarm state
Note: NO = Normally Open, NC = Normally Closed. This refers to the
condition of the relay contacts when the power to the meter is off.
Page 60
DP6060 Dual-Input Process Meter Instruction Manual
60
Front Panel LEDs
The LEDs on the front panel provide status indication for the following:
LED Status LED Status
1 Alarm 1 5 Alarm 5 2 Alarm 2 6 Alarm 6 3 Alarm 3 7 Alarm 7 4 Alarm 4 8 Alarm 8
The meter is supplied with four alarm points that include front panel LEDs to indicate alarm conditions. This standard feature is particularly useful for alarm applications that require visual-only indication. The LEDs are controlled by the set and reset points programmed by the user. When the display reaches a set point for a high or low alarm, the corresponding alarm LED will turn on. When the display returns to the reset point the LED will go off. The front panel LEDs responds differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition and always on during alarm condition, regardless of the state of the relay (e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflects the status of the relays, regardless of the alarm condition. The following tables illustrate how the alarm LEDs function in relation to the relays and the acknowledge button (Default: F3 key assigned to ACK):
Latching and Non-Latching Relay Operation
The relays can be set up for latching (manual reset) or non-latching (automatic reset) operation.
Relay terminology for following tables
Terminology Relay Condition
On Alarm (Tripped) Off Normal (Reset)
Ack Acknowledged
The On and Off terminology does not refer to the status of the relay’s coil, which depends on the fail-safe mode selected.
Warning!
In latching relay mode, latched relays will reset (unlatch) when power is cycled.
Page 61
DP6060 Dual-Input Process Meter Instruction Manual
61
Non-Latching Relay (Auto)
Automatic reset only
Condition LED Relay
Normal Off Off Alarm On On Ack (No effect) On On Normal Off Off
In this application, the meter is set up for automatic reset (non-latching relay). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm finally goes away, the relay
automatically resets and the LED also goes off.
Non-Latching Relay (A-man)
Automatic + manual reset at any time
Condition LED Relay
Normal Off Off Alarm On On Normal Off Off Next Alarm On On Ack On Off Normal Off Off
In this application, the meter is set up for automatic and manual reset at any time (non-latching relay). The LED and the relay automatically reset when the meter returns to the normal condition. The next time an alarm occurs, the operator acknowledges the alarm manually while the alarm condition still exists. This causes the relay to reset, but the LED stays on until the meter returns to the normal condition.
Latching Relay (LatcH)
Manual reset any time
Condition LED Relay
Normal Off Off Alarm On On
Ack Off Off In this application, the meter is set up for manual reset at any time. Acknowledging the alarm even if the alarm condition is still present resets the relay and turns off the LED.
Page 62
DP6060 Dual-Input Process Meter Instruction Manual
62
Latching Relay (Lt-Clr)
Manual reset only after alarm condition has cleared
Condition LED Relay
Normal Off Off Alarm On On Ack (No effect) On On Normal On On
Ack Off Off In this application, the meter is set up for manual reset only after the signal passes the reset point (alarm condition has cleared). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm is acknowledged after it returns to the normal state, the LED and the relay go off. Notice that the LED remains on, even after the meter returns to the normal condition. This is because, for latching relays, the alarm LED reflects the status of the relay, regardless of the alarm condition.
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual reset:
1. Via the programmable front panel function keys F1-F3 (Default: F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of the digital inputs and the +5 V terminals on the digital I/O modules, or using the F4 digital input, which is triggered with a contact closure to COM, or with an active low signal (see page
26).
When the ACK button or the assigned digital input is closed, all relays programmed for manual reset are acknowledged.
Figure 21. Acknowledge Relays w/Function Key or Digital Input
+5
I1 I2 I3 I4
O1 O2 O3 O4 G
DO 1-4
GND
A
CK
DPA1044 Digital I/O Module
1 2 345 6 7 8 9 10
DI 1-4
Page 63
DP6060 Dual-Input Process Meter Instruction Manual
63
Pump Alternation Control Applications (Altern)
For pump control applications where two or more similar pumps are used to control the level of a tank or a well, it is desirable to have all the pumps operate alternately. This prevents excessive wear and overheating of one pump over the lack of use of the other pumps.
Up to 8 relays can be set up to alternate every time an on/off pump cycle is completed. The set points and reset points can be programmed, so that the first pump on is the first pump off.
Application #1: Pump Alternation Using Relays 1 & 2
1. Relays 1 and 2 are set up for pump alternation.
2. Relays 3 and 4 are set up for low and high alarm indication.
Set and Reset Point Programming with Pump Alternation
Relay Set Point Reset Point Function
1 30.000 10.000 Controls pump 1 & 2 2 35.000 5.000 Sets dual pump trigger 3 4.000 9.000 Controls low alarm 4 40.000 29.000 Controls high alarm
Pump Alternation Operation
1. Pump #1 turns on when level reaches 30.000, when level drops below 10.000 pump #1 turns off.
2. The next time level reaches 30.000, pump #2 turns on, when level drops below 10.000, pump #2 turns off.
3. If the level doesn’t reach 35.000 pump #1 and pump #2 will be operating alternately.
4. If pump #1 cannot keep the level below 35.000 pump #2 will turn on at 35.000, then as the level drops to 10.000 pump #1 turns off, pump #2 is still running and shuts off below 5.000.
5. Notice that with the set and reset points of pump #2 outside the range of pump #1, the first pump on is the first pump to go off. This is true for up to 8 alternating pumps, if setup accordingly.
6. Relay #3 will go into alarm if the level drops below 4.000 and relay #4 will go into alarm if the level exceeds 40.000.
7. Adding the 4 external relays expansion module allows using the 4 SPDT internal relays for pump alternation and the 4 SPST external relays for high, high-high, low, and low-low alarm indication.
Page 64
DP6060 Dual-Input Process Meter Instruction Manual
64
Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature:
1. Access the
Setup – Relay – Action menu and set the action to off.
2. In the Advanced features –
User menu program any of the digital
inputs to
Force On any of the internal relays (1-4).
3. Connect a switch or dry contact between the +5V terminal and the
corresponding digital input (dI-1 to dI-4) terminal.
