U.S.A. Omega Eng ineering, I nc.
Headquarters: Toll-Free: 1-800- 826-6342 (USA & Can ada only)
Customer Se rvice: 1-800- 622-2378 (USA & Canada o nly)
Engin eering Serv ice: 1-800-872-9436 (USA & Ca nada only)
Tel: (203) 359-1660 Fax: (203) 359-7700
e-mail: info @omega.com
For Othe r Locations V isit omega.co m/worldwide
The infor mation cont ained in this doc ument is belie ved to be correc t, but OMEGA ac cepts no liab ility for any er rors it
contai ns, and reser ves the right to a lter specif ications wi thout notice .
Servicing North America:
Page 3
T
able of Contents
1 Model ident ification ..............................................................................................................6
2 Technical Data ........................................................................................................................6
2.1 Genera l data ..............................................................................................................6
3 Hardware data ........................................................................................................................6
3.1 Software d ata ............................................................................................................7
4 Dimensions an d Installation ...............................................................................................8
5 Electrical wi rings ....................................................................................................................8
13.11 Analo g output in mA ............................................................................................ 50
13.12 Serial co mmunication .......................................................................................... 51
4 - DP400S - User manual
Page 5
Introduction
Thanks for choosing an Omega device.
DP400S is an indicator/panel meter for acquisition and retransmission of
processes, also with fast transient. It is provided with relay outputs for
al
arm purpose, analog output for retransmission of process/setpoints and
programmable digital inputs.
Available in standard format 96 x 48 mm, the device can be configured both for
horizontal and vertical mounting.
Distinctive feature is the intuitive multilingual interface, supported by a graphic
OLED monochromatic yellow display 128 x 64 pixel.
Visualization options include bar graph and process trend with programmable
sampling time.
Software features include mathematical functions related to process value like
totalizer and sum.
Serial connectivity relies on RS485 and Modbus-RTU protocol.
Safety guide lines
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device. Disconnect power supply
before proceeding to hardware settings or electrical wirings.
Only qualified personnel should be allowed to use the device and/or service it
and in accordance to technical data and environmental conditions listed in this
manual. Do not dispose electric tools together with household waste material.
In obser vance European Dire ctive 2002/96/EC o n waste electri cal and electro nic
equipment and its implementation in accordance with national law, electric
tools that have reached the end of their life must be collected separately and
returned to an environmentally compatible recycling facility.
User manual - DP400S - 5
Page 6
1 Model identification
DP40 0S
Model 24.. 230 Vac/Vdc +/-15% 50/60 Hz – 8 VA
2 Relays 2A + 1 output mA + 2 D.I.+ RS485 + OLED
display + RFID
2 Technical Data
2.1 General data
DisplayBacklighting graphic OLED 2.42’’ (DP400S)
Operating
temperature
SealingIP54 front panel (with gasket) - IP20 box and terminals
MaterialBox: Polycarbonate V0
WeighApprox. 165 g
Temperature 0 -40 °C - Humidity 35..95 Rh%
3 Hardware data
Power supply
Analog input
Relay outputs2 Relays
Analog output
6 - DP400S - User manual
Extended power supply
range 24..230 Vac/Vdc ±15%
50/60 Hz
IN+ / INDifferential input,
software-configurable
- for strain-gauge (load
cells or Melt sensors), max
7,5 mV/V with 5V power
supply (max 4 cells 350 Ω in
parallel).
Trend
visualization
Analog
retransmission
Digital
transmission
Calibration
function
Data logging
function
Text menus
AutozeroMeasure reset at star ting
Net / FrossNet/gross weight function by key, digital input or serial.
StabilitySignaling of configurable stable weight
Absolute/Threshold, Band with instantaneous/delayed/
retentive action/activation by digital input , Sensor failure /
Activation by serial line/net weight/Gross weight/Stable
weight/Sum
By digital input or by keyboard it is possible to sum
different process measurements over time
Visualization of instant process value and total value since
last reset
Trend visualization up to 59 samples, with selectable time
basis 0,1 s to 3600 s
rocess values/alarm value via analog output
P
Process values/Setpoint/Parameters via RS485
Following options are available for calibration procedure:
• Calibration with 2-points sampling value
• Calibration on full-scale % value
• Calibration value mV/V.
Selectable time basis 1s to 3600s, tot. memory 1K
samplings
English/Italian/Deutsch/French/Spanish
User manual - DP400S - 7
Page 8
4 Dimensions and Installation
96 mm
48 mm
kg
5
(optional)
48 mm
2÷15 mm
Suggested thickness
10
5 Electrical wirings
Although t his controller has b een designed to re sist noises in an ind ustrial
Memory Card
DP-USB-CARD
USB
45 x 91 mm
Front panel cut-out
environment, please notice the following safety guidelines:
• Separate control lines from the power wires.
• Avoid the proximity of remote control switches, electromagnetic meters,
powerful engines.
• Avoid the proximity of power groups, especially those with phase control.
For permanently connected equipment:
• suppl y wiring must be ≥18 AWG with cables suita ble for temperatu res > 70° C;
• for requirements about any external switch or circuit-breaker see EN 61010-1
par. 6.11.3.1 and about external overcurrent protection devices see EN
61010-1 par. 9.6.2; the switch or circuit-breaker must be near the equipment.
8 - DP400S - User manual
Page 9
5.1 Wiring diagram
5.1. a Power supply
5
SUPPLY
24..230V
AC/DC
6
5.1. b S +IN / S -IN analog input
EXC -
13
EXC +
7
S - IN
15
S + IN
14
Switching supply, extended range 24..230 Vac/Vdc ±15%
50/60 Hz – 8 VA (galvanically isolated).
Shield/Schermo
For strain -gauge sensors (4 wires)
• Comply with p olarity.
+
Strain-gauge
• When shielded cable is used, it should be
-
connected to pin 13 (EXC-).
User manual - DP400S - 9
Page 10
EXC -
13
EXC +
7
S - IN
15
S + IN
14
CAL
1
CAL
2
EXC -
13
EXC +
7
S - IN
15
S + IN
14
5.1. c Serial input
16
17
Shield/Schermo
Shield/Schermo
+
Strain-gauge
Shield/Schermo
RS485
RS485 Modbus RTU communication
18
5.1. d Relay Q1 output
3
2A 230V
Resistive
Q1
1/8HP
4
10 - DP400S - User manual
Contacts capacity 2 A/250 Vac for resistive loads.
N
B: see picture below
For strain -gauge sensors (4 wires+ 2
calibration wires) or Melt sensors
• Comply with polarity.
••To perform semi-automatic calibration,
-
connect the 2 calibration wires to the relay
contact Q2 and set properly the parameter
for output Q2.
When shielded cable is used, it should be
connected to the pin 13 (EXC-).
For linear potentiometers
• Use potentiometers with resistive value
Pot
greater than 20 0 Ω.
• When shielded cable is used, it should be
connected to pin 13 (EXC-)
Page 11
5.1. e Relay Q2 output
1
2A 230V
Resistive
Q2
1/8HP
2
Contacts capacit y: 2A/250 Vac for resistive loads.
