START HERE
2
34
Using This Quick Start Manual
Use this Quick Start Manual to get your meter up and running
right out of the box. To do this you:
• connect power
• configure the unit
- specify input range
- specify frequency
- specify AC or DC coupling
- set decimal point position
- specify filter value
- specify units (V, mV or blank)
Before You Begin
In addition to the meter and the related parts, you will need
the following items to set up your meter:
• ac power, as listed on meter’s ID/Power Label
• 1/8” flat blade screwdriver
Safety Consideration
This device is marked with the international Caution symbol.
The instrument is a panel mount device protected in
accordance with EN61010-1 (Safety requirements for
electrical equipment for measurement, control, and laboratory
standard). Remember that the unit has no power-on switch.
Building installation should include a switch or circuit-breaker
that must be compliant to IEC 947-1 and 947-3.
SAFETY:
• Always disconnect power before changing signal and
power connections.
• Do not exceed voltage rating on the label located on the
top of the instrument housing.
• Do not use this instrument on a work bench without its
case for safety reasons.
• Do not operate this instrument in flammable or explosive
atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Whenever EMC is an issue, always use shielded cables.
• Use signal wire connections with twisted-pair cables.
•
Install Ferrite Bead(s) on signal wire close to the instrument
if EMC problems persist.
Mount the Unit
1. Cut a panel opening using
the dimensions shown to
the right.
2. Position the unit in the
opening, making sure the
front bezel is flush with the
panel.
3. Install retaining clip on the
meter and tighten against
the panel
Wiring-Signal Source
1. Remove the panel at the back of the unit.
2. Locate the P6 connector.
3. Make sure the signal source is off.
4. Insert the correct wire in each terminal as shown in the
following figure and tighten the lockdown screws.
5. Tug gently on the wires to verify the connections.
For Voltage Meter
For Current Meter
Warning: Do not connect AC power to your device until you
have completed all input and output connections. This
device must only be installed by a specially trained
electrician with corresponding qualifications. Failure to
follow all instructions and warnings may result in injury!
Connect ac Power
1. Locate the P1 connector.
2. Insert the correct wire in each terminal as shown in the
following figure and tighten the lockdown screws.
3. Tug gently on the wires to verify the connections.
Turn On the Unit
1. Plug the unit into a properly grounded 115V power
supply.
The unit initializes, scrolling the following message on
the front panel: TRUE RMS VOLT or TRUE RMS
CURRENT. Then the present value should display.
2. Verify that a value is displayed. If not:
• Unplug the unit
• Verify the P1 power connections
• Check your power source
• Plug the unit in again
Set SW Switches (If Necessary)
Range Selections for Voltage Input
Range Selections for Current Input
Configure the Unit
To configure the meter, you use the buttons on the front
panel.
To: Take This Action:
Display the Main Press the MENU button. The
Configuration Menu first function on the menu,
(examples: INPT, RDNG) INPT, displays.
Select a level 2 item submenu Press the STPTS button
(Once main menu displays) followed by the MENU
(example of level 2 RNGE button.
under the INPT menu)
Select a level 3 submenu Press the /MIN button.
item (Once level 2 item Press the /MAX button
displays) (example of level 3 to scroll through level 3
is 10V under RNGE) selections.
Select a level 4 submenu* Press the /MAX button.
item (Once level 3 item
displays) (example of level 4
is 300 under BAUD under
COM.P (Communication Protocols)
Go back to the previous Press the RESET button.
menu function
Exit the Configuration Menu Press the RESET button twice.
* If applicable
Set Range,Frequency & Coupling
1. Press MENU until the meter displays:
2. Press SETPTS, followed by
MENU until the meter displays:
3. Press /MIN. The meter flashes the
input range. Press /MAX to scroll
through choices. Your choices are:
0.1V(1mA)*, 1V (10 mA)*, 10V (0.1A)*,
100V (1A)* and 750V (5A)*
*— items in parenthesis are for current meter only
4. Press MENU to select the input range shown. The
meter displays:
5. Press /MIN. The meter flashes the
current frequency setup.
Press /MAX to scroll through choices.
Your choices are: 50HZ, 60HZ or ALL.