123456
+5 I1 I2 I3 I4 O1
78
O2 O3
910
O4 G
DI 1-4 DO 1-4
5 VDC GND
SW2
SW1
Page 65
DP6060 Dual-Input Process Meter Instruction Manual
65
Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off) when SW1 & SW2 switches (above) are closed. If the contacts to these digital inputs are opened, the corresponding front panel LEDs flash, indicating this condition. The processes being controlled by the interlock relay will stop, and will re-start only after the interlock relay is re­activated by the digital inputs (switches).
Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is (AND) – i.e. both switches must be closed to trip the relay.
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal for any display range selected. To select the channel the analog output is assigned to, see
Analog Output Source on page 80.
No equipment is needed to scale the analog output; simply program the display values to the corresponding mA output signal.
The
Analog Output menu is used to program the 4-20 mA output based
on display values.
For instructions on how to program
numeric values see
Setting Numeric
Values
, page 36.
**
* IfInstalled
Page 66
DP6060 Dual-Input Process Meter Instruction Manual
66
Reset Menu (reset)
The Reset menu is used to reset the maximum or minimum reading
(peak or valley) reached by the process; both may be reset at the same time by selecting “reset high & low” (
rst HL). The tare value used to
zero the display may be reset by selecting “reset tare” (
rst tr).
Control Menu (Contrl)
The Control menu is used to control the 4-20 mA analog output and the
relays manually, ignoring the input. Each relay and analog output can be programmed independently for manual control. Selecting automatic control sets all relays and analog output for automatic operation.
Page 67
DP6060 Dual-Input Process Meter Instruction Manual
67
Setting Up the Password (pass)
The Password menu is used for programming three levels of security to
prevent unauthorized changes to the programmed parameter settings.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs
.
Protecting or Locking the Meter
Enter the Password menu and program a six-digit password.
For instructions on how to program numeric values see
Setting Numeric
Values
, page 36.
Record the password for future reference. If appropriate, it may be recorded in the space provided.
Model: Serial Number: Password 1: __ __ __ __ __ __ Password 2: __ __ __ __ __ __ Password 3: __ __ __ __ __ __
Page 68
DP6060 Dual-Input Process Meter Instruction Manual
68
Making Changes to a Password Protected Meter
If the meter is password protected, the meter will display the message
Locd (Locked) when the Menu button is pressed. Press the Enter button
while the message is being displayed and enter the correct password to gain access to the menu. After exiting the programming mode, the meter returns to its password protected condition.
Disabling Password Protection
To disable the password protection, access the Password menu and
enter the correct password twice, as shown below. The meter is now unprotected until a new password is entered.
If the correct six-digit password is entered, the meter displays the message
unLoc (Unlocked) and the protection is disabled until a new
password is programmed. If the password entered is incorrect, the meter displays the message
Locd (Locked) for about two seconds, and then it returns to Run Mode.
To try again, press Enter while the
Locked message is displayed.
Did you forget the password?
The password may be disabled by entering a master password once. If you are authorized to make changes, enter the master password 508655 to unlock the meter.
Page 69
DP6060 Dual-Input Process Meter Instruction Manual
69
Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the
Advanced Features menu.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
Page 70
DP6060 Dual-Input Process Meter Instruction Manual
70
Advanced Features Menu & Display Messages
The following table shows the functions and messages of the Advanced
Features
menu in the order they appear in the menu.
Display Parameter Action/Setting
filtEr
Filter
Set noise filter value
Ch-A
Channel A
Set filter value for channel A
Ch-b
Channel B
Set filter value for channel B
bypASs
Bypass
Set filter bypass value
Ch-A
Channel A
Set filter bypass value for channel A
Ch-b
Channel B
Set filter bypass value for channel B
Round
Round
Set the rounding value for display variables
seriAl
Serial
Set serial communication parameters
SlaveId
Slave ID
Set slave ID or meter address
Baud
Baud rate
Select baud rate
Tr dLY
Transmit delay
Set transmit delay for serial communication
Parity
Parity
Select parity Even, Odd, or None with 1 or 2 stop bits
t-byt
Time byte
Set byte-to-byte timeout
SelEct
Select
Enter the Select menu (function, cutoff, out)
Functn
Signal input conditioning
Select linear, square root, programmable exponent, or round horizontal tank function
Ch-A
Channel A
Select menu for channel A
Ch-b
Channel B
Select menu for channel B
Linear
Linear
Set meter for linear function and select number of linearization points
No pts
Number of points
Set the number of linearization points (default: 2)
Square
Square root
Set meter for square root extraction
Prog E
Programmable exponent
Set meter for programmable exponent and enter exponent value
Rht
Round horizontal tank
Set meter for round horizontal tank volume calculation
Length
Length
Enter the tank’s length in inches
dianmr
Diameter
Enter the tank’s diameter in inches
nmath
Math
Enter the setup menu for channel C math functions
Sunm
Sum
Channel C = (A+B+P)*F
Dif
Difference
Channel C = (A-B+P)*F
difabs
Absolute difference
Channel C = ((Absolute value of (A­B))+P)*F
Avg
Average
Channel C = (((A+B)/2)+P)*F
nmulti
Multiplication
Channel C = ((A*B)+P)*F
Page 71
DP6060 Dual-Input Process Meter Instruction Manual
71
Display Parameter Action/Setting
Divide
Divide
Channel C = ((A/B)+P)*F
Hi-ab
Max of A or B
C = ((High value of channel A or B)+P)*F
Lo-ab
Min of A or B
C = ((Low value of channel A or B)+P)*F
Drauw
Draw
Channel C = ((A/B)-1)*F
uwAvg
Weighted avg.