NB: see picture below
5.1. f Output AO1 mA
9
8
Pins 8-9: analog output in mA configurable by parameters
AO1
as retransmission of process or alarm setpoints (see
0/4..20mA
param et er s 112 -116) .
5.1. g Digital Input 1
+12 V DC
10
11
(PnP)
PNP digital input.
DI.1
Digital input configurable by parameter 95
Short-circuit pins 10 and 11 to activate digital input 1.
Electrical endurance Q1 / Q2.
2 A, 250 Vac, resistive load, 10
20/2 A, 250 Vac, cosφ = 0.3, 10
User manual - DP400S - 11
5
operations.
5
operations.
Page 12
5.1. h Digital Input 2
+12 V DC
10
PNP digital input.
Digital input configurable by parameter 100
Short-circuit pins 10 and 12 to activate digital input 2.
DI2
12
(PnP)
6 Display and Key Functions
6.1 Keys
Process
Graphic
Peak values
Keys are multifunction: in correspondence of
each key its meaning is displayed.
If no description is shown, press a key to
visualize it. Some menus are visualized only
if enabled.
6.2 Display
It visualizes the process, the setpoints and all configuration parameters. The
programming/ operation interface with text menus in 5 languages makes the
navigation intuitive
English
Italiano
Deutsch
Français
Español
12 - DP400S - User manual
Sel
‹
At first start-up, display shows the language
‹
selection.
Page 13
Initial
Configuration
Simplified
Complete
1.168
Q1COM
Q2
Once selected the language, it is possible to
Sel
‹
Esc
choose between t wo configuration modes:
simplified or complete. The first mode
allows to enter directly the parameter of
‹
pre-selected Easy-Up configurations, while
selecting the second option it is possible to
enter the complete configuration menu.
“Esc” cancels configuration procedure.
kg
This page displays the process, the relays
status and the serial communication (if
available).
4.998
4.998
Q1
25.6
Q1
Bar
kg
Q2
Q2
Bar
Q1
This page displays the process, the relays
status and a graph representing the process
trend.
This page displays the process and its
Q2
graphic representation as bar graph. .
User manual - DP400S - 13
Page 14
7 Controller Functions
7.1 Modifying alarm thresholds
Selecting one or more absolute/ band alarms, it is possible to modify the alarm
thresholds directly by the user menu, without entering configuration.
AL . 1
0006.0
AL . 2
100.0
Sel
‹
kg
kg
Press “Load data” to enter the thresholds
‹
modification.
For the modification procedure refer to the following table:
PressDisplayDo
Press “n” and “m” to modify
“Sel”
1
Selects the setpoint to be
modified.
the value. Pressing “
is possible to modify single
digit
Selects the nex t setpoint (if
“Sel”
2
“Sel”“n” and “m” disappear. Press “Esc” to exit procedure.
3
activated), otherwise go to
point 3.
See point 1.
7. 2 Zero function, net/gross weight
kg
57
14 - DP400S - User manual
COM
TARE
Esc
0
These functions, enabled by the relevant
parameters during configuration, allow to
reset the measure or to switch from gross to
net weight and vieceversa. This window can
be entered by process visualization, pressing
one of the function keys.
” it
Page 15
KeyShort pressureLong pre ssure (1 s)
“>0<”
“TA RE”
Back to process
“Esc”
visualization
Switch to menu
“ ”
visualization
This func tion is enabled only if the
parameter 135 ->0<- is selected as Enabled.
Executes the reset of visualized weight.
This reset is kept also at switching off if the
parameter 13 Store is selected as Enabled.
This func tion is enabled only if the
parameter 135 TARE is selected as Enabled.
Executes the switch from gross to net
weight and vice-versa.
Ex.: once put the container on the scale,
display will show its weight. Press TARE to
visualize the net weight at 0 (on the upper
left side of display appears NE T). Putting
the weighing item into the container,
display will show the product weight.
This operation can be repeated several
consecutive times.
Net/gross value is lost at switching off.
7. 3 Calibration function
This func tion allows to acti vate a field calibrati on of linear input for s train-gauge
or potentiometer. Different calibration options are available and may be
selected by parameter, according to type of sensor/transducer and its relevant
application. To activate calibration procedure, enter configuration mode, select
the parameters group “Analog Inp.”, select Calibration parameter and chose
one of the available options pressing “Sel”. Following calibration options are
available:
User manual - DP400S - 15
Page 16
• Sampling value. This proceeding performs a calibration of the analog input
on two points of the scale taking as reference two known values (for example
for a load cell these values could be Zero balance and Reference weight). It
is possible to link the calibration lower limit (parameter 6 Lower lim.) to the
minimum val ue of the sensor or to th e minimum position o f the potentiomet er
while the ca libration upper lim it (parameter 7 Upp er lim.) may be linked to the
max value of the sensor or the maximum position of the potentiometer.
Max 1.000 kg
Min 0.000 kg
In 0.079 mV/V
kg
0.239
Esc
Press “m” to calibrate lower limit and “n” to
calibrate the upper limit.
• Full-scale % value. This proceeding is available for 6wires (4wires+2 wires
calibration) strain-gauge sensors and for Melt transducers. It is possible to
calibrate reading of analog input by choosing the percentage of the full-scale
value at which the calibration of the upper limit will be performed. At first
the operator will be asked to select the percentage for the calibration of
the upper limit. Afterward the lower limit value and upper limit value (% of
full-scale value) will also be calibrated, as for the sampling value. The two
calibration wires of the sensor can be connected to relay of output Q2 to
perform a semi-automatic calibration. In this case it is necessary to select the
option Calibration % on parameter Alarm 2 - Type of alarm. If contact Q2 will
not be used to generate sensor calibration signal, it is possible to short-circuit
externally the t wo wires, waiting for s tabilization of rea ding on the device and
then proceeding to calibration of upper limit.
Calibration 80%
Max 0.800 kg
Min 0.000 kg
16 - DP400S - User manual
OK
‹
Use the arrow keys to set the calibration
‹
percentage, then confirm with “Ok”.
Page 17
Max 0.800 kg
Min 0.000 kg
In 0.389 mV/V
kg
1.168
Esc
Press “m” to calibrate lower limit and “n” to
for the upper limit. Press “◊%” to go back to
%
calibration percentage.
Va lue mV/ V. This calibration option is available only for strain-gauge sensors
and it is basing on the setting of correct ratio mV/V for the sensor. Process
value will be calculated considering both the entered ratio mV/V and the
effective mV/V value detected by the analog input.
Out 2.000 mV/V
Range
6.000 kg
Out 2.000 mV/V
Range
6.000 kg
In 0.389 mV/V
1.168
OK
‹
mV
kg
Esc
Use the arrow keys to set the correct mV/V
‹
ratio of strain gauge. Press “Ok” to confirm.
Press “◊mV” to go back to setting of mV/V
ratio.