Channel C = ((B-A)*F)+A
ratio
Ratio
Channel C = (A/B)*F
Concen
Concentration
Channel C = (A/(A+B))*F
Const
Constant
Constant used in channel C math
adder
Adder
Addition constant used in channel C math calculations (P)
factor
Factor
Multiplication constant used in channel C math calculations (F)
CutofF
Cutoff
Set low-flow cutoff
Ch-A
Channel A
Set low-flow cutoff for Channel A
Ch-b
Channel B
Set low-flow cutoff for Channel B
AoutPr
Analog output programming
Program analog output parameters
AOut 1*
Analog output 1
Program analog output 1 (*1-3) parameters
Source
Source
Select source for the 4-20 mA output
break
Loop break
Set relay condition if loop break detected
O-rang
Overrange
Program mA output for display overrange
u-rang
Underrange
Program mA output for display underrange
nmAx
Maximum
Program maximum mA output allowed
nmin
Minimum
Program minimum mA output allowed
Calib
Calibrate
Calibrate 4-20 mA output (internal reference source used for scaling the output)
4 nmA
4 mA output
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
20 nmA
20 mA output
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
User
User I/O
Assign function keys and digital I/O
F1*
F1* function key
Assign F1 function key (*F1/F2/F3)
F4
F4 function
Assign F4 function (digital input)
dI I
Digital input 1
Assign digital input 1 – 8, if expansion modules are connected
dO 1
Digital output 1
Assign digital output 1 – 8, if expansion modules are connected
ICal
Internal calibration
Enter internal calibration (used for recalibrating the meter with a calibrated signal source)
Ch-A
Channel A
Perform calibration on channel A
Ch-b
Channel B
Perform calibration on channel B
Page 72
DP6060 Dual-Input Process Meter Instruction Manual
72
Display Parameter Action/Setting
C CAL
Current calibration
Calibrate 4-20 mA current input (internal reference source used for scaling the input)
C lo
Current low
Calibrate low current input (e.g. 4 mA)
C Hi
Current high
Calibrate high current input (e.g. 20 mA)
v CAL
Voltage calibration
Calibrate voltage input
v Lo
Voltage low
Calibrate low voltage input (e.g. 0 V)
v Hi
Voltage high
Calibrate high voltage input (e.g. 10 V)
Copy
Copy
Enter copy function
Send
Send
Send meter settings to another meter
Done
Done
Copy function completed
Diag
Diagnostics
Display parameter settings
LED t
LED test
Test all LEDs
Info
Information
Display software and S/N information
Page 73
DP6060 Dual-Input Process Meter Instruction Manual
73
Noise Filter (filter)
The noise filter is available for unusually noisy signals that cause an unstable process variable display. The noise filter averages the input signal over a certain period. The filter level determines the length of time over which the signal is averaged. The filter level can be set between 2 and 199. The higher the filter level, the longer the averaging time and so the longer it takes the display to settle to its final value. Setting the filter level to zero disables the filter function.
Noise Filter Bypass (bypass)
The noise filter bypass changes the behavior of the meter so that small variations in the signal are filtered out but large abrupt changes in the input signal are displayed immediately. The bypass value determines the minimum amount of signal change to be displayed immediately. All signal changes smaller than the bypass value are filtered or averaged by the meter. The noise filter bypass may be set between 0.1 and
99.9% of full scale.
Page 74
DP6060 Dual-Input Process Meter Instruction Manual
74
Rounding Feature (round)
The rounding feature is used to give the user a steadier display with fluctuating signals. Rounding is used in addition to the filter function.
Rounding causes the display to round to the nearest value according to the rounding selected. This setting affects the last two digits, regardless of decimal point position.
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an RS-232, RS-485, or USB adapter option is required; see
Ordering
Information
on page 9 for details.
Warning!
Do not connect any equipment other than Omega’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Note: More detailed instructions are provided with each optional serial
communications adapter. Note: Refer to the Modbus Register Tables located at www.omega.com for details.
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
Page 75
DP6060 Dual-Input Process Meter Instruction Manual
75
Select Menu (SElect)
The Select menu is used to select the signal input conditioning function
applied to the inputs (linear, square root, programmable exponent, or round horizontal tank), math function for A & B, constants, low-flow cutoff, and analog output programming. The multi-point linearization is part of the linear function selection.
Page 76
DP6060 Dual-Input Process Meter Instruction Manual
76
Signal Input Conditioning (Functn)
The Function menu is used to select the input-to-output transfer function
applied to the input signal: linear, square root, programmable exponent, or round horizontal tank volume calculation. The multi-point linearization is part of the linear function selection.
Meters are set up at the factory for linear function with 2-point linearization. The linear function provides a display that is linear with respect to the input signal.
Square Root Linearization (Square)
The square root function is used to calculate flow measured with a differential pressure transmitter. The flow rate is proportional to the square root of the differential pressure. Scale the meter so that the low input signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20 mA) is equal to the maximum flow.
Programmable Exponent Linearization (Prog E)
The programmable exponent function is used to calculate open-channel flow measured with a level transmitter in weirs and flumes. The flow rate is proportional to the head height. Scale the meter so that the low input signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20 mA) is equal to the maximum flow. This method works well for all weirs and flumes that have a simple exponent in the flow calculation formula. For weirs and flumes with complex exponents it is necessary to use a strapping table and the 32-point linearization of the meter.
Page 77
DP6060 Dual-Input Process Meter Instruction Manual
77
Multi-Point Linearization (Linear)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points can be selected for each channel under the linear function. The multi-point linearization can linearize the display for non-linear signals such as those from level transmitters used to measure volume in odd-shaped tanks or to convert level to flow using weirs and flumes with complex exponent.
Round Horizontal Tank Linearization (rHt)
This function is used to calculate volume in a round horizontal tank with flat ends. The volume is calculated based on the diameter and length of the tank. The tank’s dimensions can be entered in inches or centimeters; the meter automatically calculates the volume in gallons or liters. After entering the dimensions, complete the scaling process with the display values calculated by the meter. The meter can be re-scaled to display the volume in any engineering unit without the need to re­enter the dimensions again.
Note: After Scale is displayed continue pressing the Enter button until
the meter completes the scaling of the input and display values.
Page 78
DP6060 Dual-Input Process Meter Instruction Manual
78
Changing the Volume from Gallons to Liters
In the above graphic, entering the 48" for the diameter and 120" for the length of the round horizontal tank, the meter automatically calculates that the volume of the tank is 940.02 gallons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the
Setup menu and change the decimal point to 1 decimal.
3. Go to the
Program – Scale menu and press Enter until dis 2 is
shown on the Upper display.
4. Press Enter and change the display 2 value to 3558.4.
5. The meter is now displaying the volume in liters.
Note: The display can be scaled to display the volume in any
engineering units.
Math Function (math)
The Math menu is used to select the math function that will determine
the channel C value. These math functions are a combination of input channels A and B, and will display when channel C is selected in the
Display menu.
The following math functions are available.
Function Display Description
Sunm
Sum
Channel C = (A+B+P)*F
Dif
Difference
Channel C = (A-B+P)*F
difabs
Absolute difference
Channel C = ((Absolute value of (A­B))+P)*F
Avg
Average
Channel C = (((A+B)/2)+P)*F
nmulti
Multiplication
Channel C = ((A*B)+P)*F
Divide
Divide
Channel C = ((A/B)+P)*F
Hi-ab
Max of A or B
C = ((High value of channel A or B)+P)*F
Lo-ab
Min of A or B
C = ((Low value of channel A or B)+P)*F
Drauw
Draw
Channel C = ((A/B)-1)*F
uwAvg
Weighted avg.
Channel C = ((B-A)*F)+A
ratio
Ratio
Channel C = (A/B)*F
Concen
Concentration
Channel C = (A/(A+B))*F
Page 79
DP6060 Dual-Input Process Meter Instruction Manual
79
Math Constants (Const)
The Math Constants menu is used to set the constants used in channel
C math. The math functions include input channel A and B, as well as the adder constant P, and factor constant F.
The
Adder constant (P) may be set from -99.999 to 999.999.
The
Factor constant (F) may be set from 0.001 to 999.999.
The chart on page 78 details the math functions that may be selected in the
Math Function menu.
Low-Flow Cutoff (CutofF)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will display zero below the cutoff value. Programming the cutoff value to zero disables the cutoff feature.
Analog Output Programming (AoutPr)
The Analog Output Programming menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are programmed in this menu:
1. Source: Source for generating the 4-20 mA output
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to scale the 4-20 mA output
Page 80
DP6060 Dual-Input Process Meter Instruction Manual
80
Analog Output Source
The analog output source can be based on either of the input channels (Ch-A, Ch-B), the math channel (Ch-C), maximum stored value of either input channel (Hi-A, Hi-B), minimum stored value of either input channel (Lo-A, Lo-B), relay set points, or the Modbus input.
Analog Output Calibration
To perform the analog output calibration it is recommended to use a milliamp meter with a resolution of at least 0.1 µA to measure the output current. The values saved internally during this procedure are used for scaling the 4-20 mA output in the
Setup menu.
Page 81
DP6060 Dual-Input Process Meter Instruction Manual
81
Programmable Function Keys User Menu (user)
The User menu allows the user to assign the front panel function keys
F1, F2, F3, F4 (digital input) and up to eight digital inputs to access most of the menus or to activate functions immediately (e.g. Reset max & min). F4 is a digital input on the signal input connector. Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter (e.g. Alarms, relay acknowledgement, etc.).
Please refer to the table below, which continues on the following page.
Function Keys & Digital I/O Available Settings
Display Description Display Description
Rst HL
Reset max & min (A, B, C)
Big Hi
Max on upper display (Channel A)
relay
Relay menu
Big Lo
Min on upper display (Channel A)
Set 1
Set point 1 - 8
Big HL
Max/min upper display (Channel A)
Rly d
Disable relay
Lit Hi
Max on lower display (Channel B)
Rly E
Enable relay
Lit Lo
Min on lower display (Channel B)
O Hold
Relay output hold
Lit HL
Max/min lower display (Channel B)
D Hold
Display hold while active
Lit HC
Max on lower display (Channel C)
D AbC
Scrolls values for A, B & C when activated. Keeps the last value for 10 seconds and then it returns to its assignment. Values are displayed on the upper display and the corresponding channel and units on the Lower display.
Lit LC
Min on lower display (Channel C)
*If installed
Page 82
DP6060 Dual-Input Process Meter Instruction Manual
82
Display Description Display Description
LitHLC
Max/min lower display (Channel C)
menu
Menu button
disabl
Disable function key
Right
Right arrow button
Contrl
Control Menu
up
Up arrow button
Tare a
Set channel A display value to zero (A LED flashes – same rate as M)*
Enter
Enter button
Tare b
Set channel B display value to zero (B LED flashes – same rate as M)*
Alrm 1
Alarm 1 – 8 (Digital Output)
Rst tr
Reset tare for A & B (Channel LED off)
F on 1
Force on relay 1
AcH
Acknowledge relays
F on 2
Force on relay 2
reset
Reset Menu
F on 3
Force on relay 3
Rst Hi
Reset max
F on 4
Force on relay 4
Rst Lo
Reset min
* If math functions are displayed, the math function indicator LED “C”
will flash when either A or B channel is using a tare value (net value).
Page 83
DP6060 Dual-Input Process Meter Instruction Manual
83
Tare (tare A, tare B)
The tare function zero’s out the display. In the case of scale weight, tare is used to eliminate container weight and provide net weight readings. There are two tare functions; Capture Tare for channel A and B, and Reset Tare. Display channel indicator letter flashes when a tare is used. It will flash until the tare is reset.
Gross (without tare) and net (with tare) values can be viewed simultaneously. See page 44.
Internal Calibration (ICAL)
The meter is factory calibrated prior to shipment
to read in milliamps and volts depending on the
input selection. The calibration equipment is
certified to NIST standards.
The use of calibrated signal sources is necessary to perform the internal calibration of the meter.
Check calibration of the meter at least every 12 months. Each input and input type must be recalibrated separately.
The
Internal calibration menu is part of the Advanced Features menu.
1. Press and hold the Menu button for three seconds to access the advanced features of the meter.
2. Press the Up
arrow button to scroll to the Internal calibration menu
(
ICAL) and press Enter.
3. Select channel A (
Ch-A) or channel B (Ch-b) and press enter.
Notes:
1. If meter is in operation and it is intended to accept only one input type (e.g. 4-20 mA), recalibration of other input is not necessary.
2. Allow the meter to warm up for at least 15 minutes before performing the internal calibration pr ocedure.
0.0
lbs
0.2
lbs
0.2
lbs
Before tare
After capture tare
After reset tare
Page 84
DP6060 Dual-Input Process Meter Instruction Manual
84
4. The meter displays either current calibration (
C CAL) or voltage
calibration (
v CAL), according to the input setup. Press Enter to
start the calibration process.