For the calibration procedure refer to the following table:
PressDisplayDo
Place sensor on its minimum
1
operating position (related to
Lower limit calibration).
User manual - DP400S - 17
Page 18
PressDisplayDo
Max
Full-scale% value: enter the
% of full-scale value at which
“n”
2
and “
“Ok”
3
“◊%” and
4
“◊mV”
“m”Set the value on minimum.
5
6
“n”Set the value to maximum
“>0<”Set the vir tual zero valuePress “Esc” to exit procedure.
7
the calibration of upper limit
will be per formed.
m
”
Value mV/V: enter the
correct value mV/V of the
sensor.
Full-scale% value: confi rm
the selec ted %.
Value mV/V: Confi rm the
selected mV/V value.
Press to go back to settings
of calibration % or to
settings of mV/V value of the
sensor.
Visualization will automatically
switch to sensor calibration page
where real-time value read by
the device is visualized.
Visualization will automatically
switch to the page for the setting
of full-scale % or mv/V value.
Place the sensor on its maximum
operating position (related to
Upper limit).
To exit standard procedure
press “Esc”. For zero setting place
the sensor on the zero point
(tare).
MinZero
18 - DP400S - User manual
Page 19
7.4 Digital input functions
On the DP400S, digital inputs can be enabled by configuring the parameter 95
Digital input 1 and the parameter 100 Digital Input 2.
• Enable outputs: Enable operation of relays and analog outputs
• Hold: Lock the conversion.
• Tare zero (AI): Set to zero the process value (tare function).
• Alarm reset: if one or more alarms are selected with manual reset and alarm
conditions are no longer present, closing the digital input it is possible to
restore the output related to alarm.
• Totalizer reset: if totalizer function is active, using the digital input it is
possible to reset the counter.
• Peaks reset: Reset min. peak/max. peak /peak-to-peak values
Sum total: if sum function is active, using the digital input it is possible to
increase the Sum counter adding the process value.
• Sum reset: if the sum func tion is active, usin g the digital input it is p ossible to
reset the Sum counter.
• Config. lock: if the digit al input is acti ve it is not possibl e to enter configura tion
or to modif y the setpoints.
• Gross/net TARE: switches from the gross to the net weight visualization and
vice versa.
Selecting Digital input 1 or Digital input 2 on the alarm parameters, the
related relays will activate toge ther with the digital input; func tions selected on
parameters 95 and 100 will continue to work .
7. 5 Peak values
Maximum
25.6 kg
Minimum
15.7 kg
Peak-Peak
9.9 kg
Rst
Esc
The DP400S is provided with a page for the
visualization of peak values: max. peak , min.
peak and peak-to-peak of analog input.
Keeping pressed “Rst” it is possible to reset
the visualized values.
User manual - DP400S - 19
Page 20
7.6 Totalizer function
The totali zer function, whi ch can enabled by par ameter 9 Totalizer, perfor ms an
instant me asurement of the pro cess and sums it on a time bas is to the previously
totalized value.
Process
1178.9
Total izer
2301.4
kg/h
Rst
On the dedicated page it is possible to see
the instant process value and the totalized
Esc
value: keeping pressed “Rst” it is possible to
reset this value.
7.7 Sum function
The sum function, which can be enabled by parameter 10 Sum function, allows
to increase a counter adding the process value upon relevant command. It is a
typical application for weighing systemsand it allows gettin g the total weighed
value over a period of time.
Process
100.07
Sum
4703.29 kg
Rst
kg
+
0
Esc
Functions t are, sum and reset can a lso be managed by dig ital input if enabl ed on
parameter 95 Digital Input 1 and parameter 100 Digital Input 2.
20 - DP400S - User manual
Press “Sum function” to enter the related
page. Pressing “+” the Process value is
added to the counter. It is possible to reset
the total value keeping pressed “Rst” and to
fix zero of the process pressing “>0<”.
Page 21
7.8 Customizable linearisation of analog input
Alarm Spv
Pv
Off
OnOn
Off
Hysteresis
par. > 0
Time
Alarm
output
Selecting 16 s teps on parameter 17 V/I custom and connecting a linear sensor
it is possible to customize the linear input for a max. of 16 steps. On parameters
xx-Input value it is necessary to enter the value of the input to which the value
selected on the corresponding parameter xx-Custom value will be related.
EExample: sensor 0 -5V.
01-Input value=> 0.000V 01-Custom value =>0mBar
02-Input value => 2.000V 02-Custom value=>100mBar
03-Input value => 4.000V 03-Custom value=>500mBar
04-Input value => 5.000V 04-Custom value.=>1000mBar
At each value in Volt (input) a value in mBar (customized) is related: if the s ensor
supplies 2V the device visualizes 100mBar, if it supplies 4V the device visualizes
500mBar. For intermediate tension values the value in mBar is calculated
linearly between the entered values containing it: 1V = 50mBar, 3V=300mBar
and 4,5V=750mBar.
8 Alarm Intervention Modes
8.a Absolute alarm (absolute selection)
Absolute alarm and hysteresis value
greater than “0” (Parameter 58
1
hysteresis > 0).
N.B. The example refers to alarm 1;
the function can also be enabled for
alarms 2
User manual - DP400S - 21
Page 22
Pv
output
Pv
Hysteresis
par. < 0
Alarm Spv
2
Time
Off
OnOn
Off
Alarm
8.b Band alarm (band selection)
Dev. Spv
1
OnOnOn
OffOffOff
Pv
2
OnOnOn
OffOffOff
22 - DP400S - User manual
Alarm Spv
Alarm Spv
Hysteresis
par. > 0
Dev. Spv
Time
Alarm
output
Hysteresis
par. < 0
Dev. Spv
Dev. Spv
Hysteresis
par. < 0
Time
Alarm
output
Absolute alarm and hysteresis
value less than “0” (Parameter 58
hysteresis < 0).
N.B. The example refers to alarm 1;
the function can also be enabled for
alarms 2.
Band alarm and hysteresis value
greater than “0” (Parameter 58
hysteresis > 0).
N.B. The example refers to alarm 1;
the function can also be enabled for
alarm 2.
Band alarm and hysteresis value less
than “0” (Parameter 58 hysteresis
< 0).
N.B. The example refers to alarm 1;
the function can also be enabled for
alarm 2.
Page 23
8.c
Digital input alarm (selection “Digital input 1” or “Digital input 2”)
Alarm related to digital input: the relay activates with digital input active.
The relays are activated when the process reading is stable (stability function
enabled by parameters 137 and 138).
8.i Sum alarm (selection “Sum”)
Absolute alarm managed on the sum value. For functioning details, refer to the
graphics of the process absolute alarm.
8.j Alarm “ calibration % control “ (option “Calibration %”)
This optio n is available only for A larm 2. Relay activ ates when, during cal ibration
proceeding “Calibration on full-scale % value“, the calibration of sensor upper
limit is activated by pressing the key. At the end of calibration, relay will
automatically deactivate.