Example of Internal Calibration for current input:
5. The meter displays low input current message (C lo). Apply the
low input signal and press Enter. The display flashes for a moment while the meter is accepting the low input signal.
6. After the display stops flashing, a number is displayed with the leftmost digit brighter than the rest. The bright digit is the active digit that can be changed by pressing the Up
arrow button. Press the
Right
arrow button to move to the next digit.
7. Set the display value to correspond to the input signal being calibrated, typically 4.000 mA.
8. The display moves to the
high input calibration (C Hi). Apply the
high input signal and press Enter.
9. Set the display for the high input calibration, in the same way as it was set for the low input calibration, typically 20.000 mA.
The graphic above shows the calibration of the current input. The voltage input is calibrated in a similar way.
Tips:
Low and high input signals can be any valid values within the
range of the meter.
Observe minimum input span requirements between input 1
and input 2.
Low input should be less than high input signal.
Page 85
DP6060 Dual-Input Process Meter Instruction Manual
85
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 2 during calibration or scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is connected backwards.
2. Wrong signal selection in
Setup menu.
3. Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter.
Input Range Input 1 & Input 2 Span 4-20 mA 0.15 mA
10 VDC
0.10 VDC
Meter Copy Function (Copy)
The Copy function is used to copy (or clone) all the settings from one
meter to other meters requiring exactly the same setup and programming (
i.e. type of input, scaling, decimal point, filter, bypass,
etc.).
Warning!
Only the DPA1200 meter copy cable must be used for meter-to-meter interfacing.
Using standard CAT5 or other cable will cause damage to both meters.
Copy Function Requirements
To successfully copy settings from one meter to another, both meters must have the same software version and the same baud rate setting.
See Determining Software Version, page 89 for instructions.
Page 86
DP6060 Dual-Input Process Meter Instruction Manual
86
Meter Copy or Cloning Instructions
!
Caution!
Do not connect the two meters to the same signal source while cloning. Internal calibration may be affected.
1. Connect two meters using a DPA1200 meter copy cable.
Warning!
Using standard CAT5 or other cable will cause damage to both meters. Use DPA1200 meter copy cable only.
2. Do not connect the two meters to the same signal source.
3. Power up both meters. Leave Clone meter in Run Mode.
4. Enter the
Advanced Features menu of the Master meter; see
Advanced Features Menu on page 69.
5. Scroll to the
Copy function using the Up arrow button then press
Enter.
6. The meter displays the message
Send. Press Enter, the display
flashes while sending data. The message
done is displayed when
copying is completed.
7. The Clone meter displays the message CPY Rc while being programmed then the message
done when copying is completed.
The meter initializes and returns to Run Mode using the same settings as the Master.
8. If meter to be cloned does not respond to the data being sent, refer to
Copy Function Requirements above.
Page 87
DP6060 Dual-Input Process Meter Instruction Manual
87
METER OPERATION
The meter is capable of accepting two input channels (A and B) of either current (0-20 mA, 4-20 mA) or voltage signals (0-5 V, 1-5 V, 0-10 V,
10 V) and displaying these signals in engineering units from -99999 to 999999 (
e.g. a 4-20 mA signal could be displayed as -50.000 to
50.000).
A math function channel (C) is available to perform operations on channel A and B, with adder and factor constants, and display the results. Engineering units or tags may be displayed with these three channels.
The dual-line display can be customized by the user. Typically the upper display is used to display the math channel C, while the lower display is used to alternate between displaying input channels A and B.
Additionally the meter can be set up to display any input or math channel on the upper display and a unit or tag on the lower display. The relays and analog output can be programmed to operate based on any input or math channel.
Front Panel Buttons Operation
Button Symbol
Description
Press to enter or exit Programming Mode, view settings, or exit max/min readings
Press to reset max/min readings or other parameter/function assigned through the
User
menu
Press to display max/min readings for channel A or other parameter/function assigned through the
User menu
Press to acknowledge relays or other parameters/function assigned through the
User menu
Function Keys Operation
During operation, the programmable function keys operate according to the way they have been programmed in the
Advanced Features – User
menu. The table above shows the factory default settings for F1, F2, and F3.
Page 88
DP6060 Dual-Input Process Meter Instruction Manual
88
F4 Operation
A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active low signal. During operation, F4 operates according to the way is has been programmed in the
Advanced Features – User menu.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be displayed either continuously or momentary:
1. Display briefly by assigning to the F1-F3 function keys or to the
digital inputs in the
User menu.
2. Display continuously by assigning either display to max/min
through the
Display menu.
Any of the F1-F3 function keys (buttons) and the digital inputs can be programmed to reset the max & min readings. The meters are set at the factory to display the max reading by pressing the Up arrow/F2 button and to use the Right arrow/F1 button to access the
Reset menu.
To display max and min channel A reading using function key with factory defaults:
1. Press Up arrow/F2 button to display minimum reading of channel A since the last reset/power-up. The display will then display the maximum reading of channel A since the last reset/power-up.
2. Press the Up arrow/F2 button again to display the minimum reading of channel A since the last reset/power up.
3. To reset max/min press Right arrow/F1 button to access the Reset menu. The max & min displays are reset to actual values.
4. Press Menu to exit max/min display reading.
Page 89
DP6060 Dual-Input Process Meter Instruction Manual
89
TROUBLESHOOTING
The rugged design and the user-friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual. However, due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see.
If the meter is not working as expected, refer to the
Diagnostics menu
and recommendations below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the Advanced Features menu, to
access
Diagnostics menu see Advanced Features Menu, page 69.
It provides an easy way to view the programmed parameter settings for troubleshooting purposes. Press the Enter
button to view the settings
and the Menu button to exit at any time. For a description of the diagnostic messages,
see Advanced Features
Menu &
Display Messages, page 70.
Determining Software Version
To determine the software version of a meter:
1. Go to the
Diagnostics menu (diAG) and press Enter button.
2. Press Up arrow button and scroll to Information menu (
Info).
3. Press Enter to access the software number (
SFT) and version
(
UER) information. Write down the information as it is displayed.
Continue pressing Enter until all the information is displayed.
4. The meter returns to Run Mode after displaying all the settings.
Page 90
DP6060 Dual-Input Process Meter Instruction Manual
90
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features menu. See Advanced Featur es
Menu
, page 69.
2. Press Up arrow to go to
Diagnostics menu
3. Press and hold Right arrow for three seconds, press Enter when display flashes
reset.
Note: If Enter is not pressed within three seconds, the display returns to Run Mode.
4. The meter goes through an initialization sequence (similar as on power-up), and loads the factory default settings.
Page 91
DP6060 Dual-Input Process Meter Instruction Manual
91
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the meter. Next to the factory setting, the user may record the new setting for the particular application.
Model: ______________ S/N: _______________ Date: ___________
Parameter Display Default Setting User Setting
Input type
Input
Input type, channel A
Ch-A
4-20 mA
Input type, channel B
Ch-B
4-20 mA
Unit
unit
Unit, channel A
Ch-A
mA-A
Unit, channel B
Ch-B
mA-B
Unit, channel C
Ch-C
mA-C
Number of points
No pts
Number of points, ch A)
Ch-A
2
Number of points, ch B)
Ch-B
2
Scaling, (channel A)
Scal a
Input 1, channel A
InP 1
4.000 mA
Display 1, channel A
Dis 1
4.000
Input 2, channel A
InP 2
20.000 mA
Display 2, channel A
Dis 2
20.000
Scaling (channel B)
Scal b
Input 1, channel B
InP 1
4.000 mA
Display 1, channel B
Dis 1
4.000
Input 2, channel B
InP 2
20.000 mA
Display 2, channel B
Dis 2
20.000
Math, channel C
Sum
Sum
Adder (constant P)
Adder
0.000
Factor (constant F)
Factor
1
Filter
Filter
Filter, channel A
Ch-A
70
Filter, channel B
Ch-B
70
Bypass, channel A
bypass
0.2
Bypass, channel B
bypass
0.2
Round
Round
1
Cutoff
Cutoff
Cutoff value, channel A
Ch-a
0.000 (disabled)
Cutoff value, channel B
Ch-b
0.000 (disabled)
Display assignment
Dsplay
Upper display
D Ch-A
Channel A
Lowerdisplay
d Ch-B
Channel B
Display intensity
d-Inty
8
Relay 1 assignment
Ch-A
Channel A
Page 92
DP6060 Dual-Input Process Meter Instruction Manual
92
Parameter Display Default Setting User Setting
Relay 1 action
Act 1
Automatic
Relay 1 set point
Set 1
1.000
Relay 1 reset point
RSt 1
0.500
Relay 2 assignment
Ch-A
Channel A
Relay 2 action
Act 2
Automatic
Relay 2 set point
Set 2
2.000
Relay 2 reset point
RSt 2
1.500
Relay 3 assignment
Ch-A
Channel A
Relay 3 action
Act 3
Automatic
Relay 3 set point
Set 3
3.000
Relay 3 reset point
RSt 3
2.500
Relay 4 assignment
Ch-A
Channel A
Relay 4 action
Act 4
Automatic
Relay 4 set point
Set 4
4.000
Relay 4 reset point
RSt 4
3.500
Fail-safe relay 1
Fls 1
Off
Fail-safe relay 2
Fls 2
Off
Fail-safe relay 3
Fls 3
Off
Fail-safe relay 4
Fls 4
Off
On delay relay 1
On 1
0.0 sec
Off delay relay 1
Off 1
0.0 sec
On delay relay 2
On 2
0.0 sec
Off delay relay 2
Off 2
0.0 sec
On delay relay 3
On 3
0.0 sec
Off delay relay 3
Off 3
0.0 sec
On delay relay 4
On 4
0.0 sec
Off delay relay 4
Off 4
0.0 sec
Loop break relay 1
ignore
Ignore
Loop break relay 2
ignore
Ignore
Loop break relay 3
ignore
Ignore
Loop break relay 4
ignore
Ignore
Display 1 analog out
Dis 1
4.000
Output 1 value
Out 1
4.000 mA
Display 2 analog out
Dis 2
20.000
Output 2 value
Out 2
20.000 mA
Source analog output
Source
Channel A
Overrange output
O-rang
21.000 mA
Underrange output
u-rang
3.000 mA
Loop break output
break
1.000 mA
Maximum output
mAx
23.000 mA
Minimum output
min
1.000 mA
Slave ID (Address)
SlavId
247
Baud rate
baud
9600
Page 93
DP6060 Dual-Input Process Meter Instruction Manual
93
Parameter Display Default Setting User Setting
Transmit delay
Tr dly
50 ms
Parity
Parity
Even
Byte-to-byte timeout
t-byt
010 (0.1 sec)
F1 function key
F1
Reset max & min
F2 function key
F2
Upper Max & Min
F3 function key
F3
Acknowledge relays F4 function (digital input)
F4
Acknowledge relays
Digital input 1
DI 1
Menu Digital input 2
DI 2
Right arrow Digital input 3
DI 3
Up arrow Digital input 4
DI 4
Enter Digital output 1
DO 1
Alarm 1 Digital output 2
DO 2
Alarm 2 Digital output 3
DO 3
Alarm 3 Digital output 4
DO 4
Alarm 4 Password 1
Pass 1
000000 (unlocked) Password 2
Pass 2
000000 (unlocked) Password 3
Pass 3
000000 (unlocked)
Alphabetical List of Display Functions & Messages
Display Parameter Action/Setting Description
-99999
Flashing
Underrange condition
999999
display
Overrange condition
20 ma
20 mA output
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
4 ma
4 mA output
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
A Gros
Display A gross
Display input channel A gross (no tare)
A nt-G
Display A net and gross
Alternate display of channel A net (tare) and gross (no tare)
Ack
Acknowledge
Acknowledge relays
Act 1
Action 1
Set relay 1 action
Adder
Adder
The channel C math function adder constant P
Alm 1
Alarm 1
Assign digital output to Alarm 1-8
Altern
Alternate
Set relay for pump alternation control
A-man
Auto-manual
Set relay for automatic & manual reset
Aout
Analog output
Enter the Analog output scaling menu
AOut 1*
Aout Channel
Analog Output source channel (*1-3)
Aoutpr
Analog output programming
Enter analog output programming
Assign
Assign
Enter the relay channel assignment menu
Page 94
DP6060 Dual-Input Process Meter Instruction Manual
94
Display Parameter Action/Setting Description
Auto
Automatic
Press Enter to set automatic operation
Avg
Average
Channel C = (((A+B)/2)+P)*F
B Gros
Display B gross
Display input channel B gross (no tare)
B nt-G
Display B net and gross
Alternate display of channel B net (tare) and gross (no tare)
baud
Baud rate
Select baud rate
Big
Upper display
Press Enter to assign the upper display parameter (default: Ch-A)
Big Hi
Max on Upper display