User manual - DP400S - 23
Page 24
9 Data logger
DP400S features a basic data logger function which can be enabled on
parameter 109 Data logger. After the initial start-up following the switch-on,
the device will start to save process data on EEPROM according to a selected
time basis. Sampling time must be selected on parameter 110 Datalogger time. Stored data may be read via Modbus protocol starting from address 6001
(MSW) or 9001 (LSW) (see following section of this manual). The following table
provides info about the stored data:
60 01(H) 60 02 (L) Data logger: firmware version
6003(H) 6004 (L) Data logger: sensor type
6005(H) 6006 (L) Data logger: decimal point
6007(H) 6008 (L) Data logger: measure unit
6009(H) 6 010 (L) Data logger: sampling time in seconds
6011(H ) 6 012 (L )
6033(H) 6034(L) First analog input value stored.
6035(H) 6036(L) Second analog input value stored.
.........
8031(H) 8032(L)Last analog input value stored.
Reading of value 0x80000000 (-2147483648) stands for end of stored data:
eventual data which should be read af terwards are not valid.
10 Serial communication
DP400S is equipped with RS485, it can receive and broadcast data via serial
communication using MODBUS-RTU protocol. The device is configured as
a Slave. This function enables the control of multiple devices connected to a
super visory system . Each controller resp onds to a master quer y only if the quer y
contains the same address as that in the parameter 126 Slave address
The permitted addresses range from 1 to 254 and there must not be controllers
with the same address on the same line.
24 - DP400S - User manual
Data logger: flag end of memor y. 0 indicates that
memory is still available. 1 indicates memory is saturated
and device restarted to store data from address
6033/6034
.
Page 25
Address 255 can be used by the master to communicate with all the connected
equipme nt (broadcast mod e), while wit h 0 all the devices receive t he command,
but no response is expected.
DP400S can introduce a delay (in milliseconds) in response to the master
request. This delay must be set on parameter 129 Serial Delay
Each parameter change is saved by the controller on EEPROM memory (100000
.
writing cycles).
NB: changes made to Words that are different from those reported in the
following table can lead to malfunction.
Modbus RTU protocol features
Selection on parameter 127 Baud Rate:
1.200 baud 28.800 baud
Baud-rate
2.400 baud 38.400 baud
4.800 baud 57.600 baud
9.600 baud 115.200 baud
19.20 0 bau d
Selection on parameter 128 Serial format:
8, N, 1 (8 bit, no parity, 1 stop)
8, E, 1 (8 bit, even parity, 1 stop)
Format
8, O, 1 (8 bit, odd parity, 1 stop)
8, N, 2 (8 bit, no parity, 2 stop)
8, E, 2(8 bit, even parity, 2 stop)
8, O, 2 (8 bit, odd parity, 2 stop)
Supported
functions
WORD READING (max 20 word) (0x03, 0x04)
SINGLE WORD WRITING (0x06)
MULTIPLE WORDS WRITING (max 20 word) (0x10)
Looking at the table here below it is possible to find all available addresses and
functions:
RORead OnlyR/WRead / WriteWOWrite Only
User manual - DP400S - 25
Page 26
Modbus
Description
Address
0Device typeRO EEPROM
Read
Write
Reset value
1Software versionRO EEPROM
5Slave addressRO EEPROM
6Boot versionRO EEPROM
1000 Process (H)RO 0
1001 Process (L)RO 0
1002 Min. peak (H)RO 0
1003 Min. peak (L)RO 0
100 4 Max. peak (H)RO 0
1005 Max. peak (L)RO 0
1006 Peak-to-peak (H)RO 0
1007 Peak-to-peak (L)RO 0
1008 Totalizer value (H)RO EEPROM
1009 Totalizer value (L)RO EEPROM
1010 Sum value (H)RO EEPROM
1011Sum value (L)RO EEPROM
Relays status (0 = Off, 1 = On):
1012
Bit 0 = Relay Q1
RO 0
Bit 1 = Relay Q2
Digital inputs status (0 = Off, 1 = Active):
5300 Parameter 150 (H)*R/W EEPROM
6001 Data logger: firmware version (H)RO EEPROM
6002 Data logger: firmware version (L)RO EEPROM
6003 Data logger: sensor type (H)RO EEPROM
6004 Data logger: sensor type (L)RO EEPROM
6005 Data logger: decimal point (H)RO EEPROM
6006 Data logger: decimal point (L)RO EEPROM
6007 Data logger: measure unit (H)RO EEPROM
6008 Data logger: measure unit (L)RO EEPROM
Data logger: sampling time in seconds (H)
6009
RO EEPROM
6010 Data logger: sampling time in seconds (L)RO EEPROM
Data logger: flag end memory. 0 indicates that
memory is still available. 1 indicates memory is
6011
saturated and device restarted to store data from
RO EEPROM
address 6033/6034 (H)
Data logger: flag end memory. 0 indicates that
memory is still available. 1 indicates memory is
6012
saturated and device restarted to store data from
RO EEPROM
address 6033/6034 (L)
6033 First analog input value stored (H)RO EEPROM
6034 First analog input value stored (L)RO EEPROM
6035 Second analog input value stored (H)RO EEPROM
6036 Second analog input value stored (L)RO EEPROM
......RO EEPROM
8031 Last analog input value stored (H)RO EEPROM
8032 Last analog input value stored (L)RO EEPROM
9001 Data logger: firmware version (L)RO EEPROM
9002 Data logger: firmware version (H)RO EEPROM
User manual - DP400S - 29
Page 30
Modbus
Description
Address
9003 Data logger: sensor type (L)RO EEPROM
Read
Write
Reset value
9004 Data logger: sensor type (H)RO EEPROM
9005 Data logger: decimal point (L)RO EEPROM
9006 Data logger: decimal point (H)RO EEPROM
9007 Data logger: measure unit (L)RO EEPROM
9008 Data logger: measure unit (H)RO EEPROM
9009 Data logger: sampling time in seconds (L)RO EEPROM
9010 Data logger: sampling time in seconds (H)RO EEPROM
Data logger: flag end memory. 0 indicates that
memory is still available. 1 indicates memory is
9011
saturated and device restarted to store data from
RO EEPROM
address 9033/9034 (L)
Data logger: flag end memory. 0 indicates that
memory is still available. 1 indicates memory is
9012
saturated and device restarted to store data from
RO EEPROM
address 9033/9034 (H)
9033 First analog input value stored (L)RO EEPROM
9034 First analog input value stored (H)RO EEPROM
9035 Second analog input value stored (L)RO EEPROM
9036 Second analog input value stored (H)RO EEPROM
......RO EEPROM
10031 Last analog input value stored (L)RO EEPROM
10032 Last analog input value stored (H)RO EEPROM
* Param eters mod ified using se rial addre ss 4001 to 4300 and 5001 to 5300, will be stored on
EEPROM only af ter 10s since last writing o f one parameter.
30 - DP400S - User manual
Page 31
11 Error messages
The instrument signa ls failures/anomalies by means of messages on the display.
The following are the possible messages:
Probe error
Read EEPROM failure Error during EEPROM memory reading
Write EEPROM failError during EEPROM memory writing
Wrong tarature data Error on device calibration data
Wrong parameters Error on device configuration parameters
Wrong status dataError on device status data
Param. out of range Detected a parameter value out of range.
Missing calibration Error on device calibration data
In all of these situations, the instrument might not be able to operate correctly.
Switch it off and back on. If the problem persists, contact assistance.
Detected a fault in the load cell or on the Melt sensor.
The control on sensor is executed at each device starting.
12 Configuration
12.1 Modifying configuration parameters
For configuration parameters see paragraph 11
PressDisplayDo
1
“Configuration”
“n” and “m”
2
3
“Sel” to confirm
“n” and “m”
4
“Sel” to enter
the parameter
5
group
Shows 0000 with the 1st
digit selected.
Changes the selected digit
and moves to the next one
using “
Shows the names of the
parameter groups.
Scroll up / down the
parameter groups.
Shows the parameters of
the selected group.
”
Enter password 1234
“n” and “m” to select
parameter to be modified.
User manual - DP400S - 31
Page 32
PressDisplayDo
“Sel” to enter
6
the parameter
modification
1
2.2 Loading default values
Enter password 9999 to restore factory settings of the device. Entering password
9911, at next restarting will be required only the language selection.
12.3 Configuration by NFC/RFID
Quick device setup by Direct Link app (only for Android®) on smartphones
provided with NFC. The app is available for download on Google® PlayStore.
Configuration can also be done with device switched-off. If this operation is
done with device switched-on, display will show a restarting message.
32 - DP400S - User manual
Shows all parameter
possible selections or the
parameter numeric value.
Position of the NFC/RFID antenna for
communication with smartphone and
reading / writing of data.
Press “n” and “m” to modify
parameter. For numeric
parameters, pressing “
it is possible to modif y
digit-to-digit. Press “Sel” to
confirm modification. Press
“<-” to exit without modif y.
”
Page 33
12.4 Configuration via DP-USB-CARD
The instr ument can be confi gured quick ly via a DP-USB -CARD. Th e DP-USB- CARD
is connected to the micro-USB connector at the bottom of the instrument.
12.5 Creation of the DP-USB-CARD
To save a configuration of parameters on the DP-USB-CARD, with the
instrument on, connect it to the micro-USB connector, enter configuration, set
the parameters necessary and exit configuration. At this point, the instrument
acknowledges the presence of the DP-USB-CARD and saves the configuration
just made on the DP-USB-CARD as well.
Saving is signaled by a message on the
Memor y writi ng...
display.
12.6 Loading configuration from DP-USB-CARD
To load a configuration previo usly made and saved on a DP- USB-CARD, connect
it to the micro-USB connector and power the instrument. At this point, if the
DP-USB- CARD is detected and the data it contains is considered valid, the
display will view the request for loading data from the DP- USB-CARD.
Load data
The user can either “Load data” load the
parameters from the DP-USB-CARD or “Esc”
Esc
cancel the operation without modifying the
current configuration.
User manual - DP400S - 33
Page 34
13 Table complete of configuration parameters
13.1 Analog input
Parameters to configure the analog input.
1 Sensor t ype
Analog input configuration/sensor selection
Strain-gauge (Default) 4 wires (+ 2 optional calibration wires)
Potentiometer min. 200 Ω
2 mV/V sensor
This parameter sets the ratio mV/V for the chosen strain-gauge. It has no
meaning if a potentiometer is selected as sensor
0,001..20,000 mV/V, Default: 2,000 mV/V.
3 Decimal Point
Select type of the visualized decimal point
0 Default 0.00 2 Decimals
0.0 1 Decimal 0.000 3 Decimals
4 Measure unit
Select the visualized measure unit
g
kg (Def.)
q
t
oz
lb
bar
mbar
psi
Pa
mmHg
atm
34 - DP400S - User manual
mH2O
N
kN
Nm
kNm
kgf
kgp
kip
lbf
ozf
°C
°F
K
V
mV
A
mA
mm
cm
dm
m
km
in
m/s
m/m
m/h
l/s
l/m
l/h
m³/s
m³/m
m³/h
rpm
%rh
ph
pcs
kg/h
no unit
Ncm
MN
daN
cN
mN
in-oz
in-lb
ft-lb
Tor r
mTor r
Page 35
5 Full-scale
Full-scale value of strain-gauge sensor, used during calibration type
“Calibration on full-scale % value”.
-999999 +999999 [digit
1
], Default: 1000.
6 Lower limit
Lower limit of sensor, used during input calibration type Sampling value
or Calibration on full-scale % value.
-999999 +999999 [digit
1
], Default: 0.
7 Upper limit
Upper limit of sensor, used during input calibration type Sampling value
or Calibration on full-scale % value
-999999 +999999 [digit
1
], Default: 1000.
8 Offset calibration
Analog input offset correction. Value added / subtracted to the process
visualization.
-10000..+10000 [digit
1
], Default 0.0.
9 Gain calibration
Percentage value that is multiplied for the process value (allows to
calibrated the working point)
-100. 0%..+100 .0%, Default: 0.0
ex: to correct the range from 0..1000kg showing 0..1010kg, set the
parameter to -1.0.
10 Calibration
Selection of calibration type for the analog input. After finishing or
deleting calibration proceeding, this parameter will automatically return
to default setting (=Disabled).
Disabled (Default) Full-scale % value
Sampling value mV/V Value
User manual - DP400S - 35
Page 36
11 Totalizer
Visualize on corresponding page the total value of measured process
considering the sensor signal as unit/time value (ex. if full-scale of the
connected sensor is 2000m³/hour, parameter 11 Totalizer has to be
selected as Hour and display will visualize the total fluid volume from the
last RESET/START signal till present).
Disabled Display visualizes process value (Default)
Second Display visualizes rate in unit/s
Minute Display visualizes rate in unit /min
Hour Display visualizes rate in unit/hour
12 Sum function
Enable the sum function and its de dicated page. Allow to sum the process
value to a variable.
Disabled (Default)
Enabled
13 Store
Enable to store in EEPROM the values of peaks, totalizer, sum func tion and
zero tare. If disabled, at star ting the above-mentioned values star t from 0.
The storing is done automatically every 5 minutes.
Disabled (Default)
Enabled
14 Conversion filter
ADC Filter: defines the type of digital filter applied to the reading of the
analog input.
Filter 4th ord.
No filter
Average 2 samp.
...
Average 20 samp.
When average increase, control loop speed slows down.
Default: Average 10 samp.
36 - DP400S - User manual
Page 37
15 Sampling frequency
Sampling frequency of analog / digital converter.
NB: Increasing the conversion speed will slow down reading stability
(ex: for fast transients like pressure, it is advisable to increase sampling
frequency)
1200 Hz 0.83ms (Maximum speed conversion)
600 Hz 1.67ms
240 Hz 4.16ms
75 Hz 13.3ms
Set the max . weight value which is p ossible to reset by “>0<”, digital in puts
or serial.