Assign digital input to display max on the upper display (channel A)
Big HL
Max/min Upper display
Assign digital input to toggle max/min on the upper display (channel A)
Big Lo
Min on Upper display
Assign digital input to display min on the upper display (channel A)
break
Loop break
Set relay condition if loop break detected
bypASs
Bypass
Set filter bypass value
C CAL
Current calibration
Calibrate 4-20 mA current input (internal reference source used for scaling the input)
C Hi
Current high
Calibrate high current input (e.g. 20 mA)
C lo
Current low
Calibrate low current input (e.g. 4 mA)
Cal A
Calibrate A
Enter the Calibration menu for channel A
Cal B
Calibrate B
Enter the Calibration menu for channel B
Calib
Calibrate
Calibrate 4-20 mA output (internal reference source used for scaling the output)
Ch-A*
Channel A*
Channel A (*B or C) selection
Cm
Centimeter
Select cm as the tank unit of measurement
Concen
Concentration
Channel C = (A/(A+B))*F
Const
Constant
Enter the math function constant menu
Contrl
Control
Enter Control menu to turn relays on/off, set
analog output manually, or return meter to automatic operation
Copy
Copy
Enter copy function
CutofF
Cutoff
Set low-flow cutoff (ch-A, ch-B)
D Ab
Display A & B
Alternate display of channel A & B
D AbC
Display A, B,&C
Alternate display of channel A, B, & C
D AC
Display A & C
Alternate display of channel A & C
D a-u
Display A and units/tags
Alternate display of channel A and the unit/tag
D BC
Display B & C
Alternate display of channel B & C
D B-u
Display B and units/tags
Alternate display of channel B and the unit/tag
D Ch-A
Display Ch-A
Assign display to channel A
D Ch-B
Display Ch-B
Assign display to channel B
Page 95
DP6060 Dual-Input Process Meter Instruction Manual
95
Display Parameter Action/Setting Description
D Ch-C
Display Ch-C
Assign display to channel C (math)
D C-u
Display C and units/tags
Alternate display of channel C and the unit/tag
D Hi-A
Display Hi A
Display high value of channel A
D Hi-B
Display Hi B
Display high value of channel B
D Hi-C
Display Hi C
Display high value of channel C
D HL-A*
Display Hi/Low A*
Alternate between high/low value of channel A (*or B or C)
D Hold
Display Hold
Set digital inputs and function keys for display hold
D Lo-A
Display Lo A
Display low value of channel A
D Lo-B
Display Lo B
Display low value of channel B
D Lo-C
Display Lo C
Display low value of channel C
D off
Display off
Display off (blank)
D unit
Display unit
Display unit of channel A
Dec pt
Decimal point
Set decimal point
DeLAY
Delay
Enter relay Time Delay menu
Di 1
Digital input 1
Assign digital input 1-8, if expansion modules are connected
Diag
Diagnostics
Display parameter settings
diamr
Diameter
Enter the tank’s diameter in inches or cm
Dif
Difference
Channel C = (A-B+P)*F
difabs
Absolute difference
Channel C = ((Absolute value of (A­B))+P)*F
d-Inty
Display intensity
Set display intensity level from 1 to 8
Dis 1
Display 1
Program display 1 value
Dis 2
Display 2
Program display 2 value (up to 32 points)
disabl
Disable
Disable function key
Divide
Divide
Channel C = ((A/B)+P)*F
DLY 1
Delay 1
Enter relay 1 time delay setup (1-8)
Do 1
Digital output 1
Assign digital output 1 – 8, if expansion modules are connected
done
Done
Copy function completed
Drauw
Draw
Channel C = ((A/B)-1)*F
Dset 1
Display set 1
Select to display set point 1 (1-8)
dsplay
Display
Enter the Display menu
Enter
Enter button
Assign digital input to Enter button/F3
Error
Error
Error, calibration not successful, check signal or programmed value
F On 1
Force On 1
Force relay 1 on using and digital input
F1*
F1 function key
Assign F1 (*or F2 or F3) function key
Page 96
DP6060 Dual-Input Process Meter Instruction Manual
96
Display Parameter Action/Setting Description
F4
F4 function
Assign F4 function (digital input)
Factor
Factor
The channel C math function multiplication factor constant F
FaiLSF
Fail-safe
Enter Fail-safe menu
filter
Filter
Set noise filter value
FLS 1
Fail-safe 1
Set relay 1 fail-safe operation (1-8)
Force
Force
Force analog output value for loop break
Functn
Signal input conditioner
Select linear, square root, programmable exponent, or round horizontal tank function
Hi-ab
Max of A or B
C = ((High value of channel A or B)+P)*F
ICal
Internal calibration
Enter internal calibration (used for recalibrating the meter with a calibrated signal source)
ignore
Ignore
Ignore loop break condition
InCAL
Input Calibration
Enter the Input Calibration menu
Inch
Inch
Select inch as the tank unit of measurement
Info
Information
Display software and S/N information
Inp 1
Input 1
Calibrate input 1 signal or program input 1 value
Inp 2
Input 2
Calibrate input 2 signal or program input 2 value (up to 32 points)
Input
Input
Enter Input selection menu
LatCH
Latching
Set relay for latching operation
LED t
LED test
Test all LEDs
Length
Length
Enter the tank’s length in inches or cm
Linear
Linear
Set meter for linear function and select number of linearization points
Lit HC
Max on lower display
Assign digital input to display max of channel C on the Lower display
Lit Hi
Max on lower display
Assign digital input to display max of channel A on the Lower display
Lit HL
Max/min lower display
Assign digital input to toggle max/min of channel A on the Lower display
LitHLC
Max/Min lower display
Assign digital input to toggle max/min of channel C on the Lower display
Lit LC
Min on lower display
Assign digital input to display min of channel C on the Lower display
Lit Lo
Min on lower display
Assign digital input to display min of channel A on the Lower display
Little
Lower display
Press Enter to assign the Lower display parameter (default: Ch-B)