0..Full-scale (Default: 1000)
134 Autozero start
Sets the max. weight value which is possible to reset at starting by the
autozero function. If at starting the value of the revealed weight is less
than this value, the weight is automatically reset. To disable this function
keep the parameter to 0.
0..20% Full -scale (Default: 0)
User manual - DP400S - 37
Page 38
135 Key ->0<-
Selects if enable or not “>0<” to reset the weight.
Disabled (Default)
Enabled
136 Key TARE
Selects if enable or not “ TARE” to execute the weight net/gross function.
Disabled (Default)
Enabled
137 Show stability
Selec ts if visualize or not, on the process (we ight) visualization di splay, the
symbol which indicates measure stability.
Disabled (Default)
Enabled
138 Stability tolerance
Defines the max. tolerance allowed to consider the measure stable.
0..10% Full-scale (Default: 0)
13. 3 V/I custom
Parameters to configure the customizable linearization of analog input.
17 V/I custom
Select the linearizationtype for the analog input if selec ted as linear.
Lower and
upper limits The input will be linearized by parameters 6 and 7
16 st eps The input will be linearized by parameters 18-49
18 01-Input value
Define the input value to which the 1st customized value is assigned
0..5.000V Default: 0.
38 - DP400S - User manual
(Default)
Page 39
19 01-Custom value
Define the 1st customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
20 02-Input value
Define the input value to which the 2nd customized value is assigned
0..5.000V Default: 0.
21 02-Custom value
Define the 2nd customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 1000.
22 03-Input value
Define the input value to which the 3rd customized value is assigned
0..5.000V Default: 0.
23 03-Custom value
Define the 3rd customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
24 04-Input value
Define the input value to which the 4th customized value is assigned
0..5.000V Default: 0.
25 04-Custom value
Define the 4th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
26 05-Input value
Define the input value to which the 5th customized value is assigned
0..5.000V Default: 0.
User manual - DP400S - 39
Page 40
27 05-Custom value
Define the 5th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
28 06-Input value
Define the input value to which the 6th customized value is assigned
0..5.000V Default: 0.
29 06-Custom value
Define the 6th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
30 07-Input value
Define the input value to which the 7th customized value is assigned
0..5.000V Default: 0.
31 07-Custom value
Define the 7th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
32 08-Input value
Define the input value to which the 8th customized value is assigned
0..5.000V Default: 0.
33 08-Custom value
Define the 8th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
34 09-Input value
Define the input value to which the 9th customized value is assigned
0..5.000V Default: 0.
40 - DP400S - User manual
Page 41
35 09-Custom value
Define the 9th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
36 10-Input value
Define the input value to which the 10th customized value is assigned
0..5.000V Default: 0.
37 10-Custom value
Define the 10th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
38 11-Input value
Define the input value to which the 11th customized value is assigned
0..5.000V Default: 0.
39 11-Custom value
Define the 11th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
40 12-Input value
Define the input value to which the 12th customized value is assigned
0..5.000V Default: 0.
41 12-Custom value
Define the 12th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
42 13-Input value
Define the input value to which the 13th customized value is assigned
0..5.000V Default: 0.
User manual - DP400S - 41
Page 42
43 13-Custom value
Define the 13th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
44 14-Input value
Define the input value to which the 14th customized value is assigned
0..5.000V Default: 0.
45 14- Custom value
Define the 14th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
46 15-Input value
Define the input value to which the 15th customized value is assigned
0..5.000V Default: 0.
47 15-Custom value
Define the 15th customized value assigned to the input
-999999..+999999 [Digit
1
] Default: 0.
48 16-Input value
Define the input value to which the 16th customized value is assigned
0..5.000V Default: 0.
49 16-Custom value
Define the 16th customized value assigned to the input
-999999..+999999 [Digit
42 - DP400S - User manual
1
] Default: 0.
Page 43
13. 4 Dynisco MELT
This parameter allows to quickly set the device for operation with a selection of
Dynisco melt pressure sensors.
52 Easy-up
Select one of the listed Dynisco melt pressure sensors to automatically
configure the parameters suitable for that sensor
---------------- (Default)
ECHO-MV3-PSI-R20 ECHO-MV3-PSI-R23
ECHO-MV3-PSI-R21 PT462E-15M-6/18
ECHO-MV3-PSI-R22
In particular, these selections should be set to the following parameters:
Sensor type Contact type alarm 1
mV / V sensor Alarm threshold 1
Decimal point Hysteresis alarm 1
Measure unit Lower limit alarm 1
Full-scale Upper limit alarm 1
Lower limit Alarm typ e 2 (calibration)
Upper limit Graphic lower limit
Alarm type 1 (absolute) Graphic upper limit
13. 5 Alarm 1
Parameters to configure Alarm 1
54 Alarm type
Alarm 1 selection
Disabled (Default) Remote control
Absolute alarm Gross weight
Band alarm Net weight
Digital input 1 Stable weight
Digital input 2 Sum
Sensor failure
User manual - DP400S - 43
Page 44
55 Contact type
Select the alarm 1 output contact and intervention type
Normally open (Default) N.O. - Disabled at star ting
Normally closed N.C. - Disabled at starting
56 Alarm threshold
Select setpoint for alarm 1
-999999..+999999 [Digit
2
], Default: 0.0.
57 Deviation threshold
Select deviation value from alarm 1 setpoint for the band alarm
0..+999999 [Digit
2
], Default: 0.0.
58 Hysteresis
Alarm 1 hysteresis
-10000..+10000 [Digit
2
], Default: 0.0.
59 Reset type
Alarm 1 contact reset t ype
Automatic (Default)
Manual Manual reset by keyboard
Manual stored Keeps relay status also after an eventual power failure
60 Error contact
State of contac t for alarm 1 output in case of error
Open (Default)
Closed
62 Ac tuation delay
Alarm 1 delay.
-3600..+3600 seconds. Default: 0
Negative: delay in alarm exit phase.
Positive: delay in alarm entr y phase.
44 - DP400S - User manual
Page 45
63 Lower limit
Lower limit for alarm 1 setpoint.
-999999..+999999 [Digit
2
]. Default: 0.
64 Upper limit
Upper limit for alarm 1 setpoint.
-999999..+999999 [Digit
2
]. Default: 1000.
65 Protection
Alarm 1 set protection. Does not allow user to modify setpoint
Free Modification allowed (Default)
Lock Protected
Hide Protected and not visualized
13. 6 Alarm 2
Parameters to configure Alarm 2.
69 Alarm type
Alarm 2 selection
Disabled (Default) Remote control
Absolute alarm Gross weight
Band alarm Net weight
Digital input 1 Stable
Digital input 2 Sum
Sensor failure Calibration %
70 Contact type
Select alarm 2 output contact and intervention type
Normally open (Default)
Normally closed
N.O. - Disabled at star ting
N.C. - Disabled at starting
User manual - DP400S - 45
Page 46
71 Alarm threshold
Select setpoint for alarm 2
-999999..+999999 [Digit
2
], Default: 0.0.
72 Deviation threshold
Select deviation value from alarm 2 setpoint for the band alarm
0..+999999 [Digit
2
], Default: 0.0.
73 Hysteresis
Alarm 2 hysteresis
-10000..+10000 [Digit
2
], Default: 0.0.
74 Reset type
Alarm 2 contact reset t ype
Automatic (Default)
Manual Manual reset by keyboard
Manual stored Keeps relay status also after an eventual power failure
75 Error contact
State of contac t for alarm 2 output in case of error
Open (Default)
Closed
77 Ac tuation delay
Alarm 2 delay. -3600..+3600 s. Default: 0
Negative: delay in alarm exit phase.
Positive: delay in alarm entr y phase.
78 Lower limit
Lower limit for alarm 2 setpoint
-999999..+999999 [Digit
46 - DP400S - User manual
2
]. Default: 0.
Page 47
79 Upper limit
Upper limit for alarm 2 setpoint
-999999..+999999 [Digit
2
]. Default: 1000.
80 Protection
Alarm 2 set protection. Does not allow user to modify setpoint
Free Modification allowed (Default)
Lock Protected
Hide Protected and not visualized
13.7 Display
84 Language
Select the language of the tex t menus
English (Default) Français
Italiano Español
Deutsch
86 Contrast
Select the contrast value for the display
0%..100%, Default: 35%.
88 Screen timeout
Select the display backlighting duration
Always on (Default)
15 seconds
30 seconds
1 minute
2 minutes
5 minutes
10 minutes
30 minutes
1 hour
User manual - DP400S - 47
Page 48
89 Display direction
Select the display visualization direc tion
Horizontal (Default)
Vert ical
90 Starting page
Select the page visualized at starting after the initial splash screen
Process (Default) Tota lizer
Graphic Sum function
Peak values
13. 8 Digital input 1
Parameters to configure digital input 1.
95 Input function
Select function of digital input 1
Disabled (Default) Reset peaks
Enables outputs Sum total (pulse operation)
Hold Reset sum (pulse operation)
Tare zero »0« (pulse operation) Config. lock.
Alarms reset Gross/net TARE
Reset totalizer (pulse operation)
96 Contact type
Select inactive contact for digital input 1
Normally open (Default) Executes function with closed contact
Normally closed Executes function with open contact
48 - DP400S - User manual
Page 49
13.9 Digital input 2
Parameters to configure digital input 2.
100 Input function
Select function of digital input 2
Disabled (Default) Reset peaks
Enables outputs Sum total (pulse operation)
Hold Reset sum (pulse operation)
Tare zero »0« (pulse operation) Config. lock.
Alarms reset Gross/net TARE
Reset totalizer (pulse operation)
101 Contact type
Select inactive contact for digital input 2
Normally open (Default) Executes function with closed contact
Normally closed Executes function with open contact
13.10 Graphic
Parameters to configure trend and bar graph management.
105 Graphic type
Select the type of graph to be visualized on the relevant page
Trend (Default)
Bar graph
106 Lower limit
Trend or bar graph lower limit
-999999 +999999 [Digit
107 Upper limit
Trend or bar graph upper limit.
-999999 +999999 [Digit
2
], Default: 0.
2
], Default: 1000.
User manual - DP400S - 49
Page 50
108 Trend time
Select the trend sampling time
0,1..3600,0 seconds, Default: 60,0s.
109 Data logger
Enable the registration of process data on EEPROM
Disabled (Default)
Enabled
110 Data logger time
Select the data logger sampling time
1..3600 seconds, Default: 60s.
13 .11 Analog output in mA
Parameters to configure the analog output in mA
112 Retransmission
Enable analog output
Disabled (Default) Alarm 2
Process Remote Ctrl
Alarm 1
113 Signal type
Select the signal for the analog output in mA
0..20 mA
4..20 mA (Default)
114 Lower limit
Analog output mA lower limit range
-999999..+999999 [Digit
50 - DP400S - User manual
2
], Default: 0
Page 51
115 Upper limit
Analog output mA upper limit range
-999999..+999999 [Digit
2
] Default: 1000
116 Error value
Select the value of the analog output in mA in case of error
0 mA (Default)
4 mA
20 mA
13.12 Serial communication
Parameters to configure the serial communication port.
126 Slave address
Select slave address for serial communication
1.. 254. Default: 24 0
127 Baud Rate
Select the baud rate for serial communication
1.200 baud 28.800 baud
2.400 baud 39.400 baud
4.800 baud 57.600 baud (Default)
9.600 baud 115.200 baud
19.20 0 bau d
2
Display of d ecimal point dep ends on setting o f parameter 3 Deci mal point.
User manual - DP400S - 51
Page 52
128 ComPort setting
Select the format for serial communication
8,N,1 8bit, No parity, 1 Stop bit (Default)
8,E,1 8bit, Even parity, 1 Stop bit
8,O,1 8bit, Odd parity, 1 Stop bit
8,N,2 8bit, No parity, 2 Stop bit
8,E,2 8bit, Even parity, 2 Stop bit
8,O,2 8bit, Odd parity, 2 Stop bit
129 Serial delay
Select the serial delay.
0..100 ms. Default: 10
Notes / Updates
52 - DP400S - User manual
Page 53
User manual - DP400S - 53
Page 54
54 - DP400S - User manual
Page 55
User manual - DP400S - 55
Page 56
Table of configuration parameters
1 Sensor type 34
2 mV/V sensor 34
3 Decimal Point 34
4 Measure unit 34
5 Full-scale 35
6 Lower limit 35
7 Upper limit 35
8 Offset calibration 35
9 Gain calibration 35
10 Calibration 35
11 Totalizer 36
12 Sum function 36
13 Store 36
14 Conversion filter 36
15 Sampling frequenc y 37
133 Max zero set 37
134 Autozero start 37
135 Key ->0<- 38
136 Key TARE 38
137 Show stabilit y 38
138 Stability tolerance 38
17 V/I custom 38
18 01-Input value 38
19 01-Custom value 39
20 02-Input value 39
21 02-Custom value 39
22 03-Input value 39
23 03-Custom value 39
24 04-Input value 39
25 04-Custom value 39
26 05-Input value 39
27 05-Custom value 40
28 06-Input value 40
29 06-Custom value 40
56 - DP400S - User manual
Page 57
30 07-Input value 40
31 07-Custom value 40
32 08-Input value 40
33 08-Custom value 40
34 09-Input value 40
35 09-Custom value 41
36 10-Input value 41
37 10-Custom value 41
38 11-Input value 41
39 11-Custom value 41
40 12-Input value 41
41 12-Custom value 41
42 13-Input value 41
43 13-Custom value 42
44 14-Input value 42
45 14-Custom value 42
46 15-Input value 42
47 15-Custom value 42
48 16-Input value 42
49 16-Custom value 42
52 Easy-up 43
54 Alarm type 43
55 Contact t ype 44
56 Alarm threshold 44
57 Deviation threshold 44
58 Hysteresis 44
59 Reset type 44
60 Error contac t 44
62 Actuation delay 44
63 Lower limit 45
64 Upper limit 45
65 Protection 45
69 Alarm type 45
70 Contact t ype 45
71 Alarm threshold 46
72 Deviation threshold 46
User manual - DP400S - 57
Page 58
73 Hysteresis 46
74 Reset type 46
75 Error contac t 46
77 Actuation delay 46
78 Lower limit 46
79 Upper limit 47
80 Protection 47
84 Language 47
86 Contrast 47
88 Screen timeout 47
89 Display direction 4 8
90 Starting page 48
95 Input func tion 48
96 Contact t ype 48
100 Input function 49
101 Contact type 49
105 Graphic type 49
106 Lower limit 49
107 Upper limit 49
108 Trend time 50
109 Data logger 50
110 Data logger time 50
112 Retransmission 50
113 Signal type 50
114 Lower limit 50
115 Upper limit 51
116 Error value 51
126 Slave address 51
127 Baud Rate 51
128 ComPort setting 52
129 Serial delay 52
58 - DP400S - User manual
Page 59
OMEGA ENG INEERING , INC. war rants t his unit t o be free o f defec ts in ma terial s and work manshi p for a
period o f 13 months f rom dat e of purch ase. OM EGA’s Warrant y adds a n additi onal one (1) mont h grace
period t o the norm al one (1) year pr oduct w arrant y to cove r handlin g and ship ping tim e. This en sures t hat
OMEGA’s cus tomers rec eive maximum co verage on each p roduct.