Lo-ab
Min of A or B
C = ((Low value of channel A or B)+P)*F
Page 97
DP6060 Dual-Input Process Meter Instruction Manual
97
Display Parameter Action/Setting Description
locd
Locked
Enter password to unlock meter
Lt-CLr
Latching­cleared
Set relay for latching operation with manual reset only after alarm condition has cleared
mA
4-20 mA
Set meter for 4-20 mA input
mAn
Manual
Press Enter to manually control relays or analog output operation
math
Math
Select channel C math function
mAx
Maximum
Program maximum mA output allowed
mbus
Modbus Select to display Modbus input or to assign
Modbus input as the analog output source
menu
Menu button Assign digital input to Menu button
min
Minimum
Program minimum mA output allowed
nmulti
Multiplication
Channel C = ((A*B)+P)*F
No PtS
Num of points
Set meter for 2 to 32-point linearization
O Hold
Relays output hold
Assign digital input or function keys to hold all relay states
OFF
Off
Disable relay and front panel status LED, turn relays off, program off time delay
OFF 1
Off 1
Set relay 1 Off time delay (1-8)
on
On
Enable fail-safe operation, turn relays on, program on time delay
O-rang
Overrange
Program mA output for display overrange
Out 1
Output 1
Program output 1 value (e.g. 4.000 mA)
Out 2
Output 2
Program output 2 value (e.g. 20.000 mA)
pass
Password
Enter the Password menu
Pass 1
Password 1
Set or enter Password 1 (Allows use of the F1–F3 function keys)
Pass 2
Password 2
Set or enter Password 2 (Allows use of the F1–F3 function keys and changing the set/reset points)
Pass 3
Password 3
Set or enter Password 3 (Restricts all programming & F1–F3 keys)
prog
Program
Enter the Program menu
Prog E
Programmable exponent
Set meter for programmable exponent and enter exponent value
ratio
Ratio
Channel C = (A/B)*F
RELaY
Relay
Enter the Relay menu
reset
Reset
Press Enter to access the Reset menu
rht
Round horizontal tank
Set meter for round horizontal tank volume calculation
Right
Right arrow
Assign digital input to Right arrow button/F1
RLY 1
Relay 1
Relay 1 setup (1-8)
Rly d
Disable relay
Assign digital input and function keys to disable all relays
Rly E
Enable relay
Assign digital input to enable all relays
Page 98
DP6060 Dual-Input Process Meter Instruction Manual
98
Display Parameter Action/Setting Description
Round
Round
Enter the round menu
RSt 1
Reset 1
Program reset point 1 (1-8)
Rst Hi
Reset high
Press Enter to reset max display
Rst HL
Reset high & low
Press Enter to reset max & min displays
Rst Lo
Reset low
Press Enter to reset min display
Rst tr
Reset tare
Reset tare
Sampl
Sampling
Set relay for sampling operation
SCAL A
Scale A
Enter the Scale menu for channel A
SCAL B
Scale B
Enter the Scale menu for channel B
SelEct
Select
Enter Select menu (function, round, math, constant, cutoff, output programming)
send
Send
Send meter settings to another meter
seriAl
Serial
Set serial communication parameters
Set 1
Set 1
Program set point 1 (1-8)
setup
Setup
Enter Setup menu
SlavId
Slave ID
Set Slave ID or meter address
Source
Source
Select source for the 4-20 mA output
Square
Square root
Set meter for square root extraction
Sunm
Sum
Channel C = (A+B+P)*F
Tare A
Tare A
Activate tare on channel A
Tare b
Tare B
Activate tare on channel B
Tr dLY
Transmit delay
Set transmit delay for serial communication
units
units
Enter in channel A, B, and C input units/tags
unloc
Unlocked
Program password to lock meter
up
Up arrow
Assign digital input to Up arrow button/F2
u-rang
Underrange
Program mA output for display underrange
user
User I/O
Assign function keys and digital I/O
v CAL
Voltage calibration
Calibrate voltage input
v Hi
Voltage high
Calibrate high voltage input (e.g. 10 V)
v Lo
Voltage low
Calibrate low voltage input (e.g. 0 V)
Volt
Volt
Set meter for volt input
uwAvg
Weighted avg.
Channel C = ((B-A)*F)+A
Troubleshooting Tips
Symptom Check/Action
No display at all
Check power at power connector
Not able to change setup or programming, Locd is displayed
Meter is password-protected, enter correct six-digit password to unlock
Meter displays error message during calibration (Error)
Check:
1. Signal connections
Page 99
DP6060 Dual-Input Process Meter Instruction Manual
99
2. Input selected in Setup menu
3. Minimum input span requirements
Meter displays
1. 999999
2. -99999
Check:
1. Input selected in Setup menu
2. Corresponding signal at Signal connector
Display is unstable
Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3. Filter and bypass values (increase)
Display response is too slow
Check filter and bypass values
Display reading is not accurate
Check:
1. Signal input conditioner selected: Linear, square root, etc.
2. Scaling or calibration
Display does not respond to input changes, reading a fixed number
Check:
1. Display assignment, it might be displaying max, min, or set point.
Display alternates between
1. Hi and a number
2. Lo and a number
Press Menu to exit max/min display readings.
Relay operation is reversed
Check:
1. Fail-safe in Setup menu
2. Wiring of relay contacts
Relay and status LED do not respond to signal
Check:
1. Relay action in Setup menu
2. Set and reset points
Flashing relay status LEDs
Relays in manual control mode or relay interlock switches opened.
Meter not communicating with application programs
Check:
1. Serial adapter and cable
2. Serial settings
3. Meter address and baud rate
If the display locks up or the meter does not respond at all
Cycle the power to reboot the microprocessor.
Other symptoms not described above
Call Technical Support for assistance.
Page 100
M-5203
LIM6060OM_A
SFT065 Ver 3.100 & up
08/12
Loading...