If the uni t malfun ction s, it mus t be ret urned to t he fac tory fo r evalua tion. OM EGA’s Custo mer Ser vice
Depar tment will iss ue an Authorized R eturn (AR) numb er immediately u pon phone or writ ten reques t. Upon
examina tion by OM EGA, if t he unit is f ound to be d efec tive, it w ill be re paired o r replac ed at no c harge.
OMEGA’s WARR ANT Y does no t apply to d efec ts res ulting f rom any ac tion of t he purch aser, inc luding b ut
not limit ed to mis handlin g, improp er inte rfac ing, ope ration o utsid e of desi gn limit s, impro per rep air, or
unauth orized m odic ation. T his WARR ANT Y is VOID if th e unit sho ws evid ence of h aving be en tamp ered
with or sh ows evi dence o f having b een dama ged as a re sult of e xcess ive cor rosion; o r curre nt, hea t,
moist ure or vibr ation; im prope r speci cat ion; misa pplica tion; mi suse or ot her ope rating c ondit ions out side
of OMEGA’s co ntrol. C ompon ents in w hich wea r is not war rante d, inclu de but ar e not limit ed to con tact
points , fuses, and tr iacs.
OMEGA is p lease d to offe r sugge stion s on the us e of its var ious pro ducts . However, OM EGA
neithe r assum es res ponsi bility f or any omi ssion s or error s nor ass umes li abilit y for any
damag es that r esult fr om the us e of its pr oduct s in accor dance w ith info rmati on provi ded by
OMEGA , eithe r verbal o r writte n. OMEG A warran ts only th at the pa rts ma nufact ured by t he
compan y will be as s peci ed and fr ee of def ects. O MEGA MA KES NO OTH ER WARR ANTIE S OR
REPRE SENTATIONS O F ANY KIN D WHATSOE VER, E XPRESS ED OR IMP LIED, EXC EPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FIT NESS FOR A PAR TICUL AR PUR POSE AR E HEREBY D ISCL AIMED. L IMITATION OF
LIABI LITY: The r emed ies of pur chase r set for th her ein are exc lusive , and the to tal lia bility o f
OMEGA wi th resp ect to th is orde r, whethe r based o n contr act, wa rrant y, neglige nce, in demnicat ion, st rict lia bility o r other wise, s hall no t exceed t he purc hase pri ce of the c ompon ent
upon whi ch liabi lity is b ased. I n no event s hall OME GA be lia ble for co nsequ ential , incid ental
or special damages.
CONDIT IONS: Eq uipmen t sold by OM EGA is not i ntend ed to be us ed, nor sh all it be us ed: (1) as a “Basi c
Compon ent” un der 10 CFR 21 (N RC), used in o r with any n uclea r insta llation o r activ ity; o r (2) in medic al
applic ation s or used on h umans. S hould any P roduc t(s) be us ed in or wi th any nuc lear ins talla tion or
activ ity, med ical app licat ion, use d on human s, or misu sed in any w ay, OMEGA as sumes n o respo nsibili ty
as set fo rth in ou r basic WAR RANT Y/DI SCLA IMER lang uage, an d, addit ionall y, purchas er will in demnif y
OMEGA an d hold OMEG A harmle ss fro m any liabil ity or da mage wh atsoe ver aris ing out of t he use of th e
Produc t(s) in such a mann er.
Direc t all warr anty an d repair r eques ts/ inquir ies to the O MEGA Cus tomer S ervi ce Depa rtme nt. BEFO RE
RETUR NING ANY P RODUC T(S) TO OMEG A, PURC HASER MUS T OBTAIN AN A UTHOR IZED RET URN
(AR) NUMB ER FROM OM EGA’S CUSTO MER SERV ICE DEPAR TMENT (IN O RDER TO AVOID P ROCES SING
DELAYS). Th e assign ed AR num ber shou ld then be m arked on t he outs ide of the r eturn p ackag e and on
any corr espon dence . The pur chaser i s resp onsibl e for shipp ing char ges, fr eight, i nsuran ce and pr oper
packa ging to prevent b reakage in tran sit.
FOR WARRANTY RETURNS
follow ing infor mation a vailabl e BEFORE c ontacting
OMEGA:
1. P urchas e Order n umber un der whic h the
product was PURCHASED,
2. Model and s erial nu mber of th e produ ct unde r
warranty, and
3. Repair inst ructi ons and /or spec ific pr oblem s
relati ve to the produc t.
Rotamete rs, Gas Mass Flowmet ers & Flow Computers
Air Velocity I ndicators
Turbine/Paddlewheel Systems
Totalizers & B atch Controllers
PH/CONDUCTIVITY
pH Electro des, Testers & Accessorie s
Benchtop/Laboratory Meters
Controlle rs, Calibrators, Si mulators & Pumps
Industr ial pH & Conductivity E quipment
DATA ACQUISITION
Data Acquisit ion & Engineer ing Software
Communic ations-Based Ac quisition Systems
Plug-in Cards fo r Apple, IBM & Compatibles
Data Logging Systems
Recorders, Pr inters & Plotter
HEATERS
Heating C able
Cartr idge & Strip Heaters
Immersio n & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
Meterin g & Control Instr umentation
Refractometers
Pumps & Tubing
Air, Soil & Water Mon itors
Industr ial Water & Wastewater Treatment
pH, Conductiv ity & Dissolved Oxyg en Instrume nts
2300.10.288-Rev G
181218
M5726/0119
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.